    Single-pole thermal-magnetic trip units

    Series C types EHD, FD, and HFD 15A

    (SC-4423-88A) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3Series C types EHD, FD, and HFD 20A(SC-4424-88A) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

    Series C types EHD, FD, and HFD 25A(SC-4425-88A) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

    Series C types EHD, FD, and HFD 30A(SC-4426-88A) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

    Series C types EHD, FD, and HFD 35A(SC-4427-88A) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

    Series C types EHD, FD, and HFD 40A(SC-4428-88A) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

    Series C types EHD, FD, and HFD 45A(SC-4429-88A) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

    Series C types EHD, FD, and HFD 50A

    (SC-4430-88A) . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

    Series C types EHD, FD, and HFD 60A(SC-4431-88A) . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

    Series C types EHD, FD, and HFD 70A(SC-4432-88A) . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

    Series C types EHD, FD, and HFD 80A

    (SC-4433-88A) . . . . . . . . . . . . . . . . . . . . . . . . . . Series C types EHD, FD, and HFD 90A(SC-4434-88A) . . . . . . . . . . . . . . . . . . . . . . . . . .

    Series C types EHD, FD, and HFD 100A(SC-4435-88A) . . . . . . . . . . . . . . . . . . . . . . . . . .

    Series C types FD and HFD 110A(SC-4436-88A) . . . . . . . . . . . . . . . . . . . . . . . . . .

    Series C types FD and HFD 125A(SC-4437-88A) . . . . . . . . . . . . . . . . . . . . . . . . . .

    Series C types FD and HFD 150A(SC-4438-88A) . . . . . . . . . . . . . . . . . . . . . . . . . .

    Effective May 2009

    Supersedes June 2006Trip Curves TC01200002E

    Series C F-frame circuit breaker

    time current curvesote:N Time/current characteristic curves for Series C

    F-frame circuit breakersvoltages shown in curveheadings are maximum at which the breaker may beapplied. Interrupting capacity of individual breaker istabulated on each curve.

    Contents

    Description Page Description Pa

  • 7/26/2019 Curvas de Disparo Disyuntores

    2/562

    Trip Curves TC01200002EEffective May 2009

    Series C F-frame circuit breakertime current curves

    EATON CORPORATIONwww.eaton.com

    Two-, three-, and four-pole thermal-magnetic trip units

    Series C types ED, EHD, FDB, FD, and HFD15A (SC-4134-87B) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19

    Series C types ED, EHD, FDB, FD, and HFD20A (SC-4135-87B) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20

    Series C types ED, EHD, FDB, FD, and HFD25A (SC-4136-87B) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21

    Series C types ED, EHD, FDB, FD, and HFD30A (SC-4137-87B) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22

    Series C types ED, EHD, FDB, FD, and HFD35A (SC-4138-87B) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23

    Series C types ED, EHD, FDB, FD, and HFD40A (SC-4139-87B) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24

    Series C types ED, EHD, FDB, FD, and HFD45A (SC-4140-87B) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25

    Series C types ED, EHD, FDB, FD, and HFD50A (SC-4141-87B) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26

    Series C types ED, EHD, FDB, FD, and HFD60A (SC-4142-87B) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27

    Series C types ED, EHD, FDB, FD, and HFD70A (SC-4143-87B) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28

    Series C types ED, EHD, FDB, FD, and HFD80A (SC-4144-87B) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29

    Series C types ED, EHD, FDB, FD, and HFD90A (SC-4145-87B) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30

    Series C types ED, EDB, EDS, EDH, EDC, EHD,FDB, FD, and HFD 100A (SC-4146-87B) . . . . . . . . . . . . . . . . . . . . .31

    Series C types ED, EDB, EDS, EDH, EDC, FDB,FD, and HFD 110A (SC-4147-87B) . . . . . . . . . . . . . . . . . . . . . . . . .32

    Series C types ED, EDB, EDS, EDH, EDC, FDB,FD, and HFD 125A (SC-4148-87B) . . . . . . . . . . . . . . . . . . . . . . . . .33

    Series C types ED, EDB, EDS, EDH, EDC, FDB, FD,and HFD 150A (SC-4149-87B) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34

    Series C types FD and HFD 175225A(SC-6970-98) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .35

    Series C types ED, EDH, EDC, EDB, and EDS175225A (SC-5805-94A) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36

    Series C type FDC 15A (SC-5516-93A) . . . . . . . . . . . . . . . . . . . . . .37

    Series C type FDC 20A (SC-5517-93A) . . . . . . . . . . . . . . . . . . . . . .38

    Series C type FDC 25A (SC-5518-93A) . . . . . . . . . . . . . . . . . . . . . .39

    Series C type FDC 30A (SC-5519-93A) . . . . . . . . . . . . . . . . . . . . . .40Series C type FDC 35A (SC-5520-93A) . . . . . . . . . . . . . . . . . . . . . .41

    Series C type FDC 40A (SC-5521-93A) . . . . . . . . . . . . . . . . . . . . . .42

    Series C type FDC 45A (SC-5522-93A) . . . . . . . . . . . . . . . . . . . . . .43

    Series C type FDC 50A (SC-5523-93A) . . . . . . . . . . . . . . . . . . . . . .44

    Series C type FDC 60A (SC-5524-93A) . . . . . . . . . . . . . . . . . . . . . .45

    Series C type FDC 70A (SC-5525-93A) . . . . . . . . . . . . . . . . . . . . . .46

    Series C type FDC 80A (SC-5526-93A) . . . . . . . . . . . . . . . . . . . . . .47

    Series C type FDC 90A (SC-5527-93A) . . . . . . . . . . . . . . . . . . . . . .48

    Series C type FDC 100A (SC-5528-93A) . . . . . . . . . . . . . . . . . . . . .49

    Series C type FDC 110A (SC-5529-93A) . . . . . . . . . . . . . . . . . . . . .50

    Series C type FDC 125A (SC-5530-93A) . . . . . . . . . . . . . . . . . . . . .51

    Series C type FDC 150A (SC-5531-93A) . . . . . . . . . . . . . . . . . . . . .52

    Series C type FDC 175225A (SC-6971-98) . . . . . . . . . . . . . . . . . .53

    Three-pole electronic trip units

    Series C type FDE, HFDE, and FDCE 225A,long/short delay (TC01203015E) . . . . . . . . . . . . . . . . . . . . . . . . . . . 54

    Series C type FDE, HFDE, and FDCE 225A,

    Long/short delay and I2t (TC01203016E) . . . . . . . . . . . . . . . . . . . . .55

    Series C type FDE, HFDE, and FDCE 225A,LSIG (TC01203017E) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .56

    Contents (continued)

    Description Page Description Page

  • 7/26/2019 Curvas de Disparo Disyuntores

    3/56

    Trip Curves TC0120000Effective May 2

    Series C F-frame circuit breakertime current curves

    EATON CORPORATIONwww.eaton.com

    Single-pole thermal-magnetic trip units

    AB DE-IONcircuit breakers

    Figure 1. Types EHD, FD, and HFD 15ACurve No. SC-4423-88A

    Minimum Maximum

    Interruptingratingdeterminesend of curve

    100

    50

    30

    20

    10

    5

    3

    2

    1

    .5

    .3

    .2

    .1

    .05

    .03

    .02

    .01

    .005

    .003

    .002

    .001

    TIMEIN

    SECO

    NDS

    1,000

    500

    300

    200

    5,000

    3,000

    2,000

    1HOUR

    1MINUTE

    2HO

    URS

    10000

    8000

    6000

    9000

    7000

    5000

    4000

    3000

    2000

    1000

    800

    600

    900

    700

    500

    400

    300

    200

    100

    8060 907050403020109875 6

    TIMEINSECONDS

    10,000

    100

    50

    30

    20

    10

    5

    3

    2

    1

    .5

    .3

    .2

    .1

    .05

    .03

    .02

    .01

    .005

    .003

    .002

    .001

    1,000

    500

    300

    200

    5,000

    3,000

    2,000

    1HOUR

    1MINUTE

    2HO

    URS

    CURRENT IN AMPERES

    10000

    8000

    6000

    9000

    7000

    5000

    4000

    3000

    2000

    1000

    800

    600

    900

    700

    500

    400

    300

    200

    100

    8060 907050403020109875 6

    15A

    Maximum single-pole trip timesat 25C 1

    CURRENT IN AMPERES

    Maximum interrupting time

    Circuit breaker time/current curves

    Series C

    F-frame circuit breakersCatalog types EHD, FD and HFD circuit breakers, single-pole.

    For application and coordination purposes only.Based on 40C ambient, cold start. Connected with four (4) feet ofrated wire (60C up to 100A, 75C above 125A) per terminal.Tested in open air.

    Maximum Vac: 277 at 50/60 HzMaximum Vdc: 125

    Breaker rating

    Continuous

    Instantaneous trip, amperesamperes

    15A See curve

    Breakertype

    Symmetrical RMS amperes (kA)

    143565

    EHDFDHFD

    101010

    Single-pole test data at 25C based on NEMAprocedures(AB 4-2003) for verifying performance of molded casecircuit breakers.

    277V

    DC amps

    125V

    Interrupting rating (UL/CSA listed)

  • 7/26/2019 Curvas de Disparo Disyuntores

    4/564

    Trip Curves TC01200002EEffective May 2009

    Series C F-frame circuit breakertime current curves

    EATON CORPORATIONwww.eaton.com

    Figure 2. Types EHD, FD, and HFD 20ACurve No. SC-4424-88A

    Minimum Maximum

    Interruptingratingdeterminesend of curve

    Maximuminterruptingtime

    100

    50

    30

    20

    10

    5

    3

    2

    1

    .5

    .3

    .2

    .1

    .05

    .03

    .02

    .01

    .005

    .003

    .002

    .001

    TIMEINSECONDS

    1,000

    500

    300

    200

    5,000

    3,000

    2,000

    1HOU

    R

    1MIN

    UTE

    2HOURS

    10000

    8000

    6000

    9000

    7000

    5000

    4000

    3000

    2000

    1000

    800

    600

    900

    700

    500

    400

    300

    200

    100

    8060 907050403020109875 6

    TIMEIN

    SECONDS

    10,000

    100

    50

    30

    20

    10

    5

    3

    2

    1

    .5

    .3

    .2

    .1

    .05

    .03

    .02

    .01

    .005

    .003

    .002

    .001

    1,000

    500

    300

    200

    5,000

    3,000

    2,000

    1

    HOUR

    1M

    INUTE

    2HOURS

    CURRENT IN AMPERES

    10000

    8000

    6000

    9000

    7000

    5000

    4000

    3000

    2000

    1000

    800

    600

    900

    700

    500

    400

    300

    200

    100

    8060 907050403020109875 6

    20A

    Maximum single-pole trip timesat 25C 1

    CURRENT IN AMPERES

    Circuit breaker time/current curves

    Series CF-frame circuit breakers

    Catalog types EHD, FD and HFD circuit breakers, single-pole.

    For application and coordination purposes only.Based on 40C ambient, cold start. Connected with four (4) feet ofrated wire (60C up to 100A, 75C above 125A) per terminal.

    Tested in open air.

    Maximum Vac: 277 at 50/60 HzMaximum Vdc: 125

    Breaker rating

    ContinuousInstantaneous t rip, amperesamperes

    20A See curve

    Breakertype

    Symmetrical Rms amperes (kA )

    143565

    EHDFDHFD

    101010

    Single-pole test data at 25C based on NEMA procedures(AB 4-2003) for verifying performance of molded casecircuit breakers.

