Curvas de disparoCompact NSX100 a 250. Proteccin de los sistemas de distribucinCaractersticas tcnicas
Unidades de control termomagnticas TMTM16D / TM16G TM25D / TM25G
10 000 5 000 2 000 1 000 500 200 100 50 20 10 5t(s)
10 000 5 000 2 000 1 000 500 200 100 50 20 10 5t(s)
2 1 .5 .2 .1 .05 .02 .01 .005
TM16D : Im = 12 x In
2 1 .5 .2 .1 .05 .02 .01 .005 TM25G : Im = 3.2 x In
TM25D : Im = 12 x In
TM16G : Im = 4 x In
t < 10 ms
t < 10 ms
5
.002 .001 .5 .7 1
2 3 4 5 7 10I / Ir
20 30 50 70 100
200 300
.002 .001 .5 .7 1
2 3 4 5 7 10I / Ir
20 30 50 70 100
200 300
Disparo reejo.
TM32D / TM40D / TM40G
TM50D / TM63D / TM63G
10 000 5 000 2 000 1 000 500 200 100 50 20 10 5t(s)
10 000 5 000 2 000 1 000 500 200 100 50 20 10 5t(s)
2 1 .5 .2 .1 .05 .02 .01 .005 .002 .001 .5 .7 1 2 3 4 5 7 10I / Ir
TM40D : Im = 12 x In TM32D : Im = 12.5 x In
2 1 .5 .2 .1 .05 .02 .01 .005 TM63G : Im = 2 x In
TM63D : Im = 8 x In TM50D : Im = 10 x In
TM40G : Im = 2 x In
t < 10 ms
t < 10 ms
20 30 50 70 100
200 300
.002 .001 .5 .7 1
2 3 4 5 7 10I / Ir
20 30 50 70 100
200 300
Disparo reejo.
5/2
Curvas de disparoCompact N SX100 a 250. Proteccin de los sistemas de distribucin (continuacin)Caractersticas tcnicas
Unidades de control termomagnticas TM (continuacin)TM80D / TM100D TM125D / TM160D
10 000 5 000 2 000 1 000 500 200 100 50 20 10 5t(s)
10 000 5 000 2 000 1 000 500 200 100 50 20 10 5t(s)
TM125D : Im = 10 x In TM160D : Im = 8 x In
2 1 .5 .2 .1 .05 .02 .01 .005 .002 .001 .5 .7 1Disparo reejo.
TM80D/TM100D : Im = 8 x In
2 1 .5 .2 .1 .05 .02 .01 .005
t < 10 ms
t < 10 ms
2 3 4 5 7 10I / Ir
20 30 50 70 100
200 300
.002 .001 .5 .7 1
2 3 4 5 7 10I / Ir
20 30 50 70 100
200 300
5
TM200D / TM250D
10 000 5 000 2 000 1 000 500 200 100 50 20 10 5 2 1 .5 .2 .1 .05 .02 .01 .005 .002 .001.5 .7 1 2 3 4 5 7 10 I / Ir 20 30 50 70 100 200 300
t(s)
TM200D/TM250D : Im = 5 ... 10 x In
t < 10 ms
Disparo reejo.
5/3
Curvas de disparoCompact N SX100 a 250. Proteccin de los sistemas de distribucin (continuacin)Caractersticas tcnicas
Unidades de control electrnicas Micrologic 2.2 y 2.2 GMicrologic 2.2 - 40... 160 A Micrologic 2.2 - 250 A
10 000 5 000 2 000 1 000 500 200 100 50 20 10 5t(s)
40 A : Ir = 16 ...40 A 100 A : Ir = 36 ...100 A 160 A : Ir = 57 ...160 A
10 000 5 000 2 000 1 000 500 200 100 50 20 10 5t(s)
250 A : Ir = 90 ...250 A
2 1 .5 .2 .1 .05 .02 .01 .005
Isd = 1.5 ...10 x Ir
2 1 .5 .2 .1 .05
Isd = 1.5 ...10 x Ir
t < 10 ms Ii = 15 x In 20 30 50 70 100
.02 .01 .005 200 300 .002 .001 .5 .7 1 2 3 4 5 7 10I / Ir
t < 10 ms Ii = 12 x In 20 30 50 70 100
5
.002 .001 .5 .7 1Disparo reejo.
