INFORME IEP AR-010/2014 INFORME DE ESTUDIO DE PROTECCIONES “NUEVA SUBESTACIÓN GORBEA 66/13,2 KV” OCTUBRE 2014 Documento INFORME IEP AR-010/2014 Preparó Jorge Nahuelcheo G. Supervisor de Mantenimiento Revisó Mauricio Salgado M. Jefe Área Mantenimiento

Upload: others

Post on 03-Jul-2020

0 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

INFORME IEP AR-010/2014

INFORME DE ESTUDIO DE PROTECCIONES

“NUEVA SUBESTACIÓN GORBEA 66/13,2 KV”

OCTUBRE 2014

Documento INFORME IEP AR-010/2014

Preparó Jorge Nahuelcheo G.

Supervisor de Mantenimiento

Revisó Mauricio Salgado M.

Jefe Área Mantenimiento

Page 2: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 2 de 121

ÍNDICE

1. INTRODUCCIÓN ............................................................................... 4

2. OBJETIVOS .................................................................................... 4

3. ANTECEDENTES UTILIZADOS ............................................................... 4

3.1. PARÁMETROS UTILIZADOS EN LA MODELACIÓN DEL SISTEMA .............................. 4

3.1.1. LÍNEAS .................................................................................................... 5

3.1.2. TRANSFORMADOR ...................................................................................... 5

3.2. BASE DE DATOS UTILIZADA EN EL ESTUDIO ................................................... 5

3.3. AJUSTES ACTUALES DE LAS PROTECCIONES .................................................. 6

4. CASOS ANALIZADOS ......................................................................... 7

4.4.1. ESCENARIO 1 ............................................................................................ 7

4.4.2. ESCENARIO 2 ............................................................................................ 7

4.4.3. ESCENARIO 3 ............................................................................................ 7

4.4.4. ESCENARIO 4 ............................................................................................ 8

4.4.5. ESCENARIO 5 ............................................................................................ 8

5. CRITERIOS Y AJUSTES PROYECTADOS. .................................................. 9

5.1. S/E GORBEA PROTECCIONES TRANSFORMADOR T1 .......................................... 9

5.1.1. PROTECCIÓN DE SOBRECORRIENTE LADO 66 KV TRANSFORMADOR T1 (89BT1-F) ........... 9

5.1.2. PROTECCIÓN DE SOBRECORRIENTE LADO 13,2 KV TRANSFORMADOR T1 (CT1) .............. 9

6. NIVELES DE CORTOCIRCUITO ............................................................. 10

6.1. ESCENARIO 1 .................................................................................... 10

6.2. ESCENARIO 2 .................................................................................... 10

6.3. ESCENARIO 3 .................................................................................... 10

6.4. ESCENARIO 4 .................................................................................... 11

6.5. ESCENARIO 5 .................................................................................... 11

7. RESUMEN DE NUEVOS AJUSTES .......................................................... 12

7.1. GORBEA - PROTECCIONES TRANSFORMADOR T1 ............................................ 12

7.1.1. PROTECCIÓN DE SOBRECORRIENTE EN 66 KV TRANSFORMADOR T1 (89BT1-F) ........... 12

7.1.2. PROTECCIÓN DE SOBRECORRIENTE EN 13,2 KV TRANSFORMADOR T1 (52CT1) ........... 12

7.1. GORBEA - PROTECCIONES ALIMENTADOR 52C1 (CODINER) ................................ 12

8. DIAGRAMAS DE AJUSTE DE PROTECCIONES ............................................ 13

8.1. S/E GORBEA 89BT1-F – 52CT1 – 52C1 ........................................................ 13

9. VERIFICACIÓN DE COORDINACIÓN DE PROTECCIONES ............................... 14

9.1. ESCENARIO 1 .......................................................................................... 15

9.1.1. Ruta 1: Temuco B2 -> Gorbea 13,2 kV ........................................................... 16

Page 3: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 3 de 121

9.1.2. Ruta 2: Pullinque B4 -> Gorbea 13,2 kV .......................................................... 27

9.2. ESCENARIO 2 .......................................................................................... 38

9.2.1. Ruta 3: Temuco B6 -> Gorbea 13,2 kV ................................................................ 39

9.2.2. Ruta 4: Pullinque B2 -> Gorbea 13,2 kV .............................................................. 50

9.3. ESCENARIO 3 .......................................................................................... 61

9.3.1. Ruta 1: Temuco B2 -> Gorbea 13,2 kV ................................................................ 62

9.3.2. Ruta 2: Pullinque B4 -> Gorbea 13,2 kV .............................................................. 73

9.4. ESCENARIO 4 .......................................................................................... 84

9.4.1. Ruta 2: Pullinque B4 -> Gorbea 13,2 kV .............................................................. 85

9.5. ESCENARIO 5 .......................................................................................... 96

9.5.1. Ruta 1: Temuco B2 -> Gorbea 13,2 kV ................................................................ 97

10. CONCLUSIONES ............................................................................ 108

ANEXO - AJUSTES ACTUALES DE PROTECCIONES CONSIDERADAS .................... 110

1. TEMUCO .................................................................................... 110

1.1. INTERRUPTORES DE LINEA TEMUCO - LONCOCHE, CIRCUITOS 1 Y 2 (52B6 Y 52B2) . 110

2. LONCOCHE ................................................................................. 113

2.1.- INTERRUPTORES DE LINEA LONCOCHE - TEMUCO, CIRCUITOS 1 Y 2 (52B6 Y 52B3) . 113

2.1.1. GRUPO DE AJUSTES N°1 ........................................................................... 113

2.1.2. GRUPO DE AJUSTES N°2 ........................................................................... 116

3. PULLINQUE ................................................................................ 119

3.1. INTERRUPTORES DE LINEA PULLINQUE – LONCOCHE, CIRCUITOS 1 Y 2 (52B2 Y 52B4) 119

Page 4: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 4 de 121

1. INTRODUCCIÓN

La nueva S/E Gorbea 66/13,2 kV, de propiedad de TRANSNET, se conectará a las líneas de 66 kV

Temuco - Loncoche, quedando ubicada aproximadamente a 33,17 km desde S/E Loncoche y a 46,78 km

desde S/E Temuco. Se contempla la conexión de un transformador de 5 MVA 66/13,2 kV el cual contará

con desconectadores fusibles en 66 kV y un reconectador Siemens con unidad de control Argus como

interruptor general de media tensión 52CT1. Esta subestación alimentará los consumos del alimentador

52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como

equipos de protección

2. OBJETIVOS

El presente estudio tiene por objetivo proponer ajustes para las nuevas protecciones de

sobrecorriente que poseerá el transformador T1 y el alimentador 52C1 de S/E Gorbea.

Transformador T1-49600

Fusibles S&C SMD 1A : Protección de sobrecorriente en 66 kV

Reconectador SIEMENS : Protección de sobrecorriente en 13,2 kV

(Unidad Argus)

Alimentador 52C1:

Reconectador SIEMENS : Protección de sobrecorriente en 13,2 kV

(Unidad Argus)

3. ANTECEDENTES UTILIZADOS

3.1. PARÁMETROS UTILIZADOS EN LA MODELACIÓN DEL SISTEMA

En la modelación del sistema en estudio, se consideraron los parámetros de líneas y

transformadores, según el detalle que se indica a continuación:

Page 5: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 5 de 121

3.1.1. LÍNEAS

a) Línea 66 kV Temuco – Gorbea N°1:

Longitud 47,8 km Impedancia de secuencia positiva 17,591 + j19,549 Ω Impedancia de secuencia cero 24,674 + j73,077 Ω

b) Línea 66 kV Temuco – Gorbea N°2:

Longitud 47,8 km Impedancia de secuencia positiva 17,572 + j19,528 Ω Impedancia de secuencia cero 24,648 + j73,000 Ω

c) Línea 66 kV Loncoche – Gorbea N°1:

Longitud 33,17 km Impedancia de secuencia positiva 12,488 + j13,625 Ω Impedancia de secuencia cero 17,397 + j50,722 Ω

d) Línea 66 kV Loncoche – Gorbea N°2:

Longitud 33,17 km Impedancia de secuencia positiva 12,488 + j13,625 Ω Impedancia de secuencia cero 17,397 + j50,722 Ω

3.1.2. TRANSFORMADOR

a) S/E Gorbea Transformador T1 - 49600:

Potencia : 5/6,25 MVA

Conexión : Yz1d1

Tensiones nominales : 66/13,8/3kV

Impedancia de secuencia positiva : 7% (Base 5 MVA y tensiones nominales)

3.2. BASE DE DATOS UTILIZADA EN EL ESTUDIO

La base de datos utilizada en el estudio corresponde a la preparada por el CDEC-SIC con fecha

de actualización Agosto de 2014.

Page 6: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 6 de 121

3.3. AJUSTES ACTUALES DE LAS PROTECCIONES

Los ajustes actuales de las protecciones consideradas en este estudio se resumen en el Anexo

de este informe.

3.4. DIAGRAMA UNILINEAL DEL SISTEMA EN ESTUDIO

GORBEA

Page 7: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 7 de 121

4. CASOS ANALIZADOS

Para determinar los ajustes a implementar en las protecciones de S/E Gorbea se analizarán los

siguientes escenarios de operación:

4.4.1. ESCENARIO 1

Corresponde al escenario normal de operación:

LT 66kV Temuco – Loncoche N°1 en servicio

LT 66kV Temuco – Loncoche N°2 en servicio

LT 66kV Pullinque – Loncoche N°1 en servicio

LT 66kV Pullinque – Loncoche N°2 en servicio

S/E Gorbea conectada a la LT 66kV Temuco - Loncoche N°2

4.4.2. ESCENARIO 2

Corresponde a un escenario de operación alternativo:

LT 66kV Temuco – Loncoche N°1 en servicio

LT 66kV Temuco – Loncoche N°2 fuera de servicio

LT 66kV Pullinque – Loncoche N°1 en servicio

LT 66kV Pullinque – Loncoche N°2 en servicio

S/E Gorbea conectada a la LT 66kV Temuco - Loncoche N°1

4.4.3. ESCENARIO 3

Corresponde a un escenario de operación alternativo:

LT 66kV Temuco – Loncoche N°1 en servicio

LT 66kV Temuco – Loncoche N°2 en servicio

LT 66kV Pullinque – Loncoche N°1 fuera de servicio

LT 66kV Pullinque – Loncoche N°2 en servicio

S/E Gorbea conectada a la LT 66kV Temuco - Loncoche N°2

Page 8: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 8 de 121

4.4.4. ESCENARIO 4

Corresponde a un escenario de operación alternativo en donde S/E Gorbea es alimentada

radialmente desde S/E Loncoche a través de la LT 66kV Loncoche – Temuco. Para este caso se

considerarán los siguientes estados para los interruptores en los extremos Loncoche y Temuco:

S/E Loncoche:

52B3 Cerrado, alimentando radialmente a SE Gorbea

52B6 Cerrado

S/E Temuco:

52B2 Abierto

52B6 Cerrado

4.4.5. ESCENARIO 5

Corresponde a un escenario de operación alternativo en donde S/E Gorbea es alimentada

radialmente desde S/E Temuco a través de la LT 66kV Temuco – Loncoche. Para este caso se

considerarán los siguientes estados para los interruptores en los extremos Temuco y Loncoche

S/E Temuco:

52B2 Cerrado, alimentando radialmente a SE Gorbea

52B6 Cerrado

S/E Loncoche:

52B3 Abierto

52B6 Cerrado

Page 9: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 9 de 121

5. CRITERIOS Y AJUSTES PROYECTADOS.

Como criterio general de coordinación de protecciones se establece un paso mínimo de

coordinación de 0,3 segundos entre dos protecciones que se encuentren en forma consecutiva y que

operen frente a una misma falla.

5.1. S/E GORBEA PROTECCIONES TRANSFORMADOR T1

5.1.1. PROTECCIÓN DE SOBRECORRIENTE LADO 66 KV TRANSFORMADOR T1 (89BT1-F)

El transformador T1 contará con desconectadores fusibles como elementos de protección en

lado de 66 kV.

Para la elección del fusible a utilizar se considerará la potencia total ONAF del Transformador

más un 20% de sobrecarga:

Se elige Desconectador Fusible S&C SMD 1A Fusible: 65E Very Slow Speed

5.1.2. PROTECCIÓN DE SOBRECORRIENTE LADO 13,2 KV TRANSFORMADOR T1 (CT1)

En el paño 52CT1 se instalará un Reconectador SIEMENS con unidad de control Argus, el cual

contará con elementos de sobrecorriente de fase y residual.

El pick up de fase en 13,2 kV se ajustará a la potencia nominal ONAF del transformador T2,

considerando un 20% de sobrecarga controlada.

I nominal CT1 =

I pick up fase CT1 =

Por otro lado, el pick up residual se ajustará al aproximadamente al 10 % del ajuste de fase:

I pick up residual CT1 =

Las características tiempo-corriente del paño CT1 deberán coordinar con los fusibles en 66 kV y

los alimentadores de media tensión, ante fallas en la barra de 13,2 kV.

Page 10: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 10 de 121

6. NIVELES DE CORTOCIRCUITO

A continuación se indican los niveles de cortocircuito en S/E Gorbea para los escenarios de

operación indicados en el punto 4 de este informe.

6.1. ESCENARIO 1

Instalación Falla 3F

[kA]

Falla 2F

[kA]

Falla 2F-T

[kA]

I fase

3xI0

Falla 1F

[kA]

F F R Ω

[kA]

S/E Gorbea

Barra 66 kV 2,517 2,183

2,429

1,308 1,736 1,009

S/E Gorbea

Barra 13,2 kV 2,518 2,181

2,767

3,196 2,818 0,326

6.2. ESCENARIO 2

Instalación Falla 3F

[kA]

Falla 2F

[kA]

Falla 2F-T

[kA]

I fase

3xI0

Falla 1F

[kA]

F F R Ω

[kA]

S/E Gorbea

Barra 66 kV 2,388 2,066

2,304

1,261 1,661 0,989

S/E Gorbea

Barra 13,2 kV 2,489 2,154

2,743

3,181 2,792 0,326

6.3. ESCENARIO 3

Instalación Falla 3F

[kA]

Falla 2F

[kA]

Falla 2F-T

[kA]

I fase

3xI0

Falla 1F

[kA]

F F R Ω

[kA]

S/E Gorbea

Barra 66 kV 2,375 2,062

2,298

1,226 1,634 0,979

S/E Gorbea

Barra 13,2 kV 2,489 2,156

2,746

3,180 2,795 0,326

Page 11: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 11 de 121

6.4. ESCENARIO 4

Instalación Falla 3F

[kA]

Falla 2F

[kA]

Falla 2F-T

[kA]

I fase

3xI0

Falla 1F

[kA]

F F R Ω

[kA]

S/E Gorbea

Barra 66 kV 1,052 0,904

1,011

0,594 0,758 0,606

S/E Gorbea

Barra 13,2 kV 1,945 1,678

2,289

2,853 2,306 0,321

6.5. ESCENARIO 5

Instalación Falla 3F

[kA]

Falla 2F

[kA]

Falla 2F-T

[kA]

I fase

3xI0

Falla 1F

[kA]

F F R Ω

[kA]

S/E Gorbea

Barra 66 kV 1,408 1,224

1,357

0,673 0,923 0,689

S/E Gorbea

Barra 13,2 kV 2,181 1,891

2,513

3,005 2,532 0,322

Page 12: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 12 de 121

7. RESUMEN DE NUEVOS AJUSTES

7.1. GORBEA - PROTECCIONES TRANSFORMADOR T1

7.1.1. PROTECCIÓN DE SOBRECORRIENTE EN 66 KV TRANSFORMADOR T1 (89BT1-F)

Desconectador fusible S&C SMD 1-A Fusible: 65E Very Slow Speed

7.1.2. PROTECCIÓN DE SOBRECORRIENTE EN 13,2 KV TRANSFORMADOR T1 (52CT1)

Unidad de Control Argus

Reconectador SIEMENS

TTCC 800/1

Elemento Protección de Fase Protección Residual.

Pick Up [A] 0,41 A-sec (328 A-prim) 0,044 (35,2 A-prim)

Curva Curva 165 C1 (IEC Standard Inverse)

Multiplicador 1,10 0,55

Sumador 0,00 0,00

Reconexiones

Sin reconexión

Tiempos de operación Fase [s] Residual [s]

3 x pu 3,527 3,466

5 x pu 0,947 2,354

8 x pu 0,387 1,813

7.1. GORBEA - PROTECCIONES ALIMENTADOR 52C1 (CODINER)

Unidad de Control Argus

Reconectador SIEMENS

TTCC 800/1

Elemento Protección de Fase Protección Residual.

Pick Up [A] 0,12 A-sec (96 A-prim) 0,025 A-sec (20 A-prim)

Curva Curva 162 C1 (IEC Standard Inverse)

Multiplicador 1,60 0,40

Sumador 0,00 0,00

Reconexiones

1

Tiempo de reconexión 5 seg

Reset 10 seg

Tiempos de operación Fase [s] Residual [s]

3 x pu 2,517 2,521

5 x pu 0,778 1,712

8 x pu 0,292 1,319

Page 13: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 13 de 121

8. DIAGRAMAS DE AJUSTE DE PROTECCIONES

8.1. S/E GORBEA 89BT1-F – 52CT1 – 52C1

10 100 1000 10000 1000000,01

0,1

1

10

100

1000

10 100 1000 10000

13,20 kV

66,00 kV

Gorbea_13.2kV\Cub_1\Gorbea_52CT1 Gorbea_13.2kV\Cub_2\Gorbea_52C1

T1 Gorbea_66kV\Cub_4\Gorbea_89BT1F

T-49600 strn: 5,00 MVA uktr: 7,00 %

Gorbea_89BT1F 65E SMD-176-161

Gorbea_52C1 162 Ipset: 0,12 sec.A Tpset: 1,60

Gorbea_52CT1 165 Ipset: 0,41 sec.A Tpset: 1,10

Gorbea_52C1 C1 - IEC Class A (Standard Inverse) Ipset: 0,03 sec.A Tpset: 0,40

Gorbea_52CT1 C1 - IEC Class A (Standard Inverse) Ipset: 0,04 sec.A Tpset: 0,55

Protecciones Gorbea

Date: 11/6/2014

Annex:

DIg

SIL

EN

T

Page 14: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 14 de 121

9. VERIFICACIÓN DE COORDINACIÓN DE PROTECCIONES

En este estudio se han modelado en DigSilent Power Factory los esquemas de protección del

transformador T1 y el alimentador 52C1 de S/E Gorbea. Además, a fin de verificar la coordinación con

el resto de las protecciones del sistema, se han modelado las protecciones de los paños B2 y B6 de S/E

Temuco, B3 y B6 de S/E Loncoche y los paños B2 y B4 S/E Pullinque.

Para la verificación de coordinación de protecciones se realizaron simulaciones de

cortocircuitos para fallas trifásicas, bifásicas, bifásicas a tierra, monofásicas a tierra y monofásicas a

tierra con resistencia de 25 Ohm.

Para la realización de las simulaciones, se utilizó un barrido de cortocircuito cada 0,5 km a lo

largo de cada una de las rutas definidas para los cinco escenarios en estudio. De esta forma se

determinó el tiempo de operación de las protecciones involucradas para cada ruta estudiada. En estos

anexos se han incluido los resultados gráficos y cuantitativos de los barridos de cortocircuito efectuados

sobre cada ruta.

En cada tabla se indica el tipo de falla, la ubicación de ésta, el punto donde se realiza la

medida, la función de protección operada y el tiempo de operación de los elementos de protección.

A continuación se detallan las rutas utilizadas en la verificación de coordinación de

protecciones, de acuerdo a los escenarios de operación definidos en el punto 4 de este informe:

Escenario Rutas Descripción

Escenario 1 Ruta 1: Temuco B2 -> Gorbea 13,2 kV

Escenario Normal. Ruta 2: Pullinque B4 -> Gorbea 13,2 kV

Escenario 2 Ruta 3: Temuco B6 -> Gorbea 13,2 kV

LT 66kV Temuco – Loncoche N°2 fuera de servicio. Ruta 4: Pullinque B2 -> Gorbea 13,2 kV

Escenario 3 Ruta 1: Temuco B2 -> Gorbea 13,2 kV

LT 66kV Pullinque – Loncoche N°1 fuera de servicio. Ruta 2: Pullinque B4 -> Gorbea 13,2 kV

Escenario 4 Ruta 2: Pullinque B4 -> Gorbea 13,2 kV S/E Gorbea alimentada radialmente desde S/E Loncoche.

Escenario 5 Ruta 1: Temuco B2 -> Gorbea 13,2 kV S/E Gorbea alimentada radialmente desde S/E Temuco.

Cabe destacar que para todos los escenarios analizados se observaron tiempos de paso que

garantizan la operación selectiva de las protecciones involucradas.

Page 15: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 15 de 121

9.1. ESCENARIO 1

LT 66kV Temuco – Loncoche N°1 en servicio

LT 66kV Temuco – Loncoche N°2 en servicio

LT 66kV Pullinque – Loncoche N°1 en servicio

LT 66kV Pullinque – Loncoche N°2 en servicio

S/E Gorbea conectada a la LT 66kV Temuco - Loncoche N°2

Page 16: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 16 de 121

9.1.1. Ruta 1: Temuco B2 -> Gorbea 13,2 kV

Page 17: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 17 de 121

9.1.1.1. FALLA 3F TEMUCO B2 -> GORBEA 13,2 KV

62,81150,24937,68725,12412,5620,0000 [km]

5,00

4,00

3,00

2,00

1,00

0,00

Tem_66kV_ Tap Padre La..

Tap Licanco ..

Pitrufquen 6.. Cto2

Gorbea_66kV

Bushing_66kV

Gorbea_13.2k..