    277V

    DC amps

    125V

    Interrupting rating (UL/CSA listed)

  • 7/26/2019 Curvas de Disparo Disyuntores

    5/56

    Trip Curves TC0120000Effective May 2

    Series C F-frame circuit breakertime current curves

    EATON CORPORATIONwww.eaton.com

    Figure 3. Types EHD, FD, and HFD 25ACurve No. SC-4425-88A

    Interruptingratingdeterminesend of curve

    Minimum Maximum

    100

    50

    30

    20

    10

    5

    3

    2

    1

    .5

    .3

    .2

    .1

    .05

    .03

    .02

    .01

    .005

    .003

    .002

    .001

    TIMEIN

    SECONDS

    1,000

    500

    300

    200

    5,000

    3,000

    2,000

    1HOU

    R

    1MIN

    UTE

    2HOURS

    10000

    8000

    6000

    9000

    7000

    5000

    4000

    3000

    2000

    1000

    800

    600

    900

    700

    500

    400

    300

    200

    100

    8060 907050403020109875 6

    TIMEINSECONDS

    10,000

    100

    50

    30

    20

    10

    5

    3

    2

    1

    .5

    .3

    .2

    .1

    .05

    .03

    .02

    .01

    .005

    .003

    .002

    .001

    1,000

    500

    300

    200

    5,000

    3,000

    2,000

    1

    HOUR

    1M

    INUTE

    2HOURS

    CURRENT IN AMPERES

    10000

    8000

    6000

    9000

    7000

    5000

    4000

    3000

    2000

    1000

    800

    600

    900

    700

    500

    400

    300

    200

    100

    8060 907050403020109875 6

    25A

    Maximum single-pole t rip ti mesat 25C 1

    CURRENT IN AMPERES

    Maximum interrupting time

    Circuit breaker time/current curves

    Series CF-frame circuit breakers

    Catalog types EHD, FD and HFD circuit breakers, single-pole.

    For application and coordination purposes only.Based on 40C ambient, cold start. Connected with four (4) feet ofrated wire (60C up to 100A, 75C above 125A) per terminal.

    Tested in open air.

    Maximum Vac: 277 at 50/60 HzMaximum Vdc: 125

    Breaker rating

    ContinuousInstantaneous trip, amperesamperes

    25A See curve

    Breakertype

    Symmetrical Rms amperes (kA )

    143565

    EHDFDHFD

    101010

    Single-pole test data at 25C based on NEMA procedures(AB 4-2003) for verifying performance of molded casecircuit breakers.

    277V

    DC amps

    125V

    Interrupting rating (UL/CSA listed)

  • 7/26/2019 Curvas de Disparo Disyuntores

    6/566

    Trip Curves TC01200002EEffective May 2009

    Series C F-frame circuit breakertime current curves

    EATON CORPORATIONwww.eaton.com

    Figure 4. Types EHD, FD, and HFD 30ACurve No. SC-4426-88A

    Interruptingratingdeterminesend of curve

    Minimum Maximum

    100

    50

    30

    20

    10

    5

    3

    2

    1

    .5

    .3

    .2

    .1

    .05

    .03

    .02

    .01

    .005

    .003

    .002

    .001

    TIMEINSECONDS

    1,000

    500

    300

    200

    5,000

    3,000

    2,000

    1HOUR

    1MIN

    UTE

    2HOURS

    10000

    8000

    6000

    9000

    7000

    5000

    4000

    3000

    2000

    1000

    800

    600

    900

    700

    500

    400

    300

    200

    100

    8060 907050403020109875 6

    TIMEINSECONDS

    10,000

    100

    50

    30

    20

    10

    5

    3

    2

    1

    .5

    .3

    .2

    .1

    .05

    .03

    .02

    .01

    .005

    .003

    .002

    .001

    1,000

    500

    300

    200

    5,000

    3,000

    2,000

    1

    HOUR

    1M

    INUTE

    2HOURS

    CURRENT IN AMPERES

    10000

    8000

    6000

    9000

    7000

    5000

    4000

    3000

    2000

    1000

    800

    600

    900

    700

    500

    400

    300

    200

    100

    8060 907050403020109875 6

    30A

    Maximum single-pole trip timesat 25C 1

    CURRENT IN AMPERES

    Maximum interrupting time

    Circuit breaker time/current curves

    Series CF-trame circuit breakers

    Catalog types EHD, FD and HFD circuit breakers, single-pole

    For application and coordination purposes only.Based on 40C ambient, cold start. Connected with four (4) feet ofrated wire (60C up to 100A, 75C above 125A) per terminal.

    Tested in open air.

    Maximum Vac: 277 at 50/60 HzMaximum Vdc: 125

    Breaker rating

    Continuous Instantaneous trip, amperesamperes

    30A See Curve

    Breakertype

    Symmetrical Rms amperes (kA )

    143565

    EHDFDHFD

    101010

    Single-pole test data at 25C based on NEMA procedures(AB 4-2003) for verifying performance of molded case circuitbreakers.

    277V

    DC amps

    125V

    Interrupting rating (UL/CSA listed)

  • 7/26/2019 Curvas de Disparo Disyuntores

    7/56

    Trip Curves TC0120000Effective May 2

    Series C F-frame circuit breakertime current curves

    EATON CORPORATIONwww.eaton.com

    Figure 5. Types EHD, FD, and HFD 35ACurve No. SC-4427-88A

    Interruptingratingdeterminesend of curve

    Maximuminterruptingtime

    Minimum Maximum

    100

    50

    30

    20

    10

    5

    3

    2

    1

    .5

    .3

    .2

    .1

    .05

    .03

    .02

    .01

    .005

    .003

    .002

    .001

    TIMEINSECONDS

    1,000

    500

    300

    200

    5,000

    3,000

    2,000

    1HO

    UR

    1MIN

    UTE

    2HOURS

    10000

    8000

    6000

    9000

    7000

    5000

    4000

    3000

    2000

    1000

    800

    600

    900

    700

    500

    400

    300

    200

    100

    8060 907050403020109875 6

    TIMEINSECONDS

    10,000

    100

    50

    30

    20

    10

    5

    3

    2

    1

    .5

    .3

    .2

    .1

    .05

    .03

    .02

    .01

    .005

    .003

    .002

    .001

    1,000

    500

    300

    200

    5,000

    3,000

    2,000

    1HOUR

    1M

    INUTE

    2HOURS

    CURRENT IN AMPERES

    10000

    8000

    6000

    9000

    7000

    5000

    4000

    3000

    2000

    1000

    800

    600

    900

    700

    500

    400

    300

    200

    100

    8060 907050403020109875 6

    35A

    Maximum single-pole trip timesat 25C 1

    CURRENT IN AMPERES

    Circuit breaker time/current curves

    Series CF-frame circuit breakers

    Catalog types EHD, FD and HFD circuit breakers, single-pole.

    For application and coordination purposes only.Based on 40C ambient, cold start. Connected with four (4) feet ofrated wire (60C up to 100A, 75C above 125A) per terminal.

    Tested in open air.

    Maximum Vac: 277 at 50/60 HzMaximum Vdc: 125

    Breaker rating

    Continuousamperes Instantaneous trip, amperes

    35A See curve

    Breakertype

    Symmetrical Rms amperes (kA )

    143565

    EHDFDHFD

    101010

    Single-pole test data at 25C based on NEMA procedures(AB 4-2003) for verifying performance of molded casecircuitbreakers.

    277V

    DC amps

    125V

    Interrupting rating (UL/CSA listed)

  • 7/26/2019 Curvas de Disparo Disyuntores

    8/568

    Trip Curves TC01200002EEffective May 2009

    Series C F-frame circuit breakertime current curves

    EATON CORPORATIONwww.eaton.com

    Figure 6. Types EHD, FD, and HFD 40ACurve No. SC-4428-88A

    Interruptingratingdeterminesend of curve

    Minimum Maximum

    100

    50

    30

    20

    10

    5

    3

    2

    1

    .5

    .3

    .2

    .1

    .05

    .03

    .02

    .01

    .005

    .003

    .002

    .001

    TIMEINSECONDS

    1,000

    500

    300

    200

    5,000

    3,000

    2,000

    1HOU

    R

    1MINUTE

    2HOURS

    10000

    8000

    6000

    9000

    7000

    5000

    4000

    3000

    2000

    1000

    800

    600

    900

    700

    500

    400

    300

    200

    100

    8060 907050403020109875 6

    TIMEINSECONDS

    10,000

    100

    50

    30

    20

    10

    5

    3

    2

    1

    .5

    .3

    .2

    .1

    .05

    .03

    .02

    .01

    .005

    .003

    .002

    .001

    1,000

    500

    300

    200

    5,000

    3,000

    2,000

    1

    HOUR

    1M

    INUTE

    2HOURS

    CURRENT IN AMPERES

    10000

    8000

    6000

    9000

    7000

    5000

    4000

    3000

    2000

    1000

    800

    600

    900

    700

    500

    400

    300

    200

    100

    8060 907050403020109875 6

    40A

    Maximum single-pole trip timesat 25C 1

    CURRENT IN AMPERES

    Maximum interrupting time

    Circuit breaker time/current curves

    Series CF-frame circuit breakers

    Catalog types EHD, FD and HFD circuit breakers, single-pole.

    For application and coordination purposes only.Based on 40C ambient, cold start. Connected with four (4) feet ofrated wire (60C up to 100A, 75C above 125A) per terminal.

    Tested in open air.

    Maximum Vac: 277 at 50/60 HzMaximum Vdc: 125

    Breaker rating

    Continuousamperes Instantaneou s trip, amperes

    40A See curve

    Breakertype

    Symmetrical Rms amperes (kA )

    143565

    EHDFDHFD

    101010

    Single-pole test data at 25C based on NEMA procedures(AB 4-2003) for verifying performance of molded casecircuitbreakers.

    277V

    DC amps

    125V

    Interrupting rating (UL/CSA listed)

  • 7/26/2019 Curvas de Disparo Disyuntores

    9/56

    Trip Curves TC0120000Effective May 2

    Series C F-frame circuit breakertime current curves

    EATON CORPORATIONwww.eaton.com

    Figure 7. Types EHD, FD, and HFD 45ACurve No. SC-4429-88A

    Interruptingratingdeterminesend of curve

    Minimum Maximum

    100

    50

    30

    20

    10

    5

    3

    2

    1

    .5

    .3

    .2

    .1

    .05

    .03

    .02

    .01

    .005

    .003

    .002

    .001

    TIMEIN

    SECONDS

    1,000

    500

    300

    200

    5,000

    3,000

    2,000

    1HOU

    R

    1MINUTE

    2HOURS

    10000

    8000

    6000

    9000

    7000

    5000

    4000

    3000

    2000

    1000

    800

    600

    900

    700

    500

    400

    300

    200

    100

    8060 907050403020109875 6

    TIMEINSECONDS

    10,000

    100

    50

    30

    20

    10

    5

    3

    2

    1

    .5

    .3

    .2

    .1

    .05

    .03

    .02

    .01

    .005

    .003

    .002

    .001

    1,000

    500

    300

    200

    5,000

    3,000

    2,000

    1HOUR

    1M

    INUTE

    2HOURS

    CURRENT IN AMPERES

    10000

    8000

    6000

    9000

    7000

    5000

    4000

    3000

    2000

    1000

    800

    600

    900

    700

    500

    400

    300

    200

    100

    8060 907050403020109875 6

    45A

    Maximum single-pole trip timesat 25C 1

    CURRENT IN AMPERES

    Maximum interrupting time

    Circuit breaker time/current curves

    Series CF-frame circuit breakers

    Catalog types EHD, FD and HFD circuit breakers, single-pole.