2 3 4 5 7 10I / Ir
200 300
Micrologic 2.2 G - 40... 160 A
Micrologic 2.2 G - 250 A
10 000 5 000 2 000 1 000 500 200 100 50 20 10 5t(s)
40 A : Ir = 16 ...40 A 100 A : Ir = 36 ...100 A 160 A : Ir = 57 ...160 A
10 000 5 000 2 000 1 000 500 200 100 50 20 10 5t(s)
250 A : Ir = 90 ...250 A
2 1 .5 .2 .1 .05 .02 .01 .005 .002 .001 .5 .7 1
Isd = 1.5 ...9 x Ir
2 1 .5 .2 .1 .05
Isd = 1.5 ...9 x Ir
t < 10 ms Ii = 15 x In 20 30 50 70 100
.02 .01 .005200 300
t < 10 ms Ii = 12 x In 20 30 50 70 100
2 3 4 5 7 10I / Ir
.002 .001 .5 .7 1
2 3 4 5 7 10I / Ir
200 300
Disparo reejo.
5/4
Curvas de disparoCompact N SX100 a 250. Proteccin de los sistemas de distribucin (continuacin)Caractersticas tcnicas
Unidades de control electrnicas Micrologic 5.2 y 6.2 A o EMicrologic 5.2 y 6.2 A o E - 40... 160 A Micrologic 5.2 y 6.2 A o E - 250 A
10 000 5 000
2 000 1 000 500
40 A : Ir = 16 ...40 A 100 A : Ir = 36 ...100 A 160 A : Ir = 56 ...160 A
10 000 5 000
250 A : Ir = 90 ...250 A
2 000 1 000 500
200 100 50 20 10 5 t(s) 2 1 .5
200
tr = 0.5 ...16 s
100 50 20 10
tr = 0.5 ...16 s
Isd = 1.5 ...10 x Ir It ON0.4 0.3
5 t(s) 2 1 .5
Isd = 1.5 ...10 x Ir It ON It OFF 0.4 0.3 0.2 0.1 0 t < 10 ms Ii = 1.5 ...12 In.7 1 2 I / Ir 3 4 5 7 10 20 5 7 10 20 I / In 30 50
.2 .1 .05
It OFF
0.2 0.1
.2 .1 .05
0 t < 10 ms Ii = 1.5 ...15 In.7 1 2 I / Ir 3 4 5 7 10 20 5 7 10 20 I / In 30 50
.02 .01 .005
.02 .01 .005
.002 .001 .5
.002 .001 .5
5
Disparo reejo.
Micrologic 6.2 A o E (proteccin de defecto a tierra)
10 000 5 000 2 000 1 000 500 200 100 50 20 10 5t(s)
40 A : Ig = 0.4 ...1 x In > 40 A : Ig = 0.2 ...1 x In
2 1 .5 .2 .1 .05 .02 .01 .005 .002 .001 .05 .07 .1
It ON 0.4 0.3 0.2 0.1 0
It OFF
.2 .3 .4 .5 .7 1I / In
2
3
4
5 7 10
20 30
La curva de disparo es idntica a la de Micrologic 5. La proteccin de defecto a tierra se muestra por separado.
5/5
Curvas de disparoCompact NSX100 a 250. Proteccin de motoresCaractersticas tcnicas
Unidades de control magnticas MAMA2.5... MA100 MA150 y MA220
10 000 5 000 2 000 1 000 500 200 100 50 20 10 5t(s)
10 000 5 000 2 000 1 000 500 Resistencia trmica 200 100 50 20 10 5t(s)
Resistencia trmica MA220 MA150
2 1 .5 .2 .1 .05 .02 .01 .005
Im = 6 ... 14 x In
2 1 .5 .2 .1 .05
Im = 9 ... 14 x In
t < 10 ms
.02 .01 .005 200 300 .002 .001 .5 .7 1 2 3 4 5 7 10I / Ir
t < 10 ms
5
.002 .001 .5 .7 1
2 3 4 5 7 10I / Ir
20 30 50 70 100
20 30 50 70 100
200 300
Disparo reejo.
