boca de tormenta tiposiapa.gob.mx/sites/default/files/3.2.1.1_boca_de_tormenta_2do_tramo.pdf ·...

1
ANGULO 1" x 1" x 1/4" @ 35 cms ANCLAS EN EL CONCRETO DE REJILLA ELECTROFORJADA EN ACERO (ASTM - A 36) TIPO IRVING DE TIPO 1/2 IS-05 DE 3/8" x 4" FUERA DE ESCALA DETALLE "B" DE 4" x 4" x 1/4" CONTRA MARCO DE ANGULO LOSA PERIMETRAL LOSA PERIMETRAL DE CONCRETO REFORZADO EN AMBOS SENTIDOS EN EL LECHO INFERIOR. f 'c=250kg/cm2 CON VARILLAS DEL No. 4, @ 20cms RULHQWDFLyQ GH OD VDOLGD Ver planta para ubicar ESCALERA MARINA VAR. No.6 0.40 0.40 ESCALERA MARINA VAR. No.6 40 20 10 BANQUETA 0.61 1.38 1571.90 10.00 1571.32 0.60 1.18 1571.02 1572.50 BT-18 0.45 1.80 1572.04 6.00 1571.14 0.60 1.50 1570.84 1572.64 BT-17 RULHQWDFLyQ GH OD VDOLGD Ver planta para ubicar 6DOLGD YHU WDEOD DIAMETRO TUBERIA 0.45 0.45 0.45 0.61 (A) PARRILLA LARGO (H3) 1.60 1.25 1.39 1.70 PROF. (H2) (H1) 1571.93 1571.96 1573.57 1571.79 NIVEL (N.B.) N.B. 78%2 '6 9DULDEOH 78%2 $3 9DULDEOH HOMBRE ENTRADA ENTRADA HOMBRE 6DOLGD YHU WDEOD (QWUDGD YHU WDEOD BOMBEO 2% BOMBEO 2% SUPERFICIE DE RODAMEINTO (QWUDGD YHU WDEOD 8.60 7.20 7.20 4.00 MODULO 1571.23 0.60 1.30 1570.93 1572.53 BT-19 1571.61 0.60 0.95 1571.31 1572.56 BT-16 1572.08 0.60 1.09 1571.78 1573.17 BT-15 A' N.A. N.S. 3/$17,//$ &21&5(72 6,03/( IF NJFPð MAMPOSTERIA DE PIEDRA BRAZA JUNTEADA CON MORTERO CEM. A.RIO PROP.1:4 N.T. ESCALA 1:25 CON VAR.#4@ESQUINA Y ESPESOR DE 1 Cm DALA DE CONCRETO REFORZADO Y ESTRIBOS DE VAR. #3 @25 cm MURO DE LADRILLO A TEZON ASENTADO CON MORTERO CEM. A. RIO PROP 1:4 ENJARRE EXTERIOR E INTERIOR PULIDO CON MORTERO CEM. A. DE RIO PROP. 1:3 PERIMETRAL LOSA SECCION A-A' ENJARRE EXTERIOR E DE CEM. A. RIO PROP 1:4 INTERIOR PULIDO CON MORTERO Y ESPESOR DE 1 cm ACABADO LISO NEGRO REJILLA ELECTROFORJADA EN ACERO (ASTM - A 36) TIPO IRVING TIPO 1/2 IS-05 DE SOLERA DE 3/8" X 4" N.A. ASENTADO MORTERO CEM. A. RIO PROP 1:4 MURO DE LADRILLO A TEZON N.S. REVESTIMIENTO DE CONCRETO CIMENTACION DE DALA Var.#4@ESQUINA EST. #3 @25 cm 3/$17,//$ '( &21&5(72 6,03/( IF NJFPð PARA DESPLANTE DE LA CIMENTACION 6,03/( IF NJFPð MAMPOSTERIA CON PIEDRA BRAZA JUNTEADA CON MORTERO CEM. A.RIO PROP.1:4 ESCALA 1:25 SECCION LONGITUDINAL B-B' N.T. HOMBRE ENTRADA BANQUETA LOSA PERIMETRAL ENTRADA HOMBRE LOSA PERIMETRAL ACABADO LISO NEGRO REJILLA ELECTROFORJADA EN ACERO (ASTM - A 36) TIPO IRVING MODELO 1/2 IS-05 DE 3/8 X 4" B' B ESCALA 1:25 PLANTA CONTRA MARCO DE ANGULO 1/2 IS-05 FUERA DE ESCALA ENTRADA HOMBRE SOLERA DE CARGA DE 3/8" X 4" VARILLA ATIEZADORA DE 3/8" sin escala DETALLE MODULO MARCO DE SOLERA 3/8" X 4" 1570.99 0.60 1.40 1570.69 1572.39 BT-14 A TUBO PROF. NIVEL (N.S,) B.T. PROF. (N.T.) NIVEL NIVEL RASANTE (N.A.) DATOS PROYECTO B.T. No. BOCA ANGULO 1" x 1" x 1/4" @ 35 cms ANCLAS EN EL CONCRETO DE REJILLA ELECTROFORJADA EN ACERO (ASTM - A 36) TIPO IRVING DE TIPO 1/2 IS-05 DE 3/8" x 4" FUERA DE ESCALA DETALLE "B" DE 4" x 4" x 1/4" CONTRA MARCO DE ANGULO LOSA