    For application and coordination purposes only.Based on 40C ambient, cold start. Connected with four (4) feet ofrated wire (60C up to 100A, 75C above 125A) per terminal.

    Tested in open air.

    Maximum Vac: 277 at 50/60 HzMaximum Vdc: 125

    Breaker rating

    Continuousamperes Instantane ous trip, amperes

    45A See curve

    Breakertype

    Symmetrical Rms amperes (kA )

    143565

    EHDFDHFD

    101010

    Single-pole test data at 25C based on NEMA procedures(AB 4-2003) for verifying performance of molded casecircuit breakers.

    277V

    DC amps

    125V

    Interrupting rating (UL/CSA listed)

  • 7/26/2019 Curvas de Disparo Disyuntores

    10/5610

    Trip Curves TC01200002EEffective May 2009

    Series C F-frame circuit breakertime current curves

    EATON CORPORATIONwww.eaton.com

    Figure 8. Types EHD, FD, and HFD 50ACurve No. SC-4430-88A

    Interruptingratingdeterminesend of curve

    Minimum Maximum

    100

    50

    30

    20

    10

    5

    3

    2

    1

    .5

    .3

    .2

    .1

    .05

    .03

    .02

    .01

    .005

    .003

    .002

    .001

    TIMEINSECONDS

    1,000

    500

    300

    200

    5,000

    3,000

    2,000

    1HO

    UR

    1MIN

    UTE

    2HOURS

    10000

    8000

    6000

    9000

    7000

    5000

    4000

    3000

    2000

    1000

    800

    600

    900

    700

    500

    400

    300

    200

    100

    8060 907050403020109875 6

    TIMEINSECONDS

    10,000

    100

    50

    30

    20

    10

    5

    3

    2

    1

    .5

    .3

    .2

    .1

    .05

    .03

    .02

    .01

    .005

    .003

    .002

    .001

    1,000

    500

    300

    200

    5,000

    3,000

    2,000

    1HOUR

    1MINUTE

    2HOURS

    CURRENT IN AMPERES

    10000

    8000

    6000

    9000

    7000

    5000

    4000

    3000

    2000

    1000

    800

    600

    900

    700

    500

    400

    300

    200

    100

    8060 907050403020109875 6

    50A

    Maximum single-pole trip timesat 25C 1

    CURRENT IN AMPERES

    Maximum interrupting time

    Circuit breaker time/current curves

    Series CF-frame circuit breakers

    Catalog types EHD, FD and HFD circuit breakers, single-pole.

    For application and coordination purposes only.Based on 40C ambient, cold start. Connected with four (4) feet ofrated wire (60C up to 100A, 75C above 125A) per terminal.Tested in open air.

    Maximum Vac: 277 at 50/60 HzMaximum Vdc: 125

    Breaker rating

    Continuousamperes Instantaneous trip, amperes

    50A See curve

    Breakertype

    Symmetrical Rms amperes (kA )

    1435

    65

    EHDFD

    HFD

    1010

    10

    Single-pole test data at 25C based on NEMA procedures(AB 4-2003) for verifying performance of molded casecircuitbreakers.

    277V

    DC amps

    125V

    Interrupting rating (UL/CSA listed)

  • 7/26/2019 Curvas de Disparo Disyuntores

    11/56

    Trip Curves TC0120000Effective May 2

    Series C F-frame circuit breakertime current curves

    EATON CORPORATIONwww.eaton.com

    Figure 9. Types EHD, FD, and HFD 60ACurve No. SC-4431-88A

    Interruptingratingdeterminesend of curve

    Minimum Maximum

    100

    50

    30

    20

    10

    5

    3

    2

    1

    .5

    .3

    .2

    .1

    .05

    .03

    .02

    .01

    .005

    .003

    .002

    .001

    TIMEIN

    SECONDS

    1,000

    500

    300

    200

    5,000

    3,000

    2,000

    1HOU

    R

    1MIN

    UTE

    2HOURS

    10000

    8000

    6000

    9000

    7000

    5000

    4000

    3000

    2000

    1000

    800

    600

    900

    700

    500

    400

    300

    200

    100

    8060 907050403020109875 6

    TIMEIN

    SECONDS

    10,000

    100

    50

    30

    20

    10

    5

    3

    2

    1

    .5

    .3

    .2

    .1

    .05

    .03

    .02

    .01

    .005

    .003

    .002

    .001

    1,000

    500

    300

    200

    5,000

    3,000

    2,000

    1

    HOUR

    1M

    INUTE

    2HOURS

    CURRENT IN AMPERES

    10000

    8000

    6000

    9000

    7000

    5000

    4000

    3000

    2000

    1000

    800

    600

    900

    700

    500

    400

    300

    200

    100

    8060 907050403020109875 6

    60A

    Maximum single-pole trip timesat 25C 1

    CURRENT IN AMPERES

    Maximum interrupting time

    Circuit breaker time/current curves

    Series CF-frame circuit breakers

    Catalog types EHD, FD and HFD circuit breakers, single-pole.

    For application and coordination purposes only.Based on 40C ambient, cold start. Connected with four (4) feet ofrated wire (60C up to 100A, 75C above 125A) per terminal.Tested in open air.

    Maximum Vac: 277 at 50/60 HzMaximum Vdc: 125

    Breaker rating

    Continuousamperes Instantaneous trip, amperes

    60A See curve

    Single-pole test data at 25C based on NEMA procedures(AB4-2003) for verifying performance of molded case

    circuit breakers.

    Breakertype

    Symmetrical Rms amperes (kA )

    143565

    EHDFDHFD

    101010

    277V

    DC amps

    125V

    Interrupting rating (UL/CSA listed)

  • 7/26/2019 Curvas de Disparo Disyuntores

    12/5612

    Trip Curves TC01200002EEffective May 2009

    Series C F-frame circuit breakertime current curves

    EATON CORPORATIONwww.eaton.com

    Figure 10. Types EHD, FD, and HFD 70ACurve No. SC-4432-88A

    Interruptingratingdeterminesend of curve

    Minimum Maximum

    100

    50

    30

    20

    10

    5

    3

    2

    1

    .5

    .3

    .2

    .1

    .05

    .03

    .02

    .01

    .005

    .003

    .002

    .001

    TIMEINSECONDS

    1,000

    500

    300

    200

    5,000

    3,000

    2,000

    1HOU

    R

    1MINUTE

    2HOURS

    10000

    8000

    6000

    9000

    7000

    5000

    4000

    3000

    2000

    1000

    800

    600

    900

    700

    500

    400

    300

    200

    100

    8060 907050403020109875 6

    TIMEINSECONDS

    10,000

    100

    50

    30

    20

    10

    5

    3

    2

    1

    .5

    .3

    .2

    .1

    .05

    .03

    .02

    .01

    .005

    .003

    .002

    .001

    1,000

    500

    300

    200

    5,000

    3,000

    2,000

    1

    HOUR

    1M

    INUTE

    2HOURS

    CURRENT IN AMPERES

    10000

    8000

    6000

    9000

    7000

    5000

    4000

    3000

    2000

    1000

    800

    600

    900

    700

    500

    400

    300

    200

    100

    8060 907050403020109875 6

    70A

    Maximum single-pole trip timesat 25C 1

    CURRENT IN AMPERES

    Maximuminterrupting

    time

    Circuit breaker time/current curves

    Series CF-frame circuit breakers

    Catalog types EHD, FD and HFD circuit breakers, single-pole.

    For application and coordination purposes only.Based on 40C ambient, cold start. Connected with four (4) feet ofrated wire (60C up to 100A, 75C above 125A) per terminal.

    Tested in open air.

    Maximum Vac: 277 at 50/60 HzMaximum Vdc: 125

    Breaker rating

    Continuousamperes Instantaneous trip, amperes

    70A See curve

    Single-pole test data at 25C based on NEMA procedures(AB 4-2003) for verifying performance of molded casecircuitbreakers.

    Breakertype

    Symmetrical Rms amperes (kA )

    143565

    EHDFDHFD

    101010

    277V

    DC amps

    125V

    Interrupting rating (UL/CSA listed)

  • 7/26/2019 Curvas de Disparo Disyuntores

    13/56

    Trip Curves TC0120000Effective May 2

    Series C F-frame circuit breakertime current curves

    EATON CORPORATIONwww.eaton.com

    Figure 11. Types EHD, FD, and HFD 80ACurve No. SC-4433-88A

    Interruptingratingdeterminesend of curve

    Minimum Maximum

    100

    50

    30

    20

    10

    5

    3

    2

    1

    .5

    .3

    .2

    .1

    .05

    .03

    .02

    .01

    .005

    .003

    .002

    .001

    TIMEINSECONDS

    1,000

    500

    300

    200

    5,000

    3,000

    2,000

    1HOU

    R

    1MINUTE

    2HOURS

    10000

    8000

    6000

    9000

    7000

    5000

    4000

    3000

    2000

    1000

    800

    600

    900

    700

    500

    400

    300

    200

    100

    8060 907050403020109875 6

    TIMEINSECONDS

    10,000

    100

    50

    30

    20

    10

    5

    3

    2

    1

    .5

    .3

    .2

    .1

    .05

    .03

    .02

    .01

    .005

    .003

    .002

    .001

    1,000

    500

    300

    200

    5,000

    3,000

    2,000

    1

    HOUR

    1M

    INUTE

    2HOURS

    CURRENT IN AMPERES

    10000

    8000

    6000

    9000

    7000

    5000

    4000

    3000

    2000

    1000

    800

    600

    900

    700

    500

    400

    300

    200

    100

    8060 907050403020109875 6

    80A

    Maximum single-pole trip timesat 25C 1

    CURRENT IN AMPERES

    Maximum

    interruptingtime

    Circuit breaker time/current curves

    Series CF-frame circuit breakers

    Catalog types EHD, FD and HFD circuit breakers, single-pole.

    For application and coordination purposes only.Based on 40C ambient, cold start. Connected with four (4) feet ofrated wire (60C up to 100A, 75C above 125A) per terminal.

    Tested in open air.

    Maximum Vac: 277 at 50/60 HzMaximum Vdc: 125

    Breaker rating

    Continuousamperes Instantaneous trip, amperes

    80A See curve

    Single-pole test data at 25C based on NEMA procedures(AB 4-2003) for verifying performance of molded casecircuitbreakers.