Unidades de control electrnicas Micrologic 2.2-MMicrologic 2.2 M - 25 A Micrologic 2.2 M - 50... 220 A
10 000 5 000
25 A : Ir = 12 ...25 A clase 20 clase 10 clase 5
10 000 5 000 2 000 1 000 500 200 100 50 20 10 5t(s)
2 000 1 000 500
50 A : Ir = 25 ...50 A 100 A : Ir = 50 ...100 A 150 A : Ir = 70 ...150 A 220 A : Ir = 100 ...220 A clase 20 clase 10 clase 5
200 100 50 20 10 5 t(s) 2 1 .5
Isd = 5 ...13 x Ir
2 1 .5 .2 .1 .05
Isd = 5 ...13 x Ir
.2 .1 .05
.02 .01 .005
t < 10 msIi = 17 x In
.02 .01 .005 .002 .001 .5 .7 1 2 3 4 5 7 10I / Ir
t < 10 ms Ii = 15 x In 20 30 50 70 100
.002 .001 .5 .7 1 2 3 4 5 7 10 I / Ir 20 30
50 70 100
200 300
200 300
Disparo reejo.
5/6
Curvas de disparoCompact NSX100 a 250. Proteccin de motores (continuacin)Caractersticas tcnicas
Unidades de control electrnicas Micrologic 6.2 E-M y 6 E-MMicrologic 6.2 E-M - 25 A Micrologic 6.2 E-M - 50... 220 A
10 000 5 000 2 000 1 000 500 200 100 50 20 10 5t(s)
25 A : Ir = 12 ...25 A clase 30 clase 20 clase 10 clase 5
10 000 5 000 2 000 1 000 500 200 100 50 20 10 5t(s)
50 A : Ir = 25 ...50 A 80 A : Ir = 35 ...80 A 150 A : Ir = 70 ...150 A 220 A : Ir = 100 ...220 A clase 30 clase 20 clase 10 clase 5
2 1 .5 .2 .1 .05 .02 .01 .005 .002 .001 .5 .7 1 2 3 4 5 7 10I / Ir
Isd = 5 ...13 x Ir
2 1 .5 .2 .1 .05
Isd = 5 ...13 x Ir
t < 10 ms Ii = 17 x In 20 30 50 70 100
.02 .01 .005 200 300 .002 .001 .5 .7 1 2 3 4 5 7 10I / Ir
t < 10 ms Ii = 15 x In 20 30 50 70 100
200 300
5
Disparo reejo.
Micrologic 6 E-M (proteccin de defecto a tierra)
10 000 5 000 2 000 1 000 500 200 100 50 20 10 5t(s)
25 A : Ig = 0.6 ...1 x In 50 A : Ig = 0.3 ...1 x In > 50 A : Ig = 0.2 ...1 x In
2 1 .5 .2 .1 .05 .02 .01 .005 .002 .001 .05 .07 .1
0.4 0.3 0.2 0.1 0
0.4 0.3 0.2 0.1 0
.2 .3 .4 .5 .7 1I / In
2
3
4
5 7 10
20 30
La curva de control es idntica a la de Micrologic 6. La proteccin de defecto a tierra se muestra por separado.
5/7
Curvas de disparoCompact NSX400 a 630. Proteccin de los sistemas de distribucinCaractersticas tcnicas
Unidades de control electrnicas Micrologic 2.3, 5.3 y 6.3 A o EMicrologic 2.3 - 250... 400 A Micrologic 2.3 - 630 A
10 000 5 000 2 000 1 000 500 200 100 50 20 10 5t(s)
250 A : Ir = 63 ...250 A 400 A : Ir = 144 ...400 A
10 000 5 000 2 000 1 000 500 200 100 50 20 10 5t(s)
630 A : Ir = 225 ...630 A
2 1 .5 .2 .1 .05 .02 .01 .005
Isd = 1.5 ...10 x Ir
2 1 .5 .2 .1 .05
Isd = 1.5 ...10 x Ir
t < 10 ms Ii = 12 x In 20 30 50 70 100
.02 .01 .005 200 300 .002 .001.5 .7 1 2 3 4 5 7 10 I / Ir 20
t < 10 ms Ii = 11 x In30 50 70 100 200 300
5
.002 .001 .5 .7 1
2 3 4 5 7 10I / Ir
Disparo reejo.