LMT_13.2

x-Axis: Length Tem\52B2\Tem_52B2 Gorbea_66kV\Cub_4\Gorbea_89BT1F Gorbea_13.2kV\Cub_1\Gorbea_52CT1

Gorbea_13.2kV\Cub_2\Gorbea_52C1

TD1_Tem -> Gorbea MT_3F

Date: 11/6/2014

Annex:

DIg

SIL

EN

T

Page 18: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 18 de 121

Tipo Falla : 3F RF= 0 Ohm

Ruta : Temuco B2 - Gorbea 13,2kV

Tiempos de Operación en segundos

S/E Paño Relé NEMA Temuco

66kV

LT 66kV Temuco - Gorbea

Gorbea 66kV

Gorbea Bushing 66kV T1

Gorbea Barra

13,2kV

Línea de Media Tensión 13,2 kV

Padre Las Casas 66kV

Tap Licanco

66kV

Pitrufquén 66 kV

1% 25% 50% 75% 99%

Temuco 52B2 SEL-311C Trip --- 0,02 0,02 0,02 0,02 0,02 --- --- --- --- --- ---

Temuco 52B2 SEL-311C 21-Z1 --- 0,02 0,02 0,02 0,02 0,02 --- --- --- --- --- ---

Temuco 52B2 SEL-311C 21-Z2 --- 0,82 0,82 0,82 0,82 0,82 --- --- --- --- --- ---

Temuco 52B2 SEL-311C 21-Z3 --- 2,72 2,72 2,72 2,72 2,72 --- --- --- --- --- ---

Temuco 52B2 SEL-311C 21N-Z1 --- --- --- --- --- --- --- --- --- --- --- ---

Temuco 52B2 SEL-311C 21N-Z2 --- --- --- --- --- --- --- --- --- --- --- ---

Temuco 52B2 SEL-311C 21N-Z3 --- --- --- --- --- --- --- --- --- --- --- ---

Temuco 52B2 SEL-311C 51N --- --- --- --- --- --- --- --- --- --- --- ---

Temuco 52B2 SEL-311C 67N --- --- --- --- --- --- --- --- --- --- --- ---

Gorbea 89BT1-F Fuse SMD 65E Trip --- --- --- --- --- 0,04 0,87 0,98 2,19 4,16 8,23 14,56

Gorbea 52CT1 Siemens Argus Trip --- --- --- --- --- --- 0,42 0,47 0,95 1,86 3,73 6,32

Gorbea 52CT1 Siemens Argus 51N --- --- --- --- --- --- --- --- --- --- --- ---

Gorbea 52CT1 Siemens Argus 51 --- --- --- --- --- --- 0,42 0,47 0,95 1,86 3,73 6,32

Gorbea 52C1 Siemens Argus Trip --- --- --- --- --- --- --- 0,04 0,07 0,12 0,18 0,25

Gorbea 52C1 Siemens Argus 51N --- --- --- --- --- --- --- --- --- --- --- ---

Gorbea 52C1 Siemens Argus 51 --- --- --- --- --- --- --- 0,04 0,07 0,12 0,18 0,25

Page 19: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 19 de 121

9.1.1.2. FALLA 2F TEMUCO B2 -> GORBEA 13,2 KV

62,81150,24937,68725,12412,5620,0000 [km]

5,00

4,00

3,00

2,00

1,00

0,00

Tem_66kV_ Tap Padre La..

Tap Licanco ..

Pitrufquen 6.. Cto2

Gorbea_66kV

Bushing_66kV

Gorbea_13.2k..

LMT_13.2

x-Axis: Length Tem\52B2\Tem_52B2 Gorbea_66kV\Cub_4\Gorbea_89BT1F Gorbea_13.2kV\Cub_1\Gorbea_52CT1

Gorbea_13.2kV\Cub_2\Gorbea_52C1

TD1_Tem -> Gorbea MT_2F

Date: 11/6/2014

Annex:

DIg

SIL

EN

T

Page 20: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 20 de 121

Tipo Falla : 2F RF= 0 Ohm

Ruta : Temuco B2 - Gorbea 13,2kV

Tiempos de Operación en segundos

S/E Paño Relé NEMA Temuco

66kV

LT 66kV Temuco - Gorbea

Gorbea 66kV

Gorbea Bushing 66kV T1

Gorbea Barra

13,2kV

Línea de Media Tensión 13,2 kV

Padre Las Casas 66kV

Tap Licanco

66kV

Pitrufquén 66 kV

1% 25% 50% 75% 99%

Temuco 52B2 SEL-311C Trip --- 0,02 0,02 0,02 0,02 0,02 --- --- --- --- --- ---

Temuco 52B2 SEL-311C 21-Z1 --- 0,02 0,02 0,02 0,02 0,02 --- --- --- --- --- ---

Temuco 52B2 SEL-311C 21-Z2 --- 0,82 0,82 0,82 0,82 0,82 --- --- --- --- --- ---

Temuco 52B2 SEL-311C 21-Z3 --- 2,72 2,72 2,72 2,72 2,72 --- --- --- --- --- ---

Temuco 52B2 SEL-311C 21N-Z1 --- --- --- --- --- --- --- --- --- --- --- ---

Temuco 52B2 SEL-311C 21N-Z2 --- --- --- --- --- --- --- --- --- --- --- ---

Temuco 52B2 SEL-311C 21N-Z3 --- --- --- --- --- --- --- --- --- --- --- ---

Temuco 52B2 SEL-311C 51N --- --- --- --- --- --- --- --- --- --- --- ---

Temuco 52B2 SEL-311C 67N --- --- --- --- --- --- --- --- --- --- --- ---

Gorbea 89BT1-F Fuse SMD 65E Trip --- --- --- --- --- 0,05 0,87 0,98 2,19 4,16 8,23 14,55

Gorbea 52CT1 Siemens Argus Trip --- --- --- --- --- --- 0,54 0,61 1,34 2,69 6,12 10,37

Gorbea 52CT1 Siemens Argus 51N --- --- --- --- --- --- --- --- --- --- --- ---

Gorbea 52CT1 Siemens Argus 51 --- --- --- --- --- --- 0,54 0,61 1,34 2,69 6,12 10,37

Gorbea 52C1 Siemens Argus Trip --- --- --- --- --- --- --- 0,05 0,09 0,15 0,25 0,33

Gorbea 52C1 Siemens Argus 51N --- --- --- --- --- --- --- --- --- --- --- ---

Gorbea 52C1 Siemens Argus 51 --- --- --- --- --- --- --- 0,05 0,09 0,15 0,25 0,33

Page 21: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 21 de 121

9.1.1.3. FALLA 2F-T TEMUCO B2 -> GORBEA 13,2 KV

62,81150,24937,68725,12412,5620,0000 [km]

5,00

4,00

3,00

2,00

1,00

0,00

Tem_66kV_ Tap Padre La..

Tap Licanco ..

Pitrufquen 6.. Cto2

Gorbea_66kV

Bushing_66kV

Gorbea_13.2k..

LMT_13.2

x-Axis: Length Tem\52B2\Tem_52B2 Gorbea_66kV\Cub_4\Gorbea_89BT1F Gorbea_13.2kV\Cub_1\Gorbea_52CT1

Gorbea_13.2kV\Cub_2\Gorbea_52C1

TD1_Tem -> Gorbea MT_2F-T

Date: 11/6/2014

Annex:

DIg

SIL

EN

T

Page 22: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 22 de 121

Tipo Falla : 2FT RF= 0 Ohm

Ruta : Temuco B2 - Gorbea 13,2kV

Tiempos de Operación en segundos

S/E Paño Relé NEMA Temuco

66kV

LT 66kV Temuco - Gorbea

Gorbea 66kV

Gorbea Bushing 66kV T1

Gorbea Barra

13,2kV

Línea de Media Tensión 13,2 kV

Padre Las Casas 66kV

Tap Licanco

66kV

Pitrufquén 66 kV

1% 25% 50% 75% 99%

Temuco 52B2 SEL-311C Trip --- 0,01 0,01 0,01 0,02 0,02 --- --- --- --- --- ---

Temuco 52B2 SEL-311C 21-Z1 --- 0,02 0,02 0,02 0,02 0,02 --- --- --- --- --- ---

Temuco 52B2 SEL-311C 21-Z2 --- 0,82 0,82 0,82 0,82 0,82 --- --- --- --- --- ---

Temuco 52B2 SEL-311C 21-Z3 --- 2,72 2,72 2,72 2,72 2,72 --- --- --- --- --- ---

Temuco 52B2 SEL-311C 21N-Z1 --- 0,02 0,02 0,02 0,02 0,02 --- --- --- --- --- ---

Temuco 52B2 SEL-311C 21N-Z2 --- 0,82 0,82 0,82 0,82 0,82 --- --- --- --- --- ---

Temuco 52B2 SEL-311C 21N-Z3 --- 2,72 2,72 2,72 2,72 2,72 --- --- --- --- --- ---

Temuco 52B2 SEL-311C 51N --- 0,23 0,23 0,31 0,39 0,39 --- --- --- --- --- ---

Temuco 52B2 SEL-311C 67N --- 0,01 0,01 0,01 --- --- --- --- --- --- --- ---

Gorbea 89BT1-F Fuse SMD 65E Trip --- --- --- --- --- 0,04 0,87 0,98 2,19 4,16 8,23 14,55

Gorbea 52CT1 Siemens Argus Trip --- --- --- --- --- --- 0,35 0,43 1,04 1,25 1,42 1,54

Gorbea 52CT1 Siemens Argus 51N --- --- --- --- --- --- 0,82 0,86 1,08 1,25 1,42 1,54

Gorbea 52CT1 Siemens Argus 51 --- --- --- --- --- --- 0,35 0,43 1,04 2,10 4,44 7,55

Gorbea 52C1 Siemens Argus Trip --- --- --- --- --- --- --- 0,04 0,08 0,12 0,20 0,28

Gorbea 52C1 Siemens Argus 51N --- --- --- --- --- --- --- 0,56 0,67 0,76 0,84 0,90

Gorbea 52C1 Siemens Argus 51 --- --- --- --- --- --- --- 0,04 0,08 0,12 0,20 0,28

Page 23: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 23 de 121

9.1.1.4. FALLA 1F TEMUCO B2 -> GORBEA 13,2 KV

62,81150,24937,68725,12412,5620,0000 [km]

5,00

4,00

3,00

2,00

1,00

0,00

Tem_66kV_ Tap Padre La..

Tap Licanco ..

Pitrufquen 6.. Cto2

Gorbea_66kV

Bushing_66kV

Gorbea_13.2k..

LMT_13.2

x-Axis: Length Tem\52B2\Tem_52B2 Gorbea_66kV\Cub_4\Gorbea_89BT1F Gorbea_13.2kV\Cub_1\Gorbea_52CT1

Gorbea_13.2kV\Cub_2\Gorbea_52C1

TD1_Tem -> Gorbea MT_1F

Date: 11/6/2014

Annex:

DIg

SIL

EN

T

Page 24: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 24 de 121

Tipo Falla : 1FT RF= 0 Ohm

Ruta : Temuco B2 - Gorbea 13,2kV

Tiempos de Operación en segundos

S/E Paño Relé NEMA Temuco

66kV

LT 66kV Temuco - Gorbea

Gorbea 66kV

Gorbea Bushing 66kV T1

Gorbea Barra

13,2kV

Línea de Media Tensión 13,2 kV

Padre Las Casas 66kV

Tap Licanco

66kV

Pitrufquén 66 kV

1% 25% 50% 75% 99%

Temuco 52B2 SEL-311C Trip --- 0,01 0,01 0,01 0,02 0,02 --- --- --- --- --- ---

Temuco 52B2 SEL-311C 21-Z1 --- 0,02 0,02 --- --- --- --- --- --- --- --- ---

Temuco 52B2 SEL-311C 21-Z2 --- 0,82 0,82 --- --- --- --- --- --- --- --- ---

Temuco 52B2 SEL-311C 21-Z3 --- 2,72 2,72 2,72 2,72 2,72 --- --- --- --- --- ---

Temuco 52B2 SEL-311C 21N-Z1 --- 0,02 0,02 0,02 0,02 0,02 --- --- --- --- --- ---

Temuco 52B2 SEL-311C 21N-Z2 --- 0,82 0,82 0,82 0,82 0,82 --- --- --- --- --- ---

Temuco 52B2 SEL-311C 21N-Z3 --- 2,72 2,72 2,72 2,72 2,72 --- --- --- --- --- ---

Temuco 52B2 SEL-311C 51N --- 0,23 0,23 0,27 0,32 0,32 --- --- --- --- --- ---

Temuco 52B2 SEL-311C 67N --- 0,01 0,01 0,01 --- --- --- --- --- --- --- ---

Gorbea 89BT1-F Fuse SMD 65E Trip --- --- --- --- --- 0,08 2,21 2,95 21,16 --- --- ---

Gorbea 52CT1 Siemens Argus Trip --- --- --- --- --- --- 0,34 0,43 1,02 1,15 1,28 1,36

Gorbea 52CT1 Siemens Argus 51N --- --- --- --- --- --- 0,84 0,87 1,02 1,15 1,28 1,36

Gorbea 52CT1 Siemens Argus 51 --- --- --- --- --- --- 0,34 0,43 1,58 4,81 14,05 25,32

Gorbea 52C1 Siemens Argus Trip --- --- --- --- --- --- --- 0,04 0,10 0,21 0,39 0,58

Gorbea 52C1 Siemens Argus 51N --- --- --- --- --- --- --- 0,56 0,64 0,71 0,77 0,82

Gorbea 52C1 Siemens Argus 51 --- --- --- --- --- --- --- 0,04 0,10 0,21 0,39 0,58

Page 25: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 25 de 121

9.1.1.5. F LL 1F (R = Ω) TEMUCO B2 -> GORBEA 13,2 KV

62,81150,24937,68725,12412,5620,0000 [km]

5,00

4,00

3,00

2,00

1,00

0,00

Tem_66kV_ Tap Padre La..

Tap Licanco ..

Pitrufquen 6.. Cto2

Gorbea_66kV

Bushing_66kV

Gorbea_13.2k..

LMT_13.2

x-Axis: Length Tem\52B2\Tem_52B2 Gorbea_66kV\Cub_4\Gorbea_89BT1F Gorbea_13.2kV\Cub_1\Gorbea_52CT1

Gorbea_13.2kV\Cub_2\Gorbea_52C1

TD1_Tem -> Gorbea MT_1F_R25

Date: 11/6/2014

Annex:

DIg

SIL

EN

T

Page 26: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 26 de 121

Tipo Falla : 1FT RF= 25 Ohm

Ruta : Temuco B2 - Gorbea 13,2kV

Tiempos de Operación en segundos

S/E Paño Relé NEMA Temuco

66kV

LT 66kV Temuco - Gorbea

Gorbea 66kV

Gorbea Bushing 66kV T1

Gorbea Barra

13,2kV

Línea de Media Tensión 13,2 kV

Padre Las Casas 66kV

Tap Licanco

66kV

Pitrufquén 66 kV

1% 25% 50% 75% 99%

Temuco 52B2 SEL-311C Trip --- 0,01 0,01 0,38 0,50 0,50 --- --- --- --- --- ---

Temuco 52B2 SEL-311C 21-Z1 --- --- --- --- --- --- --- --- --- --- --- ---

Temuco 52B2 SEL-311C 21-Z2 --- --- --- --- --- --- --- --- --- --- --- ---

Temuco 52B2 SEL-311C 21-Z3 --- 2,72 2,72 --- --- --- --- --- --- --- --- ---

Temuco 52B2 SEL-311C 21N-Z1 --- 0,02 0,02 --- --- --- --- --- --- --- --- ---

Temuco 52B2 SEL-311C 21N-Z2 --- 0,82 0,82 0,82 --- --- --- --- --- --- --- ---

Temuco 52B2 SEL-311C 21N-Z3 --- 2,72 2,72 2,72 2,72 2,72 --- --- --- --- --- ---

Temuco 52B2 SEL-311C 51N --- 0,27 0,27 0,38 0,50 0,50 --- --- --- --- --- ---

Temuco 52B2 SEL-311C 67N --- 0,01 0,01 --- --- --- --- --- --- --- --- ---

Gorbea 89BT1-F Fuse SMD 65E Trip --- --- --- --- --- 0,23 --- --- --- --- --- ---

Gorbea 52CT1 Siemens Argus Trip --- --- --- --- --- --- 1,69 1,70 1,75 1,80 1,88 1,93

Gorbea 52CT1 Siemens Argus 51N --- --- --- --- --- --- 1,69 1,70 1,75 1,80 1,88 1,93

Gorbea 52CT1 Siemens Argus 51 --- --- --- --- --- --- --- --- --- --- --- ---

Gorbea 52C1 Siemens Argus Trip --- --- --- --- --- --- --- 0,98 1,00 1,03 1,06 1,08

Gorbea 52C1 Siemens Argus 51N --- --- --- --- --- --- --- 0,98 1,00 1,03 1,06 1,08

Gorbea 52C1 Siemens Argus 51 --- --- --- --- --- --- --- 1,95 2,24 2,59 3,06 3,46

Page 27: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 27 de 121

9.1.2. Ruta 2: Pullinque B4 -> Gorbea 13,2 kV

Page 28: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 28 de 121

9.1.2.1. FALLA 3F PULLINQUE B4 -> GORBEA 13,2 kV

91,82973,46355,09736,73218,3660,0000 [km]

5,00

4,00

3,00

2,00

1,00

0,00

Pull_66kV_ Lonc_66kV_ Cto2

Gorbea_66kV

Bushing_66kV

Gorbea_13.2k..

LMT_13.2

x-Axis: Length Pull\52B4\Pull_52B4 Lonc\52B3\Lonc_52B3_G1 Gorbea_66kV\Cub_4\Gorbea_89BT1F

Gorbea_13.2kV\Cub_1\Gorbea_52CT1 Gorbea_13.2kV\Cub_2\Gorbea_52C1

TD2_Pull -> Gorbea MT_3F

Date: 11/6/2014

Annex:

DIg

SIL

EN

T

Page 29: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 29 de 121

Tipo Falla : 3F RF= 0 Ohm Ruta : Pullinque B4 - Gorbea 13,kV Tiempos de Operación en segundos

S/E Paño Relé NEMA Pullinque

66kV

LT 66kV Pullinque - Loncoche

Loncoche 66kV

LT 66kV Loncoche - Gorbea

Gorbea 66kV

Gorbea Bushing

66kV T1

Gorbea 13,2kV

Línea de Media Tensión 13,2 kV

1% 25% 50% 75% 99% 1% 25% 50% 75% 99% 1% 25% 50% 75% 99%

Pullinque 52B4 SEL-311C Trip --- --- 0,02 0,02 0,02 0,82 0,82 0,82 0,82 2,72 2,72 2,72 2,72 2,72 --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21-Z1 --- --- 0,02 0,02 0,02 --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21-Z2 --- --- 0,82 0,82 0,82 0,82 0,82 0,82 0,82 --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21-Z3 --- --- 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21N-Z1 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21N-Z2 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21N-Z3 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21N_Q-Z1 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21N_Q-Z2 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21N_Q-Z3 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Loncoche 52B3 SEL-311C Trip --- --- --- --- --- --- 0,02 0,02 0,02 0,02 0,02 0,02 0,02 0,02 --- --- --- --- --- ---

Loncoche 52B3 SEL-311C 21-Z1 --- --- --- --- --- --- 0,02 0,02 0,02 0,02 0,02 0,02 0,02 0,02 --- --- --- --- --- ---

Loncoche 52B3 SEL-311C 21-Z2 --- --- --- --- --- --- 0,72 0,72 0,72 0,72 0,72 0,72 0,72 0,72 --- --- --- --- --- ---

Loncoche 52B3 SEL-311C 21-Z3 --- --- --- --- --- --- 2,02 2,02 2,02 2,02 2,02 2,02 2,02 2,02 --- --- --- --- --- ---

Loncoche 52B3 SEL-311C 21N-Z1 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Loncoche 52B3 SEL-311C 21N-Z2 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Loncoche 52B3 SEL-311C 21N-Z3 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Loncoche 52B3 SEL-311C 51N --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Gorbea 89BT1-F Fuse SMD 65E Trip --- --- --- --- --- --- --- --- --- --- --- --- --- 0,04 0,87 0,98 2,19 4,16 8,23 14,56

Gorbea 52CT1 Siemens Argus Trip --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,42 0,47 0,95 1,86 3,73 6,32

Gorbea 52CT1 Siemens Argus 51N --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Gorbea 52CT1 Siemens Argus 51 --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,42 0,47 0,95 1,86 3,73 6,32

Gorbea 52C1 Siemens Argus Trip --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,04 0,07 0,12 0,18 0,25

Gorbea 52C1 Siemens Argus 51N --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Gorbea 52C1 Siemens Argus 51 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,04 0,07 0,12 0,18 0,25

Page 30: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 30 de 121

9.1.2.2. FALLA 2F PULLINQUE B4 -> GORBEA 13,2 kV

91,82973,46355,09736,73218,3660,0000 [km]

5,00

4,00

3,00

2,00

1,00

0,00

Pull_66kV_ Lonc_66kV_ Cto2

Gorbea_66kV

Bushing_66kV

Gorbea_13.2k..