    Breakertype

    Symmetrical Rms amperes (kA )

    143565

    EHDFDHFD

    101010

    277V

    DC amps

    125V

    Interrupting rating (UL/CSA listed)

  • 7/26/2019 Curvas de Disparo Disyuntores

    14/5614

    Trip Curves TC01200002EEffective May 2009

    Series C F-frame circuit breakertime current curves

    EATON CORPORATIONwww.eaton.com

    Figure 12. Types EHD, FD, and HFD 90ACurve No. SC-4434-88A

    Interruptingratingdeterminesend of curve

    Minimum Maximum

    100

    50

    30

    20

    10

    5

    3

    2

    1

    .5

    .3

    .2

    .1

    .05

    .03

    .02

    .01

    .005

    .003

    .002

    .001

    TIMEINSECONDS

    1,000

    500

    300

    200

    5,000

    3,000

    2,000

    1HOU

    R

    1MIN

    UTE

    2HOURS

    10000

    8000

    6000

    9000

    7000

    5000

    4000

    3000

    2000

    1000

    800

    600

    900

    700

    500

    400

    300

    200

    100

    8060 907050403020109875 6

    TIMEIN

    SECONDS

    10,000

    100

    50

    30

    20

    10

    5

    3

    2

    1

    .5

    .3

    .2

    .1

    .05

    .03

    .02

    .01

    .005

    .003

    .002

    .001

    1,000

    500

    300

    200

    5,000

    3,000

    2,000

    1

    HOUR

    1M

    INUTE

    2HOURS

    CURRENT IN AMPERES

    10000

    8000

    6000

    9000

    7000

    5000

    4000

    3000

    2000

    1000

    800

    600

    900

    700

    500

    400

    300

    200

    100

    8060 907050403020109875 6

    90A

    Maximum single-pole trip timesat 25C 1

    CURRENT IN AMPERES

    Maximum

    interruptingtime

    Circuit breaker time/current curves

    Series CF-frame circuit breakers

    Catalog types EHD, FD and HFD circuit breakers, single-pole.

    For application and coordination purposes only.Based on 40C ambient, cold start. Connected with four (4) feet ofrated wire (60C up to 100A, 75C above 125A) per terminal.

    Tested in open air.

    Maximum Vac: 277 at 50/60 HzMaximum Vdc: 125

    Breaker rating

    Continuousamperes Instantaneo us trip, amperes

    90A See curve

    Single-pole test data at 25C based on NEMA procedures

    (AB 4-2003) for verifying performance of molded case circuitbreakers.

    Breakertype

    Symmetrical Rms amperes (kA )

    143565

    EHDFDHFD

    101010

    277V

    DC amps

    125V

    Interrupting rating (UL/CSA listed)

  • 7/26/2019 Curvas de Disparo Disyuntores

    15/56

    Trip Curves TC0120000Effective May 2

    Series C F-frame circuit breakertime current curves

    EATON CORPORATIONwww.eaton.com

    Figure 13. Types EHD, FD, and HFD 100ACurve No. SC-4435-88A

    Interruptingratingdeterminesend of curve

    Minimum Maximum

    100

    50

    30

    20

    10

    5

    3

    2

    1

    .5

    .3

    .2

    .1

    .05

    .03

    .02

    .01

    .005

    .003

    .002

    .001

    TIMEINSECONDS

    1,000

    500

    300

    200

    5,000

    3,000

    2,000

    1HOUR

    1MI

    NUTE

    2HOURS

    10000

    8000

    6000

    9000

    7000

    5000

    4000

    3000

    2000

    1000

    800

    600

    900

    700

    500

    400

    300

    200

    100

    8060 907050403020109875 6

    TIMEINSECONDS

    10,000

    100

    50

    30

    20

    10

    5

    3

    2

    1

    .5

    .3

    .2

    .1

    .05

    .03

    .02

    .01

    .005

    .003

    .002

    .001

    1,000

    500

    300

    200

    5,000

    3,000

    2,000

    1H

    OUR

    1MINUTE

    2HOURS

    CURRENT IN AMPERES

    10000

    8000

    6000

    9000

    7000

    5000

    4000

    3000

    2000

    1000

    800

    600

    900

    700

    500

    400

    300

    200

    100

    8060 907050403020109875 6

    100A

    Maximum single-pole trip timesat 25C 1

    CURRENT IN AMPERES

    Maximum

    interruptingtime

    Circuit breaker time/current curves

    Series CF-frame circuit breakers

    Catalog types EHD, FD and HFD circuit breakers, single-pole.

    For application and coordination purposes only.Based on 40C ambient, cold start. Connected with four (4) feet of

    rated wire (60C up to 100A, 75C above 125A) per terminal.Tested in open air.

    Maximum Vac: 277 at 50/60 HzMaximum Vdc: 125

    Breaker rating

    Continuousamperes Instantaneous trip, amperes

    100A See curve

    Single-pole test data at 25C based on NEMA procedures(AB 4-2003) for verifying performance of molded casecircuit breakers.

    Breakertype

    Symmetrical Rms amperes (kA )

    14

    35

    65

    EHD

    FD

    HFD

    10

    10

    10

    277V

    DC amps

    125V

    Interrupting rating (UL/CSA listed)

  • 7/26/2019 Curvas de Disparo Disyuntores

    16/5616

    Trip Curves TC01200002EEffective May 2009

    Series C F-frame circuit breakertime current curves

    EATON CORPORATIONwww.eaton.com

    Figure 14. Types FD and HFD 110ACurve No. SC-4436-88A

    Interruptingratingdeterminesend of curve

    Minimum Maximum

    100

    50

    30

    20

    10

    5

    3

    2

    1

    .5

    .3

    .2

    .1

    .05

    .03

    .02

    .01

    .005

    .003

    .002

    .001

    TIMEINSECONDS

    1,000

    500

    300

    200

    5,000

    3,000

    2,000

    1HOUR

    1MIN

    UTE

    2HOURS

    10000

    8000

    6000

    9000

    7000

    5000

    4000

    3000

    2000

    1000

    800

    600

    900

    700

    500

    400

    300

    200

    100

    8060 907050403020109875 6

    TIMEINSECONDS

    10,000

    100

    50

    30

    20

    10

    5

    3

    2

    1

    .5

    .3

    .2

    .1

    .05

    .03

    .02

    .01

    .005

    .003

    .002

    .001

    1,000

    500

    300

    200

    5,000

    3,000

    2,000

    1

    HOUR

    1M

    INUTE

    2HOURS

    CURRENT IN AMPERES

    10000

    8000

    6000

    9000

    7000

    5000

    4000

    3000

    2000

    1000

    800

    600

    900

    700

    500

    400

    300

    200

    100

    8060 907050403020109875 6

    110A

    Maximum single-pole trip timesat 25C 1

    CURRENT IN AMPERES

    Maximuminterruptingtime

    Circuit breaker time/current curves

    Series CF-frame circuit breakers

    Catalog types FD & HFD circuit breakers, single-pole.

    For application and coordination purposes only.Based on 40C ambient, cold start. Connected with four (4) feet ofrated wire (60C up to 100A, 75C above 125A) per terminal.

    Tested in open air.

    Maximum Vac: 277 at 50/60 HzMaximum Vdc: 125

    Breaker rating

    Continuousamperes Instantaneous trip, amperes

    110A See curve

    Single-pole test data at 25C based on NEMA procedures(AB 4-2003) for verifying performance of molded casecircuit breakers.

    Breakertype

    Symmetrical Rms amperes (kA )

    35

    65

    FD

    HFD

    10

    10

    277V

    DC amps

    125V

    Interrupting rating (UL/CSA listed)

  • 7/26/2019 Curvas de Disparo Disyuntores

    17/56

    Trip Curves TC0120000Effective May 2

    Series C F-frame circuit breakertime current curves

    EATON CORPORATIONwww.eaton.com

    Figure 15. Types FD and HFD 125ACurve No. SC-4437-88A

    Interruptingratingdeterminesend of curve

    Minimum Maximum

    100

    50

    30

    20

    10

    5

    3

    2

    1

    .5

    .3

    .2

    .1

    .05

    .03

    .02

    .01

    .005

    .003

    .002

    .001

    TIMEINSECONDS

    1,000

    500

    300

    200

    5,000

    3,000

    2,000

    1HOU

    R

    1MINUTE

    2HOURS

    10000

    8000

    6000

    9000

    7000

    5000

    4000

    3000

    2000

    1000

    800

    600

    900

    700

    500

    400

    300

    200

    1008060 907050403020109875 6

    TIMEIN

    SECONDS

    10,000

    100

    50

    30

    20

    10

    5

    3

    2

    1

    .5

    .3

    .2

    .1

    .05

    .03

    .02

    .01

    .005

    .003

    .002

    .001

    1,000

    500

    300

    200

    5,000

    3,000

    2,000

    1

    HOUR

    1M

    INUTE

    2HOURS

    CURRENT IN AMPERES

    10000

    8000

    6000

    9000

    7000

    5000

    4000

    3000

    2000

    1000

    800

    600

    900

    700

    500

    400

    300

    200

    100

    8060 907050403020109875 6

    125A

    Maximum single-pole trip timesat 25C 1

    CURRENT IN AMPERES

    Maximum

    interruptingtime

    Circuit breaker time/current curves

    Series CF-frame circuit breakers

    Catalog types FD and HFD circuit breakers, single-pole.

    For application and coordination purposes only.Based on 40C ambient, cold start. Connected with four (4) feet ofrated wire (60C up to 100A, 75C above 125A) per terminal.

    Tested in open air.

    Maximum Vac: 277 at 50/60 HzMaximum Vdc: 125

    Breaker rating

    Continuousamperes Instantaneous trip, amperes

    125A See curve

    Single-pole test data at 25C based on NEMA procedures(AB 4-2003) for verifying performance of molded casecircuit breakers.

    Breakertype

    Symmetrical Rms amperes (kA )

    3565

    FDHFD

    1010

    277V

    DC amps

    125V

    Interrupting rating (UL/CSA listed)

  • 7/26/2019 Curvas de Disparo Disyuntores

    18/5618

    Trip Curves TC01200002EEffective May 2009

    Series C F-frame circuit breakertime current curves

    EATON CORPORATIONwww.eaton.com

    Figure 16. Types FD and HFD 150ACurve No. SC-4438-88A

    Interruptingratingdeterminesend of curve

    Minimum Maximum

    100

    50

    30

    20

    10

    5

    3

    2

    1

    .5

    .3

    .2

    .1

    .05

    .03

    .02

    .01

    .005

    .003

    .002

    .001

    TIMEINSECONDS

    1,000

    500

    300

    200

    5,000

    3,000

    2,000

    1HOU

    R

    1MIN

    UTE

    2HOURS

    10000

    8000

    6000

    9000

    7000

    5000

    4000

    3000

    2000

    1000

    800

    600

    900

    700

    500

    400

    300

    200

    100

    8060 907050403020109875 6

    TIMEIN

    SECONDS

    10,000

    100

    50

    30

    20

    10

    5

    3

    2

    1

    .5

    .3

    .2

    .1

    .05

    .03

    .02

    .01

    .005

    .003

    .002

    .001

    1,000

    500

    300

    200

    5,000

    3,000

    2,000

    1

    HOUR

    1M

    INUTE

    2HOURS

    CURRENT IN AMPERES

    10000

    8000

    6000

    9000

    7000

    5000

    4000

    3000

    2000

    1000

    800

    600

    900

    700

    500

    400

    300

    200

    100

    8060 907050403020109875 6

    150A

    Maximum single-pole trip timesat 25C 1

    CURRENT IN AMPERES

    Maximum

    interruptingtime

    Circuit breaker time/current curves

    Series CF-frame circuit breakers

    Catalog types FD and HFD circuit breakers, single-pole.

    For application and coordination purposes only.Based on 40C ambient, cold start. Connected with four (4) feet ofrated wire (60C up to 100A, 75C above 125A) per terminal.