Micrologic 5.3 y 6.3 A o E - 400 A
Micrologic 5.3 y 6.3 A o E - 630 A
10 000 5 000
10 000
400 A : Ir = 100 ...400 A
5 000
630 A : Ir = 225 ...630 A
2 000 1 000 500
2 000 1 000 500
200 100 50 20 10 5 t(s) 2 1 .5
200
tr = 0.5 ...16 s
100 50 20 10
tr = 0.5 ...16 s
Isd = 1.5 ...10 x Ir It ON It OFF 0.4 0.3 0.2 0.1 0 t < 10 ms Ii = 1.5 ...12 In.7 1 2 I / Ir 3 4 5 7 10 20 5 7 10 20 I / In 30 50
5 t(s) 2 1 .5
Isd = 1.5 ...10 x Ir It ON It OFF 0.4 0.3 0.2 0.1 0 t < 10 ms Ii = 1.5 ...11 In.7 1 2 I / Ir 3 4 5 7 10 20 5 7 10 20 I / In 30 50
.2 .1 .05
.2 .1 .05
.02 .01 .005
.02 .01 .005
.002 .001 .5
.002 .001 .5
Disparo reejo.
5/8
Curvas de disparoCompact N SX400 a 630. Proteccin de los sistemas de distribucin (continuacin)Caractersticas tcnicas
Unidades de control electrnicas Micrologic 6.3 A o E (continuacin)Micrologic 6,3 A o E (proteccin de defecto a tierra)
10 000 5 000 2 000 1 000 500 200 100 50 20 10 5t(s)
40 A : Ig = 0.4 ...1 x In > 40 A : Ig = 0.2 ...1 x In
2 1 .5 .2 .1 .05 .02 .01 .005 .002 .001 .05 .07 .1
It ON 0.4 0.3 0.2 0.1 0
It OFF
.2 .3 .4 .5 .7 1I / In
2
3
4
5 7 10
20 30
5
La curva de disparo es idntica a la de Micrologic 6. La proteccin de defecto a tierra se muestra por separado.
5/9
Curvas de disparoCompact NSX400 a 630. Proteccin de motoresCaractersticas tcnicas
Unidades de control electrnicas Micrologic 1.3 M y 2.3 MMicrologic 1.3 M - 320 A Micrologic 1.3 M - 500 A
10 000 5 000
10 000 5 000 2 000 1 000 500
2 000 1 000 500
200 100 50 20 10 5 t(s) 2 1 .5t(s)
Resistencia trmica
200 100 50 20 10 5 2 1 .5 .2 .1 .05 .02 .01 .005 .002 .001 .5 .7 1
Resistencia trmica
.2 .1 .05
Isd = 5 ...13 x In
Isd = 5 ...13 x In
.02 .01 .005
t < 10 msIi = 15 x In
t < 10 ms Ii = 13 x In 20 30 50 70 100
5
.002 .001 .5 .7 1 2 3 4 5 7 10 I / In 20 30
50 70 100
200 300
2 3 4 5 7 10I / In
200 300
Disparo reejo.
Micrologic 2.3 M - 320 A
Micrologic 2.3 M - 500 A
10 000 5 000 2 000 1 000 500 200 100 50 20 10 5t(s)
320 A : Ir = 160 ...320 A clase 20 clase 10 clase 5
10 000 5 000 2 000 1 000 500 200 100 50 20 10 5t(s)
500 A : Ir = 250 ...500 A clase 20 clase 10 clase 5
2 1 .5 .2 .1 .05 .02 .01 .005 .002 .001 .5 .7 1Disparo reejo.
Isd = 5 ...13 x Ir
2 1 .5 .2 .1 .05
Isd = 5 ...13 x Ir
t < 10 msIi = 15 x In
.02 .01 .005 200 300 .002 .001 .5 .7 1 2 3 4 5 7 10I / Ir
t < 10 ms Ii = 13 x In 20 30 50 70 100
2 3 4 5 7 10I / Ir
20 30 50 70 100
200 300
5/10
Curvas de disparoCompact NSX400 a 630. Proteccin de motores (continuacin)Caractersticas tcnicas
Unidades de control electrnicas Micrologic 6.3 E-M y 6 E-MMicrologic 6.3 E-M - 320 A Micrologic 6.3 E-M - 500 A
10 000 5 000 2 000 1 000 500 200 100 50 20 10 5t(s)
320 A : Ir = 160 ...320 A clase 30 clase 20 clase 10 clase 5
10 000 5 000 2 000 1 000 500 200 100 50 20 10 5t(s)
500 A : Ir = 250 ...500 A clase 30 clase 20 clase 10 clase 5
2 1 .5 .2 .1 .05 .02 .01 .005 .002 .001 .5 .7 1 2 3 4 5 7 10I / Ir
Isd = 5 ...13 x Ir
2 1 .5 .2 .1 .05
Isd = 5 ...13 x Ir
t < 10 ms Ii = 15 x In 20 30 50 70 100
.02 .01 .005200 300
t < 10 ms Ii = 13 x In 20 30 50 70 100
.002 .001 .5 .7 1
2 3 4 5 7 10I / Ir
200 300
5
Disparo reejo.