LMT_13.2

x-Axis: Length Pull\52B4\Pull_52B4 Lonc\52B3\Lonc_52B3_G1 Gorbea_66kV\Cub_4\Gorbea_89BT1F

Gorbea_13.2kV\Cub_1\Gorbea_52CT1 Gorbea_13.2kV\Cub_2\Gorbea_52C1

TD2_Pull -> Gorbea MT_2F

Date: 11/6/2014

Annex:

DIg

SIL

EN

T

Page 31: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 31 de 121

Tipo Falla : 2F RF= 0 Ohm Ruta : Pullinque B4 - Gorbea 13,kV Tiempos de Operación en segundos

S/E Paño Relé NEMA Pullinque

66kV

LT 66kV Pullinque - Loncoche

Loncoche 66kV

LT 66kV Loncoche - Gorbea

Gorbea 66kV

Gorbea Bushing

66kV T1

Gorbea 13,2kV

Línea de Media Tensión 13,2 kV

1% 25% 50% 75% 99% 1% 25% 50% 75% 99% 1% 25% 50% 75% 99%

Pullinque 52B4 SEL-311C Trip --- 0,02 0,02 0,02 0,02 0,82 0,82 0,82 0,82 2,72 2,72 2,72 2,72 2,72 --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21-Z1 --- 0,02 0,02 0,02 0,02 --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21-Z2 --- 0,82 0,82 0,82 0,82 0,82 0,82 0,82 0,82 --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21-Z3 --- 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21N-Z1 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21N-Z2 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21N-Z3 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21N_Q-Z1 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21N_Q-Z2 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21N_Q-Z3 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Loncoche 52B3 SEL-311C Trip --- --- --- --- --- --- --- 0,02 0,02 0,02 0,02 0,02 0,02 0,02 --- --- --- --- --- ---

Loncoche 52B3 SEL-311C 21-Z1 --- --- --- --- --- --- --- 0,02 0,02 0,02 0,02 0,02 0,02 0,02 --- --- --- --- --- ---

Loncoche 52B3 SEL-311C 21-Z2 --- --- --- --- --- --- --- 0,72 0,72 0,72 0,72 0,72 0,72 0,72 --- --- --- --- --- ---

Loncoche 52B3 SEL-311C 21-Z3 --- --- --- --- --- --- --- 2,02 2,02 2,02 2,02 2,02 2,02 2,02 --- --- --- --- --- ---

Loncoche 52B3 SEL-311C 21N-Z1 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Loncoche 52B3 SEL-311C 21N-Z2 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Loncoche 52B3 SEL-311C 21N-Z3 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Loncoche 52B3 SEL-311C 51N --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Gorbea 89BT1-F Fuse SMD 65E Trip --- --- --- --- --- --- --- --- --- --- --- --- --- 0,05 0,87 0,98 2,19 4,16 8,23 14,55

Gorbea 52CT1 Siemens Argus Trip --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,54 0,61 1,34 2,69 6,12 10,37

Gorbea 52CT1 Siemens Argus 51N --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Gorbea 52CT1 Siemens Argus 51 --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,54 0,61 1,34 2,69 6,12 10,37

Gorbea 52C1 Siemens Argus Trip --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,05 0,09 0,15 0,25 0,33

Gorbea 52C1 Siemens Argus 51N --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Gorbea 52C1 Siemens Argus 51 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,05 0,09 0,15 0,25 0,33

Page 32: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 32 de 121

9.1.2.3. FALLA 2F-T PULLINQUE B4 -> GORBEA 13,2 kV

91,82973,46355,09736,73218,3660,0000 [km]

5,00

4,00

3,00

2,00

1,00

0,00

Pull_66kV_ Lonc_66kV_ Cto2

Gorbea_66kV

Bushing_66kV

Gorbea_13.2k..

LMT_13.2

x-Axis: Length Pull\52B4\Pull_52B4 Lonc\52B3\Lonc_52B3_G1 Gorbea_66kV\Cub_4\Gorbea_89BT1F

Gorbea_13.2kV\Cub_1\Gorbea_52CT1 Gorbea_13.2kV\Cub_2\Gorbea_52C1

TD2_Pull -> Gorbea MT_2F-T

Date: 11/6/2014

Annex:

DIg

SIL

EN

T

Page 33: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 33 de 121

Tipo Falla : 2FT RF= 0 Ohm Ruta : Pullinque B4 - Gorbea 13,kV Tiempos de Operación en segundos

S/E Paño Relé NEMA Pullinque

66kV

LT 66kV Pullinque - Loncoche

Loncoche 66kV

LT 66kV Loncoche - Gorbea

Gorbea 66kV

Gorbea Bushing

66kV T1

Gorbea 13,2kV

Línea de Media Tensión 13,2 kV

1% 25% 50% 75% 99% 1% 25% 50% 75% 99% 1% 25% 50% 75% 99%

Pullinque 52B4 SEL-311C Trip --- 0,02 0,02 0,02 0,02 0,82 0,82 0,82 0,82 2,72 2,72 2,72 2,72 2,72 --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21-Z1 --- 0,02 0,02 0,02 0,02 --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21-Z2 --- 0,82 0,82 0,82 0,82 0,82 0,82 0,82 0,82 --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21-Z3 --- 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21N-Z1 --- 0,02 0,02 0,02 0,02 --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21N-Z2 --- 0,82 0,82 0,82 0,82 0,82 0,82 0,82 0,82 --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21N-Z3 --- 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21N_Q-Z1 --- 0,02 0,02 0,02 0,02 --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21N_Q-Z2 --- 0,82 0,82 0,82 0,82 0,82 0,82 0,82 0,82 --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21N_Q-Z3 --- 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 --- --- --- --- --- ---

Loncoche 52B3 SEL-311C Trip --- --- --- --- --- --- --- 0,02 0,02 0,02 0,02 0,02 0,02 0,02 --- --- --- --- --- ---

Loncoche 52B3 SEL-311C 21-Z1 --- --- --- --- --- --- --- 0,02 0,02 0,02 0,02 0,02 0,02 0,02 --- --- --- --- --- ---

Loncoche 52B3 SEL-311C 21-Z2 --- --- --- --- --- --- --- 0,72 0,72 0,72 0,72 0,72 0,72 0,72 --- --- --- --- --- ---

Loncoche 52B3 SEL-311C 21-Z3 --- --- --- --- --- --- --- 2,02 2,02 2,02 2,02 2,02 2,02 2,02 --- --- --- --- --- ---

Loncoche 52B3 SEL-311C 21N-Z1 --- --- --- --- --- --- --- 0,02 0,02 0,02 0,02 0,02 0,02 0,02 --- --- --- --- --- ---

Loncoche 52B3 SEL-311C 21N-Z2 --- --- --- --- --- --- --- 0,72 0,72 0,72 0,72 0,72 0,72 0,72 --- --- --- --- --- ---

Loncoche 52B3 SEL-311C 21N-Z3 --- --- --- --- --- --- --- 2,02 2,02 2,02 2,02 2,02 2,02 2,02 --- --- --- --- --- ---

Loncoche 52B3 SEL-311C 51N --- --- --- --- --- --- --- 0,24 0,25 0,27 0,29 0,32 0,32 0,32 --- --- --- --- --- ---

Gorbea 89BT1-F Fuse SMD 65E Trip --- --- --- --- --- --- --- --- --- --- --- --- --- 0,04 0,87 0,98 2,19 4,16 8,23 14,55

Gorbea 52CT1 Siemens Argus Trip --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,35 0,43 1,04 1,25 1,42 1,54

Gorbea 52CT1 Siemens Argus 51N --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,82 0,86 1,08 1,25 1,42 1,54

Gorbea 52CT1 Siemens Argus 51 --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,35 0,43 1,04 2,10 4,44 7,55

Gorbea 52C1 Siemens Argus Trip --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,04 0,08 0,12 0,20 0,28

Gorbea 52C1 Siemens Argus 51N --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,56 0,67 0,76 0,84 0,90

Gorbea 52C1 Siemens Argus 51 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,04 0,08 0,12 0,20 0,28

Page 34: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 34 de 121

9.1.2.4. FALLA 1F PULLINQUE B4 -> GORBEA 13,2 kV

91,82973,46355,09736,73218,3660,0000 [km]

5,00

4,00

3,00

2,00

1,00

0,00

Pull_66kV_ Lonc_66kV_ Cto2

Gorbea_66kV

Bushing_66kV

Gorbea_13.2k..

LMT_13.2

x-Axis: Length Pull\52B4\Pull_52B4 Lonc\52B3\Lonc_52B3_G1 Gorbea_66kV\Cub_4\Gorbea_89BT1F

Gorbea_13.2kV\Cub_1\Gorbea_52CT1 Gorbea_13.2kV\Cub_2\Gorbea_52C1

TD2_Pull -> Gorbea MT_1F

Date: 11/6/2014

Annex:

DIg

SIL

EN

T

Page 35: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 35 de 121

Tipo Falla : 1FT RF= 0 Ohm Ruta : Pullinque B4 - Gorbea 13,kV Tiempos de Operación en segundos

S/E Paño Relé NEMA Pullinque

66kV

LT 66kV Pullinque - Loncoche

Loncoche 66kV

LT 66kV Loncoche - Gorbea

Gorbea 66kV

Gorbea Bushing

66kV T1

Gorbea 13,2kV

Línea de Media Tensión 13,2 kV

1% 25% 50% 75% 99% 1% 25% 50% 75% 99% 1% 25% 50% 75% 99%

Pullinque 52B4 SEL-311C Trip --- 0,02 0,02 0,02 0,02 0,82 0,82 0,82 0,82 2,72 2,72 2,72 2,72 2,72 --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21-Z1 --- 0,02 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21-Z2 --- 0,82 0,82 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21-Z3 --- 2,72 2,72 2,72 2,72 2,72 2,72 2,72 --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21N-Z1 --- 0,02 0,02 0,02 0,02 --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21N-Z2 --- 0,82 0,82 0,82 0,82 0,82 0,82 0,82 0,82 --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21N-Z3 --- 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21N_Q-Z1 --- 0,02 0,02 0,02 0,02 --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21N_Q-Z2 --- 0,82 0,82 0,82 0,82 0,82 0,82 0,82 0,82 --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21N_Q-Z3 --- 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 --- --- --- --- --- ---

Loncoche 52B3 SEL-311C Trip --- --- --- --- --- --- --- 0,02 0,02 0,02 0,02 0,02 0,02 0,02 --- --- --- --- --- ---

Loncoche 52B3 SEL-311C 21-Z1 --- --- --- --- --- --- --- 0,02 0,02 --- --- --- --- --- --- --- --- --- --- ---

Loncoche 52B3 SEL-311C 21-Z2 --- --- --- --- --- --- --- 0,72 0,72 0,72 0,72 0,72 0,72 0,72 --- --- --- --- --- ---

Loncoche 52B3 SEL-311C 21-Z3 --- --- --- --- --- --- --- 2,02 2,02 2,02 2,02 2,02 2,02 2,02 --- --- --- --- --- ---

Loncoche 52B3 SEL-311C 21N-Z1 --- --- --- --- --- --- --- 0,02 0,02 0,02 0,02 0,02 0,02 0,02 --- --- --- --- --- ---

Loncoche 52B3 SEL-311C 21N-Z2 --- --- --- --- --- --- --- 0,72 0,72 0,72 0,72 0,72 0,72 0,72 --- --- --- --- --- ---

Loncoche 52B3 SEL-311C 21N-Z3 --- --- --- --- --- --- --- 2,02 2,02 2,02 2,02 2,02 2,02 2,02 --- --- --- --- --- ---

Loncoche 52B3 SEL-311C 51N --- --- --- --- --- --- --- 0,23 0,24 0,25 0,26 0,28 0,28 0,28 --- --- --- --- --- ---

Gorbea 89BT1-F Fuse SMD 65E Trip --- --- --- --- --- --- --- --- --- --- --- --- --- 0,08 2,21 2,95 21,16 --- --- ---

Gorbea 52CT1 Siemens Argus Trip --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,34 0,43 1,02 1,15 1,28 1,36

Gorbea 52CT1 Siemens Argus 51N --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,84 0,87 1,02 1,15 1,28 1,36

Gorbea 52CT1 Siemens Argus 51 --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,34 0,43 1,58 4,81 14,05 25,32

Gorbea 52C1 Siemens Argus Trip --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,04 0,10 0,21 0,39 0,58

Gorbea 52C1 Siemens Argus 51N --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,56 0,64 0,71 0,77 0,82

Gorbea 52C1 Siemens Argus 51 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,04 0,10 0,21 0,39 0,58

Page 36: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 36 de 121

9.1.2.5. F LL 1F (R = Ω) PULLINQUE B4 -> GORBEA 13,2 kV

91,82973,46355,09736,73218,3660,0000 [km]

5,00

4,00

3,00

2,00

1,00

0,00

Pull_66kV_ Lonc_66kV_ Cto2

Gorbea_66kV

Bushing_66kV

Gorbea_13.2k..

LMT_13.2

x-Axis: Length Pull\52B4\Pull_52B4 Lonc\52B3\Lonc_52B3_G1 Gorbea_66kV\Cub_4\Gorbea_89BT1F

Gorbea_13.2kV\Cub_1\Gorbea_52CT1 Gorbea_13.2kV\Cub_2\Gorbea_52C1

TD2_Pull -> Gorbea MT_1F_R25

Date: 11/6/2014

Annex:

DIg

SIL

EN

T

Page 37: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 37 de 121

Tipo Falla : 1FT RF= 25 Ohm Ruta : Pullinque B4 - Gorbea 13,kV Tiempos de Operación en segundos

S/E Paño Relé NEMA Pullinque

66kV

LT 66kV Pullinque - Loncoche

Loncoche 66kV

LT 66kV Loncoche - Gorbea

Gorbea 66kV

Gorbea Bushing

66kV T1

Gorbea 13,2kV

Línea de Media Tensión 13,2 kV

1% 25% 50% 75% 99% 1% 25% 50% 75% 99% 1% 25% 50% 75% 99%

Pullinque 52B4 SEL-311C Trip --- 0,82 0,82 0,82 0,82 2,72 2,72 2,72 2,72 2,72 2,72 --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21-Z1 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21-Z2 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21-Z3 --- 2,72 2,72 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21N-Z1 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21N-Z2 --- 0,82 0,82 0,82 0,82 --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21N-Z3 --- 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21N_Q-Z1 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21N_Q-Z2 --- 0,82 0,82 0,82 0,82 --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21N_Q-Z3 --- 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 --- --- --- --- --- --- --- --- ---

Loncoche 52B3 SEL-311C Trip --- --- --- --- --- --- --- 0,02 0,02 0,02 0,34 0,38 0,39 0,39 --- --- --- --- --- ---

Loncoche 52B3 SEL-311C 21-Z1 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Loncoche 52B3 SEL-311C 21-Z2 --- --- --- --- --- --- --- 0,72 0,72 --- --- --- --- --- --- --- --- --- --- ---

Loncoche 52B3 SEL-311C 21-Z3 --- --- --- --- --- --- --- 2,02 2,02 2,02 --- --- --- --- --- --- --- --- --- ---

Loncoche 52B3 SEL-311C 21N-Z1 --- --- --- --- --- --- --- 0,02 0,02 0,02 --- --- --- --- --- --- --- --- --- ---

Loncoche 52B3 SEL-311C 21N-Z2 --- --- --- --- --- --- --- 0,72 0,72 0,72 0,72 0,72 0,72 0,72 --- --- --- --- --- ---

Loncoche 52B3 SEL-311C 21N-Z3 --- --- --- --- --- --- --- 2,02 2,02 2,02 2,02 2,02 2,02 2,02 --- --- --- --- --- ---

Loncoche 52B3 SEL-311C 51N --- --- --- --- --- --- --- 0,27 0,28 0,31 0,34 0,38 0,39 0,39 --- --- --- --- --- ---

Gorbea 89BT1-F Fuse SMD 65E Trip --- --- --- --- --- --- --- --- --- --- --- --- --- 0,23 --- --- --- --- --- ---

Gorbea 52CT1 Siemens Argus Trip --- --- --- --- --- --- --- --- --- --- --- --- --- --- 1,69 1,70 1,75 1,80 1,88 1,93

Gorbea 52CT1 Siemens Argus 51N --- --- --- --- --- --- --- --- --- --- --- --- --- --- 1,69 1,70 1,75 1,80 1,88 1,93

Gorbea 52CT1 Siemens Argus 51 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Gorbea 52C1 Siemens Argus Trip --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,98 1,00 1,03 1,06 1,08

Gorbea 52C1 Siemens Argus 51N --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,98 1,00 1,03 1,06 1,08

Gorbea 52C1 Siemens Argus 51 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 1,95 2,24 2,59 3,06 3,46

Page 38: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 38 de 121

9.2. ESCENARIO 2

LT 66kV Temuco – Loncoche N°1 en servicio

LT 66kV Temuco – Loncoche N°2 fuera de servicio

LT 66kV Pullinque – Loncoche N°1 en servicio

LT 66kV Pullinque – Loncoche N°2 en servicio

S/E Gorbea conectada a la LT 66kV Temuco - Loncoche N°1

Page 39: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 39 de 121

9.2.1. Ruta 3: Temuco B6 -> Gorbea 13,2 kV

Page 40: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 40 de 121

9.2.1.1. FALLA 3F TEMUCO B6 -> GORBEA 13,2 kV

62,86150,28937,71725,14412,5720,0000 [km]

5,00

4,00

3,00

2,00

1,00

0,00

Tem_66kV Tap Padre La..

Tap Licanco ..

Arr. Metrenc.. Cto1

Gorbea_66kV

Bushing_66kV

Gorbea_13.2k..

LMT_13.2

x-Axis: Length Tem\52B\Tem_52B6 Gorbea_66kV\Cub_4\Gorbea_89BT1F Gorbea_13.2kV\Cub_1\Gorbea_52CT1

Gorbea_13.2kV\Cub_2\Gorbea_52C1

TD3_Tem B6 -> Gorbea MT_3F

Date: 11/6/2014

Annex:

DIg

SIL

EN

T

Page 41: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 41 de 121

Tipo Falla : 3F RF= 0 Ohm

Ruta : Temuco B6 - Gorbea 13,2kV

Tiempos de Operación en segundos

S/E Paño Relé NEMA Temuco

66kV

LT 66kV Temuco - Gorbea

Gorbea 66kV

Gorbea Bushing 66kV T1

Gorbea Barra

13,2kV

Línea de Media Tensión 13,2 kV

Padre Las Casas 66kV

Tap Licanco

66kV

Pitrufquén 66 kV

1% 25% 50% 75% 99%

Temuco 52B6 SEL-311C Trip --- 0,02 0,02 0,02 0,02 0,02 --- --- --- --- --- ---

Temuco 52B6 SEL-311C 21-Z1 --- 0,02 0,02 0,02 0,02 0,02 --- --- --- --- --- ---

Temuco 52B6 SEL-311C 21-Z2 --- 0,82 0,82 0,82 0,82 0,82 --- --- --- --- --- ---

Temuco 52B6 SEL-311C 21-Z3 --- 2,72 2,72 2,72 2,72 2,72 --- --- --- --- --- ---

Temuco 52B6 SEL-311C 21N-Z1 --- --- --- --- --- --- --- --- --- --- --- ---

Temuco 52B6 SEL-311C 21N-Z2 --- --- --- --- --- --- --- --- --- --- --- ---

Temuco 52B6 SEL-311C 21N-Z3 --- --- --- --- --- --- --- --- --- --- --- ---

Temuco 52B6 SEL-311C 51N --- --- --- --- --- --- --- --- --- --- --- ---

Temuco 52B6 SEL-311C 67N --- --- --- --- --- --- --- --- --- --- --- ---

Gorbea 89BT1-F Fuse SMD 65E Trip --- --- --- --- --- 0,04 0,89 1,01 2,23 4,23 8,36 14,81

Gorbea 52CT1 Siemens Argus Trip --- --- --- --- --- --- 0,43 0,48 0,97 1,89 3,79 6,40

Gorbea 52CT1 Siemens Argus 51N --- --- --- --- --- --- --- --- --- --- --- ---

Gorbea 52CT1 Siemens Argus 51 --- --- --- --- --- --- 0,43 0,48 0,97 1,89 3,79 6,40

Gorbea 52C1 Siemens Argus Trip --- --- --- --- --- --- --- 0,04 0,07 0,12 0,19 0,25

Gorbea 52C1 Siemens Argus 51N --- --- --- --- --- --- --- --- --- --- --- ---

Gorbea 52C1 Siemens Argus 51 --- --- --- --- --- --- --- 0,04 0,07 0,12 0,19 0,25

Page 42: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 42 de 121

9.2.1.2. FALLA 2F TEMUCO B6 -> GORBEA 13,2 kV

62,86150,28937,71725,14412,5720,0000 [km]

5,00

4,00

3,00

2,00

1,00

0,00

Tem_66kV Tap Padre La..

Tap Licanco ..

Arr. Metrenc.. Cto1

Gorbea_66kV

Bushing_66kV

Gorbea_13.2k..