    Tested in open air.

    Maximum Vac: 277 at 50/60 HzMaximum Vdc: 125

    Breaker rating

    Continuousamperes Instantaneou s trip, amperes

    150A See curve

    Single-pole test data at 25C based on NEMA procedures(AB 4-2003) for verifying performance of molded case

    circuit breakers.

    Breakertype

    Symmetrical Rms amperes (kA )

    3565

    FDHFD

    1010

    277V

    DC amps

    125V

    Interrupting rating (UL/CSA listed)

  • 7/26/2019 Curvas de Disparo Disyuntores

    19/56

    Trip Curves TC0120000Effective May 2

    Series C F-frame circuit breakertime current curves

    EATON CORPORATIONwww.eaton.com

    AB DE-ION Circuit Breakerstwo-, three-, and four-poles

    Figure 17. Types ED, EHD, FDB, FD, and HFD 15ACurve No. SC-4134-87B

    Minimum Maximum

    Maximum interrupting time

    Interruptingratingdeterminesend of curve(see above)

    1

    100

    50

    30

    20

    10

    5

    3

    2

    1

    .5

    .3

    .2

    .1

    .05

    .03

    .02

    .01

    .005

    .003

    .002

    .001

    TIMEINSECONDS

    1,000

    500

    300

    200

    5,000

    3,000

    2,000

    1HOUR

    1MINUTE

    2HOU

    RS

    CURRENT IN AMPERES10000

    8000

    6000

    9000

    7000

    5000

    4000

    3000

    2000

    1000

    800

    600

    900

    700

    500

    400

    300

    200

    1008060 907050403020109875 6

    TIMEINSECONDS

    10,000

    100

    50

    30

    20

    10

    5

    3

    2

    1

    .5

    .3

    .2

    .1

    .05

    .03

    .02

    .01

    .005

    .003

    .002

    .001

    1,000

    500

    300

    200

    5,000

    3,000

    2,000

    1HOUR

    1MINUTE

    2H

    OURS

    CURRENT IN AMPERES

    10000

    8000

    6000

    9000

    7000

    5000

    4000

    3000

    2000

    1000

    800

    600

    900

    700

    500

    400

    300

    200

    100

    8060 907050403020109875 6

    15A

    Maximum single-pole trip timesat 25C 1

    Circuit breaker time/current curves

    Series C

    F-frame circuit breakers

    Catalog types ED, EHD, FDB, FD and HFD circuit breakers, t wo-, three -and four-poles.

    For application and coordination purposes only.Based on 40C ambient, cold start. Con nected with four (4) feet ofrated wire (60C up to 125A, 75C above 125A) per terminal.Tested in open air with current in all poles.

    Maximum Vac: 600 at 50/60 HzMaximum Vdc: 250

    Breaker rating

    Continuous amperes Instantaneous trip amperes

    15A See curve

    181865

    100

    EHDFDBFDHFD

    14143565

    141825

    10101022

    Single-pole test data at 25C based on NEMA procedures(AB4-2003) for verifying performance of molded casecircuit breakers.

    ED 65

    Interrupting Rating (UL/CSA Listed)Breaker Symmetrical Rms amperes (KA) Amps (KA)type @ 240 Vac @ 480 Vac @ 600 Vac 250 Vac 125V

    10

  • 7/26/2019 Curvas de Disparo Disyuntores

    20/5620

    Trip Curves TC01200002EEffective May 2009

    Series C F-frame circuit breakertime current curves

    EATON CORPORATIONwww.eaton.com

    Figure 18. Types ED, EHD, FDB, FD, and HFD 20ACurve No. SC-4135-87B

    Minimum

    Maximum interrupting time

    Interruptingratingdeterminesend of curve(see above)

    Maximum single-pole trip timesat 25C 1

    20A

    1

    100

    50

    30

    20

    10

    5

    3

    2

    1

    .5

    .3

    .2

    .1

    .05

    .03

    .02

    .01

    .005

    .003

    .002

    .001

    TIMEINSECONDS

    1,000

    500

    300

    200

    5,000

    3,000

    2,000

    1HOUR

    1M

    INUTE

    2HOURS

    CURRENT IN AMPERES10000

    8000

    6000

    9000

    7000

    5000

    4000

    3000

    2000

    1000

    800

    600

    900

    700

    500

    400

    300

    200

    1008060 907050403020109875 6

    TIMEINSECOND

    S

    10,000

    100

    50

    30

    20

    10

    5

    3

    2

    1

    .5

    .3

    .2

    .1

    .05

    .03

    .02

    .01

    .005

    .003

    .002

    .001

    1,000

    500

    300

    200

    5,000

    3,000

    2,000

    1HOUR

    1MINUTE

    2HOURS

    CURRENT IN AMPERES

    10000

    8000

    6000

    9000

    7000

    5000

    4000

    3000

    2000

    1000

    800

    600

    900

    700

    500

    400

    300

    200

    100

    8060 907050403020109875 6

    Maximum

    Circuit breaker time/current curves

    Series CF-frame circuit breakers

    Catalog types ED, EHD, FDB, FD and HFD circuit breakers, two-, three-and four-poles.

    For application and coordination purposes o nly.Based on 40C ambient, cold start. Conn ected with four (4) feet ofrated wire (60C up to 125A, 75C above 125A) per terminal.Tested in open air with current in all pol es.

    Maximum Vac: 600 at 50/60 HzMaximum Vdc: 250

    Breaker rating

    Continuous amperes Instantaneous trip amperes

    20A See curve

    181865

    100

    EHDFDBFDHFD

    14143565

    141825

    10101022

    Single-pole test data at 25C based on NEMA procedures(AB4-2003) for verifying performance of molded casecircuit breakers.

    Interrupting rating (UL/CSA listed)

    Breaker Symmetrical Rms amperes (KA) Amps (KA)type @ 240 Vac @ 480 Vac @ 600 Vac 250 Vdc 125 Vdc

    ED 65 10

  • 7/26/2019 Curvas de Disparo Disyuntores

    21/56

    Trip Curves TC0120000Effective May 2

    Series C F-frame circuit breakertime current curves

    EATON CORPORATIONwww.eaton.com

    Figure 19. Types ED, EHD, FDB, FD, and HFD 25ACurve No. SC-4136-87B

    Minimum Maximum

    Maximum interrupting time

    Interruptingratingdeterminesend of curve(see above)

    Maximum single-pole trip timesat 25C 1

    25A

    1

    181865

    100

    EHDFDBFDHFD

    14143565

    141825

    10101022

    100

    50

    30

    20

    10

    5

    3

    2

    1

    .5

    .3

    .2

    .1

    .05

    .03

    .02

    .01

    .005

    .003

    .002

    .001

    TIMEINSECONDS

    1,000

    500

    300

    200

    5,000

    3,000

    2,000

    1HOUR

    1MINUTE

    2HOURS

    CURRENT IN AMPERES

    10000

    8000

    6000

    9000

    7000

    5000

    4000

    3000

    2000

    1000

    800

    600

    900

    700

    500

    400

    300

    200

    100

    8060 907050403020109875 6

    TIMEINSECONDS

    10,000

    100

    50

    30

    20

    10

    5

    3

    2

    1

    .5

    .3

    .2

    .1

    .05

    .03

    .02

    .01

    .005

    .003

    .002

    .001

    1,000

    500

    300

    200

    5,000

    3,000

    2,000

    1HOUR

    1MINU

    TE

    2HOURS

    CURRENT IN AMPERES

    10000

    8000

    6000

    9000

    7000

    5000

    4000

    3000

    2000

    1000

    800

    600

    900

    700

    500

    400

    300

    200

    100

    8060 907050403020109875 6

    Circuit breaker time/current curves

    Series CF-frame circuit breakers

    Catalog types ED, EHD, FDB, FD and HFD circuit breakers, two-, three-and four-poles.

    For application and coordination purposes only.Based on 40C ambient, cold start. Connected with four (4) feet ofrated wire (60C up to 125A, 75C above 125A) per terminal.Tested in open air with current in all poles.

    Maximum Vac: 600 at 50/60 HzMaximum Vdc: 250

    Breaker rating

    Continuous amperes Instantaneous trip amperes

    25A See curve

    Single-pole test data at 25C based on NEMA procedures(AB4-2003) for verifying performance of molded casecircuit breakers.

    Interrupting rating (UL/CSA listed)

    Breaker

    type

    Symmetrical Rms amperes (KA) Amps (KA)

    @ 240 Vac @ 480 Vac @ 600 Vac 250 Vdc 125 Vdc

    ED 65 10

  • 7/26/2019 Curvas de Disparo Disyuntores

    22/5622

    Trip Curves TC01200002EEffective May 2009

    Series C F-frame circuit breakertime current curves

    EATON CORPORATIONwww.eaton.com

    Figure 20. Types ED, EHD, FDB, FD, and HFD 30ACurve No. SC-4137-87B

    Maximum

    Maximum interrupting time

    Interruptingratingdeterminesend of curve(see above)

    Maximum single-pole trip timesat 25C 1

    Minimum

    30A

    1

    100

    50

    30

    20

    10

    5

    3

    2

    1

    .5

    .3

    .2

    .1

    .05

    .03

    .02

    .01

    .005

    .003

    .002

    .001

    TIMEINSECONDS

    1,000

    500

    300

    200

    5,000

    3,000

    2,000

    1HOUR

    1MINUTE

    2HOURS

    CURRENT IN AMPERES10000

    8000

    6000

    9000

    7000

    5000

    4000

    3000

    2000

    1000

    800

    600

    900

    700

    500

    400

    300

    200

    1008060 907050403020109875 6

    TIMEINSECONDS

    10,000

    100

    50

    30

    20

    10

    5

    3

    2

    1

    .5

    .3

    .2

    .1

    .05

    .03

    .02

    .01

    .005

    .003

    .002

    .001

    1,000

    500

    300

    200

    5,000

    3,000

    2,000

    1HOUR

    1MINU

    TE

    2HOURS

    CURRENT IN AMPERES

    10000

    8000

    6000

    9000

    7000

    5000

    4000

    3000

    2000

    1000

    800

    600

    900

    700

    500

    400

    300

    200

    100

    8060 907050403020109875 6

    Circuit breaker time/current curves

    Series CF-frame circuit breakers

    Catalog types ED, EHD, FDB, FD and HFD circuit breakers, two-, three-and four-poles.

    For application and coordination purposes only.Based on 40C ambient, cold start. Connected with four (4) feet ofrated wire (60C up to 125A, 75C above 125A) per terminal.Tested in open air with current in all poles.

    Maximum Vac: 600 at 50/60 HzMaximum Vdc: 250

    Breaker Rating

    Continuous amperes Instantaneous trip amperes

    30A See curve

    181865

    100

    EHDFDBFDHFD

    14143565

    141825

    10101022

    Single-pole test data at 25C based on NEMA procedures(AB4-2003) for verifying performance of molded casecircuit breakers.