Micrologic 6 E-M (proteccin de motor)
10 000 5 000
2 000Ig = 0.2 ...1 x In
1 000 500
200 100 50 20 10 5 t(s) 2 1 .50.4 0.3 0.2 0.1 0.4 0.3 0.2 0.1
.2 .1 .05
0
0
.02 .01 .005
.002 .001 .05 .07 .1 .2 .3 .4 .5 .7 1 I / In 2 3
4
5
7
10
20
30
La curva de disparo es idntica a la de Micrologic 6. La proteccin de defecto a tierra se muestra por separado.
5/11
Curvas de disparoCompact NSX100 a 630. Disparo re ejoCaractersticas tcnicas
Los Interruptores automticos Compact NSX100 a 630 estn equipados con el sistema exclusivo de disparo reflejo. El sistema interrumpe intensidades de defecto muy elevadas. El aparato se dispara mecnicamente a travs de un "pistn" que se acciona directamente mediante la presin que produce el cortocircuito en las unidades de corte. Para cortocircuitos elevados, este sistema ofrece una interrupcin ms rpida, por lo que se garantiza la selectividad. Las curvas de disparo reflejo slo estn en funcin del calibre del interruptor automtico.
20 NSX630
10
NSX400
t (ms)
8 7 6 5 4 3 2 3 4 6 10 20 NSX250
NSX100 NSX160 30 40 60 100 200
kA rms
5
5/12
Curvas de limitacin de energa e intensidadCaractersticas tcnicas
La capacidad de limitacin de un interruptor automtico es la capacidad para permitir el acceso de una intensidad durante un cortocircuito, que sea inferior a la intensidad prevista del cortocircuito.
Icc = 100% IcuLa extraordinaria capacidad de limitacin de la gama NSX reduce en gran medida las fuerzas que crean las intensidades de defecto en los aparatos. Esto se traduce en un importante aumento de las prestaciones de la interrupcin. En particular, la capacidad de corte en servicio Icc es igual al 100% de Icu. El valor de Icc, denido por la norma IEC 60947-2, se garantiza mediante ensayos que incluyen los siguientes pasos: interrupcin tres veces consecutivas de una intensidad de defecto igual al 100% de Icu comprobacin de que el aparato sigue funcionando de forma normal, es decir: conduce la intensidad nominal sin un aumento anmalo de la temperatura las funciones de proteccin se realizan dentro de los lmites especicados por la norma la idoneidad para la aislacin no se ve afectada.
(Icc)
Icc cresta prevista Intensidad prevista Icc prevista Icc cresta limitada Intensidad real (t)
Durabilidad de las instalaciones elctricasLos interruptores automticos de limitacin de intensidad reducen en gran medida los efectos negativos de los cortocircuitos en las instalaciones. Efectos trmicos Se produce un aumento menor de la temperatura en los conductores, por lo que se prolonga la vida til de los cables. Efectos mecnicos Se producen menos fuerzas electrodinmicas, por lo que existe menos riesgo de que los contactos elctricos o los juegos de barras se deformen o se destruyan. Efectos electromagnticos Menos perturbaciones en los aparatos de control y medicin situados junto a los circuitos elctricos.
Icc limitada
La extraordinaria capacidad de limitacin de la gama Compact NSX se consigue gracias a la tcnica de doble interrupcin giratoria (repulsin natural muy rpida de los contactos y la aparicin de dos tensiones de arco en serie con una curva frontal muy pronunciada).