LMT_13.2

x-Axis: Length Tem\52B\Tem_52B6 Gorbea_66kV\Cub_4\Gorbea_89BT1F Gorbea_13.2kV\Cub_1\Gorbea_52CT1

Gorbea_13.2kV\Cub_2\Gorbea_52C1

TD3_Tem B6 -> Gorbea MT_2F

Date: 11/6/2014

Annex:

DIg

SIL

EN

T

Page 43: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 43 de 121

Tipo Falla : 2F RF= 0 Ohm

Ruta : Temuco B6 - Gorbea 13,2kV

Tiempos de Operación en segundos

S/E Paño Relé NEMA Temuco

66kV

LT 66kV Temuco - Gorbea

Gorbea 66kV

Gorbea Bushing 66kV T1

Gorbea Barra

13,2kV

Línea de Media Tensión 13,2 kV

Padre Las Casas 66kV

Tap Licanco

66kV

Pitrufquén 66 kV

1% 25% 50% 75% 99%

Temuco 52B6 SEL-311C Trip --- 0,02 0,02 0,02 0,02 0,02 --- --- --- --- --- ---

Temuco 52B6 SEL-311C 21-Z1 --- 0,02 0,02 0,02 0,02 0,02 --- --- --- --- --- ---

Temuco 52B6 SEL-311C 21-Z2 --- 0,82 0,82 0,82 0,82 0,82 --- --- --- --- --- ---

Temuco 52B6 SEL-311C 21-Z3 --- 2,72 2,72 2,72 2,72 2,72 --- --- --- --- --- ---

Temuco 52B6 SEL-311C 21N-Z1 --- --- --- --- --- --- --- --- --- --- --- ---

Temuco 52B6 SEL-311C 21N-Z2 --- --- --- --- --- --- --- --- --- --- --- ---

Temuco 52B6 SEL-311C 21N-Z3 --- --- --- --- --- --- --- --- --- --- --- ---

Temuco 52B6 SEL-311C 51N --- --- --- --- --- --- --- --- --- --- --- ---

Temuco 52B6 SEL-311C 67N --- --- --- --- --- --- --- --- --- --- --- ---

Gorbea 89BT1-F Fuse SMD 65E Trip --- --- --- --- --- 0,06 0,89 1,01 2,23 4,23 8,37 14,81

Gorbea 52CT1 Siemens Argus Trip --- --- --- --- --- --- 0,56 0,63 1,37 2,73 6,23 10,52

Gorbea 52CT1 Siemens Argus 51N --- --- --- --- --- --- --- --- --- --- --- ---

Gorbea 52CT1 Siemens Argus 51 --- --- --- --- --- --- 0,56 0,63 1,37 2,73 6,23 10,52

Gorbea 52C1 Siemens Argus Trip --- --- --- --- --- --- --- 0,05 0,09 0,15 0,25 0,33

Gorbea 52C1 Siemens Argus 51N --- --- --- --- --- --- --- --- --- --- --- ---

Gorbea 52C1 Siemens Argus 51 --- --- --- --- --- --- --- 0,05 0,09 0,15 0,25 0,33

Page 44: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 44 de 121

9.2.1.3. FALLA 2F-T TEMUCO B6 -> GORBEA 13,2 kV

62,86150,28937,71725,14412,5720,0000 [km]

5,00

4,00

3,00

2,00

1,00

0,00

Tem_66kV Tap Padre La..

Tap Licanco ..

Arr. Metrenc.. Cto1

Gorbea_66kV

Bushing_66kV

Gorbea_13.2k..

LMT_13.2

x-Axis: Length Tem\52B\Tem_52B6 Gorbea_66kV\Cub_4\Gorbea_89BT1F Gorbea_13.2kV\Cub_1\Gorbea_52CT1

Gorbea_13.2kV\Cub_2\Gorbea_52C1

TD3_Tem B6 -> Gorbea MT_2F-T

Date: 11/6/2014

Annex:

DIg

SIL

EN

T

Page 45: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 45 de 121

Tipo Falla : 2FT RF= 0 Ohm

Ruta : Temuco B6 - Gorbea 13,2kV

Tiempos de Operación en segundos

S/E Paño Relé NEMA Temuco

66kV

LT 66kV Temuco - Gorbea

Gorbea 66kV

Gorbea Bushing 66kV T1

Gorbea Barra

13,2kV

Línea de Media Tensión 13,2 kV

Padre Las Casas 66kV

Tap Licanco

66kV

Pitrufquén 66 kV

1% 25% 50% 75% 99%

Temuco 52B6 SEL-311C Trip --- 0,01 0,01 0,01 0,02 0,02 --- --- --- --- --- ---

Temuco 52B6 SEL-311C 21-Z1 --- 0,02 0,02 0,02 0,02 0,02 --- --- --- --- --- ---

Temuco 52B6 SEL-311C 21-Z2 --- 0,82 0,82 0,82 0,82 0,82 --- --- --- --- --- ---

Temuco 52B6 SEL-311C 21-Z3 --- 2,72 2,72 2,72 2,72 2,72 --- --- --- --- --- ---

Temuco 52B6 SEL-311C 21N-Z1 --- 0,02 0,02 0,02 0,02 0,02 --- --- --- --- --- ---

Temuco 52B6 SEL-311C 21N-Z2 --- 0,82 0,82 0,82 0,82 0,82 --- --- --- --- --- ---

Temuco 52B6 SEL-311C 21N-Z3 --- 2,72 2,72 2,72 2,72 2,72 --- --- --- --- --- ---

Temuco 52B6 SEL-311C 51N --- 0,23 0,23 0,25 0,39 0,39 --- --- --- --- --- ---

Temuco 52B6 SEL-311C 67N --- 0,01 0,01 0,01 --- --- --- --- --- --- --- ---

Gorbea 89BT1-F Fuse SMD 65E Trip --- --- --- --- --- 0,04 0,89 1,01 2,23 4,23 8,36 14,81

Gorbea 52CT1 Siemens Argus Trip --- --- --- --- --- --- 0,36 0,44 1,06 1,25 1,42 1,54

Gorbea 52CT1 Siemens Argus 51N --- --- --- --- --- --- 0,82 0,86 1,08 1,25 1,42 1,54

Gorbea 52CT1 Siemens Argus 51 --- --- --- --- --- --- 0,36 0,44 1,06 2,13 4,51 7,65

Gorbea 52C1 Siemens Argus Trip --- --- --- --- --- --- --- 0,04 0,08 0,12 0,21 0,28

Gorbea 52C1 Siemens Argus 51N --- --- --- --- --- --- --- 0,56 0,67 0,76 0,84 0,90

Gorbea 52C1 Siemens Argus 51 --- --- --- --- --- --- --- 0,04 0,08 0,12 0,21 0,28

Page 46: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 46 de 121

9.2.1.4. FALLA 1F TEMUCO B6 -> GORBEA 13,2 kV

62,86150,28937,71725,14412,5720,0000 [km]

5,00

4,00

3,00

2,00

1,00

0,00

Tem_66kV Tap Padre La..

Tap Licanco ..

Arr. Metrenc.. Cto1

Gorbea_66kV

Bushing_66kV

Gorbea_13.2k..

LMT_13.2

x-Axis: Length Tem\52B\Tem_52B6 Gorbea_66kV\Cub_4\Gorbea_89BT1F Gorbea_13.2kV\Cub_1\Gorbea_52CT1

Gorbea_13.2kV\Cub_2\Gorbea_52C1

TD3_Tem B6 -> Gorbea MT_1F

Date: 11/6/2014

Annex:

DIg

SIL

EN

T

Page 47: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 47 de 121

Tipo Falla : 1FT RF= 0 Ohm

Ruta : Temuco B6 - Gorbea 13,2kV

Tiempos de Operación en segundos

S/E Paño Relé NEMA Temuco

66kV

LT 66kV Temuco - Gorbea

Gorbea 66kV

Gorbea Bushing 66kV T1

Gorbea Barra

13,2kV

Línea de Media Tensión 13,2 kV

Padre Las Casas 66kV

Tap Licanco

66kV

Pitrufquén 66 kV

1% 25% 50% 75% 99%

Temuco 52B6 SEL-311C Trip --- 0,01 0,01 0,01 0,02 0,02 --- --- --- --- --- ---

Temuco 52B6 SEL-311C 21-Z1 --- 0,02 0,02 0,02 --- --- --- --- --- --- --- ---

Temuco 52B6 SEL-311C 21-Z2 --- 0,82 0,82 0,82 --- --- --- --- --- --- --- ---

Temuco 52B6 SEL-311C 21-Z3 --- 2,72 2,72 2,72 2,72 2,72 --- --- --- --- --- ---

Temuco 52B6 SEL-311C 21N-Z1 --- 0,02 0,02 0,02 0,02 0,02 --- --- --- --- --- ---

Temuco 52B6 SEL-311C 21N-Z2 --- 0,82 0,82 0,82 0,82 0,82 --- --- --- --- --- ---

Temuco 52B6 SEL-311C 21N-Z3 --- 2,72 2,72 2,72 2,72 2,72 --- --- --- --- --- ---

Temuco 52B6 SEL-311C 51N --- 0,23 0,23 0,24 0,32 0,32 --- --- --- --- --- ---

Temuco 52B6 SEL-311C 67N --- 0,01 0,01 0,01 --- --- --- --- --- --- --- ---

Gorbea 89BT1-F Fuse SMD 65E Trip --- --- --- --- --- 0,09 2,26 3,00 21,74 --- --- ---

Gorbea 52CT1 Siemens Argus Trip --- --- --- --- --- --- 0,35 0,44 1,03 1,15 1,28 1,36

Gorbea 52CT1 Siemens Argus 51N --- --- --- --- --- --- 0,84 0,87 1,03 1,15 1,28 1,36

Gorbea 52CT1 Siemens Argus 51 --- --- --- --- --- --- 0,35 0,44 1,60 4,86 14,15 25,46

Gorbea 52C1 Siemens Argus Trip --- --- --- --- --- --- --- 0,04 0,10 0,21 0,39 0,58

Gorbea 52C1 Siemens Argus 51N --- --- --- --- --- --- --- 0,56 0,64 0,71 0,77 0,82

Gorbea 52C1 Siemens Argus 51 --- --- --- --- --- --- --- 0,04 0,10 0,21 0,39 0,58

Page 48: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 48 de 121

9.2.1.5. F LL 1F (R = Ω) TEMUCO B6 -> GORBEA 13,2 kV

62,86150,28937,71725,14412,5720,0000 [km]

5,00

4,00

3,00

2,00

1,00

0,00

Tem_66kV Tap Padre La..

Tap Licanco ..

Arr. Metrenc.. Cto1

Gorbea_66kV

Bushing_66kV

Gorbea_13.2k..

LMT_13.2

x-Axis: Length Tem\52B\Tem_52B6 Gorbea_66kV\Cub_4\Gorbea_89BT1F Gorbea_13.2kV\Cub_1\Gorbea_52CT1

Gorbea_13.2kV\Cub_2\Gorbea_52C1

TD3_Tem B6 -> Gorbea MT_1F_R25

Date: 11/6/2014

Annex:

DIg

SIL

EN

T

Page 49: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 49 de 121

Tipo Falla : 1FT RF= 25 Ohm

Ruta : Temuco B6 - Gorbea 13,2kV

Tiempos de Operación en segundos

S/E Paño Relé NEMA Temuco

66kV

LT 66kV Temuco - Gorbea

Gorbea 66kV

Gorbea Bushing 66kV T1

Gorbea Barra

13,2kV

Línea de Media Tensión 13,2 kV

Padre Las Casas 66kV

Tap Licanco

66kV

Pitrufquén 66 kV

1% 25% 50% 75% 99%

Temuco 52B6 SEL-311C Trip --- 0,01 0,01 0,01 0,49 0,49 --- --- --- --- --- ---

Temuco 52B6 SEL-311C 21-Z1 --- --- --- --- --- --- --- --- --- --- --- ---

Temuco 52B6 SEL-311C 21-Z2 --- --- --- --- --- --- --- --- --- --- --- ---

Temuco 52B6 SEL-311C 21-Z3 --- 2,72 2,72 2,72 --- --- --- --- --- --- --- ---

Temuco 52B6 SEL-311C 21N-Z1 --- 0,02 0,02 0,02 --- --- --- --- --- --- --- ---

Temuco 52B6 SEL-311C 21N-Z2 --- 0,82 0,82 0,82 --- --- --- --- --- --- --- ---

Temuco 52B6 SEL-311C 21N-Z3 --- 2,72 2,72 2,72 2,72 2,72 --- --- --- --- --- ---

Temuco 52B6 SEL-311C 51N --- 0,27 0,27 0,29 0,49 0,49 --- --- --- --- --- ---

Temuco 52B6 SEL-311C 67N --- 0,01 0,01 0,01 --- --- --- --- --- --- --- ---

Gorbea 89BT1-F Fuse SMD 65E Trip --- --- --- --- --- 0,24 --- --- --- --- --- ---

Gorbea 52CT1 Siemens Argus Trip --- --- --- --- --- --- 1,69 1,70 1,75 1,81 1,88 1,93

Gorbea 52CT1 Siemens Argus 51N --- --- --- --- --- --- 1,69 1,70 1,75 1,81 1,88 1,93

Gorbea 52CT1 Siemens Argus 51 --- --- --- --- --- --- --- --- --- --- --- ---

Gorbea 52C1 Siemens Argus Trip --- --- --- --- --- --- --- 0,98 1,00 1,03 1,06 1,08

Gorbea 52C1 Siemens Argus 51N --- --- --- --- --- --- --- 0,98 1,00 1,03 1,06 1,08

Gorbea 52C1 Siemens Argus 51 --- --- --- --- --- --- --- 1,95 2,24 2,60 3,07 3,47

Page 50: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 50 de 121

9.2.2. Ruta 4: Pullinque B2 -> Gorbea 13,2 kV

Page 51: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 51 de 121

9.2.2.1. FALLA 3F PULLINQUE B2 -> GORBEA 13,2 kV

91,82973,46355,09736,73218,3660,0000 [km]

5,00

4,00

3,00

2,00

1,00

0,00

Pull_66kV Lonc_66kV Cto1

Gorbea_66kV

Bushing_66kV

Gorbea_13.2k..

LMT_13.2

x-Axis: Length Pull\52B2\Pull_52B2 Lonc_66kV\Cub_5\Lonc_52B6 Gorbea_66kV\Cub_4\Gorbea_89BT1F

Gorbea_13.2kV\Cub_1\Gorbea_52CT1 Gorbea_13.2kV\Cub_2\Gorbea_52C1

TD4_Pull B2 -> Gorbea MT_3F

Date: 11/6/2014

Annex:

DIg

SIL

EN

T

Page 52: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 52 de 121

Tipo Falla : 3F RF= 0 Ohm Ruta : Pullinque B2 - Gorbea 13,2kV Tiempos de Operación en segundos

S/E Paño Relé NEMA Pullinque

66kV

LT 66kV Pullinque - Loncoche

Loncoche 66kV

LT 66kV Loncoche - Gorbea

Gorbea 66kV

Gorbea Bushing

66kV T1

Gorbea 13,2kV

Línea de Media Tensión 13,2 kV

1% 25% 50% 75% 99% 1% 25% 50% 75% 99% 1% 25% 50% 75% 99%

Pullinque 52B2 SEL-311C Trip --- 0,02 0,02 0,02 0,02 0,82 0,82 0,82 0,82 0,82 2,72 2,72 2,72 2,72 --- --- --- --- --- ---

Pullinque 52B2 SEL-311C 21-Z1 --- 0,02 0,02 0,02 0,02 --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B2 SEL-311C 21-Z2 --- 0,82 0,82 0,82 0,82 0,82 0,82 0,82 0,82 0,82 --- --- --- --- --- --- --- --- --- ---

Pullinque 52B2 SEL-311C 21-Z3 --- 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 --- --- --- --- --- ---

Pullinque 52B2 SEL-311C 21N-Z1 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B2 SEL-311C 21N-Z2 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B2 SEL-311C 21N-Z3 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B2 SEL-311C 21N_Q-Z1 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B2 SEL-311C 21N_Q-Z2 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B2 SEL-311C 21N_Q-Z3 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Loncoche 52B6 SEL-311C Trip --- --- --- --- --- --- 0,02 0,02 0,02 0,02 0,02 0,02 0,02 0,02 --- --- --- --- --- ---

Loncoche 52B6 SEL-311C 21-Z1 --- --- --- --- --- --- 0,02 0,02 0,02 0,02 0,02 0,02 0,02 0,02 --- --- --- --- --- ---

Loncoche 52B6 SEL-311C 21-Z2 --- --- --- --- --- --- 0,72 0,72 0,72 0,72 0,72 0,72 0,72 0,72 --- --- --- --- --- ---

Loncoche 52B6 SEL-311C 21-Z3 --- --- --- --- --- --- 2,02 2,02 2,02 2,02 2,02 2,02 2,02 2,02 --- --- --- --- --- ---

Loncoche 52B6 SEL-311C 21N-Z1 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Loncoche 52B6 SEL-311C 21N-Z2 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Loncoche 52B6 SEL-311C 21N-Z3 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Loncoche 52B6 SEL-311C 51N --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Gorbea 89BT1-F Fuse SMD 65E Trip --- --- --- --- --- --- --- --- --- --- --- --- --- 0,04 0,89 1,01 2,23 4,23 8,36 14,81

Gorbea 52CT1 Siemens Argus Trip --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,43 0,48 0,97 1,89 3,79 6,40

Gorbea 52CT1 Siemens Argus 51N --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Gorbea 52CT1 Siemens Argus 51 --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,43 0,48 0,97 1,89 3,79 6,40

Gorbea 52C1 Siemens Argus Trip --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,04 0,07 0,12 0,19 0,25

Gorbea 52C1 Siemens Argus 51N --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Gorbea 52C1 Siemens Argus 51 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,04 0,07 0,12 0,19 0,25

Page 53: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 53 de 121

9.2.2.2. FALLA 2F PULLINQUE B2 -> GORBEA 13,2 kV

91,82973,46355,09736,73218,3660,0000 [km]

5,00

4,00

3,00

2,00

1,00

0,00

Pull_66kV Lonc_66kV Cto1

Gorbea_66kV

Bushing_66kV

Gorbea_13.2k..

LMT_13.2

x-Axis: Length Pull\52B2\Pull_52B2 Lonc_66kV\Cub_5\Lonc_52B6 Gorbea_66kV\Cub_4\Gorbea_89BT1F

Gorbea_13.2kV\Cub_1\Gorbea_52CT1 Gorbea_13.2kV\Cub_2\Gorbea_52C1

TD4_Pull B2 -> Gorbea MT_2F

Date: 11/6/2014

Annex:

DIg

SIL

EN

T

Page 54: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 54 de 121

Tipo Falla : 2F RF= 0 Ohm Ruta : Pullinque B2 - Gorbea 13,2kV Tiempos de Operación en segundos

S/E Paño Relé NEMA Pullinque

66kV

LT 66kV Pullinque - Loncoche

Loncoche 66kV

LT 66kV Loncoche - Gorbea

Gorbea 66kV

Gorbea Bushing

66kV T1

Gorbea 13,2kV

Línea de Media Tensión 13,2 kV

1% 25% 50% 75% 99% 1% 25% 50% 75% 99% 1% 25% 50% 75% 99%

Pullinque 52B2 SEL-311C Trip --- 0,02 0,02 0,02 0,02 0,82 0,82 0,82 0,82 0,82 2,72 2,72 2,72 2,72 --- --- --- --- --- ---

Pullinque 52B2 SEL-311C 21-Z1 --- 0,02 0,02 0,02 0,02 --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B2 SEL-311C 21-Z2 --- 0,82 0,82 0,82 0,82 0,82 0,82 0,82 0,82 0,82 --- --- --- --- --- --- --- --- --- ---

Pullinque 52B2 SEL-311C 21-Z3 --- 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 --- --- --- --- --- ---

Pullinque 52B2 SEL-311C 21N-Z1 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B2 SEL-311C 21N-Z2 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B2 SEL-311C 21N-Z3 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B2 SEL-311C 21N_Q-Z1 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B2 SEL-311C 21N_Q-Z2 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B2 SEL-311C 21N_Q-Z3 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Loncoche 52B6 SEL-311C Trip --- --- --- --- --- --- --- 0,02 0,02 0,02 0,02 0,02 0,02 0,02 --- --- --- --- --- ---

Loncoche 52B6 SEL-311C 21-Z1 --- --- --- --- --- --- --- 0,02 0,02 0,02 0,02 0,02 0,02 0,02 --- --- --- --- --- ---

Loncoche 52B6 SEL-311C 21-Z2 --- --- --- --- --- --- --- 0,72 0,72 0,72 0,72 0,72 0,72 0,72 --- --- --- --- --- ---

Loncoche 52B6 SEL-311C 21-Z3 --- --- --- --- --- --- --- 2,02 2,02 2,02 2,02 2,02 2,02 2,02 --- --- --- --- --- ---

Loncoche 52B6 SEL-311C 21N-Z1 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Loncoche 52B6 SEL-311C 21N-Z2 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Loncoche 52B6 SEL-311C 21N-Z3 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Loncoche 52B6 SEL-311C 51N --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Gorbea 89BT1-F Fuse SMD 65E Trip --- --- --- --- --- --- --- --- --- --- --- --- --- 0,06 0,89 1,01 2,23 4,23 8,37 14,81

Gorbea 52CT1 Siemens Argus Trip --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,56 0,63 1,37 2,73 6,23 10,52

Gorbea 52CT1 Siemens Argus 51N --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Gorbea 52CT1 Siemens Argus 51 --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,56 0,63 1,37 2,73 6,23 10,52

Gorbea 52C1 Siemens Argus Trip --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,05 0,09 0,15 0,25 0,33

Gorbea 52C1 Siemens Argus 51N --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Gorbea 52C1 Siemens Argus 51 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,05 0,09 0,15 0,25 0,33

Page 55: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 55 de 121

9.2.2.3. FALLA 2F-T PULLINQUE B2 -> GORBEA 13,2 kV

91,82973,46355,09736,73218,3660,0000 [km]

5,00

4,00

3,00

2,00

1,00

0,00

Pull_66kV Lonc_66kV Cto1

Gorbea_66kV

Bushing_66kV

Gorbea_13.2k..