    Interrupting rating (UL/CSA listed)

    Breaker Symmetrical RMS amperes (KA) Amps (KA)

    type @ 240 Vac @ 480 Vac @ 600 Vac 250 Vdc 125 Vdc

    ED 65

    10

  • 7/26/2019 Curvas de Disparo Disyuntores

    23/56

    Trip Curves TC0120000Effective May 2

    Series C F-frame circuit breakertime current curves

    EATON CORPORATIONwww.eaton.com

    Figure 21. Types ED, EHD, FDB, FD, and HFD 35ACurve No. SC-4138-87B

    Minimum

    Maximum interrupting time

    Interruptingratingdeterminesend of curve(see above)

    Maximum single-pole trip times

    at 25C 1

    35A

    Maximum

    1

    100

    50

    30

    20

    10

    5

    3

    2

    1

    .5

    .3

    .2

    .1

    .05

    .03

    .02

    .01

    .005

    .003

    .002

    .001

    TIMEINSECONDS

    1,000

    500

    300

    200

    5,000

    3,000

    2,000

    1HOUR

    1

    MINUTE

    2HOURS

    CURRENT IN AMPERES10000

    8000

    6000

    9000

    7000

    5000

    4000

    3000

    2000

    1000

    800

    600

    900

    700

    500

    400

    300

    200

    1008060 907050403020109875 6

    TIMEINSECONDS

    10,000

    100

    50

    30

    20

    10

    5

    3

    2

    1

    .5

    .3

    .2

    .1

    .05

    .03

    .02

    .01

    .005

    .003

    .002

    .001

    1,000

    500

    300

    200

    5,000

    3,000

    2,000

    1HOUR

    1MINU

    TE

    2HOURS

    CURRENT IN AMPERES

    10000

    8000

    6000

    9000

    7000

    5000

    4000

    3000

    2000

    1000

    800

    600

    900

    700

    500

    400

    300

    200

    100

    8060 907050403020109875 6

    Circuit breaker time/current curves

    Series CF-frame circuit breakers

    Catalog types ED, EHD, FDB, FD and HFD circuit breakers, two-, three-and four-poles.

    For application and coordination purposes only.Based on 40C ambient, cold start. Connected with four (4) feet ofrated wire (60C up to 125A, 75C above 125A) per terminal.Tested in open air with current in all poles.

    Maximum Vac: 600 at 50/60 HzMaximum Vdc: 250

    Breaker rating

    Continuous amperes Instantaneous trip amperes

    35A See curve

    181865

    100

    EHDFDBFDHFD

    14143565

    141825

    10101022

    Single-pole test data at 25C based on NE MA procedures(AB4-2003) for verifying performance of molded casecircuit breakers.

    Interrupting rating (UL/CSA listed)

    Breaker Symmetrical Rms amperes (KA) Amps (KA)

    type @ 240 Vac @ 480 Vac @ 600 Vac 250 Vdc 125 Vdc

    ED 65 10

  • 7/26/2019 Curvas de Disparo Disyuntores

    24/5624

    Trip Curves TC01200002EEffective May 2009

    Series C F-frame circuit breakertime current curves

    EATON CORPORATIONwww.eaton.com

    Figure 22. Types ED, EHD, FDB, FD, and HFD 40ACurve No. SC-4139-87B

    Minimum Maximum

    Maximum interrupting time

    Interruptingratingdeterminesend of curve(see above)

    Maximum single-pole trip timesat 25C 1

    40A

    1

    100

    50

    30

    20

    10

    5

    3

    2

    1

    .5

    .3

    .2

    .1

    .05

    .03

    .02

    .01

    .005

    .003

    .002

    .001

    TIMEINSECONDS

    1,000

    500

    300

    200

    5,000

    3,000

    2,000

    1HOUR

    1

    MINUTE

    2HOURS

    CURRENT IN AMPERES10000

    8000

    6000

    9000

    7000

    5000

    4000

    3000

    2000

    1000

    800

    600

    900

    700

    500

    400

    300

    200

    1008060 907050403020109875 6

    TIMEINSECONDS

    10,000

    100

    50

    30

    20

    10

    5

    3

    2

    1

    .5

    .3

    .2

    .1

    .05

    .03

    .02

    .01

    .005

    .003

    .002

    .001

    1,000

    500

    300

    200

    5,000

    3,000

    2,000

    1HOUR

    1MINU

    TE

    2HOURS

    CURRENT IN AMPERES

    10000

    8000

    6000

    9000

    7000

    5000

    4000

    3000

    2000

    1000

    800

    600

    900

    700

    500

    400

    300

    200

    100

    8060 907050403020109875 6

    Circuit breaker time/current curves

    Series CF-frame circuit breakers

    Catalog types ED, EHD, FDB, FD and HFD circuit breakers, two-, three -and four-poles.

    For application and coordination purposes o nly.Based on 40C ambient, cold start. Connected with four (4) feet ofrated wire (60C up to 125A, 75C above 125A) per terminal.Tested in open air with current in all pol es.

    Maximum Vac: 600 at 50/60 HzMaximum Vdc: 250

    Breaker Rating

    Continuous amperes Instantaneous trip amperes

    40A See curve

    181865

    100

    EHDFDBFDHFD

    14143565

    141825

    10101022

    Single-pole test data at 25C based on N EMA procedures(AB4-2003) for verifying performance of molded casecircuit breakers.

    Interrupting rating (UL/CSA listed)

    Breaker Symmetrical Rms amperes (KA) Amps (KA)

    type @ 240 Vac @ 480 Vac @ 600 Vac 250 Vdc 125 Vdc

    ED 65 10

  • 7/26/2019 Curvas de Disparo Disyuntores

    25/56

    Trip Curves TC0120000Effective May 2

    Series C F-frame circuit breakertime current curves

    EATON CORPORATIONwww.eaton.com

    Figure 23. Types ED, EHD, FDB, FD, and HFD 45ACurve No. SC-4140-87B

    Minimum Maximum

    Maximum interrupting time

    Interruptingratingdeterminesend of curve(see above)

    45A

    1

    100

    50

    30

    20

    10

    5

    3

    2

    1

    .5

    .3

    .2

    .1

    .05

    .03

    .02

    .01

    .005

    .003

    .002

    .001

    TIMEINSECONDS

    1,000

    500

    300

    200

    5,000

    3,000

    2,000

    1HOUR

    1

    MINUTE

    2HOURS

    CURRENT IN AMPERES10000

    8000

    6000

    9000

    7000

    5000

    4000

    3000

    2000

    1000

    800

    600

    900

    700

    500

    400

    300

    200

    1008060 907050403020109875 6

    TIMEINSECONDS

    10,000

    100

    50

    30

    20

    10

    5

    3

    2

    1

    .5

    .3

    .2

    .1

    .05

    .03

    .02

    .01

    .005

    .003

    .002

    .001

    1,000

    500

    300

    200

    5,000

    3,000

    2,000

    1HOUR

    1MINU

    TE

    2HOURS

    CURRENT IN AMPERES

    10000

    8000

    6000

    9000

    7000

    5000

    4000

    3000

    2000

    1000

    800

    600

    900

    700

    500

    400

    300

    200

    100

    8060 907050403020109875 6

    Maximum single-pole trip times

    at 25C 1

    Circuit breaker time/current curves

    Series CF-frame circuit breakers

    Catalog types ED, EHD, FDB, FD and HFD circuit breakers, two-, three-and four-poles.

    For application and coordination purposes o nly.Based on 40C ambient, cold start. Conn ected with four (4) feet ofrated wire (60C up to 125A, 75C above 125A) per terminal.Tested in open air with current in all po les.

    Maximum Vac: 600 at 50/60 HzMaximum Vdc: 250

    Breaker rating

    Continuous amperes Instantaneous trip amperes

    45A See curve

    181865

    100

    EHDFDBFDHFD

    14143565

    141825

    10101022

    Single-pole test data at 25C based on NEMA procedures(AB4-2003) for verifying performance of molded casecircuit breakers.

    Interrupting rating (UL/CSA lsted)

    Symmetrical Rms amperes (KA) Amps (KA)Breaker

    type @ 240 Vac @ 480 Vac @ 600 Vac 250 Vdc 125 Vdc

    ED 65 10

  • 7/26/2019 Curvas de Disparo Disyuntores

    26/5626

    Trip Curves TC01200002EEffective May 2009

    Series C F-frame circuit breakertime current curves

    EATON CORPORATIONwww.eaton.com

    Figure 24. Types ED, EHD, FDB, FD, and HFD 50ACurve No. SC-4141-87B

    Minimum Maximum

    Maximum interrupting time

    Interruptingratingdeterminesend of curve(see above)

    Maximum single-pole trip timesat 25C 1

    50A

    1

    100

    50

    30

    20

    10

    5

    3

    2

    1

    .5

    .3

    .2

    .1

    .05

    .03

    .02

    .01

    .005

    .003

    .002

    .001

    TIMEINSECONDS

    1,000

    500

    300

    200

    5,000

    3,000

    2,000

    1HOUR

    1

    MINUTE

    2HOURS

    CURRENT IN AMPERES10000

    8000

    6000

    9000

    7000

    5000

    4000

    3000

    2000

    1000

    800

    600

    900

    700

    500

    400

    300

    200

    1008060 907050403020109875 6

    TIMEINSECONDS

    10,000

    100

    50

    30

    20

    10

    5

    3

    2

    1

    .5

    .3

    .2

    .1

    .05

    .03

    .02

    .01

    .005

    .003

    .002

    .001

    1,000

    500

    300

    200

    5,000

    3,000

    2,000

    1HOUR

    1MINU

    TE

    2HOURS

    CURRENT IN AMPERES

    10000

    8000

    6000

    9000

    7000

    5000

    4000

    3000

    2000

    1000

    800

    600

    900

    700

    500

    400

    300

    200

    100

    8060 907050403020109875 6

    Circuit breaker time/current curves

    Series CF-frame circuit breakers

    Catalog types ED, EHD, FDB, FD and HFD circuit breakers, two-, three-and four-poles.

    For application and coordination purposes only.Based on 40C ambient, cold start. Connected with four (4) feet ofrated wire (60C up to 125A, 75C above 125A) per terminal.Tested in open air with current in all poles.

    Maximum Vac: 600 at 50/60 HzMaximum Vdc: 250

    Breaker rating

    Continuous amperes Instantaneous trip amperes

    50A See curve

    181865

    100

    EHDFDBFDHFD

    14143565

    --141825

    10101022

    Single-pole test data at 25C based on NEMA procedures(AB4-2003) for verifying performance of molded casecircuit breakers.

    ED 65

    Interrupting rating (UL/CSA listed)

    Symmetrical Rms amperes (KA) Amps (KA)Breakertype @ 240 Vac @ 480 Vac @ 600 Vac 250 Vdc 125 Vdc

    10

  • 7/26/2019 Curvas de Disparo Disyuntores

    27/56

    Trip Curves TC0120000Effective May 2

    Series C F-frame circuit breakertime current curves

    EATON CORPORATIONwww.eaton.com

    Figure 25. Types ED, EHD, FDB, FD, and HFD 60ACurve No. SC-4142-87B

    Minimum Maximum

    Maximum interrupting time

    Interruptingratingdeterminesend of curve(see above)

    Maximum single-pole trip timesat 25C 1

    60A

    1

    100

    50

    30

    20

    10

    5

    3

    2

    1

    .5

    .3

    .2

    .1

    .05

    .03

    .02

    .01

    .005

    .003

    .002

    .001

    TIMEINSECONDS

    1,000

    500

    300

    200

    5,000

    3,000

    2,000

    1HOUR

    1M

    INUTE

    2HOURS

    CURRENT IN AMPERES10000

    8000

    6000

    9000

    7000

    5000

    4000

    3000

    2000

    1000

    800

    600

    900

    700

    500

    400

    300

    200

    1008060 907050403020109875 6

    TIMEINSECOND

    S

    10,000

    100

    50

    30

    20

    10

    5

    3

    2

    1

    .5

    .3

    .2

    .1

    .05

    .03

    .02

    .01

    .005

    .003

    .002

    .001

    1,000

    500

    300

    200

    5,000

    3,000

    2,000

    1HOUR

    1MIN

    UTE

    2HOURS

    CURRENT IN AMPERES

    10000

    8000

    6000

    9000

    7000

    5000

    4000

    3000

    2000

    1000

    800

    600

    900

    700

    500

    400

    300

    200

    100

    8060 907050403020109875 6

    Circuit breaker time/current curves

    Series CF-frame circuit breakers

    Catalog types ED, EHD, FDB, FD and HFD circuit breakers, two-, three-

    and four-poles.