PERIMETRAL LOSA PERIMETRAL DE CONCRETO REFORZADO EN AMBOS SENTIDOS EN EL LECHO INFERIOR. f 'c=250kg/cm2 CON VARILLAS DEL No. 4, @ 20cms RULHQWDFLyQ GH OD VDOLGD Ver planta para ubicar ESCALERA MARINA VAR. No.6 0.40 0.40 ESCALERA MARINA VAR. No.6 40 20 10 BANQUETA 0.61 1.38 1571.90 10.00 1571.32 0.60 1.18 1571.02 1572.50 BT-18 0.45 1.80 1572.04 6.00 1571.14 0.60 1.50 1570.84 1572.64 BT-17 RULHQWDFLyQ GH OD VDOLGD Ver planta para ubicar 6DOLGD YHU WDEOD DIAMETRO TUBERIA 0.45 0.45 0.45 0.61 (A) PARRILLA LARGO (H3) 1.60 1.25 1.39 1.70 PROF. (H2) (H1) 1571.93 1571.96 1573.57 1571.79 NIVEL (N.B.) N.B. 78%2 '6 9DULDEOH 78%2 $3 9DULDEOH HOMBRE ENTRADA ENTRADA HOMBRE 6DOLGD YHU WDEOD (QWUDGD YHU WDEOD BOMBEO 2% BOMBEO 2% SUPERFICIE DE RODAMEINTO (QWUDGD YHU WDEOD 8.60 7.20 7.20 4.00 MODULO 1571.23 0.60 1.30 1570.93 1572.53 BT-19 1571.61 0.60 0.95 1571.31 1572.56 BT-16 1572.08 0.60 1.09 1571.78 1573.17 BT-15 A' N.A. N.S. 3/$17,//$ &21&5(72 6,03/( IF NJFPð MAMPOSTERIA DE PIEDRA BRAZA JUNTEADA CON MORTERO CEM. A.RIO PROP.1:4 N.T. ESCALA 1:25 CON VAR.#4@ESQUINA Y ESPESOR DE 1 Cm DALA DE CONCRETO REFORZADO Y ESTRIBOS DE VAR. #3 @25 cm MURO DE LADRILLO A TEZON ASENTADO CON MORTERO CEM. A. RIO PROP 1:4 ENJARRE EXTERIOR E INTERIOR PULIDO CON MORTERO CEM. A. DE RIO PROP. 1:3 PERIMETRAL LOSA SECCION A-A' ENJARRE EXTERIOR E DE CEM. A. RIO PROP 1:4 INTERIOR PULIDO CON MORTERO Y ESPESOR DE 1 cm ACABADO LISO NEGRO REJILLA ELECTROFORJADA EN ACERO (ASTM - A 36) TIPO IRVING TIPO 1/2 IS-05 DE SOLERA DE 3/8" X 4" N.A. ASENTADO MORTERO CEM. A. RIO PROP 1:4 MURO DE LADRILLO A TEZON N.S. REVESTIMIENTO DE CONCRETO CIMENTACION DE DALA Var.#4@ESQUINA EST. #3 @25 cm 3/$17,//$ '( &21&5(72 6,03/( IF NJFPð PARA DESPLANTE DE LA CIMENTACION 6,03/( IF NJFPð MAMPOSTERIA CON PIEDRA BRAZA JUNTEADA CON MORTERO CEM. A.RIO PROP.1:4 ESCALA 1:25 SECCION LONGITUDINAL B-B' N.T. HOMBRE ENTRADA BANQUETA LOSA PERIMETRAL ENTRADA HOMBRE LOSA PERIMETRAL ACABADO LISO NEGRO REJILLA ELECTROFORJADA EN ACERO (ASTM - A 36) TIPO IRVING MODELO 1/2 IS-05 DE 3/8 X 4" B' B ESCALA 1:25 PLANTA CONTRA MARCO DE ANGULO 1/2 IS-05 FUERA DE ESCALA ENTRADA HOMBRE SOLERA DE CARGA DE 3/8" X 4" VARILLA ATIEZADORA DE 3/8" sin escala DETALLE MODULO MARCO DE SOLERA 3/8" X 4" 1570.99 0.60 1.40 1570.69 1572.39 BT-14 A TUBO PROF. NIVEL (N.S,) B.T. PROF. (N.T.) NIVEL NIVEL RASANTE (N.A.) DATOS PROYECTO B.T. No. BOCA ANGULO 1" x 1" x 1/4" @ 35 cms ANCLAS EN EL CONCRETO DE REJILLA ELECTROFORJADA EN ACERO (ASTM - A 36) TIPO IRVING DE TIPO 1/2 IS-05 DE 3/8" x 4" FUERA DE ESCALA DETALLE "B" DE 4" x 4" x 1/4" CONTRA MARCO DE ANGULO LOSA PERIMETRAL LOSA PERIMETRAL DE CONCRETO REFORZADO EN AMBOS SENTIDOS EN EL LECHO INFERIOR. f 'c=250kg/cm2 CON VARILLAS DEL No. 4, @ 20cms RULHQWDFLyQ GH OD VDOLGD Ver planta para ubicar ESCALERA MARINA VAR. No.6 0.40 0.40 ESCALERA MARINA VAR. No.6 40 20 10 BANQUETA 0.61 1.38 1571.90 10.00 1571.32 0.60 1.18 1571.02 1572.50 BT-18 