LMT_13.2

x-Axis: Length Pull\52B2\Pull_52B2 Lonc_66kV\Cub_5\Lonc_52B6 Gorbea_66kV\Cub_4\Gorbea_89BT1F

Gorbea_13.2kV\Cub_1\Gorbea_52CT1 Gorbea_13.2kV\Cub_2\Gorbea_52C1

TD4_Pull B2 -> Gorbea MT_2F-T

Date: 11/6/2014

Annex:

DIg

SIL

EN

T

Page 56: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 56 de 121

Tipo Falla : 2FT RF= 0 Ohm Ruta : Pullinque B2 - Gorbea 13,2kV Tiempos de Operación en segundos

S/E Paño Relé NEMA Pullinque

66kV

LT 66kV Pullinque - Loncoche

Loncoche 66kV

LT 66kV Loncoche - Gorbea

Gorbea 66kV

Gorbea Bushing

66kV T1

Gorbea 13,2kV

Línea de Media Tensión 13,2 kV

1% 25% 50% 75% 99% 1% 25% 50% 75% 99% 1% 25% 50% 75% 99%

Pullinque 52B2 SEL-311C Trip --- 0,02 0,02 0,02 0,02 0,82 0,82 0,82 0,82 0,82 2,72 2,72 2,72 2,72 --- --- --- --- --- ---

Pullinque 52B2 SEL-311C 21-Z1 --- 0,02 0,02 0,02 0,02 --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B2 SEL-311C 21-Z2 --- 0,82 0,82 0,82 0,82 0,82 0,82 0,82 0,82 0,82 --- --- --- --- --- --- --- --- --- ---

Pullinque 52B2 SEL-311C 21-Z3 --- 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 --- --- --- --- --- ---

Pullinque 52B2 SEL-311C 21N-Z1 --- 0,02 0,02 0,02 0,02 --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B2 SEL-311C 21N-Z2 --- 0,82 0,82 0,82 0,82 0,82 0,82 0,82 0,82 0,82 --- --- --- --- --- --- --- --- --- ---

Pullinque 52B2 SEL-311C 21N-Z3 --- 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 --- --- --- --- --- ---

Pullinque 52B2 SEL-311C 21N_Q-Z1 --- 0,02 0,02 0,02 0,02 --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B2 SEL-311C 21N_Q-Z2 --- 0,82 0,82 0,82 0,82 0,82 0,82 0,82 0,82 0,82 --- --- --- --- --- --- --- --- --- ---

Pullinque 52B2 SEL-311C 21N_Q-Z3 --- 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 --- --- --- --- --- ---

Loncoche 52B6 SEL-311C Trip --- --- --- --- --- --- --- 0,02 0,02 0,02 0,02 0,02 0,02 0,02 --- --- --- --- --- ---

Loncoche 52B6 SEL-311C 21-Z1 --- --- --- --- --- --- --- 0,02 0,02 0,02 0,02 0,02 0,02 0,02 --- --- --- --- --- ---

Loncoche 52B6 SEL-311C 21-Z2 --- --- --- --- --- --- --- 0,72 0,72 0,72 0,72 0,72 0,72 0,72 --- --- --- --- --- ---

Loncoche 52B6 SEL-311C 21-Z3 --- --- --- --- --- --- --- 2,02 2,02 2,02 2,02 2,02 2,02 2,02 --- --- --- --- --- ---

Loncoche 52B6 SEL-311C 21N-Z1 --- --- --- --- --- --- --- 0,02 0,02 0,02 0,02 0,02 0,02 0,02 --- --- --- --- --- ---

Loncoche 52B6 SEL-311C 21N-Z2 --- --- --- --- --- --- --- 0,72 0,72 0,72 0,72 0,72 0,72 0,72 --- --- --- --- --- ---

Loncoche 52B6 SEL-311C 21N-Z3 --- --- --- --- --- --- --- 2,02 2,02 2,02 2,02 2,02 2,02 2,02 --- --- --- --- --- ---

Loncoche 52B6 SEL-311C 51N --- --- --- --- --- --- --- 0,25 0,26 0,28 0,31 0,34 0,34 0,34 --- --- --- --- --- ---

Gorbea 89BT1-F Fuse SMD 65E Trip --- --- --- --- --- --- --- --- --- --- --- --- --- 0,04 0,89 1,01 2,23 4,23 8,36 14,81

Gorbea 52CT1 Siemens Argus Trip --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,36 0,44 1,06 1,25 1,42 1,54

Gorbea 52CT1 Siemens Argus 51N --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,82 0,86 1,08 1,25 1,42 1,54

Gorbea 52CT1 Siemens Argus 51 --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,36 0,44 1,06 2,13 4,51 7,65

Gorbea 52C1 Siemens Argus Trip --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,04 0,08 0,12 0,21 0,28

Gorbea 52C1 Siemens Argus 51N --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,56 0,67 0,76 0,84 0,90

Gorbea 52C1 Siemens Argus 51 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,04 0,08 0,12 0,21 0,28

Page 57: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 57 de 121

9.2.2.4. FALLA 1F PULLINQUE B2 -> GORBEA 13,2 kV

91,82973,46355,09736,73218,3660,0000 [km]

5,00

4,00

3,00

2,00

1,00

0,00

Pull_66kV Lonc_66kV Cto1

Gorbea_66kV

Bushing_66kV

Gorbea_13.2k..

LMT_13.2

x-Axis: Length Pull\52B2\Pull_52B2 Lonc_66kV\Cub_5\Lonc_52B6 Gorbea_66kV\Cub_4\Gorbea_89BT1F

Gorbea_13.2kV\Cub_1\Gorbea_52CT1 Gorbea_13.2kV\Cub_2\Gorbea_52C1

TD4_Pull B2 -> Gorbea MT_1F

Date: 11/6/2014

Annex:

DIg

SIL

EN

T

Page 58: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 58 de 121

Tipo Falla : 1FT RF= 0 Ohm Ruta : Pullinque B2 - Gorbea 13,2kV Tiempos de Operación en segundos

S/E Paño Relé NEMA Pullinque

66kV

LT 66kV Pullinque - Loncoche

Loncoche 66kV

LT 66kV Loncoche - Gorbea

Gorbea 66kV

Gorbea Bushing

66kV T1

Gorbea 13,2kV

Línea de Media Tensión 13,2 kV

1% 25% 50% 75% 99% 1% 25% 50% 75% 99% 1% 25% 50% 75% 99%

Pullinque 52B2 SEL-311C Trip --- 0,02 0,02 0,02 0,02 0,82 0,82 0,82 0,82 0,82 2,72 2,72 2,72 2,72 --- --- --- --- --- ---

Pullinque 52B2 SEL-311C 21-Z1 --- 0,02 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B2 SEL-311C 21-Z2 --- 0,82 0,82 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B2 SEL-311C 21-Z3 --- 2,72 2,72 2,72 2,72 2,72 2,72 2,72 --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B2 SEL-311C 21N-Z1 --- 0,02 0,02 0,02 0,02 --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B2 SEL-311C 21N-Z2 --- 0,82 0,82 0,82 0,82 0,82 0,82 0,82 0,82 0,82 --- --- --- --- --- --- --- --- --- ---

Pullinque 52B2 SEL-311C 21N-Z3 --- 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 --- --- --- --- --- ---

Pullinque 52B2 SEL-311C 21N_Q-Z1 --- 0,02 0,02 0,02 0,02 --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B2 SEL-311C 21N_Q-Z2 --- 0,82 0,82 0,82 0,82 0,82 0,82 0,82 0,82 0,82 --- --- --- --- --- --- --- --- --- ---

Pullinque 52B2 SEL-311C 21N_Q-Z3 --- 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 --- --- --- --- --- ---

Loncoche 52B6 SEL-311C Trip --- --- --- --- --- --- --- 0,02 0,02 0,02 0,02 0,02 0,02 0,02 --- --- --- --- --- ---

Loncoche 52B6 SEL-311C 21-Z1 --- --- --- --- --- --- --- 0,02 --- --- --- --- --- --- --- --- --- --- --- ---

Loncoche 52B6 SEL-311C 21-Z2 --- --- --- --- --- --- --- 0,72 0,72 0,72 0,72 0,72 0,72 0,72 --- --- --- --- --- ---

Loncoche 52B6 SEL-311C 21-Z3 --- --- --- --- --- --- --- 2,02 2,02 2,02 2,02 2,02 2,02 2,02 --- --- --- --- --- ---

Loncoche 52B6 SEL-311C 21N-Z1 --- --- --- --- --- --- --- 0,02 0,02 0,02 0,02 0,02 0,02 0,02 --- --- --- --- --- ---

Loncoche 52B6 SEL-311C 21N-Z2 --- --- --- --- --- --- --- 0,72 0,72 0,72 0,72 0,72 0,72 0,72 --- --- --- --- --- ---

Loncoche 52B6 SEL-311C 21N-Z3 --- --- --- --- --- --- --- 2,02 2,02 2,02 2,02 2,02 2,02 2,02 --- --- --- --- --- ---

Loncoche 52B6 SEL-311C 51N --- --- --- --- --- --- --- 0,24 0,25 0,26 0,27 0,29 0,29 0,29 --- --- --- --- --- ---

Gorbea 89BT1-F Fuse SMD 65E Trip --- --- --- --- --- --- --- --- --- --- --- --- --- 0,09 2,26 3,00 21,74 --- --- ---

Gorbea 52CT1 Siemens Argus Trip --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,35 0,44 1,03 1,15 1,28 1,36

Gorbea 52CT1 Siemens Argus 51N --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,84 0,87 1,03 1,15 1,28 1,36

Gorbea 52CT1 Siemens Argus 51 --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,35 0,44 1,60 4,86 14,15 25,46

Gorbea 52C1 Siemens Argus Trip --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,04 0,10 0,21 0,39 0,58

Gorbea 52C1 Siemens Argus 51N --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,56 0,64 0,71 0,77 0,82

Gorbea 52C1 Siemens Argus 51 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,04 0,10 0,21 0,39 0,58

Page 59: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 59 de 121

9.2.2.5. F LL 1F (R = Ω) PULLINQUE B2 -> GORBEA 13,2 kV

91,82973,46355,09736,73218,3660,0000 [km]

5,00

4,00

3,00

2,00

1,00

0,00

Pull_66kV Lonc_66kV Cto1

Gorbea_66kV

Bushing_66kV

Gorbea_13.2k..

LMT_13.2

x-Axis: Length Pull\52B2\Pull_52B2 Lonc_66kV\Cub_5\Lonc_52B6 Gorbea_66kV\Cub_4\Gorbea_89BT1F

Gorbea_13.2kV\Cub_1\Gorbea_52CT1 Gorbea_13.2kV\Cub_2\Gorbea_52C1

TD4_Pull B2 -> Gorbea MT_1F_R25

Date: 11/6/2014

Annex:

DIg

SIL

EN

T

Page 60: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 60 de 121

Tipo Falla : 1FT RF= 25 Ohm Ruta : Pullinque B2 - Gorbea 13,2kV Tiempos de Operación en segundos

S/E Paño Relé NEMA Pullinque

66kV

LT 66kV Pullinque - Loncoche

Loncoche 66kV

LT 66kV Loncoche - Gorbea

Gorbea 66kV

Gorbea Bushing

66kV T1

Gorbea 13,2kV

Línea de Media Tensión 13,2 kV

1% 25% 50% 75% 99% 1% 25% 50% 75% 99% 1% 25% 50% 75% 99%

Pullinque 52B2 SEL-311C Trip --- 0,82 0,82 0,82 0,82 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 --- --- --- --- --- ---

Pullinque 52B2 SEL-311C 21-Z1 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B2 SEL-311C 21-Z2 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B2 SEL-311C 21-Z3 --- 2,72 2,72 2,72 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B2 SEL-311C 21N-Z1 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B2 SEL-311C 21N-Z2 --- 0,82 0,82 0,82 0,82 --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B2 SEL-311C 21N-Z3 --- 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 --- --- --- --- --- ---

Pullinque 52B2 SEL-311C 21N_Q-Z1 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B2 SEL-311C 21N_Q-Z2 --- 0,82 0,82 0,82 0,82 --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B2 SEL-311C 21N_Q-Z3 --- 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 --- --- --- --- --- ---

Loncoche 52B6 SEL-311C Trip --- --- --- --- --- --- --- 0,02 0,02 0,02 0,36 0,40 0,41 0,41 --- --- --- --- --- ---

Loncoche 52B6 SEL-311C 21-Z1 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Loncoche 52B6 SEL-311C 21-Z2 --- --- --- --- --- --- --- 0,72 --- --- --- --- --- --- --- --- --- --- --- ---

Loncoche 52B6 SEL-311C 21-Z3 --- --- --- --- --- --- --- 2,02 2,02 --- --- --- --- --- --- --- --- --- --- ---

Loncoche 52B6 SEL-311C 21N-Z1 --- --- --- --- --- --- --- 0,02 0,02 0,02 --- --- --- --- --- --- --- --- --- ---

Loncoche 52B6 SEL-311C 21N-Z2 --- --- --- --- --- --- --- 0,72 0,72 0,72 0,72 0,72 0,72 0,72 --- --- --- --- --- ---

Loncoche 52B6 SEL-311C 21N-Z3 --- --- --- --- --- --- --- 2,02 2,02 2,02 2,02 2,02 2,02 2,02 --- --- --- --- --- ---

Loncoche 52B6 SEL-311C 51N --- --- --- --- --- --- --- 0,28 0,30 0,32 0,36 0,40 0,41 0,41 --- --- --- --- --- ---

Gorbea 89BT1-F Fuse SMD 65E Trip --- --- --- --- --- --- --- --- --- --- --- --- --- 0,24 --- --- --- --- --- ---

Gorbea 52CT1 Siemens Argus Trip --- --- --- --- --- --- --- --- --- --- --- --- --- --- 1,69 1,70 1,75 1,81 1,88 1,93

Gorbea 52CT1 Siemens Argus 51N --- --- --- --- --- --- --- --- --- --- --- --- --- --- 1,69 1,70 1,75 1,81 1,88 1,93

Gorbea 52CT1 Siemens Argus 51 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Gorbea 52C1 Siemens Argus Trip --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,98 1,00 1,03 1,06 1,08

Gorbea 52C1 Siemens Argus 51N --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,98 1,00 1,03 1,06 1,08

Gorbea 52C1 Siemens Argus 51 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 1,95 2,24 2,60 3,07 3,47

Page 61: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 61 de 121

9.3. ESCENARIO 3

LT 66kV Temuco – Loncoche N°1 en servicio

LT 66kV Temuco – Loncoche N°2 en servicio

LT 66kV Pullinque – Loncoche N°1 fuera de servicio

LT 66kV Pullinque – Loncoche N°2 en servicio

S/E Gorbea conectada a la LT 66kV Temuco - Loncoche N°2

Page 62: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 62 de 121

9.3.1. Ruta 1: Temuco B2 -> Gorbea 13,2 kV

Page 63: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 63 de 121

9.3.1.1. FALLA 3F TEMUCO B2 -> GORBEA 13,2 kV

62,81150,24937,68725,12412,5620,0000 [km]

5,00

4,00

3,00

2,00

1,00

0,00

Tem_66kV_ Tap Padre La..

Tap Licanco ..

Pitrufquen 6.. Cto2

Gorbea_66kV

Bushing_66kV

Gorbea_13.2k..

LMT_13.2

x-Axis: Length Tem\52B2\Tem_52B2 Gorbea_66kV\Cub_4\Gorbea_89BT1F Gorbea_13.2kV\Cub_1\Gorbea_52CT1

Gorbea_13.2kV\Cub_2\Gorbea_52C1

TD1_Tem B2 -> Gorbea MT_3F

Date: 11/7/2014

Annex:

DIg

SIL

EN

T

Page 64: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 64 de 121

Tipo Falla : 3F RF= 0 Ohm

Ruta : Temuco B2 - Gorbea 13,2kV

Tiempos de Operación en segundos

S/E Paño Relé NEMA Temuco

66kV

LT 66kV Temuco - Gorbea

Gorbea 66kV

Gorbea Bushing 66kV T1

Gorbea Barra

13,2kV

Línea de Media Tensión 13,2 kV

Padre Las Casas 66kV

Tap Licanco

66kV

Pitrufquén 66 kV

1% 25% 50% 75% 99%

Temuco 52B2 SEL-311C Trip --- 0,02 0,02 0,02 0,02 0,02 --- --- --- --- --- ---

Temuco 52B2 SEL-311C 21-Z1 --- 0,02 0,02 0,02 0,02 0,02 --- --- --- --- --- ---

Temuco 52B2 SEL-311C 21-Z2 --- 0,82 0,82 0,82 0,82 0,82 --- --- --- --- --- ---

Temuco 52B2 SEL-311C 21-Z3 --- 2,72 2,72 2,72 2,72 2,72 --- --- --- --- --- ---

Temuco 52B2 SEL-311C 21N-Z1 --- --- --- --- --- --- --- --- --- --- --- ---

Temuco 52B2 SEL-311C 21N-Z2 --- --- --- --- --- --- --- --- --- --- --- ---

Temuco 52B2 SEL-311C 21N-Z3 --- --- --- --- --- --- --- --- --- --- --- ---

Temuco 52B2 SEL-311C 51N --- --- --- --- --- --- --- --- --- --- --- ---

Temuco 52B2 SEL-311C 67N --- --- --- --- --- --- --- --- --- --- --- ---

Gorbea 89BT1-F Fuse SMD 65E Trip --- --- --- --- --- 0,04 0,89 1,01 2,23 4,23 8,37 14,82

Gorbea 52CT1 Siemens Argus Trip --- --- --- --- --- --- 0,43 0,48 0,97 1,89 3,79 6,41

Gorbea 52CT1 Siemens Argus 51N --- --- --- --- --- --- --- --- --- --- --- ---

Gorbea 52CT1 Siemens Argus 51 --- --- --- --- --- --- 0,43 0,48 0,97 1,89 3,79 6,41

Gorbea 52C1 Siemens Argus Trip --- --- --- --- --- --- --- 0,04 0,07 0,12 0,19 0,25

Gorbea 52C1 Siemens Argus 51N --- --- --- --- --- --- --- --- --- --- --- ---

Gorbea 52C1 Siemens Argus 51 --- --- --- --- --- --- --- 0,04 0,07 0,12 0,19 0,25

Page 65: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 65 de 121

9.3.1.2. FALLA 2F TEMUCO B2 -> GORBEA 13,2 kV

62,81150,24937,68725,12412,5620,0000 [km]

5,00

4,00

3,00

2,00

1,00

0,00

Tem_66kV_ Tap Padre La..

Tap Licanco ..

Pitrufquen 6.. Cto2

Gorbea_66kV

Bushing_66kV

Gorbea_13.2k..

LMT_13.2

x-Axis: Length Tem\52B2\Tem_52B2 Gorbea_66kV\Cub_4\Gorbea_89BT1F Gorbea_13.2kV\Cub_1\Gorbea_52CT1

Gorbea_13.2kV\Cub_2\Gorbea_52C1

TD1_Tem B2 -> Gorbea MT_2F

Date: 11/7/2014

Annex:

DIg

SIL

EN

T

Page 66: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 66 de 121

Tipo Falla : 2F RF= 0 Ohm

Ruta : Temuco B2 - Gorbea 13,2kV

Tiempos de Operación en segundos

S/E Paño Relé NEMA Temuco

66kV

LT 66kV Temuco - Gorbea

Gorbea 66kV

Gorbea Bushing 66kV T1

Gorbea Barra

13,2kV

Línea de Media Tensión 13,2 kV

Padre Las Casas 66kV

Tap Licanco

66kV

Pitrufquén 66 kV

1% 25% 50% 75% 99%

Temuco 52B2 SEL-311C Trip --- 0,02 0,02 0,02 0,02 0,02 --- --- --- --- --- ---

Temuco 52B2 SEL-311C 21-Z1 --- 0,02 0,02 0,02 0,02 0,02 --- --- --- --- --- ---

Temuco 52B2 SEL-311C 21-Z2 --- 0,82 0,82 0,82 0,82 0,82 --- --- --- --- --- ---

Temuco 52B2 SEL-311C 21-Z3 --- 2,72 2,72 2,72 2,72 2,72 --- --- --- --- --- ---

Temuco 52B2 SEL-311C 21N-Z1 --- --- --- --- --- --- --- --- --- --- --- ---

Temuco 52B2 SEL-311C 21N-Z2 --- --- --- --- --- --- --- --- --- --- --- ---

Temuco 52B2 SEL-311C 21N-Z3 --- --- --- --- --- --- --- --- --- --- --- ---

Temuco 52B2 SEL-311C 51N --- --- --- --- --- --- --- --- --- --- --- ---

Temuco 52B2 SEL-311C 67N --- --- --- --- --- --- --- --- --- --- --- ---

Gorbea 89BT1-F Fuse SMD 65E Trip --- --- --- --- --- 0,06 0,89 1,01 2,23 4,23 8,37 14,81

Gorbea 52CT1 Siemens Argus Trip --- --- --- --- --- --- 0,55 0,63 1,37 2,73 6,23 10,52

Gorbea 52CT1 Siemens Argus 51N --- --- --- --- --- --- --- --- --- --- --- ---

Gorbea 52CT1 Siemens Argus 51 --- --- --- --- --- --- 0,55 0,63 1,37 2,73 6,23 10,52

Gorbea 52C1 Siemens Argus Trip --- --- --- --- --- --- --- 0,05 0,09 0,15 0,25 0,33

Gorbea 52C1 Siemens Argus 51N --- --- --- --- --- --- --- --- --- --- --- ---

Gorbea 52C1 Siemens Argus 51 --- --- --- --- --- --- --- 0,05 0,09 0,15 0,25 0,33

Page 67: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 67 de 121

9.3.1.3. FALLA 2F-T TEMUCO B2 -> GORBEA 13,2 kV

62,81150,24937,68725,12412,5620,0000 [km]

5,00

4,00

3,00

2,00

1,00

0,00

Tem_66kV_ Tap Padre La..

Tap Licanco ..

Pitrufquen 6.. Cto2

Gorbea_66kV

Bushing_66kV

Gorbea_13.2k..