    For application and coordination purposes only.Based on 40C ambient, cold start. Connected with four (4) feet ofrated wire (60C up to 125A, 75C above 125A) per terminal.Tested in open air with current in all poles.

    Maximum Vac: 600 at 50/60 HzMaximum Vdc: 250

    Breaker rating

    Continuous amperes Instantaneous trip amperes

    60A See curve

    181865

    100

    EHDFDBFDHFD

    14143565

    141825

    10101022

    Single-pole test data at 25C based on NEMA procedures(AB4-2003) for verifying performance of molded casecircuit breakers.

    Interrupting rating (UL/CSA listed)Breaker Symmetrical Rms amperes (KA) Amps (KA)

    type @ 240 Vac @ 480 Vac @ 600 Vac 250 Vdc 125 Vdc

    ED 65 10

  • 7/26/2019 Curvas de Disparo Disyuntores

    28/5628

    Trip Curves TC01200002EEffective May 2009

    Series C F-frame circuit breakertime current curves

    EATON CORPORATIONwww.eaton.com

    Figure 26. Types ED, EHD, FDB, FD, and HFD 70ACurve No. SC-4143-87B

    Maximum single-pole trip timesat 25C 1

    70A

    Interruptingratingdeterminesend of curve(see above)

    MaximumMinimum

    1

    100

    50

    30

    20

    10

    5

    3

    2

    1

    .5

    .3

    .2

    .1

    .05

    .03

    .02

    .01

    .005

    .003

    .002

    .001

    TIMEINSECONDS

    1,000

    500

    300

    200

    5,000

    3,000

    2,000

    1HOUR

    1MINUTE

    2HOURS

    CURRENT IN AMPERES10000

    8000

    6000

    9000

    7000

    5000

    4000

    3000

    2000

    1000

    800

    600

    900

    700

    500

    400

    300

    200

    1008060 907050403020109875 6

    TIMEINSECONDS

    10,000

    100

    50

    30

    20

    10

    5

    3

    2

    1

    .5

    .3

    .2

    .1

    .05

    .03

    .02

    .01

    .005

    .003

    .002

    .001

    1,000

    500

    300

    200

    5,000

    3,000

    2,000

    1HOUR

    1MINU

    TE

    2HOURS

    CURRENT IN AMPERES

    10000

    8000

    6000

    9000

    7000

    5000

    4000

    3000

    2000

    1000

    800

    600

    900

    700

    500

    400

    300

    200

    100

    8060 907050403020109875 6

    Circuit breaker time/current curves

    Series CF-frame circuit breakers

    Catalog types ED, EHD, FDB, FD and HFD circuit breakers, two-, three-and four-poles.

    For application and coordination purposes only.Based on 40C ambient, cold start. Con nected with four (4) feet ofrated wire (60C up to 125A, 75C above 125A) per terminal.Tested in open air with current in all poles.

    Maximum Vac: 600 at 50/60 HzMaximum Vdc: 250

    Breaker rating

    Continuous amperes Instantaneous trip amperes

    70A See curve

    181865

    100

    EHDFDBFDHFD

    14143565

    141825

    10101022

    Single-pole test data at 25C based on NEMA procedures(AB4-2003) for verifying performance of molded casecircuit breakers.

    Interrupting rating (UL/CSA listed)

    Symmetrical Rms amperes (KA) Amps (KA)Breakertype @ 240 Vac @ 480 Vac @ 600Vac 250 Vdc 125 Vdc

    ED 65 10

    Maximum interrupting time

  • 7/26/2019 Curvas de Disparo Disyuntores

    29/56

    Trip Curves TC0120000Effective May 2

    Series C F-frame circuit breakertime current curves

    EATON CORPORATIONwww.eaton.com

    Figure 27. Types ED, EHD, FDB, FD, and HFD 80ACurve No. SC-4144-87B

    Maximum interrupting time

    MaximumMinimum

    Maximum single-pole trip timesat 25C 1

    80A

    Interruptingratingdeterminesend of curve(see above)

    1

    100

    50

    30

    20

    10

    5

    3

    2

    1

    .5

    .3

    .2

    .1

    .05

    .03

    .02

    .01

    .005

    .003

    .002

    .001

    TIMEINSECONDS

    1,000

    500

    300

    200

    5,000

    3,000

    2,000

    1HOUR

    1MINUTE

    2HOURS

    CURRENT IN AMPERES10000

    8000

    6000

    9000

    7000

    5000

    4000

    3000

    2000

    1000

    800

    600

    900

    700

    500

    400

    300

    200

    1008060 907050403020109875 6

    TIMEINSECONDS

    10,000

    100

    50

    30

    20

    10

    5

    3

    2

    1

    .5

    .3

    .2

    .1

    .05

    .03

    .02

    .01

    .005

    .003

    .002

    .001

    1,000

    500

    300

    200

    5,000

    3,000

    2,000

    1HOUR

    1MINU

    TE

    2HOURS

    CURRENT IN AMPERES

    10000

    8000

    6000

    9000

    7000

    5000

    4000

    3000

    2000

    1000

    800

    600

    900

    700

    500

    400

    300

    200

    100

    8060 907050403020109875 6

    Circuit breaker time/current curves

    Series CF-frame circuit breakers

    Catalog types ED, EHD, FDB, FD and HFD circuit breakers, two-, three-and four-poles.

    For application and coordination purposes only.Based on 40C ambient, cold start. Con nected with four (4) feet ofrated wire (60C up to 125A, 75C above 125A) per terminal.Tested in open air with current in all poles.

    Maximum Vac: 600 at 50/60 HzMaximum Vdc: 250

    Breaker rating

    Continuous amperes Instantaneous trip amperes

    80A See curve

    181865

    100

    EHDFDBFDHFD

    14143565

    141825

    10101022

    Single-pole test data at 25C based on NEMA procedures(AB4-2003) for verifying performance of molded casecircuit breakers.

    Interrupting rating (UL/CSA listed)

    Symmetrical Rms amperes (KA) Amps (KA)Breakertype @ 240 Vac @ 480 Vac @ 600 Vac 250 Vdc 125 Vdc

    ED 65 10

  • 7/26/2019 Curvas de Disparo Disyuntores

    30/5630

    Trip Curves TC01200002EEffective May 2009

    Series C F-frame circuit breakertime current curves

    EATON CORPORATIONwww.eaton.com

    Figure 28. Types ED, EHD, FDB, FD, and HFD 90ACurve No. SC-4145-87B

    MaximumMinimum

    Maximum single-pole trip timesat 25C 1

    Maximum interrupting time

    90A

    Interruptingratingdeterminesend of curve(see above)

    1

    100

    50

    30

    20

    10

    5

    3

    2

    1

    .5

    .3

    .2

    .1

    .05

    .03

    .02

    .01

    .005

    .003

    .002

    .001

    TIMEINSECONDS

    1,000

    500

    300

    200

    5,000

    3,000

    2,000

    1HOUR

    1M

    INUTE

    2HOURS

    CURRENT IN AMPERES10000

    8000

    6000

    9000

    7000

    5000

    4000

    3000

    2000

    1000

    800

    600

    900

    700

    500

    400

    300

    200

    1008060 907050403020109875 6

    TIMEINSECOND

    S

    10,000

    100

    50

    30

    20

    10

    5

    3

    2

    1

    .5

    .3

    .2

    .1

    .05

    .03

    .02

    .01

    .005

    .003

    .002

    .001

    1,000

    500

    300

    200

    5,000

    3,000

    2,000

    1HOUR

    1MINUTE

    2HOURS

    CURRENT IN AMPERES

    10000

    8000

    6000

    9000

    7000

    5000

    4000

    3000

    2000

    1000

    800

    600

    900

    700

    500

    400

    300

    200

    100

    8060 907050403020109875 6

    Circuit breaker time/current curves

    Series CF-frame circuit breakers

    Catalog types ED, EHD, FDB, FD and HFD circuit breakers, two-, three-and four-poles.

    For application and coordination purposes only.Based on 40C ambient, cold start. Connected with four (4) feet ofrated wire (60C up to 125A, 75C above 125A) per terminal.Tested in open air with current in all poles.

    Maximum Vac: 600 at 50/60 HzMaximum Vdc: 250

    Breaker rating

    Continuous amperes Instantaneous trip amperes

    90A See curve

    181865

    100

    EHDFDBFDHFD

    14143565

    141825

    10101022

    Single-pole test data at 25C based on NEMA procedures(AB4-2003) for verifying performance of molded casecircuit breakers.

    Interrupting rating (UL/CSA listed)Breaker Symmetrical Rms amperes (KA) Amps (KA)type @ 240 Vac @ 480 Vac @ 600 Vac 250 Vdc 125 Vdc

    ED 65 10

  • 7/26/2019 Curvas de Disparo Disyuntores

    31/56

    Trip Curves TC0120000Effective May 2

    Series C F-frame circuit breakertime current curves

    EATON CORPORATIONwww.eaton.com

    Figure 29. Types ED, EDB, EDS, EDH, EDC, EHD, FDB, FD, and HFD 100ACurve No. SC-4146-87B

    MaximumMinimum

    Maximum single-pole trip timesat 25C 1

    Maximum interrupting time

    100A

    Interruptingratingdeterminesend of curve(see above)

    100

    50

    30

    20

    10

    5

    3

    2

    1

    .5

    .3

    .2

    .1

    .05

    .03

    .02

    .01

    .005

    .003

    .002

    .001

    TIMEINSECONDS

    1,000

    500

    300

    200

    5,000

    3,000

    2,000

    1HOUR

    1M

    INUTE

    2HOURS

    CURRENT IN AMPERES10000

    8000

    6000

    9000

    7000

    5000

    4000

    3000

    2000

    1000

    800

    600

    900

    700

    500

    400

    300

    200

    1008060 907050403020109875 6

    TIMEINSECOND

    S

    10,000

    100

    50

    30

    20

    10

    5

    3

    2

    1

    .5

    .3

    .2

    .1

    .05

    .03

    .02

    .01

    .005

    .003

    .002

    .001

    1,000

    500

    300

    200

    5,000

    3,000

    2,000

    1HOUR

    1MIN

    UTE

    2HOURS

    CURRENT IN AMPERES

    10000

    8000

    6000

    9000

    7000

    5000

    4000

    3000

    2000

    1000

    800

    600

    900

    700

    500

    400

    300

    200

    100

    8060 907050403020109875 6

    Circuit breaker time/current curves

    Series CF-frame circuit breakers

    Catalog types ED, EDB, EDS, EDH, EDC, EHD, FDB, FD and HFD circuit

    breakers, two-, three- and four-poles.