0.45 1.80 1572.04 6.00 1571.14 0.60 1.50 1570.84 1572.64 BT-17 RULHQWDFLyQ GH OD VDOLGD Ver planta para ubicar 6DOLGD YHU WDEOD DIAMETRO TUBERIA 0.45 0.45 0.45 0.61 (A) PARRILLA LARGO (H3) 1.60 1.25 1.39 1.70 PROF. (H2) (H1) 1571.93 1571.96 1573.57 1571.79 NIVEL (N.B.) N.B. 78%2 '6 9DULDEOH 78%2 $3 9DULDEOH HOMBRE ENTRADA ENTRADA HOMBRE 6DOLGD YHU WDEOD (QWUDGD YHU WDEOD BOMBEO 2% BOMBEO 2% SUPERFICIE DE RODAMEINTO (QWUDGD YHU WDEOD 8.60 7.20 7.20 4.00 MODULO 1571.23 0.60 1.30 1570.93 1572.53 BT-19 1571.61 0.60 0.95 1571.31 1572.56 BT-16 1572.08 0.60 1.09 1571.78 1573.17 BT-15 A' N.A. N.S. 3/$17,//$ &21&5(72 6,03/( IF NJFPð MAMPOSTERIA DE PIEDRA BRAZA JUNTEADA CON MORTERO CEM. A.RIO PROP.1:4 N.T. ESCALA 1:25 CON VAR.#4@ESQUINA Y ESPESOR DE 1 Cm DALA DE CONCRETO REFORZADO Y ESTRIBOS DE VAR. #3 @25 cm MURO DE LADRILLO A TEZON ASENTADO CON MORTERO CEM. A. RIO PROP 1:4 ENJARRE EXTERIOR E INTERIOR PULIDO CON MORTERO CEM. A. DE RIO PROP. 1:3 PERIMETRAL LOSA SECCION A-A' ENJARRE EXTERIOR E DE CEM. A. RIO PROP 1:4 INTERIOR PULIDO CON MORTERO Y ESPESOR DE 1 cm ACABADO LISO NEGRO REJILLA ELECTROFORJADA EN ACERO (ASTM - A 36) TIPO IRVING TIPO 1/2 IS-05 DE SOLERA DE 3/8" X 4" N.A. ASENTADO MORTERO CEM. A. RIO PROP 1:4 MURO DE LADRILLO A TEZON N.S. REVESTIMIENTO DE CONCRETO CIMENTACION DE DALA Var.#4@ESQUINA EST. #3 @25 cm 3/$17,//$ '( &21&5(72 6,03/( IF NJFPð PARA DESPLANTE DE LA CIMENTACION 6,03/( IF NJFPð MAMPOSTERIA CON PIEDRA BRAZA JUNTEADA CON MORTERO CEM. A.RIO PROP.1:4 ESCALA 1:25 SECCION LONGITUDINAL B-B' N.T. HOMBRE ENTRADA BANQUETA LOSA PERIMETRAL ENTRADA HOMBRE LOSA PERIMETRAL ACABADO LISO NEGRO REJILLA ELECTROFORJADA EN ACERO (ASTM - A 36) TIPO IRVING MODELO 1/2 IS-05 DE 3/8 X 4" B' B ESCALA 1:25 PLANTA CONTRA MARCO DE ANGULO 1/2 IS-05 FUERA DE ESCALA ENTRADA HOMBRE SOLERA DE CARGA DE 3/8" X 4" VARILLA ATIEZADORA DE 3/8" sin escala DETALLE MODULO MARCO DE SOLERA 3/8" X 4" 1570.99 0.60 1.40 1570.69 1572.39 BT-14 A TUBO PROF. NIVEL (N.S,) B.T. PROF. (N.T.) NIVEL NIVEL RASANTE (N.A.) DATOS PROYECTO B.T. No. BOCA ANGULO 1" x 1" x 1/4" @ 35 cms ANCLAS EN EL CONCRETO DE REJILLA ELECTROFORJADA EN ACERO (ASTM - A 36) TIPO IRVING DE TIPO 1/2 IS-05 DE 3/8" x 4" FUERA DE ESCALA DETALLE "B" DE 4" x 4" x 1/4" CONTRA MARCO DE ANGULO LOSA PERIMETRAL LOSA PERIMETRAL DE CONCRETO REFORZADO EN AMBOS SENTIDOS EN EL LECHO INFERIOR. f 'c=250kg/cm2 CON VARILLAS DEL No. 4, @ 20cms RULHQWDFLyQ GH OD VDOLGD Ver planta para ubicar ESCALERA MARINA VAR. No.6 0.40 0.40 ESCALERA MARINA VAR. No.6 40 20 10 BANQUETA 0.61 1.38 1571.90 10.00 1571.32 0.60 1.18 1571.02 1572.50 BT-18 0.45 1.80 1572.04 6.00 1571.14 0.60 1.50 1570.84 1572.64 BT-17 RULHQWDFLyQ GH OD VDOLGD Ver planta para ubicar 6DOLGD YHU WDEOD DIAMETRO TUBERIA 0.45 0.45 0.45 0.61 (A) PARRILLA LARGO (H3) 1.60 1.25 1.39 1.70 PROF. (H2) (H1) 1571.93 1571.96 1573.57 1571.79 NIVEL (N.B.) N.B. 78%2 '6 9DULDEOH 78%2 $3 9DULDEOH HOMBRE ENTRADA ENTRADA HOMBRE 6DOLGD YHU WDEOD (QWUDGD YHU WDEOD BOMBEO 2% BOMBEO 2% SUPERFICIE DE RODAMEINTO (QWUDGD YHU WDEOD 8.60 7.20 7.20 4.00 MODULO 1571.23 0.60 1.30 1570.93 1572.53 BT-19 1571.61 0.60 0.95 1571.31 1572.56 BT-16 1572.08 0.60 1.09 1571.78 1573.17 BT-15 A' N.A. N.S. 3/$17,//$ &21&5(72 6,03/( IF NJFPð MAMPOSTERIA DE PIEDRA BRAZA JUNTEADA CON MORTERO CEM. A.RIO PROP.1:4 N.T. ESCALA 1:25 CON VAR.