LMT_13.2

x-Axis: Length Tem\52B2\Tem_52B2 Gorbea_66kV\Cub_4\Gorbea_89BT1F Gorbea_13.2kV\Cub_1\Gorbea_52CT1

Gorbea_13.2kV\Cub_2\Gorbea_52C1

TD1_Tem B2 -> Gorbea MT_2F-T

Date: 11/7/2014

Annex:

DIg

SIL

EN

T

Page 68: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 68 de 121

Tipo Falla : 2FT RF= 0 Ohm

Ruta : Temuco B2 - Gorbea 13,2kV

Tiempos de Operación en segundos

S/E Paño Relé NEMA Temuco

66kV

LT 66kV Temuco - Gorbea

Gorbea 66kV

Gorbea Bushing 66kV T1

Gorbea Barra

13,2kV

Línea de Media Tensión 13,2 kV

Padre Las Casas 66kV

Tap Licanco

66kV

Pitrufquén 66 kV

1% 25% 50% 75% 99%

Temuco 52B2 SEL-311C Trip --- 0,01 0,01 0,01 0,02 0,02 --- --- --- --- --- ---

Temuco 52B2 SEL-311C 21-Z1 --- 0,02 0,02 0,02 0,02 0,02 --- --- --- --- --- ---

Temuco 52B2 SEL-311C 21-Z2 --- 0,82 0,82 0,82 0,82 0,82 --- --- --- --- --- ---

Temuco 52B2 SEL-311C 21-Z3 --- 2,72 2,72 2,72 2,72 2,72 --- --- --- --- --- ---

Temuco 52B2 SEL-311C 21N-Z1 --- 0,02 0,02 0,02 0,02 0,02 --- --- --- --- --- ---

Temuco 52B2 SEL-311C 21N-Z2 --- 0,82 0,82 0,82 0,82 0,82 --- --- --- --- --- ---

Temuco 52B2 SEL-311C 21N-Z3 --- 2,72 2,72 2,72 2,72 2,72 --- --- --- --- --- ---

Temuco 52B2 SEL-311C 51N --- 0,23 0,23 0,31 0,39 0,39 --- --- --- --- --- ---

Temuco 52B2 SEL-311C 67N --- 0,01 0,01 0,01 --- --- --- --- --- --- --- ---

Gorbea 89BT1-F Fuse SMD 65E Trip --- --- --- --- --- 0,05 0,89 1,01 2,23 4,23 8,37 14,81

Gorbea 52CT1 Siemens Argus Trip --- --- --- --- --- --- 0,36 0,44 1,06 1,25 1,42 1,54

Gorbea 52CT1 Siemens Argus 51N --- --- --- --- --- --- 0,82 0,86 1,08 1,25 1,42 1,54

Gorbea 52CT1 Siemens Argus 51 --- --- --- --- --- --- 0,36 0,44 1,06 2,13 4,51 7,65

Gorbea 52C1 Siemens Argus Trip --- --- --- --- --- --- --- 0,04 0,08 0,12 0,21 0,28

Gorbea 52C1 Siemens Argus 51N --- --- --- --- --- --- --- 0,56 0,67 0,76 0,84 0,90

Gorbea 52C1 Siemens Argus 51 --- --- --- --- --- --- --- 0,04 0,08 0,12 0,21 0,28

Page 69: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 69 de 121

9.3.1.4. FALLA 1F TEMUCO B2 -> GORBEA 13,2 kV

62,81150,24937,68725,12412,5620,0000 [km]

5,00

4,00

3,00

2,00

1,00

0,00

Tem_66kV_ Tap Padre La..

Tap Licanco ..

Pitrufquen 6.. Cto2

Gorbea_66kV

Bushing_66kV

Gorbea_13.2k..

LMT_13.2

x-Axis: Length Tem\52B2\Tem_52B2 Gorbea_66kV\Cub_4\Gorbea_89BT1F Gorbea_13.2kV\Cub_1\Gorbea_52CT1

Gorbea_13.2kV\Cub_2\Gorbea_52C1

TD1_Tem B2 -> Gorbea MT_1F

Date: 11/7/2014

Annex:

DIg

SIL

EN

T

Page 70: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 70 de 121

Tipo Falla : 1FT RF= 0 Ohm

Ruta : Temuco B2 - Gorbea 13,2kV

Tiempos de Operación en segundos

S/E Paño Relé NEMA Temuco

66kV

LT 66kV Temuco - Gorbea

Gorbea 66kV

Gorbea Bushing 66kV T1

Gorbea Barra

13,2kV

Línea de Media Tensión 13,2 kV

Padre Las Casas 66kV

Tap Licanco

66kV

Pitrufquén 66 kV

1% 25% 50% 75% 99%

Temuco 52B2 SEL-311C Trip --- 0,01 0,01 0,01 0,02 0,02 --- --- --- --- --- ---

Temuco 52B2 SEL-311C 21-Z1 --- 0,02 0,02 --- --- --- --- --- --- --- --- ---

Temuco 52B2 SEL-311C 21-Z2 --- 0,82 0,82 --- --- --- --- --- --- --- --- ---

Temuco 52B2 SEL-311C 21-Z3 --- 2,72 2,72 2,72 2,72 2,72 --- --- --- --- --- ---

Temuco 52B2 SEL-311C 21N-Z1 --- 0,02 0,02 0,02 0,02 0,02 --- --- --- --- --- ---

Temuco 52B2 SEL-311C 21N-Z2 --- 0,82 0,82 0,82 0,82 0,82 --- --- --- --- --- ---

Temuco 52B2 SEL-311C 21N-Z3 --- 2,72 2,72 2,72 2,72 2,72 --- --- --- --- --- ---

Temuco 52B2 SEL-311C 51N --- 0,23 0,23 0,27 0,32 0,32 --- --- --- --- --- ---

Temuco 52B2 SEL-311C 67N --- 0,01 0,01 0,01 --- --- --- --- --- --- --- ---

Gorbea 89BT1-F Fuse SMD 65E Trip --- --- --- --- --- 0,09 2,25 3,00 21,72 --- --- ---

Gorbea 52CT1 Siemens Argus Trip --- --- --- --- --- --- 0,35 0,44 1,03 1,15 1,28 1,36

Gorbea 52CT1 Siemens Argus 51N --- --- --- --- --- --- 0,84 0,87 1,03 1,15 1,28 1,36

Gorbea 52CT1 Siemens Argus 51 --- --- --- --- --- --- 0,35 0,44 1,60 4,86 14,15 25,46

Gorbea 52C1 Siemens Argus Trip --- --- --- --- --- --- --- 0,04 0,10 0,21 0,39 0,58

Gorbea 52C1 Siemens Argus 51N --- --- --- --- --- --- --- 0,56 0,64 0,71 0,77 0,82

Gorbea 52C1 Siemens Argus 51 --- --- --- --- --- --- --- 0,04 0,10 0,21 0,39 0,58

Page 71: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 71 de 121

9.3.1.5. F LL 1F (R = Ω) TEMUCO B2 -> GORBEA 13,2 kV

62,81150,24937,68725,12412,5620,0000 [km]

5,00

4,00

3,00

2,00

1,00

0,00

Tem_66kV_ Tap Padre La..

Tap Licanco ..

Pitrufquen 6.. Cto2

Gorbea_66kV

Bushing_66kV

Gorbea_13.2k..

LMT_13.2

x-Axis: Length Tem\52B2\Tem_52B2 Gorbea_66kV\Cub_4\Gorbea_89BT1F Gorbea_13.2kV\Cub_1\Gorbea_52CT1

Gorbea_13.2kV\Cub_2\Gorbea_52C1

TD1_Tem B2 -> Gorbea MT_1F_R25

Date: 11/7/2014

Annex:

DIg

SIL

EN

T

Page 72: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 72 de 121

Tipo Falla : 1FT RF= 25 Ohm

Ruta : Temuco B2 - Gorbea 13,2kV

Tiempos de Operación en segundos

S/E Paño Relé NEMA Temuco

66kV

LT 66kV Temuco - Gorbea

Gorbea 66kV

Gorbea Bushing 66kV T1

Gorbea Barra

13,2kV

Línea de Media Tensión 13,2 kV

Padre Las Casas 66kV

Tap Licanco

66kV

Pitrufquén 66 kV

1% 25% 50% 75% 99%

Temuco 52B2 SEL-311C Trip --- 0,01 0,01 0,37 0,48 0,48 --- --- --- --- --- ---

Temuco 52B2 SEL-311C 21-Z1 --- --- --- --- --- --- --- --- --- --- --- ---

Temuco 52B2 SEL-311C 21-Z2 --- 0,82 --- --- --- --- --- --- --- --- --- ---

Temuco 52B2 SEL-311C 21-Z3 --- 2,72 2,72 --- --- --- --- --- --- --- --- ---

Temuco 52B2 SEL-311C 21N-Z1 --- 0,02 0,02 --- --- --- --- --- --- --- --- ---

Temuco 52B2 SEL-311C 21N-Z2 --- 0,82 0,82 0,82 0,82 0,82 --- --- --- --- --- ---

Temuco 52B2 SEL-311C 21N-Z3 --- 2,72 2,72 2,72 2,72 2,72 --- --- --- --- --- ---

Temuco 52B2 SEL-311C 51N --- 0,27 0,27 0,37 0,48 0,48 --- --- --- --- --- ---

Temuco 52B2 SEL-311C 67N --- 0,01 0,01 --- --- --- --- --- --- --- --- ---

Gorbea 89BT1-F Fuse SMD 65E Trip --- --- --- --- --- 0,25 --- --- --- --- --- ---

Gorbea 52CT1 Siemens Argus Trip --- --- --- --- --- --- 1,69 1,70 1,75 1,81 1,88 1,93

Gorbea 52CT1 Siemens Argus 51N --- --- --- --- --- --- 1,69 1,70 1,75 1,81 1,88 1,93

Gorbea 52CT1 Siemens Argus 51 --- --- --- --- --- --- --- --- --- --- --- ---

Gorbea 52C1 Siemens Argus Trip --- --- --- --- --- --- --- 0,98 1,00 1,03 1,06 1,08

Gorbea 52C1 Siemens Argus 51N --- --- --- --- --- --- --- 0,98 1,00 1,03 1,06 1,08

Gorbea 52C1 Siemens Argus 51 --- --- --- --- --- --- --- 1,95 2,24 2,60 3,07 3,47

Page 73: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 73 de 121

9.3.2. Ruta 2: Pullinque B4 -> Gorbea 13,2 kV

Page 74: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 74 de 121

9.3.2.1. FALLA 3F PULLINQUE B4 -> GORBEA 13,2 kV

91,82973,46355,09736,73218,3660,0000 [km]

5,00

4,00

3,00

2,00

1,00

0,00

Pull_66kV_ Lonc_66kV_ Cto2

Gorbea_66kV

Bushing_66kV

Gorbea_13.2k..

LMT_13.2

x-Axis: Length Pull\52B4\Pull_52B4 Lonc\52B3\Lonc_52B3_G1 Gorbea_66kV\Cub_4\Gorbea_89BT1F

Gorbea_13.2kV\Cub_1\Gorbea_52CT1 Gorbea_13.2kV\Cub_2\Gorbea_52C1

TD2_Pull B4 -> Gorbea MT_3F

Date: 11/7/2014

Annex:

DIg

SIL

EN

T

Page 75: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 75 de 121

Tipo Falla : 3F RF= 0 Ohm Ruta : Pullinque B4 - Gorbea 13,kV Tiempos de Operación en segundos

S/E Paño Relé NEMA Pullinque

66kV

LT 66kV Pullinque - Loncoche

Loncoche 66kV

LT 66kV Loncoche - Gorbea

Gorbea 66kV

Gorbea Bushing

66kV T1

Gorbea 13,2kV

Línea de Media Tensión 13,2 kV

1% 25% 50% 75% 99% 1% 25% 50% 75% 99% 1% 25% 50% 75% 99%

Pullinque 52B4 SEL-311C Trip --- 0,02 0,02 0,02 0,02 0,82 0,82 0,82 0,82 0,82 2,72 2,72 2,72 2,72 --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21-Z1 --- 0,02 0,02 0,02 0,02 --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21-Z2 --- 0,82 0,82 0,82 0,82 0,82 0,82 0,82 0,82 0,82 --- --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21-Z3 --- 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21N-Z1 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21N-Z2 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21N-Z3 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21N_Q-Z1 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21N_Q-Z2 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21N_Q-Z3 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Loncoche 52B3 SEL-311C Trip --- --- --- --- --- --- 0,02 0,02 0,02 0,02 0,02 0,02 0,02 0,02 --- --- --- --- --- ---

Loncoche 52B3 SEL-311C 21-Z1 --- --- --- --- --- --- 0,02 0,02 0,02 0,02 0,02 0,02 0,02 0,02 --- --- --- --- --- ---

Loncoche 52B3 SEL-311C 21-Z2 --- --- --- --- --- --- 0,72 0,72 0,72 0,72 0,72 0,72 0,72 0,72 --- --- --- --- --- ---

Loncoche 52B3 SEL-311C 21-Z3 --- --- --- --- --- --- 2,02 2,02 2,02 2,02 2,02 2,02 2,02 2,02 --- --- --- --- --- ---

Loncoche 52B3 SEL-311C 21N-Z1 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Loncoche 52B3 SEL-311C 21N-Z2 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Loncoche 52B3 SEL-311C 21N-Z3 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Loncoche 52B3 SEL-311C 51N --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Gorbea 89BT1-F Fuse SMD 65E Trip --- --- --- --- --- --- --- --- --- --- --- --- --- 0,04 0,89 1,01 2,23 4,23 8,37 14,82

Gorbea 52CT1 Siemens Argus Trip --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,43 0,48 0,97 1,89 3,79 6,41

Gorbea 52CT1 Siemens Argus 51N --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Gorbea 52CT1 Siemens Argus 51 --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,43 0,48 0,97 1,89 3,79 6,41

Gorbea 52C1 Siemens Argus Trip --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,04 0,07 0,12 0,19 0,25

Gorbea 52C1 Siemens Argus 51N --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Gorbea 52C1 Siemens Argus 51 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,04 0,07 0,12 0,19 0,25

Page 76: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 76 de 121

9.3.2.2. FALLA 2F PULLINQUE B4 -> GORBEA 13,2 kV

91,82973,46355,09736,73218,3660,0000 [km]

5,00

4,00

3,00

2,00

1,00

0,00

Pull_66kV_ Lonc_66kV_ Cto2

Gorbea_66kV

Bushing_66kV

Gorbea_13.2k..

LMT_13.2

x-Axis: Length Pull\52B4\Pull_52B4 Lonc\52B3\Lonc_52B3_G1 Gorbea_66kV\Cub_4\Gorbea_89BT1F

Gorbea_13.2kV\Cub_1\Gorbea_52CT1 Gorbea_13.2kV\Cub_2\Gorbea_52C1

TD2_Pull B4 -> Gorbea MT_2F

Date: 11/7/2014

Annex:

DIg

SIL

EN

T

Page 77: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 77 de 121

Tipo Falla : 2F RF= 0 Ohm Ruta : Pullinque B4 - Gorbea 13,kV Tiempos de Operación en segundos

S/E Paño Relé NEMA Pullinque

66kV

LT 66kV Pullinque - Loncoche

Loncoche 66kV

LT 66kV Loncoche - Gorbea

Gorbea 66kV

Gorbea Bushing

66kV T1

Gorbea 13,2kV

Línea de Media Tensión 13,2 kV

1% 25% 50% 75% 99% 1% 25% 50% 75% 99% 1% 25% 50% 75% 99%

Pullinque 52B4 SEL-311C Trip --- 0,02 0,02 0,02 0,02 0,82 0,82 0,82 0,82 0,82 2,72 2,72 2,72 2,72 --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21-Z1 --- 0,02 0,02 0,02 0,02 --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21-Z2 --- 0,82 0,82 0,82 0,82 0,82 0,82 0,82 0,82 0,82 --- --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21-Z3 --- 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21N-Z1 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21N-Z2 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21N-Z3 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21N_Q-Z1 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21N_Q-Z2 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21N_Q-Z3 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Loncoche 52B3 SEL-311C Trip --- --- --- --- --- --- --- 0,02 0,02 0,02 0,02 0,02 0,02 0,02 --- --- --- --- --- ---

Loncoche 52B3 SEL-311C 21-Z1 --- --- --- --- --- --- --- 0,02 0,02 0,02 0,02 0,02 0,02 0,02 --- --- --- --- --- ---

Loncoche 52B3 SEL-311C 21-Z2 --- --- --- --- --- --- --- 0,72 0,72 0,72 0,72 0,72 0,72 0,72 --- --- --- --- --- ---

Loncoche 52B3 SEL-311C 21-Z3 --- --- --- --- --- --- --- 2,02 2,02 2,02 2,02 2,02 2,02 2,02 --- --- --- --- --- ---

Loncoche 52B3 SEL-311C 21N-Z1 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Loncoche 52B3 SEL-311C 21N-Z2 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Loncoche 52B3 SEL-311C 21N-Z3 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Loncoche 52B3 SEL-311C 51N --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Gorbea 89BT1-F Fuse SMD 65E Trip --- --- --- --- --- --- --- --- --- --- --- --- --- 0,06 0,89 1,01 2,23 4,23 8,37 14,81

Gorbea 52CT1 Siemens Argus Trip --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,55 0,63 1,37 2,73 6,23 10,52

Gorbea 52CT1 Siemens Argus 51N --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Gorbea 52CT1 Siemens Argus 51 --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,55 0,63 1,37 2,73 6,23 10,52

Gorbea 52C1 Siemens Argus Trip --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,05 0,09 0,15 0,25 0,33

Gorbea 52C1 Siemens Argus 51N --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Gorbea 52C1 Siemens Argus 51 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,05 0,09 0,15 0,25 0,33

Page 78: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 78 de 121

9.3.2.3. FALLA 2F-T PULLINQUE B4 -> GORBEA 13,2 kV

91,82973,46355,09736,73218,3660,0000 [km]

5,00

4,00

3,00

2,00

1,00

0,00

Pull_66kV_ Lonc_66kV_ Cto2

Gorbea_66kV

Bushing_66kV

Gorbea_13.2k..

LMT_13.2

x-Axis: Length Pull\52B4\Pull_52B4 Lonc\52B3\Lonc_52B3_G1 Gorbea_66kV\Cub_4\Gorbea_89BT1F

Gorbea_13.2kV\Cub_1\Gorbea_52CT1 Gorbea_13.2kV\Cub_2\Gorbea_52C1

TD2_Pull B4 -> Gorbea MT_2F-T

Date: 11/7/2014

Annex:

DIg

SIL

EN

T

Page 79: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 79 de 121

Tipo Falla : 2FT RF= 0 Ohm Ruta : Pullinque B4 - Gorbea 13,kV Tiempos de Operación en segundos

S/E Paño Relé NEMA Pullinque

66kV

LT 66kV Pullinque - Loncoche

Loncoche 66kV

LT 66kV Loncoche - Gorbea

Gorbea 66kV

Gorbea Bushing

66kV T1

Gorbea 13,2kV

Línea de Media Tensión 13,2 kV

1% 25% 50% 75% 99% 1% 25% 50% 75% 99% 1% 25% 50% 75% 99%

Pullinque 52B4 SEL-311C Trip --- 0,02 0,02 0,02 0,02 0,82 0,82 0,82 0,82 0,82 0,82 2,72 2,72 2,72 --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21-Z1 --- 0,02 0,02 0,02 0,02 --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21-Z2 --- 0,82 0,82 0,82 0,82 0,82 0,82 0,82 0,82 0,82 --- --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21-Z3 --- 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21N-Z1 --- 0,02 0,02 0,02 0,02 --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21N-Z2 --- 0,82 0,82 0,82 0,82 0,82 0,82 0,82 0,82 0,82 0,82 --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21N-Z3 --- 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21N_Q-Z1 --- 0,02 0,02 0,02 0,02 --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21N_Q-Z2 --- 0,82 0,82 0,82 0,82 0,82 0,82 0,82 0,82 0,82 0,82 --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21N_Q-Z3 --- 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 --- --- --- --- --- ---

Loncoche 52B3 SEL-311C Trip --- --- --- --- --- --- --- 0,02 0,02 0,02 0,02 0,02 0,02 0,02 --- --- --- --- --- ---

Loncoche 52B3 SEL-311C 21-Z1 --- --- --- --- --- --- --- 0,02 0,02 0,02 0,02 0,02 0,02 0,02 --- --- --- --- --- ---

Loncoche 52B3 SEL-311C 21-Z2 --- --- --- --- --- --- --- 0,72 0,72 0,72 0,72 0,72 0,72 0,72 --- --- --- --- --- ---

Loncoche 52B3 SEL-311C 21-Z3 --- --- --- --- --- --- --- 2,02 2,02 2,02 2,02 2,02 2,02 2,02 --- --- --- --- --- ---

Loncoche 52B3 SEL-311C 21N-Z1 --- --- --- --- --- --- --- 0,02 0,02 0,02 0,02 0,02 0,02 0,02 --- --- --- --- --- ---

Loncoche 52B3 SEL-311C 21N-Z2 --- --- --- --- --- --- --- 0,72 0,72 0,72 0,72 0,72 0,72 0,72 --- --- --- --- --- ---

Loncoche 52B3 SEL-311C 21N-Z3 --- --- --- --- --- --- --- 2,02 2,02 2,02 2,02 2,02 2,02 2,02 --- --- --- --- --- ---

Loncoche 52B3 SEL-311C 51N --- --- --- --- --- --- --- 0,25 0,27 0,29 0,32 0,35 0,35 0,35 --- --- --- --- --- ---

Gorbea 89BT1-F Fuse SMD 65E Trip --- --- --- --- --- --- --- --- --- --- --- --- --- 0,05 0,89 1,01 2,23 4,23 8,37 14,81

Gorbea 52CT1 Siemens Argus Trip --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,36 0,44 1,06 1,25 1,42 1,54

Gorbea 52CT1 Siemens Argus 51N --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,82 0,86 1,08 1,25 1,42 1,54

Gorbea 52CT1 Siemens Argus 51 --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,36 0,44 1,06 2,13 4,51 7,65

Gorbea 52C1 Siemens Argus Trip --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,04 0,08 0,12 0,21 0,28

Gorbea 52C1 Siemens Argus 51N --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,56 0,67 0,76 0,84 0,90

Gorbea 52C1 Siemens Argus 51 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,04 0,08 0,12 0,21 0,28

Page 80: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 80 de 121

9.3.2.4. FALLA 1F PULLINQUE B4 -> GORBEA 13,2 kV

91,82973,46355,09736,73218,3660,0000 [km]

5,00

4,00

3,00

2,00

1,00

0,00

Pull_66kV_ Lonc_66kV_ Cto2

Gorbea_66kV

Bushing_66kV

Gorbea_13.2k..