    For application and coordination purposes o nly.Based on 40C ambient, cold start. Connected with four (4) feet ofrated wire (60C up to 125A, 75C above 125A) per terminal.Tested in open air with current in all pol es.

    Single-pole test data at 25C based on NEMA procedures(AB4-2003) for verifying performance of molded casecircuit breakers.

    Maximum Vac: 600 at 50/60 HzMaximum Vdc: 250

    Breaker rating

    Continuous amperes Instantaneous trip amperes

    100A See curve

    Interrupting rating (UL/CSA listed)Breaker Symmetrical Rms amperes (KA) Amps (KA)type @ 240 Vac @ 480 Vac @ 600 Vac 250 Vdc 125 Vdc

    1

    EDEDB

    HFDFDFDBEHD

    EDSEDHEDC

    100 65 25 22 65 35 18 10 18 14 14 10 18 14 10 200 10100 1042 1022 1065 10

  • 7/26/2019 Curvas de Disparo Disyuntores

    32/5632

    Trip Curves TC01200002EEffective May 2009

    Series C F-frame circuit breakertime current curves

    EATON CORPORATIONwww.eaton.com

    Figure 30. Types ED, EDB, EDS, EDH, EDC, FDB, FD, and HFD 110ACurve No. SC-4147-87B

    MaximumMinimum

    Maximum interrupting time

    Maximum single-pole trip timesat 25C 1

    110A

    Interruptingratingdeterminesend of curve(see above)

    100

    50

    30

    20

    10

    5

    3

    2

    1

    .5

    .3

    .2

    .1

    .05

    .03

    .02

    .01

    .005

    .003

    .002

    .001

    TIMEINSECONDS

    1,000

    500

    300

    200

    5,000

    3,000

    2,000

    1HOUR

    1MINUTE

    2HOURS

    CURRENT IN AMPERES10000

    8000

    6000

    9000

    7000

    5000

    4000

    3000

    2000

    1000

    800

    600

    900

    700

    500

    400

    300

    200

    1008060 907050403020109875 6

    TIMEINSECONDS

    10,000

    100

    50

    30

    20

    10

    5

    3

    2

    1

    .5

    .3

    .2

    .1

    .05

    .03

    .02

    .01

    .005

    .003

    .002

    .001

    1,000

    500

    300

    200

    5,000

    3,000

    2,000

    1HOUR

    1MIN

    UTE

    2HOURS

    CURRENT IN AMPERES

    10000

    8000

    6000

    9000

    7000

    5000

    4000

    3000

    2000

    1000

    800

    600

    900

    700

    500

    400

    300

    200

    100

    8060 907050403020109875 6

    Circuit breaker time/current curves

    Series CF-frame circuit breakers

    Catalog types ED, EDB, EDS, EDH, EDC, FDB, FD and HFD circuitbreakers, two-, three- and four-poles.

    For application and coordination purposes only.Based on 40C ambient, cold start. Connected with four (4) feet ofrated wire (60C up to 125A, 75C above 125A) per terminal.Tested in open air with current in all poles.

    Single-pole test data at 25C based on NEMA procedures(AB4-2003) for verifying performance of molded casecircuit breakers.

    1

    Maximum Vac: 600 at 50/60 HzMaximum Vdc: 250Breaker rating

    Continuous amperes Instantaneous trip amperes

    110A See curve

    Interrupting rating (UL/CSA listed)Breaker Symmetrical Rms amperes (KA) Amps (KA)type @ 240 Vac @ 480 Vac @ 600 Vac 250 Vdc 125 Vdc

    HFDFDFDB

    EDEDBEDSEDHEDC

    100 65 25 22 65 35 18 10 18 14 14 10 200 10100 1042 1022 1065 10

  • 7/26/2019 Curvas de Disparo Disyuntores

    33/56

    Trip Curves TC0120000Effective May 2

    Series C F-frame circuit breakertime current curves

    EATON CORPORATIONwww.eaton.com

    Figure 31. Types ED, EDB, EDS, EDH, EDC, FDB, FD, and HFD 125ACurve No. SC-4148-87B

    MaximumMinimum

    Maximum single-pole trip timesat 25C 1

    Maximum interrupting t ime

    125A

    Interruptingratingdeterminesend of curve(see above)

    100

    50

    30

    20

    10

    5

    3

    2

    1

    .5

    .3

    .2

    .1

    .05

    .03

    .02

    .01

    .005

    .003

    .002

    .001

    TIMEINSECONDS

    1,000

    500

    300

    200

    5,000

    3,000

    2,000

    1HOUR

    1

    MINUTE

    2HOURS

    CURRENT IN AMPERES10000

    8000

    6000

    9000

    7000

    5000

    4000

    3000

    2000

    1000

    800

    600

    900

    700

    500

    400

    300

    200

    1008060 907050403020109875 6

    TIMEINSECONDS

    10,000

    100

    50

    30

    20

    10

    5

    3

    2

    1

    .5

    .3

    .2

    .1

    .05

    .03

    .02

    .01

    .005

    .003

    .002

    .001

    1,000

    500

    300

    200

    5,000

    3,000

    2,000

    1HOUR

    1MINU

    TE

    2HOURS

    CURRENT IN AMPERES

    10000

    8000

    6000

    9000

    7000

    5000

    4000

    3000

    2000

    1000

    800

    600

    900

    700

    500

    400

    300

    200

    100

    8060 907050403020109875 6

    Circuit breaker time/current curves

    Series CF-frame circuit breakers

    Catalog types ED, EDB, EDS, EDH, EDC, FDB, FD and HFD circuitbreakers, two-, three- and four-poles.

    For application and coordination purposes only.Based on 40C ambient, cold start. Connected with four (4) feet ofrated wire (60C up to 125A, 75C above 125A) per terminal.Tested in open air with current in all poles.

    Single-pole test data at 25C based on NEMA procedures(AB4-2003) for verifying performance of molded casecircuit breakers.

    Maximum Vac: 600 at 50/60 HzMaximum Vdc: 250

    Breaker rating

    Continuous amperes Instantaneous trip amperes

    125A See curve

    Interrupting rating (UL/CSA listed)

    Symmetrical Rms amperes (KA) Amps (KA)Breaker

    @ 240 Vac @ 480 Vac @ 600 Vac 250 Vdc 125 Vdctype

    1

    HFDFDFDB

    100 65 25 22 65 35 18 10

    18 14 14 10

    EDEDBEDSEDHEDC

    65 1022 1042 10100 10200 10

  • 7/26/2019 Curvas de Disparo Disyuntores

    34/5634

    Trip Curves TC01200002EEffective May 2009

    Series C F-frame circuit breakertime current curves

    EATON CORPORATIONwww.eaton.com

    Figure 32. Types ED, EDB, EDS, EDH, EDC, FDB, FD, and HFD 150ACurve No. SC-4149-87B

    MaximumMinimum

    Maximum single-pole trip timesat 25C 1

    Maximum interrupting time

    150A

    Interruptingratingdeterminesend of curve(see above)

    100

    50

    30

    20

    10

    5

    3

    2

    1

    .5

    .3

    .2

    .1

    .05

    .03

    .02

    .01

    .005

    .003

    .002

    .001

    TIMEINSECONDS

    1,000

    500

    300

    200

    5,000

    3,000

    2,000

    1HOUR

    1MINUTE

    2HOURS

    CURRENT IN AMPERES10000

    8000

    6000

    9000

    7000

    5000

    4000

    3000

    2000

    1000

    800

    600

    900

    700

    500

    400

    300

    200

    1008060 907050403020109875 6

    TIMEINSECONDS

    10,000

    100

    50

    30

    20

    10

    5

    3

    2

    1

    .5

    .3

    .2

    .1

    .05

    .03

    .02

    .01

    .005

    .003

    .002

    .001

    1,000

    500

    300

    200

    5,000

    3,000

    2,000

    1HOUR

    1MINUTE

    2HOURS

    CURRENT IN AMPERES

    10000

    8000

    6000

    9000

    7000

    5000

    4000

    3000

    2000

    1000

    800

    600

    900

    700

    500

    400

    300

    200

    100

    8060 907050403020109875 6

    Circuit breaker time/current curves

    Series CF-frame circuit breakers

    Catalog types ED, EDB, EDS, EDH, EDC, FDB, FD and HFD circuitbreakers, two-, three- and four-poles.

    For application and coordination purposes only.Based on 40C ambient, cold start. Connected with four (4) feet ofrated wire (60C up to 125A, 75C above 125A) per terminal.Tested in open air with current in all poles.

    Single-pole test data at 25C based on NEMA procedures(AB4-2003) for verifying performance of molded casecircuit breakers.

    1

    Maximum Vac: 600 at 50/60 HzMaximum Vdc: 250

    Breaker rating

    Continuous amperes Instantaneous trip amperes

    150A See curve

    Interrupting rating (UL/CSA listed)

    Breaker Symmetrical Rms amperes (KA) Amps (KA)type @ 240 Vac @ 480 Vac @ 600 Vac 250 Vdc 125 Vdc

    HFDFDFDB

    100 65 25 22 65 35 18 10 18 14 14 10

    EDEDBEDSEDHEDC

    65 1022 1042 10

    100 10200 10

  • 7/26/2019 Curvas de Disparo Disyuntores

    35/56

    Trip Curves TC0120000Effective May 2

    Series C F-frame circuit breakertime current curves

    EATON CORPORATIONwww.eaton.com

    Figure 33. Types FD and HFD 175225ACurve No. SC-6970-98

    Maximum single-pole trip timesat 25C

    Maximumtrip time

    Minimumtrip time

    175 A

    200 A

    225 A

    100

    50

    30

    20

    10

    5

    3

    2

    1

    .5

    .3

    .2

    .1

    .05

    .03

    .02

    .01

    .005

    .003

    .002

    .001

    TIMEINSECONDS

    1,000

    500

    300

    200

    5,000

    3,000

    2,000

    1HOU

    R

    1MINUT

    E

    2HOURS

    TIMEINSECO

    NDS

    10,000

    100

    50

    30

    20

    10

    5

    3

    2

    1

    .5

    .3

    .2

    .1

    .05

    .03

    .02

    .01

    .005

    .003

    .002

    .001

    1,000

    500

    300

    200

    5,000

    3,000

    2,000

    1HOUR

    1

    MINUTE

    2HOURS

    175225A

    Circuit breaker time/current curves

    molded-case circuit breakers

    Catalog types FD/HFD circuit breakers, two-, three- and four-poles.

    For application and coordination purposes only.Based on 40C ambient, cold start. Connected with four (4) feet of ratedwire (75C) per terminal. Tested in open air with current in all poles.

    Maximum Vac: 600 at 50/60 HzMaximum Vdc: 250

    Breaker rating

    Inamperes Instantaneous pick-up, amperes Rms

    175 2400

    200 2400

    225 2400

    Breakertype

    Symmetrical Rms amperes (kA), Icu

    FDHFD

    Fixed inverse time overcurrent release.

    Single-pole test data at 25 C based on NEMA procedures (AB4-2003)for verifying performances of molded case circuit breakers.Total operation time.

    terrupting rating determines end of curve.In this interruption region:

    The curve is drawn for In= 200A. Fo