#4@ESQUINA Y ESPESOR DE 1 Cm DALA DE CONCRETO REFORZADO Y ESTRIBOS DE VAR. #3 @25 cm MURO DE LADRILLO A TEZON ASENTADO CON MORTERO CEM. A. RIO PROP 1:4 ENJARRE EXTERIOR E INTERIOR PULIDO CON MORTERO CEM. A. DE RIO PROP. 1:3 PERIMETRAL LOSA SECCION A-A' ENJARRE EXTERIOR E DE CEM. A. RIO PROP 1:4 INTERIOR PULIDO CON MORTERO Y ESPESOR DE 1 cm ACABADO LISO NEGRO REJILLA ELECTROFORJADA EN ACERO (ASTM - A 36) TIPO IRVING TIPO 1/2 IS-05 DE SOLERA DE 3/8" X 4" N.A. ASENTADO MORTERO CEM. A. RIO PROP 1:4 MURO DE LADRILLO A TEZON N.S. REVESTIMIENTO DE CONCRETO CIMENTACION DE DALA Var.#4@ESQUINA EST. #3 @25 cm 3/$17,//$ '( &21&5(72 6,03/( IF NJFPð PARA DESPLANTE DE LA CIMENTACION 6,03/( IF NJFPð MAMPOSTERIA CON PIEDRA BRAZA JUNTEADA CON MORTERO CEM. A.RIO PROP.1:4 ESCALA 1:25 SECCION LONGITUDINAL B-B' N.T. HOMBRE ENTRADA BANQUETA LOSA PERIMETRAL ENTRADA HOMBRE LOSA PERIMETRAL ACABADO LISO NEGRO REJILLA ELECTROFORJADA EN ACERO (ASTM - A 36) TIPO IRVING MODELO 1/2 IS-05 DE 3/8 X 4" B' B ESCALA 1:25 PLANTA CONTRA MARCO DE ANGULO 1/2 IS-05 FUERA DE ESCALA ENTRADA HOMBRE SOLERA DE CARGA DE 3/8" X 4" VARILLA ATIEZADORA DE 3/8" sin escala DETALLE MODULO MARCO DE SOLERA 3/8" X 4" 1570.99 0.60 1.40 1570.69 1572.39 BT-14 A TUBO PROF. NIVEL (N.S,) B.T. PROF. (N.T.) NIVEL NIVEL RASANTE (N.A.) DATOS PROYECTO B.T. No. BOCA LAMINA CLAVE DE ARCHIVO CLAVE DE PLANO 1/1 SUPERINTENDENCIA DE OBRAS Y PROYECTOS DATOS DE PROYECTO: JEFE SECCION ESTUDIOS Y PROYECTOS 68%',5(&725 '( ,1*(1,(5Ë$ -------------------------------------- SUPERINTENDENTE DE OBRAS Y PROYECTOS ,1* -8$1 $1721,2 -,0e1(= 62/7(52 N O R T E CALLE ALDAMA COORDINADOR DE PROYECTOS ING. RUBEN DOMINGUEZ HERNANDEZ SUPERINTENDENCIA DE OPERACION PARA SU VALIDACION OPERATIVA DIRECCION TECNICA ING. ALEJANDRO GUTIERREZ MORENO DIRECTOR TECNICO DE AGUA POTABLE Y ALCANTARILLADO SISTEMA INTERMUNICIPAL DE LOS SERVICIOS ENCARGADO SUBDIRECCION DE ALCANTARILLADO ING. MARIA ELENA PARRAL ACOSTA ENCARGADO SECC. DE ALCANTARILLADO S. R. ING. ERICK ALBERTO ALVAREZ ZAMORANO ,1* -26( /8,6 0217$f2 2&+2$ ENCARGADO DE LA SUPERINTENDENCIA DE OPERACION CALLE CIPRES AV. ZALATITAN JUAN GIL PRECIADO CALLE LOMA BONITA PUNTO DE DESCARGA PUNTO DE INICIO PROL. GIGANTES AV. CONSTITUCION "BOCA DE TORMENTA TIPO" PROYECTO: ING. PABLO GUTIERREZ RANGEL -RVp %HOWUDQ 1R Col. Residencial la Soledad Tlaquepaque, Jalisco. Tel: (33) 1933.5852 Cel: 044 (33) 1172.3811 [email protected] No. DE CONTRATO: (2DO TRAMO) PROYECTO DEL COLECTOR PLUVIAL LOMA BONITA, EN EL MUNICIPIO DE TONALA, JAL