LMT_13.2

x-Axis: Length Pull\52B4\Pull_52B4 Lonc\52B3\Lonc_52B3_G1 Gorbea_66kV\Cub_4\Gorbea_89BT1F

Gorbea_13.2kV\Cub_1\Gorbea_52CT1 Gorbea_13.2kV\Cub_2\Gorbea_52C1

TD2_Pull B4 -> Gorbea MT_1F

Date: 11/7/2014

Annex:

DIg

SIL

EN

T

Page 81: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 81 de 121

Tipo Falla : 1FT RF= 0 Ohm Ruta : Pullinque B4 - Gorbea 13,kV Tiempos de Operación en segundos

S/E Paño Relé NEMA Pullinque

66kV

LT 66kV Pullinque - Loncoche

Loncoche 66kV

LT 66kV Loncoche - Gorbea

Gorbea 66kV

Gorbea Bushing

66kV T1

Gorbea 13,2kV

Línea de Media Tensión 13,2 kV

1% 25% 50% 75% 99% 1% 25% 50% 75% 99% 1% 25% 50% 75% 99%

Pullinque 52B4 SEL-311C Trip --- 0,02 0,02 0,02 0,02 0,82 0,82 0,82 0,82 0,82 2,72 2,72 2,72 2,72 --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21-Z1 --- 0,02 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21-Z2 --- 0,82 0,82 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21-Z3 --- 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21N-Z1 --- 0,02 0,02 0,02 0,02 --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21N-Z2 --- 0,82 0,82 0,82 0,82 0,82 0,82 0,82 0,82 0,82 --- --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21N-Z3 --- 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21N_Q-Z1 --- 0,02 0,02 0,02 0,02 --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21N_Q-Z2 --- 0,82 0,82 0,82 0,82 0,82 0,82 0,82 0,82 0,82 --- --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21N_Q-Z3 --- 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 --- --- --- --- --- ---

Loncoche 52B3 SEL-311C Trip --- --- --- --- --- --- --- 0,02 0,02 0,02 0,02 0,02 0,02 0,02 --- --- --- --- --- ---

Loncoche 52B3 SEL-311C 21-Z1 --- --- --- --- --- --- --- 0,02 --- --- --- --- --- --- --- --- --- --- --- ---

Loncoche 52B3 SEL-311C 21-Z2 --- --- --- --- --- --- --- 0,72 0,72 0,72 0,72 0,72 0,72 0,72 --- --- --- --- --- ---

Loncoche 52B3 SEL-311C 21-Z3 --- --- --- --- --- --- --- 2,02 2,02 2,02 2,02 2,02 2,02 2,02 --- --- --- --- --- ---

Loncoche 52B3 SEL-311C 21N-Z1 --- --- --- --- --- --- --- 0,02 0,02 0,02 0,02 0,02 0,02 0,02 --- --- --- --- --- ---

Loncoche 52B3 SEL-311C 21N-Z2 --- --- --- --- --- --- --- 0,72 0,72 0,72 0,72 0,72 0,72 0,72 --- --- --- --- --- ---

Loncoche 52B3 SEL-311C 21N-Z3 --- --- --- --- --- --- --- 2,02 2,02 2,02 2,02 2,02 2,02 2,02 --- --- --- --- --- ---

Loncoche 52B3 SEL-311C 51N --- --- --- --- --- --- --- 0,24 0,25 0,26 0,28 0,30 0,30 0,30 --- --- --- --- --- ---

Gorbea 89BT1-F Fuse SMD 65E Trip --- --- --- --- --- --- --- --- --- --- --- --- --- 0,09 2,25 3,00 21,72 --- --- ---

Gorbea 52CT1 Siemens Argus Trip --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,35 0,44 1,03 1,15 1,28 1,36

Gorbea 52CT1 Siemens Argus 51N --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,84 0,87 1,03 1,15 1,28 1,36

Gorbea 52CT1 Siemens Argus 51 --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,35 0,44 1,60 4,86 14,15 25,46

Gorbea 52C1 Siemens Argus Trip --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,04 0,10 0,21 0,39 0,58

Gorbea 52C1 Siemens Argus 51N --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,56 0,64 0,71 0,77 0,82

Gorbea 52C1 Siemens Argus 51 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,04 0,10 0,21 0,39 0,58

Page 82: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 82 de 121

9.3.2.5. F LL 1F (R = Ω) PULLINQUE B4 -> GORBEA 13,2 kV

91,82973,46355,09736,73218,3660,0000 [km]

5,00

4,00

3,00

2,00

1,00

0,00

Pull_66kV_ Lonc_66kV_ Cto2

Gorbea_66kV

Bushing_66kV

Gorbea_13.2k..

LMT_13.2

x-Axis: Length Pull\52B4\Pull_52B4 Lonc\52B3\Lonc_52B3_G1 Gorbea_66kV\Cub_4\Gorbea_89BT1F

Gorbea_13.2kV\Cub_1\Gorbea_52CT1 Gorbea_13.2kV\Cub_2\Gorbea_52C1

TD2_Pull B4 -> Gorbea MT_1F_R25

Date: 11/7/2014

Annex:

DIg

SIL

EN

T

Page 83: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 83 de 121

Tipo Falla : 1FT RF= 25 Ohm Ruta : Pullinque B4 - Gorbea 13,kV Tiempos de Operación en segundos

S/E Paño Relé NEMA Pullinque

66kV

LT 66kV Pullinque - Loncoche

Loncoche 66kV

LT 66kV Loncoche - Gorbea

Gorbea 66kV

Gorbea Bushing

66kV T1

Gorbea 13,2kV

Línea de Media Tensión 13,2 kV

1% 25% 50% 75% 99% 1% 25% 50% 75% 99% 1% 25% 50% 75% 99%

Pullinque 52B4 SEL-311C Trip --- 0,82 0,82 0,82 0,82 0,82 0,82 0,82 2,72 2,72 2,72 2,72 2,72 2,72 --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21-Z1 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21-Z2 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21-Z3 --- 2,72 2,72 2,72 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21N-Z1 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21N-Z2 --- 0,82 0,82 0,82 0,82 0,82 0,82 0,82 --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21N-Z3 --- 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21N_Q-Z1 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21N_Q-Z2 --- 0,82 0,82 0,82 0,82 0,82 0,82 0,82 --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21N_Q-Z3 --- 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 --- --- --- --- --- ---

Loncoche 52B3 SEL-311C Trip --- --- --- --- --- --- --- 0,02 0,02 0,02 0,37 0,42 0,42 0,42 --- --- --- --- --- ---

Loncoche 52B3 SEL-311C 21-Z1 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Loncoche 52B3 SEL-311C 21-Z2 --- --- --- --- --- --- --- 0,72 0,72 --- --- --- --- --- --- --- --- --- --- ---

Loncoche 52B3 SEL-311C 21-Z3 --- --- --- --- --- --- --- 2,02 2,02 2,02 --- --- --- --- --- --- --- --- --- ---

Loncoche 52B3 SEL-311C 21N-Z1 --- --- --- --- --- --- --- 0,02 0,02 0,02 --- --- --- --- --- --- --- --- --- ---

Loncoche 52B3 SEL-311C 21N-Z2 --- --- --- --- --- --- --- 0,72 0,72 0,72 0,72 0,72 0,72 0,72 --- --- --- --- --- ---

Loncoche 52B3 SEL-311C 21N-Z3 --- --- --- --- --- --- --- 2,02 2,02 2,02 2,02 2,02 2,02 2,02 --- --- --- --- --- ---

Loncoche 52B3 SEL-311C 51N --- --- --- --- --- --- --- 0,28 0,30 0,33 0,37 0,42 0,42 0,42 --- --- --- --- --- ---

Gorbea 89BT1-F Fuse SMD 65E Trip --- --- --- --- --- --- --- --- --- --- --- --- --- 0,25 --- --- --- --- --- ---

Gorbea 52CT1 Siemens Argus Trip --- --- --- --- --- --- --- --- --- --- --- --- --- --- 1,69 1,70 1,75 1,81 1,88 1,93

Gorbea 52CT1 Siemens Argus 51N --- --- --- --- --- --- --- --- --- --- --- --- --- --- 1,69 1,70 1,75 1,81 1,88 1,93

Gorbea 52CT1 Siemens Argus 51 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Gorbea 52C1 Siemens Argus Trip --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,98 1,00 1,03 1,06 1,08

Gorbea 52C1 Siemens Argus 51N --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,98 1,00 1,03 1,06 1,08

Gorbea 52C1 Siemens Argus 51 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 1,95 2,24 2,60 3,07 3,47

Page 84: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 84 de 121

9.4. ESCENARIO 4

S/E Loncoche:

52B3 Cerrado, alimentando radialmente a SE Gorbea

52B6 Cerrado

S/E Temuco:

52B2 Abierto

52B6 Cerrado

Page 85: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 85 de 121

9.4.1. Ruta 2: Pullinque B4 -> Gorbea 13,2 kV

Page 86: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 86 de 121

9.4.1.1. FALLA 3F PULLINQUE B4 -> GORBEA 13,2 kV

91,82973,46355,09736,73218,3660,0000 [km]

5,00

4,00

3,00

2,00

1,00

0,00

Pull_66kV_ Lonc_66kV_ Cto2

Gorbea_66kV

Bushing_66kV

Gorbea_13.2k..

LMT_13.2

x-Axis: Length Pull\52B4\Pull_52B4 Lonc\52B3\Lonc_52B3_G2 Gorbea_66kV\Cub_4\Gorbea_89BT1F

Gorbea_13.2kV\Cub_1\Gorbea_52CT1 Gorbea_13.2kV\Cub_2\Gorbea_52C1

TD2_Pull B4 -> Gorbea MT_3F

Date: 11/7/2014

Annex:

DIg

SIL

EN

T

Page 87: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 87 de 121

Tipo Falla : 3F RF= 0 Ohm Ruta : Pullinque B4 - Gorbea 13,kV Tiempos de Operación en segundos

S/E Paño Relé NEMA Pullinque

66kV

LT 66kV Pullinque - Loncoche

Loncoche 66kV

LT 66kV Loncoche - Gorbea

Gorbea 66kV

Gorbea Bushing

66kV T1

Gorbea 13,2kV

Línea de Media Tensión 13,2 kV

1% 25% 50% 75% 99% 1% 25% 50% 75% 99% 1% 25% 50% 75% 99%

Pullinque 52B4 SEL-311C Trip --- 0,02 0,02 0,02 0,02 0,82 0,82 0,82 0,82 2,72 2,72 2,72 2,72 2,72 --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21-Z1 --- 0,02 0,02 0,02 0,02 --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21-Z2 --- 0,82 0,82 0,82 0,82 0,82 0,82 0,82 0,82 --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21-Z3 --- 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21N-Z1 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21N-Z2 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21N-Z3 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21N_Q-Z1 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21N_Q-Z2 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21N_Q-Z3 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Loncoche 52B3 SEL-311C Trip --- --- --- --- --- --- --- 0,02 0,02 0,02 0,02 0,02 0,02 0,02 2,02 2,02 --- --- --- ---

Loncoche 52B3 SEL-311C 21-Z1 --- --- --- --- --- --- --- 0,02 0,02 0,02 0,02 0,02 0,02 0,02 --- --- --- --- --- ---

Loncoche 52B3 SEL-311C 21-Z2 --- --- --- --- --- --- --- 0,72 0,72 0,72 0,72 0,72 0,72 0,72 --- --- --- --- --- ---

Loncoche 52B3 SEL-311C 21-Z3 --- --- --- --- --- --- --- 2,02 2,02 2,02 2,02 2,02 2,02 2,02 2,02 2,02 --- --- --- ---

Loncoche 52B3 SEL-311C 21N-Z1 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Loncoche 52B3 SEL-311C 21N-Z2 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Loncoche 52B3 SEL-311C 21N-Z3 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Loncoche 52B3 SEL-311C 51N --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Gorbea 89BT1-F Fuse SMD 65E Trip --- --- --- --- --- --- --- --- --- --- --- --- --- 0,21 1,50 1,67 3,25 6,03 12,19 22,52

Gorbea 52CT1 Siemens Argus Trip --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,68 0,75 1,46 2,66 5,47 8,80

Gorbea 52CT1 Siemens Argus 51N --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Gorbea 52CT1 Siemens Argus 51 --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,68 0,75 1,46 2,66 5,47 8,80

Gorbea 52C1 Siemens Argus Trip --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,06 0,10 0,15 0,23 0,30

Gorbea 52C1 Siemens Argus 51N --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Gorbea 52C1 Siemens Argus 51 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,06 0,10 0,15 0,23 0,30

Page 88: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 88 de 121

9.4.1.2. FALLA 2F PULLINQUE B4 -> GORBEA 13,2 kV

91,82973,46355,09736,73218,3660,0000 [km]

5,00

4,00

3,00

2,00

1,00

0,00

Pull_66kV_ Lonc_66kV_ Cto2

Gorbea_66kV

Bushing_66kV

Gorbea_13.2k..

LMT_13.2

x-Axis: Length Pull\52B4\Pull_52B4 Lonc\52B3\Lonc_52B3_G2 Gorbea_66kV\Cub_4\Gorbea_89BT1F

Gorbea_13.2kV\Cub_1\Gorbea_52CT1 Gorbea_13.2kV\Cub_2\Gorbea_52C1

TD2_Pull B4 -> Gorbea MT_2F

Date: 11/7/2014

Annex:

DIg

SIL

EN

T

Page 89: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 89 de 121

Tipo Falla : 2F RF= 0 Ohm Ruta : Pullinque B4 - Gorbea 13,kV Tiempos de Operación en segundos

S/E Paño Relé NEMA Pullinque

66kV

LT 66kV Pullinque - Loncoche

Loncoche 66kV

LT 66kV Loncoche - Gorbea

Gorbea 66kV

Gorbea Bushing

66kV T1

Gorbea 13,2kV

Línea de Media Tensión 13,2 kV

1% 25% 50% 75% 99% 1% 25% 50% 75% 99% 1% 25% 50% 75% 99%

Pullinque 52B4 SEL-311C Trip --- 0,02 0,02 0,02 0,02 0,82 0,82 0,82 0,82 2,72 2,72 2,72 2,72 2,72 --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21-Z1 --- 0,02 0,02 0,02 0,02 --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21-Z2 --- 0,82 0,82 0,82 0,82 0,82 0,82 0,82 0,82 --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21-Z3 --- 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21N-Z1 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21N-Z2 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21N-Z3 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21N_Q-Z1 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21N_Q-Z2 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21N_Q-Z3 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Loncoche 52B3 SEL-311C Trip --- --- --- --- --- --- --- 0,02 0,02 0,02 0,02 0,02 0,02 0,02 2,02 2,02 --- --- --- ---

Loncoche 52B3 SEL-311C 21-Z1 --- --- --- --- --- --- --- 0,02 0,02 0,02 0,02 0,02 0,02 0,02 --- --- --- --- --- ---

Loncoche 52B3 SEL-311C 21-Z2 --- --- --- --- --- --- --- 0,72 0,72 0,72 0,72 0,72 0,72 0,72 --- --- --- --- --- ---

Loncoche 52B3 SEL-311C 21-Z3 --- --- --- --- --- --- --- 2,02 2,02 2,02 2,02 2,02 2,02 2,02 2,02 2,02 --- --- --- ---

Loncoche 52B3 SEL-311C 21N-Z1 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Loncoche 52B3 SEL-311C 21N-Z2 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Loncoche 52B3 SEL-311C 21N-Z3 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Loncoche 52B3 SEL-311C 51N --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Gorbea 89BT1-F Fuse SMD 65E Trip --- --- --- --- --- --- --- --- --- --- --- --- --- 0,21 1,50 1,67 3,25 6,03 12,19 22,52

Gorbea 52CT1 Siemens Argus Trip --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,68 0,75 1,46 2,66 5,47 8,80

Gorbea 52CT1 Siemens Argus 51N --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Gorbea 52CT1 Siemens Argus 51 --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,68 0,75 1,46 2,66 5,47 8,80

Gorbea 52C1 Siemens Argus Trip --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,06 0,10 0,15 0,23 0,30

Gorbea 52C1 Siemens Argus 51N --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Gorbea 52C1 Siemens Argus 51 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,06 0,10 0,15 0,23 0,30

Page 90: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 90 de 121

9.4.1.3. FALLA 2F-T PULLINQUE B4 -> GORBEA 13,2 kV

91,82973,46355,09736,73218,3660,0000 [km]

5,00

4,00

3,00

2,00

1,00

0,00

Pull_66kV_ Lonc_66kV_ Cto2

Gorbea_66kV

Bushing_66kV

Gorbea_13.2k..

LMT_13.2

x-Axis: Length Pull\52B4\Pull_52B4 Lonc\52B3\Lonc_52B3_G2 Gorbea_66kV\Cub_4\Gorbea_89BT1F

Gorbea_13.2kV\Cub_1\Gorbea_52CT1 Gorbea_13.2kV\Cub_2\Gorbea_52C1

TD2_Pull B4 -> Gorbea MT_2F-T

Date: 11/7/2014

Annex:

DIg

SIL

EN

T

Page 91: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 91 de 121

Tipo Falla : 2FT RF= 0 Ohm Ruta : Pullinque B4 - Gorbea 13,kV Tiempos de Operación en segundos

S/E Paño Relé NEMA Pullinque

66kV

LT 66kV Pullinque - Loncoche

Loncoche 66kV

LT 66kV Loncoche - Gorbea

Gorbea 66kV

Gorbea Bushing

66kV T1

Gorbea 13,2kV

Línea de Media Tensión 13,2 kV

1% 25% 50% 75% 99% 1% 25% 50% 75% 99% 1% 25% 50% 75% 99%

Pullinque 52B4 SEL-311C Trip --- 0,02 0,02 0,02 0,02 0,82 0,82 0,82 0,82 0,82 2,72 2,72 2,72 2,72 --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21-Z1 --- 0,02 0,02 0,02 0,02 --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21-Z2 --- 0,82 0,82 0,82 0,82 0,82 0,82 0,82 0,82 --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21-Z3 --- 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21N-Z1 --- 0,02 0,02 0,02 0,02 --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21N-Z2 --- 0,82 0,82 0,82 0,82 0,82 0,82 0,82 0,82 0,82 --- --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21N-Z3 --- 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21N_Q-Z1 --- 0,02 0,02 0,02 0,02 --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21N_Q-Z2 --- 0,82 0,82 0,82 0,82 0,82 0,82 0,82 0,82 0,82 --- --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21N_Q-Z3 --- 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 --- --- --- --- --- ---

Loncoche 52B3 SEL-311C Trip --- --- --- --- --- --- --- 0,02 0,02 0,02 0,02 0,02 0,02 0,02 2,02 2,02 --- --- --- ---

Loncoche 52B3 SEL-311C 21-Z1 --- --- --- --- --- --- --- 0,02 0,02 0,02 0,02 0,02 0,02 0,02 --- --- --- --- --- ---

Loncoche 52B3 SEL-311C 21-Z2 --- --- --- --- --- --- --- 0,72 0,72 0,72 0,72 0,72 0,72 0,72 --- --- --- --- --- ---

Loncoche 52B3 SEL-311C 21-Z3 --- --- --- --- --- --- --- 2,02 2,02 2,02 2,02 2,02 2,02 2,02 2,02 2,02 --- --- --- ---

Loncoche 52B3 SEL-311C 21N-Z1 --- --- --- --- --- --- --- 0,02 0,02 0,02 0,02 0,02 0,02 0,02 --- --- --- --- --- ---

Loncoche 52B3 SEL-311C 21N-Z2 --- --- --- --- --- --- --- 0,72 0,72 0,72 0,72 0,72 0,72 0,72 --- --- --- --- --- ---

Loncoche 52B3 SEL-311C 21N-Z3 --- --- --- --- --- --- --- 2,02 2,02 2,02 2,02 2,02 2,02 2,02 --- --- --- --- --- ---

Loncoche 52B3 SEL-311C 51N --- --- --- --- --- --- --- 0,25 0,26 0,28 0,31 0,34 0,34 0,34 --- --- --- --- --- ---

Gorbea 89BT1-F Fuse SMD 65E Trip --- --- --- --- --- --- --- --- --- --- --- --- --- 0,23 1,50 1,68 3,27 6,05 12,25 22,66

Gorbea 52CT1 Siemens Argus Trip --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,50 0,61 1,09 1,26 1,43 1,55

Gorbea 52CT1 Siemens Argus 51N --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,84 0,88 1,09 1,26 1,43 1,55

Gorbea 52CT1 Siemens Argus 51 --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,50 0,61 1,50 2,89 6,30 10,24

Gorbea 52C1 Siemens Argus Trip --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,05 0,10 0,16 0,25 0,33

Gorbea 52C1 Siemens Argus 51N --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,56 0,68 0,76 0,85 0,91

Gorbea 52C1 Siemens Argus 51 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,05 0,10 0,16 0,25 0,33

Page 92: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 92 de 121

9.4.1.4. FALLA 1F PULLINQUE B4 -> GORBEA 13,2 kV

91,82973,46355,09736,73218,3660,0000 [km]

5,00

4,00

3,00

2,00

1,00

0,00

Pull_66kV_ Lonc_66kV_ Cto2

Gorbea_66kV

Bushing_66kV

Gorbea_13.2k..