5
Economa gracias a la filiacinLa liacin es una tcnica que se deriva directamente de la limitacin de intensidades. Los interruptores automticos con capacidades de interrupcin inferiores a las de la intensidad de cortocircuito prevista se pueden instalar aguas abajo de un limitador. La capacidad de interrupcin se refuerza por la capacidad de limitacin del aparato aguas arriba. Por consiguiente, se pueden obtener importantes ahorros en los equipos y tableros aguas abajo.
5/13
Curvas de limitacin de energa e intensidad(continuacin) Caractersticas tcnicas
Curvas de limitacin de energa e intensidadLa capacidad de limitacin de un interruptor automtico se expresa mediante dos curvas que estn en funcin de la intensidad de cortocircuito prevista (la intensidad que uira si no se instalaran aparatos de proteccin): la intensidad mxima real (intensidad limitada) esfuerzo trmico (A2s), es decir, la energa disipada por el cortocircuito en un conductor con una resistencia de 1 . Ejemplo Cul es el valor real de un cortocircuito previsto de 150 kA rms (es decir, de 330 kA de pico) limitado por un NSX250L aguas arriba? La respuestas es 30 kA como mximo (curva pg. 5/15).
Esfuerzos mximos admisibles de los cablesLa siguiente tabla indica los esfuerzos trmicos mximos admisibles de los cables, en funcin de su aislacin, el conductor (Cu o Al) y su rea de seccin (CSA). Los valores de la seccin se expresan en mm y los esfuerzos trmicos en A2s.CSA PVC PRC CSA PVC Cu Al PRC Cu Al Cu Al Cu Al 16 mm 3,4 x 106 1,39 x 106 4,69 x 106 1,93 x 106 25 mm 8,26 x 106 3,38 x 106 1,39 x 107 4,70 x 106 35 mm 1,62 x 107 6,64 x 106 2,23 x 107 9,23 x 106 50 mm 3,31 x 107 1,35 x 107 4,56 x 107 1,88 x 107 4,10 x104 1,39 x105 2,92 x105 6,56 x 105 1,5 mm 2,97 x104 2,5 mm 8,26 x104 4 mm 2,12 x105 6 mm 4,76 x105 10 mm 1,32 x 106 5,41 x 105 1,82 x 106 7,52 x 105
5
Ejemplo Un cable de Cu/PVC con una seccin de 10 mm se encuentra protegido correctamente mediante un NSX160F? La tabla anterior indica que el esfuerzo admisible es de 1,32 x 106 A2s. Todas las intensidades de cortocircuito en el punto en el que se ha instalado el NSX160F (Icu = 35 kA) se limitan con un esfuerzo trmico inferior a 6 x 105 A2s (curva pg. 5/15). Por consiguiente, la proteccin del cable se garantiza hasta el lmite de la capacidad de interrupcin del interruptor automtico.
5/14
Curvas de limitacin de energa e intensidad(continuacin) Caractersticas tcnicas
Curvas de limitacin de intensidadTensin 400/440 Vca Intensidad de cortocircuito limitada (k mxima) Tensin 660/690 Vca Intensidad de cortocircuito limitada (k mxima)
300 200 146 100 80 70 60 50 40 30 20 10 8 7 6 5 4 2 F
300
200 146
100 80 70 60 50
k
N N
H H
S S
L NSX630NSX400
L NSX250NSX100 NSX160
k
40 30 H
L S
NSX630 NSX400
20
N
S
L
NSX250 NSX100 NSX160
10 8 7 6 5 F
N, H
3
4
6
10
kA rms
20
30 40 50 70 100
200 300
4 2 3 4 6 10 20 30 40 60 65 100 200 300
kA rms
5Curvas de limitacin de energaTensin 400/440 Vca Energa limitada Tensin 660/690 Vca Energa limitada109
10
9
5 3 2 1.41 108
5 3 2 1.41 108
5 3 27
5 3 27
10
10
A2s
5 N 3 26
H
S
L
NSX630 NSX400
A 2s
5 3 26
H
S
L
NSX630
NSX400
N S N, H FNSX100 NSX160
10
F
N
H
S
L
L
NSX250 NSX100 NSX160
10
NSX250
5 3 25
5 3 25
10
10
5 3 2
5 3
2
3
4
6
10
20
30 40 50 70 100 150200 300
2 2 3 4 6 10 20 30 40 50 70 100 150 200 300
kA rms