Upload: others

Post on 26-Mar-2020

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: BOCA DE TORMENTA TIPOsiapa.gob.mx/sites/default/files/3.2.1.1_boca_de_tormenta_2do_tramo.pdf · enjarre exterior e de cem. a. rio prop 1:4 interior pulido con mortero y espesor de

ANGULO 1" x 1" x 1/4" @ 35 cms

ANCLAS EN EL CONCRETO DE

REJILLA ELECTROFORJADA EN ACERO

(ASTM - A 36) TIPO IRVING DE

TIPO 1/2 IS-05 DE 3/8" x 4"

FUERA DE ESCALA

DETALLE "B"

DE 4" x 4" x 1/4"

CONTRA MARCO DE ANGULO

LOSA PERIMETRAL

LOSA PERIMETRAL DE CONCRETO REFORZADO

EN AMBOS SENTIDOS EN EL LECHO INFERIOR.

f 'c=250kg/cm2 CON VARILLAS DEL No. 4, @ 20cms

orientación de la salida

Ver planta para ubicar

ESCALERA MARINA

VAR. No.6

0.40

0.40

ESCALERA MARINA

VAR. No.6

40

20

10

BANQUETA

0.611.381571.90 10.001571.32 0.60 1.181571.021572.50BT-18

0.451.801572.04 6.001571.14 0.60 1.501570.841572.64BT-17

orientación de la salida

Ver planta para ubicar

ØSalida (ver tabla)

DIAMETRO

TUBERIA

0.45

0.45

0.45

0.61

(A)

PARRILLA

LARGO

(H3)

1.60

1.25

1.39

1.70

PROF.

(H2)(H1)

1571.93

1571.96

1573.57

1571.79

NIVEL

(N.B.)

N.B.

TUBO D.S. Ø=Variable

TUBO A.P. Ø= Variable

HOMBRE

ENTRADA

ENTRADA HOMBRE

ØSalida (ver tabla)

ØEntrada (ver tabla)

BOMBEO

2%

BOMBEO

2%

SUPERFICIE DE

RODAMEINTO

ØEntrada (ver tabla)

8.60

7.20

7.20

4.00

MODULO

1571.23 0.60 1.301570.931572.53BT-19

1571.61 0.60 0.951571.311572.56BT-16

1572.08 0.60 1.091571.781573.17BT-15

A'

N.A.

N.S.

PLANTILLA CONCRETO SIMPLE f'c=200 kg/cm²

MAMPOSTERIA DE PIEDRA

BRAZA JUNTEADA CON MORTERO

CEM. A.RIO PROP.1:4

N.T.

ESCALA 1:25

CON VAR.#4@ESQUINA

Y ESPESOR DE 1 Cm

DALA DE CONCRETO REFORZADO

Y ESTRIBOS DE VAR. #3 @25 cm

MURO DE LADRILLO A TEZON

ASENTADO CON MORTERO

CEM. A. RIO PROP 1:4

ENJARRE EXTERIOR E

INTERIOR PULIDO CON MORTERO

CEM. A. DE RIO PROP. 1:3

PERIMETRAL

LOSA

SECCION A-A'

ENJARRE EXTERIOR E

DE CEM. A. RIO PROP 1:4

INTERIOR PULIDO CON MORTERO

Y ESPESOR DE 1 cm

ACABADO LISO NEGRO

REJILLA ELECTROFORJADA EN ACERO

(ASTM - A 36) TIPO IRVING TIPO

1/2 IS-05 DE SOLERA DE 3/8" X 4"

N.A.

ASENTADO MORTERO

CEM. A. RIO PROP 1:4

MURO DE LADRILLO A TEZON

N.S.

REVESTIMIENTO DE CONCRETO

CIMENTACION DE

DALA Var.#4@ESQUINA

EST. #3 @25 cm

PLANTILLA DE CONCRETO SIMPLE f'c=100 kg/cm²

PARA DESPLANTE DE LA CIMENTACION

SIMPLE f'c=200 kg/cm²

MAMPOSTERIA CON PIEDRA

BRAZA JUNTEADA CON MORTERO

CEM. A.RIO PROP.1:4

ESCALA 1:25

SECCION LONGITUDINAL B-B'

N.T.

HOMBRE

ENTRADA

BANQUETA

LOSA PERIMETRAL

ENTRADA HOMBRE

LOSA PERIMETRAL

ACABADO LISO NEGRO

REJILLA ELECTROFORJADA EN ACERO

(ASTM - A 36) TIPO IRVING

MODELO 1/2 IS-05 DE 3/8 X 4"

B'B

ESCALA 1:25

PLANTA

CONTRA MARCO DE ANGULO

1/2 IS-05

FUERA DE ESCALA

ENTRADA HOMBRE

SOLERA DE CARGA DE

3/8" X 4"

VARILLA ATIEZADORA DE 3/8"

sin escala

DETALLE MODULO

MARCO DE SOLERA 3/8" X 4"

1570.99 0.60 1.401570.691572.39BT-14

A TUBO

PROF.

NIVEL

(N.S,)

B.T.

PROF.

(N.T.)

NIVEL

NIVEL

RASANTE

(N.A.)

DATOS PROYECTO B.T.

No. BOCA

ANGULO 1" x 1" x 1/4" @ 35 cms

ANCLAS EN EL CONCRETO DE

REJILLA ELECTROFORJADA EN ACERO

(ASTM - A 36) TIPO IRVING DE

TIPO 1/2 IS-05 DE 3/8" x 4"

FUERA DE ESCALA

DETALLE "B"

DE 4" x 4" x 1/4"

CONTRA MARCO DE ANGULO

LOSA PERIMETRAL

LOSA PERIMETRAL DE CONCRETO REFORZADO

EN AMBOS SENTIDOS EN EL LECHO INFERIOR.

f 'c=250kg/cm2 CON VARILLAS DEL No. 4, @ 20cms

orientación de la salida

Ver planta para ubicar

ESCALERA MARINA

VAR. No.6

0.40

0.40

ESCALERA MARINA

VAR. No.6

40

20

10

BANQUETA

0.611.381571.90 10.001571.32 0.60 1.181571.021572.50BT-18

0.451.801572.04 6.001571.14 0.60 1.501570.841572.64BT-17

orientación de la salida

Ver planta para ubicar

ØSalida (ver tabla)

DIAMETRO

TUBERIA

0.45

0.45

0.45

0.61

(A)

PARRILLA

LARGO

(H3)

1.60

1.25

1.39

1.70

PROF.

(H2)(H1)

1571.93

1571.96

1573.57

1571.79

NIVEL

(N.B.)

N.B.

TUBO D.S. Ø=Variable

TUBO A.P. Ø= Variable

HOMBRE

ENTRADA

ENTRADA HOMBRE

ØSalida (ver tabla)

ØEntrada (ver tabla)

BOMBEO

2%

BOMBEO

2%

SUPERFICIE DE

RODAMEINTO

ØEntrada (ver tabla)

8.60

7.20

7.20

4.00

MODULO

1571.23 0.60 1.301570.931572.53BT-19

1571.61 0.60 0.951571.311572.56BT-16

1572.08 0.60 1.091571.781573.17BT-15

A'

N.A.

N.S.

PLANTILLA CONCRETO SIMPLE f'c=200 kg/cm²

MAMPOSTERIA DE PIEDRA

BRAZA JUNTEADA CON MORTERO

CEM. A.RIO PROP.1:4

N.T.

ESCALA 1:25

CON VAR.#4@ESQUINA

Y ESPESOR DE 1 Cm

DALA DE CONCRETO REFORZADO

Y ESTRIBOS DE VAR. #3 @25 cm

MURO DE LADRILLO A TEZON

ASENTADO CON MORTERO

CEM. A. RIO PROP 1:4

ENJARRE EXTERIOR E

INTERIOR PULIDO CON MORTERO

CEM. A. DE RIO PROP. 1:3

PERIMETRAL

LOSA

SECCION A-A'

ENJARRE EXTERIOR E

DE CEM. A. RIO PROP 1:4

INTERIOR PULIDO CON MORTERO

Y ESPESOR DE 1 cm

ACABADO LISO NEGRO

REJILLA ELECTROFORJADA EN ACERO

(ASTM - A 36) TIPO IRVING TIPO

1/2 IS-05 DE SOLERA DE 3/8" X 4"

N.A.

ASENTADO MORTERO

CEM. A. RIO PROP 1:4

MURO DE LADRILLO A TEZON

N.S.

REVESTIMIENTO DE CONCRETO

CIMENTACION DE

DALA Var.#4@ESQUINA

EST. #3 @25 cm

PLANTILLA DE CONCRETO SIMPLE f'c=100 kg/cm²

PARA DESPLANTE DE LA CIMENTACION

SIMPLE f'c=200 kg/cm²

MAMPOSTERIA CON PIEDRA

BRAZA JUNTEADA CON MORTERO

CEM. A.RIO PROP.1:4

ESCALA 1:25

SECCION LONGITUDINAL B-B'

N.T.

HOMBRE

ENTRADA

BANQUETA

LOSA PERIMETRAL

ENTRADA HOMBRE

LOSA PERIMETRAL

ACABADO LISO NEGRO

REJILLA ELECTROFORJADA EN ACERO

(ASTM - A 36) TIPO IRVING

MODELO 1/2 IS-05 DE 3/8 X 4"

B'B

ESCALA 1:25

PLANTA

CONTRA MARCO DE ANGULO

1/2 IS-05

FUERA DE ESCALA

ENTRADA HOMBRE

SOLERA DE CARGA DE

3/8" X 4"

VARILLA ATIEZADORA DE 3/8"

sin escala

DETALLE MODULO

MARCO DE SOLERA 3/8" X 4"

1570.99 0.60 1.401570.691572.39BT-14

A TUBO

PROF.

NIVEL

(N.S,)

B.T.

PROF.

(N.T.)

NIVEL

NIVEL

RASANTE

(N.A.)

DATOS PROYECTO B.T.

No. BOCA

ANGULO 1" x 1" x 1/4" @ 35 cms

ANCLAS EN EL CONCRETO DE

REJILLA ELECTROFORJADA EN ACERO

(ASTM - A 36) TIPO IRVING DE

TIPO 1/2 IS-05 DE 3/8" x 4"

FUERA DE ESCALA

DETALLE "B"

DE 4" x 4" x 1/4"

CONTRA MARCO DE ANGULO

LOSA PERIMETRAL

LOSA PERIMETRAL DE CONCRETO REFORZADO

EN AMBOS SENTIDOS EN EL LECHO INFERIOR.

f 'c=250kg/cm2 CON VARILLAS DEL No. 4, @ 20cms

orientación de la salida

Ver planta para ubicar

ESCALERA MARINA

VAR. No.6

0.40

0.40

ESCALERA MARINA

VAR. No.6

40

20

10

BANQUETA

0.611.381571.90 10.001571.32 0.60 1.181571.021572.50BT-18

0.451.801572.04 6.001571.14 0.60 1.501570.841572.64BT-17

orientación de la salida

Ver planta para ubicar

ØSalida (ver tabla)

DIAMETRO

TUBERIA

0.45

0.45

0.45

0.61

(A)

PARRILLA

LARGO

(H3)

1.60

1.25

1.39

1.70

PROF.

(H2)(H1)

1571.93

1571.96

1573.57

1571.79

NIVEL

(N.B.)

N.B.

TUBO D.S. Ø=Variable

TUBO A.P. Ø= Variable

HOMBRE

ENTRADA

ENTRADA HOMBRE

ØSalida (ver tabla)

ØEntrada (ver tabla)

BOMBEO

2%

BOMBEO

2%

SUPERFICIE DE

RODAMEINTO

ØEntrada (ver tabla)

8.60

7.20

7.20

4.00

MODULO

1571.23 0.60 1.301570.931572.53BT-19

1571.61 0.60 0.951571.311572.56BT-16

1572.08 0.60 1.091571.781573.17BT-15

A'

N.A.

N.S.

PLANTILLA CONCRETO SIMPLE f'c=200 kg/cm²

MAMPOSTERIA DE PIEDRA

BRAZA JUNTEADA CON MORTERO

CEM. A.RIO PROP.1:4

N.T.

ESCALA 1:25

CON VAR.#4@ESQUINA

Y ESPESOR DE 1 Cm

DALA DE CONCRETO REFORZADO

Y ESTRIBOS DE VAR. #3 @25 cm

MURO DE LADRILLO A TEZON

ASENTADO CON MORTERO

CEM. A. RIO PROP 1:4

ENJARRE EXTERIOR E

INTERIOR PULIDO CON MORTERO

CEM. A. DE RIO PROP. 1:3

PERIMETRAL

LOSA

SECCION A-A'

ENJARRE EXTERIOR E

DE CEM. A. RIO PROP 1:4

INTERIOR PULIDO CON MORTERO

Y ESPESOR DE 1 cm

ACABADO LISO NEGRO

REJILLA ELECTROFORJADA EN ACERO

(ASTM - A 36) TIPO IRVING TIPO

1/2 IS-05 DE SOLERA DE 3/8" X 4"

N.A.

ASENTADO MORTERO

CEM. A. RIO PROP 1:4

MURO DE LADRILLO A TEZON

N.S.

REVESTIMIENTO DE CONCRETO

CIMENTACION DE

DALA Var.#4@ESQUINA

EST. #3 @25 cm

PLANTILLA DE CONCRETO SIMPLE f'c=100 kg/cm²

PARA DESPLANTE DE LA CIMENTACION

SIMPLE f'c=200 kg/cm²

MAMPOSTERIA CON PIEDRA

BRAZA JUNTEADA CON MORTERO

CEM. A.RIO PROP.1:4

ESCALA 1:25

SECCION LONGITUDINAL B-B'

N.T.

HOMBRE

ENTRADA

BANQUETA

LOSA PERIMETRAL

ENTRADA HOMBRE

LOSA PERIMETRAL

ACABADO LISO NEGRO

REJILLA ELECTROFORJADA EN ACERO

(ASTM - A 36) TIPO IRVING

MODELO 1/2 IS-05 DE 3/8 X 4"

B'B

ESCALA 1:25

PLANTA

CONTRA MARCO DE ANGULO

1/2 IS-05

FUERA DE ESCALA

ENTRADA HOMBRE

SOLERA DE CARGA DE

3/8" X 4"

VARILLA ATIEZADORA DE 3/8"

sin escala

DETALLE MODULO

MARCO DE SOLERA 3/8" X 4"

1570.99 0.60 1.401570.691572.39BT-14

A TUBO

PROF.

NIVEL

(N.S,)

B.T.

PROF.

(N.T.)

NIVEL

NIVEL

RASANTE

(N.A.)

DATOS PROYECTO B.T.

No. BOCA

ANGULO 1" x 1" x 1/4" @ 35 cms

ANCLAS EN EL CONCRETO DE

REJILLA ELECTROFORJADA EN ACERO

(ASTM - A 36) TIPO IRVING DE

TIPO 1/2 IS-05 DE 3/8" x 4"

FUERA DE ESCALA

DETALLE "B"

DE 4" x 4" x 1/4"

CONTRA MARCO DE ANGULO

LOSA PERIMETRAL

LOSA PERIMETRAL DE CONCRETO REFORZADO

EN AMBOS SENTIDOS EN EL LECHO INFERIOR.

f 'c=250kg/cm2 CON VARILLAS DEL No. 4, @ 20cms

orientación de la salida

Ver planta para ubicar

ESCALERA MARINA

VAR. No.6

0.40

0.40

ESCALERA MARINA

VAR. No.6

40

20

10

BANQUETA

0.611.381571.90 10.001571.32 0.60 1.181571.021572.50BT-18

0.451.801572.04 6.001571.14 0.60 1.501570.841572.64BT-17

orientación de la salida

Ver planta para ubicar

ØSalida (ver tabla)

DIAMETRO

TUBERIA

0.45

0.45

0.45

0.61

(A)

PARRILLA

LARGO

(H3)

1.60

1.25

1.39

1.70

PROF.

(H2)(H1)

1571.93

1571.96

1573.57

1571.79

NIVEL

(N.B.)

N.B.

TUBO D.S. Ø=Variable

TUBO A.P. Ø= Variable

HOMBRE

ENTRADA

ENTRADA HOMBRE

ØSalida (ver tabla)

ØEntrada (ver tabla)

BOMBEO

2%

BOMBEO

2%

SUPERFICIE DE

RODAMEINTO

ØEntrada (ver tabla)

8.60

7.20

7.20

4.00

MODULO

1571.23 0.60 1.301570.931572.53BT-19

1571.61 0.60 0.951571.311572.56BT-16

1572.08 0.60 1.091571.781573.17BT-15

A'

N.A.

N.S.

PLANTILLA CONCRETO SIMPLE f'c=200 kg/cm²

MAMPOSTERIA DE PIEDRA

BRAZA JUNTEADA CON MORTERO

CEM. A.RIO PROP.1:4

N.T.

ESCALA 1:25

CON VAR.#4@ESQUINA

Y ESPESOR DE 1 Cm

DALA DE CONCRETO REFORZADO

Y ESTRIBOS DE VAR. #3 @25 cm

MURO DE LADRILLO A TEZON

ASENTADO CON MORTERO

CEM. A. RIO PROP 1:4

ENJARRE EXTERIOR E

INTERIOR PULIDO CON MORTERO

CEM. A. DE RIO PROP. 1:3

PERIMETRAL

LOSA

SECCION A-A'

ENJARRE EXTERIOR E

DE CEM. A. RIO PROP 1:4

INTERIOR PULIDO CON MORTERO

Y ESPESOR DE 1 cm

ACABADO LISO NEGRO

REJILLA ELECTROFORJADA EN ACERO

(ASTM - A 36) TIPO IRVING TIPO

1/2 IS-05 DE SOLERA DE 3/8" X 4"

N.A.

ASENTADO MORTERO

CEM. A. RIO PROP 1:4

MURO DE LADRILLO A TEZON

N.S.

REVESTIMIENTO DE CONCRETO

CIMENTACION DE

DALA Var.#4@ESQUINA

EST. #3 @25 cm

PLANTILLA DE CONCRETO SIMPLE f'c=100 kg/cm²

PARA DESPLANTE DE LA CIMENTACION

SIMPLE f'c=200 kg/cm²

MAMPOSTERIA CON PIEDRA

BRAZA JUNTEADA CON MORTERO

CEM. A.RIO PROP.1:4

ESCALA 1:25

SECCION LONGITUDINAL B-B'

N.T.

HOMBRE

ENTRADA

BANQUETA

LOSA PERIMETRAL

ENTRADA HOMBRE

LOSA PERIMETRAL

ACABADO LISO NEGRO

REJILLA ELECTROFORJADA EN ACERO

(ASTM - A 36) TIPO IRVING

MODELO 1/2 IS-05 DE 3/8 X 4"

B'B

ESCALA 1:25

PLANTA

CONTRA MARCO DE ANGULO

1/2 IS-05

FUERA DE ESCALA

ENTRADA HOMBRE

SOLERA DE CARGA DE

3/8" X 4"

VARILLA ATIEZADORA DE 3/8"

sin escala

DETALLE MODULO

MARCO DE SOLERA 3/8" X 4"

1570.99 0.60 1.401570.691572.39BT-14

A TUBO

PROF.

NIVEL

(N.S,)

B.T.

PROF.

(N.T.)

NIVEL

NIVEL

RASANTE

(N.A.)

DATOS PROYECTO B.T.

No. BOCA

LAMINACLAVE DE ARCHIVOCLAVE DE PLANO

1/1

SUPERINTENDENCIA DE OBRAS Y PROYECTOS

DATOS DE PROYECTO:

JEFE SECCION ESTUDIOS Y PROYECTOSSUBDIRECTOR DE INGENIERÍA

--------------------------------------

SUPERINTENDENTE DE OBRAS Y PROYECTOS

ING. JUAN ANTONIO JIMÉNEZ SOLTERO

N O R T E

C

A

L

L

E

A

L

D

A

M

A

COORDINADOR DE PROYECTOS

ING. RUBEN DOMINGUEZ HERNANDEZ

SUPERINTENDENCIA DE OPERACION

PARA SU VALIDACION OPERATIVA

DIRECCION TECNICA

ING. ALEJANDRO GUTIERREZ MORENO

DIRECTOR TECNICO

DE AGUA POTABLE Y ALCANTARILLADO

SISTEMA INTERMUNICIPAL DE LOS SERVICIOS

ENCARGADO SUBDIRECCION DE ALCANTARILLADO

ING. MARIA ELENA PARRAL ACOSTA

ENCARGADO SECC. DE ALCANTARILLADO S. R.

ING. ERICK ALBERTO ALVAREZ ZAMORANO ING. JOSE LUIS MONTAÑO OCHOA

ENCARGADO DE LA SUPERINTENDENCIA DE OPERACION

C

A

L

L

E

C

IP

R

E

S

A

V

. Z

A

L

A

T

IT

A

N

JU

A

N

G

IL

P

R

E

C

IA

D

O

CALLE L

OM

A B

ON

ITA

PUNTO DE

DESCARGA

PUNTO DE

INICIO

PRO

L. G

IGAN

TES

AV. CO

NSTITU

CIO

N

"BOCA DE TORMENTA TIPO"

PROYECTO:

ING. PABLO GUTIERREZ RANGEL

José Beltran No. 1436

Col. Residencial la Soledad

Tlaquepaque, Jalisco.

Tel: (33) 1933.5852

Cel: 044 (33) 1172.3811

[email protected]

No. DE CONTRATO:

(2DO TRAMO)

PROYECTO DEL COLECTOR PLUVIAL LOMA

BONITA, EN EL MUNICIPIO DE TONALA, JAL