LMT_13.2

x-Axis: Length Pull\52B4\Pull_52B4 Lonc\52B3\Lonc_52B3_G2 Gorbea_66kV\Cub_4\Gorbea_89BT1F

Gorbea_13.2kV\Cub_1\Gorbea_52CT1 Gorbea_13.2kV\Cub_2\Gorbea_52C1

TD2_Pull B4 -> Gorbea MT_1F

Date: 11/7/2014

Annex:

DIg

SIL

EN

T

Page 93: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 93 de 121

Tipo Falla : 1FT RF= 0 Ohm Ruta : Pullinque B4 - Gorbea 13,kV Tiempos de Operación en segundos

S/E Paño Relé NEMA Pullinque

66kV

LT 66kV Pullinque - Loncoche

Loncoche 66kV

LT 66kV Loncoche - Gorbea

Gorbea 66kV

Gorbea Bushing

66kV T1

Gorbea 13,2kV

Línea de Media Tensión 13,2 kV

1% 25% 50% 75% 99% 1% 25% 50% 75% 99% 1% 25% 50% 75% 99%

Pullinque 52B4 SEL-311C Trip --- 0,02 0,02 0,02 0,02 0,82 0,82 0,82 0,82 0,82 2,72 2,72 2,72 2,72 --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21-Z1 --- 0,02 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21-Z2 --- 0,82 0,82 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21-Z3 --- 2,72 2,72 2,72 2,72 2,72 2,72 2,72 --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21N-Z1 --- 0,02 0,02 0,02 0,02 --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21N-Z2 --- 0,82 0,82 0,82 0,82 0,82 0,82 0,82 0,82 0,82 --- --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21N-Z3 --- 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21N_Q-Z1 --- 0,02 0,02 0,02 0,02 --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21N_Q-Z2 --- 0,82 0,82 0,82 0,82 0,82 0,82 0,82 0,82 0,82 --- --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21N_Q-Z3 --- 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 --- --- --- --- --- ---

Loncoche 52B3 SEL-311C Trip --- --- --- --- --- --- --- 0,02 0,02 0,02 0,02 0,02 0,02 0,02 --- --- --- --- --- ---

Loncoche 52B3 SEL-311C 21-Z1 --- --- --- --- --- --- --- 0,02 --- --- --- --- --- --- --- --- --- --- --- ---

Loncoche 52B3 SEL-311C 21-Z2 --- --- --- --- --- --- --- 0,72 0,72 0,72 --- --- --- --- --- --- --- --- --- ---

Loncoche 52B3 SEL-311C 21-Z3 --- --- --- --- --- --- --- 2,02 2,02 2,02 2,02 2,02 2,02 2,02 --- --- --- --- --- ---

Loncoche 52B3 SEL-311C 21N-Z1 --- --- --- --- --- --- --- 0,02 0,02 0,02 0,02 0,02 0,02 0,02 --- --- --- --- --- ---

Loncoche 52B3 SEL-311C 21N-Z2 --- --- --- --- --- --- --- 0,72 0,72 0,72 0,72 0,72 0,72 0,72 --- --- --- --- --- ---

Loncoche 52B3 SEL-311C 21N-Z3 --- --- --- --- --- --- --- 2,02 2,02 2,02 2,02 2,02 2,02 2,02 --- --- --- --- --- ---

Loncoche 52B3 SEL-311C 51N --- --- --- --- --- --- --- 0,24 0,25 0,26 0,28 0,29 0,30 0,30 --- --- --- --- --- ---

Gorbea 89BT1-F Fuse SMD 65E Trip --- --- --- --- --- --- --- --- --- --- --- --- --- 0,41 3,44 4,60 43,83 --- --- ---

Gorbea 52CT1 Siemens Argus Trip --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,49 0,60 1,05 1,18 1,30 1,39

Gorbea 52CT1 Siemens Argus 51N --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,88 0,91 1,05 1,18 1,30 1,39

Gorbea 52CT1 Siemens Argus 51 --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,49 0,60 2,04 6,13 16,77 28,97

Gorbea 52C1 Siemens Argus Trip --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,05 0,12 0,25 0,43 0,64

Gorbea 52C1 Siemens Argus 51N --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,58 0,66 0,72 0,79 0,83

Gorbea 52C1 Siemens Argus 51 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,05 0,12 0,25 0,43 0,64

Page 94: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 94 de 121

9.4.1.5. F LL 1F (R = Ω) PULLINQUE B4 -> GORBEA 13,2 kV

91,82973,46355,09736,73218,3660,0000 [km]

5,00

4,00

3,00

2,00

1,00

0,00

Pull_66kV_ Lonc_66kV_ Cto2

Gorbea_66kV

Bushing_66kV

Gorbea_13.2k..

LMT_13.2

x-Axis: Length Pull\52B4\Pull_52B4 Lonc\52B3\Lonc_52B3_G2 Gorbea_66kV\Cub_4\Gorbea_89BT1F

Gorbea_13.2kV\Cub_1\Gorbea_52CT1 Gorbea_13.2kV\Cub_2\Gorbea_52C1

TD2_Pull B4 -> Gorbea MT_1F_R25

Date: 11/7/2014

Annex:

DIg

SIL

EN

T

Page 95: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 95 de 121

Tipo Falla : 1FT RF= 25 Ohm Ruta : Pullinque B4 - Gorbea 13,kV Tiempos de Operación en segundos

S/E Paño Relé NEMA Pullinque

66kV

LT 66kV Pullinque - Loncoche

Loncoche 66kV

LT 66kV Loncoche - Gorbea

Gorbea 66kV

Gorbea Bushing

66kV T1

Gorbea 13,2kV

Línea de Media Tensión 13,2 kV

1% 25% 50% 75% 99% 1% 25% 50% 75% 99% 1% 25% 50% 75% 99%

Pullinque 52B4 SEL-311C Trip --- 0,02 0,82 0,82 0,82 0,82 0,82 0,82 0,82 0,82 2,72 2,72 2,72 2,72 --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21-Z1 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21-Z2 --- 0,82 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21-Z3 --- 2,72 2,72 2,72 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21N-Z1 --- 0,02 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21N-Z2 --- 0,82 0,82 0,82 0,82 0,82 0,82 0,82 0,82 0,82 --- --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21N-Z3 --- 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21N_Q-Z1 --- 0,02 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21N_Q-Z2 --- 0,82 0,82 0,82 0,82 0,82 0,82 0,82 0,82 0,82 --- --- --- --- --- --- --- --- --- ---

Pullinque 52B4 SEL-311C 21N_Q-Z3 --- 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 2,72 --- --- --- --- --- ---

Loncoche 52B3 SEL-311C Trip --- --- --- --- --- --- --- 0,02 0,02 0,02 0,02 0,02 0,02 0,02 --- --- --- --- --- ---

Loncoche 52B3 SEL-311C 21-Z1 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Loncoche 52B3 SEL-311C 21-Z2 --- --- --- --- --- --- --- 0,72 --- --- --- --- --- --- --- --- --- --- --- ---

Loncoche 52B3 SEL-311C 21-Z3 --- --- --- --- --- --- --- 2,02 2,02 2,02 2,02 2,02 2,02 2,02 --- --- --- --- --- ---

Loncoche 52B3 SEL-311C 21N-Z1 --- --- --- --- --- --- --- 0,02 0,02 0,02 0,02 0,02 0,02 0,02 --- --- --- --- --- ---

Loncoche 52B3 SEL-311C 21N-Z2 --- --- --- --- --- --- --- 0,72 0,72 0,72 0,72 0,72 0,72 0,72 --- --- --- --- --- ---

Loncoche 52B3 SEL-311C 21N-Z3 --- --- --- --- --- --- --- 2,02 2,02 2,02 2,02 2,02 2,02 2,02 --- --- --- --- --- ---

Loncoche 52B3 SEL-311C 51N --- --- --- --- --- --- --- 0,27 0,28 0,30 0,31 0,33 0,33 0,33 --- --- --- --- --- ---

Gorbea 89BT1-F Fuse SMD 65E Trip --- --- --- --- --- --- --- --- --- --- --- --- --- 0,65 --- --- --- --- --- ---

Gorbea 52CT1 Siemens Argus Trip --- --- --- --- --- --- --- --- --- --- --- --- --- --- 1,70 1,71 1,76 1,82 1,89 1,95

Gorbea 52CT1 Siemens Argus 51N --- --- --- --- --- --- --- --- --- --- --- --- --- --- 1,70 1,71 1,76 1,82 1,89 1,95

Gorbea 52CT1 Siemens Argus 51 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---

Gorbea 52C1 Siemens Argus Trip --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,98 1,01 1,03 1,07 1,09

Gorbea 52C1 Siemens Argus 51N --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,98 1,01 1,03 1,07 1,09

Gorbea 52C1 Siemens Argus 51 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 2,02 2,32 2,69 3,17 3,59

Page 96: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 96 de 121

9.5. ESCENARIO 5

S/E Temuco:

52B2 Cerrado, alimentando radialmente a SE Gorbea

52B6 Cerrado

S/E Loncoche:

52B3 Abierto

52B6 Cerrado

Page 97: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 97 de 121

9.5.1. Ruta 1: Temuco B2 -> Gorbea 13,2 kV

Page 98: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 98 de 121

9.5.1.1. FALLA 3F TEMUCO B2 -> GORBEA 13,2 kV

62,81150,24937,68725,12412,5620,0000 [km]

5,00

4,00

3,00

2,00

1,00

0,00

Tem_66kV_ Tap Padre La..

Tap Licanco ..

Pitrufquen 6.. Cto2

Gorbea_66kV

Bushing_66kV

Gorbea_13.2k..

LMT_13.2

x-Axis: Length Tem\52B2\Tem_52B2 Gorbea_66kV\Cub_4\Gorbea_89BT1F Gorbea_13.2kV\Cub_1\Gorbea_52CT1

Gorbea_13.2kV\Cub_2\Gorbea_52C1

TD1_Tem B2 -> Gorbea MT_3F

Date: 11/7/2014

Annex:

DIg

SIL

EN

T

Page 99: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 99 de 121

Tipo Falla : 3F RF= 0 Ohm

Ruta : Temuco B2 - Gorbea 13,2kV

Tiempos de Operación en segundos

S/E Paño Relé NEMA Temuco

66kV

LT 66kV Temuco - Gorbea

Gorbea 66kV

Gorbea Bushing 66kV T1

Gorbea Barra

13,2kV

Línea de Media Tensión 13,2 kV

Padre Las Casas 66kV

Tap Licanco

66kV

Pitrufquén 66 kV

1% 25% 50% 75% 99%

Temuco 52B2 SEL-311C Trip --- 0,02 0,02 0,02 0,02 0,02 --- --- --- --- --- ---

Temuco 52B2 SEL-311C 21-Z1 --- 0,02 0,02 0,02 0,02 0,02 --- --- --- --- --- ---

Temuco 52B2 SEL-311C 21-Z2 --- 0,82 0,82 0,82 0,82 0,82 --- --- --- --- --- ---

Temuco 52B2 SEL-311C 21-Z3 --- 2,72 2,72 2,72 2,72 2,72 --- --- --- --- --- ---

Temuco 52B2 SEL-311C 21N-Z1 --- --- --- --- --- --- --- --- --- --- --- ---

Temuco 52B2 SEL-311C 21N-Z2 --- --- --- --- --- --- --- --- --- --- --- ---

Temuco 52B2 SEL-311C 21N-Z3 --- --- --- --- --- --- --- --- --- --- --- ---

Temuco 52B2 SEL-311C 51N --- --- --- --- --- --- --- --- --- --- --- ---

Temuco 52B2 SEL-311C 67N --- --- --- --- --- --- --- --- --- --- --- ---

Gorbea 89BT1-F Fuse SMD 65E Trip --- --- --- --- --- 0,12 1,16 1,32 2,74 5,13 10,18 18,37

Gorbea 52CT1 Siemens Argus Trip --- --- --- --- --- --- 0,54 0,60 1,21 2,28 4,63 7,62

Gorbea 52CT1 Siemens Argus 51N --- --- --- --- --- --- --- --- --- --- --- ---

Gorbea 52CT1 Siemens Argus 51 --- --- --- --- --- --- 0,54 0,60 1,21 2,28 4,63 7,62

Gorbea 52C1 Siemens Argus Trip --- --- --- --- --- --- --- 0,05 0,09 0,13 0,21 0,28

Gorbea 52C1 Siemens Argus 51N --- --- --- --- --- --- --- --- --- --- --- ---

Gorbea 52C1 Siemens Argus 51 --- --- --- --- --- --- --- 0,05 0,09 0,13 0,21 0,28

Page 100: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 100 de 121

9.5.1.2. FALLA 2F TEMUCO B2 -> GORBEA 13,2 kV

62,81150,24937,68725,12412,5620,0000 [km]

5,00

4,00

3,00

2,00

1,00

0,00

Tem_66kV_ Tap Padre La..

Tap Licanco ..

Pitrufquen 6.. Cto2

Gorbea_66kV

Bushing_66kV

Gorbea_13.2k..

LMT_13.2

x-Axis: Length Tem\52B2\Tem_52B2 Gorbea_66kV\Cub_4\Gorbea_89BT1F Gorbea_13.2kV\Cub_1\Gorbea_52CT1

Gorbea_13.2kV\Cub_2\Gorbea_52C1

TD1_Tem B2 -> Gorbea MT_2F

Date: 11/7/2014

Annex:

DIg

SIL

EN

T

Page 101: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 101 de 121

Tipo Falla : 2F RF= 0 Ohm

Ruta : Temuco B2 - Gorbea 13,2kV

Tiempos de Operación en segundos

S/E Paño Relé NEMA Temuco

66kV

LT 66kV Temuco - Gorbea

Gorbea 66kV

Gorbea Bushing 66kV T1

Gorbea Barra

13,2kV

Línea de Media Tensión 13,2 kV

Padre Las Casas 66kV

Tap Licanco

66kV

Pitrufquén 66 kV

1% 25% 50% 75% 99%

Temuco 52B2 SEL-311C Trip --- 0,02 0,02 0,02 0,02 0,02 --- --- --- --- --- ---

Temuco 52B2 SEL-311C 21-Z1 --- 0,02 0,02 0,02 0,02 0,02 --- --- --- --- --- ---

Temuco 52B2 SEL-311C 21-Z2 --- 0,82 0,82 0,82 0,82 0,82 --- --- --- --- --- ---

Temuco 52B2 SEL-311C 21-Z3 --- 2,72 2,72 2,72 2,72 2,72 --- --- --- --- --- ---

Temuco 52B2 SEL-311C 21N-Z1 --- --- --- --- --- --- --- --- --- --- --- ---

Temuco 52B2 SEL-311C 21N-Z2 --- --- --- --- --- --- --- --- --- --- --- ---

Temuco 52B2 SEL-311C 21N-Z3 --- --- --- --- --- --- --- --- --- --- --- ---

Temuco 52B2 SEL-311C 51N --- --- --- --- --- --- --- --- --- --- --- ---

Temuco 52B2 SEL-311C 67N --- --- --- --- --- --- --- --- --- --- --- ---

Gorbea 89BT1-F Fuse SMD 65E Trip --- --- --- --- --- 0,16 1,16 1,31 2,73 5,12 10,16 18,34

Gorbea 52CT1 Siemens Argus Trip --- --- --- --- --- --- 0,72 0,80 1,71 3,43 7,60 12,48

Gorbea 52CT1 Siemens Argus 51N --- --- --- --- --- --- --- --- --- --- --- ---

Gorbea 52CT1 Siemens Argus 51 --- --- --- --- --- --- 0,72 0,80 1,71 3,43 7,60 12,48

Gorbea 52C1 Siemens Argus Trip --- --- --- --- --- --- --- 0,06 0,11 0,18 0,28 0,36

Gorbea 52C1 Siemens Argus 51N --- --- --- --- --- --- --- --- --- --- --- ---

Gorbea 52C1 Siemens Argus 51 --- --- --- --- --- --- --- 0,06 0,11 0,18 0,28 0,36

Page 102: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 102 de 121

9.5.1.3. FALLA 2F-T TEMUCO B2 -> GORBEA 13,2 kV

62,81150,24937,68725,12412,5620,0000 [km]

5,00

4,00

3,00

2,00

1,00

0,00

Tem_66kV_ Tap Padre La..

Tap Licanco ..

Pitrufquen 6.. Cto2

Gorbea_66kV

Bushing_66kV

Gorbea_13.2k..

LMT_13.2

x-Axis: Length Tem\52B2\Tem_52B2 Gorbea_66kV\Cub_4\Gorbea_89BT1F Gorbea_13.2kV\Cub_1\Gorbea_52CT1

Gorbea_13.2kV\Cub_2\Gorbea_52C1

TD1_Tem B2 -> Gorbea MT_2F-T

Date: 11/7/2014

Annex:

DIg

SIL

EN

T

Page 103: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 103 de 121

Tipo Falla : 2FT RF= 0 Ohm

Ruta : Temuco B2 - Gorbea 13,2kV

Tiempos de Operación en segundos

S/E Paño Relé NEMA Temuco

66kV

LT 66kV Temuco - Gorbea

Gorbea 66kV

Gorbea Bushing 66kV T1

Gorbea Barra

13,2kV

Línea de Media Tensión 13,2 kV

Padre Las Casas 66kV

Tap Licanco

66kV

Pitrufquén 66 kV

1% 25% 50% 75% 99%

Temuco 52B2 SEL-311C Trip --- 0,01 0,01 0,01 0,02 0,02 --- --- --- --- --- ---

Temuco 52B2 SEL-311C 21-Z1 --- 0,02 0,02 0,02 0,02 0,02 --- --- --- --- --- ---

Temuco 52B2 SEL-311C 21-Z2 --- 0,82 0,82 0,82 0,82 0,82 --- --- --- --- --- ---

Temuco 52B2 SEL-311C 21-Z3 --- 2,72 2,72 2,72 2,72 2,72 --- --- --- --- --- ---

Temuco 52B2 SEL-311C 21N-Z1 --- 0,02 0,02 0,02 0,02 0,02 --- --- --- --- --- ---

Temuco 52B2 SEL-311C 21N-Z2 --- 0,82 0,82 0,82 0,82 0,82 --- --- --- --- --- ---

Temuco 52B2 SEL-311C 21N-Z3 --- 2,72 2,72 2,72 2,72 2,72 --- --- --- --- --- ---

Temuco 52B2 SEL-311C 51N --- 0,23 0,23 0,31 0,38 0,38 --- --- --- --- --- ---

Temuco 52B2 SEL-311C 67N --- 0,01 0,01 0,01 --- --- --- --- --- --- --- ---

Gorbea 89BT1-F Fuse SMD 65E Trip --- --- --- --- --- 0,13 1,16 1,31 2,73 5,12 10,16 18,34

Gorbea 52CT1 Siemens Argus Trip --- --- --- --- --- --- 0,42 0,51 1,09 1,25 1,42 1,54

Gorbea 52CT1 Siemens Argus 51N --- --- --- --- --- --- 0,83 0,87 1,09 1,25 1,42 1,54

Gorbea 52CT1 Siemens Argus 51 --- --- --- --- --- --- 0,42 0,51 1,26 2,49 5,35 8,89

Gorbea 52C1 Siemens Argus Trip --- --- --- --- --- --- --- 0,04 0,09 0,14 0,23 0,30

Gorbea 52C1 Siemens Argus 51N --- --- --- --- --- --- --- 0,56 0,67 0,76 0,85 0,90

Gorbea 52C1 Siemens Argus 51 --- --- --- --- --- --- --- 0,04 0,09 0,14 0,23 0,30

Page 104: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 104 de 121

9.5.1.4. FALLA 1F TEMUCO B2 -> GORBEA 13,2 kV

62,81150,24937,68725,12412,5620,0000 [km]

5,00

4,00

3,00

2,00

1,00

0,00

Tem_66kV_ Tap Padre La..

Tap Licanco ..

Pitrufquen 6.. Cto2

Gorbea_66kV

Bushing_66kV

Gorbea_13.2k..

LMT_13.2

x-Axis: Length Tem\52B2\Tem_52B2 Gorbea_66kV\Cub_4\Gorbea_89BT1F Gorbea_13.2kV\Cub_1\Gorbea_52CT1

Gorbea_13.2kV\Cub_2\Gorbea_52C1

TD1_Tem B2 -> Gorbea MT_1F

Date: 11/7/2014

Annex:

DIg

SIL

EN

T

Page 105: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 105 de 121

Tipo Falla : 1FT RF= 0 Ohm

Ruta : Temuco B2 - Gorbea 13,2kV

Tiempos de Operación en segundos

S/E Paño Relé NEMA Temuco

66kV

LT 66kV Temuco - Gorbea

Gorbea 66kV

Gorbea Bushing 66kV T1

Gorbea Barra

13,2kV

Línea de Media Tensión 13,2 kV

Padre Las Casas 66kV

Tap Licanco

66kV

Pitrufquén 66 kV

1% 25% 50% 75% 99%

Temuco 52B2 SEL-311C Trip --- 0,01 0,01 0,01 0,01 0,01 --- --- --- --- --- ---

Temuco 52B2 SEL-311C 21-Z1 --- 0,02 0,02 --- --- --- --- --- --- --- --- ---

Temuco 52B2 SEL-311C 21-Z2 --- 0,82 0,82 --- --- --- --- --- --- --- --- ---

Temuco 52B2 SEL-311C 21-Z3 --- 2,72 2,72 2,72 2,72 2,72 --- --- --- --- --- ---

Temuco 52B2 SEL-311C 21N-Z1 --- 0,02 0,02 0,02 0,02 0,02 --- --- --- --- --- ---

Temuco 52B2 SEL-311C 21N-Z2 --- 0,82 0,82 0,82 0,82 0,82 --- --- --- --- --- ---

Temuco 52B2 SEL-311C 21N-Z3 --- 2,72 2,72 2,72 2,72 2,72 --- --- --- --- --- ---

Temuco 52B2 SEL-311C 51N --- 0,23 0,23 0,27 0,31 0,31 --- --- --- --- --- ---

Temuco 52B2 SEL-311C 67N --- 0,01 0,01 0,01 0,01 0,01 --- --- --- --- --- ---

Gorbea 89BT1-F Fuse SMD 65E Trip --- --- --- --- --- 0,28 2,80 3,69 29,72 --- --- ---

Gorbea 52CT1 Siemens Argus Trip --- --- --- --- --- --- 0,41 0,51 1,04 1,16 1,29 1,38

Gorbea 52CT1 Siemens Argus 51N --- --- --- --- --- --- 0,86 0,89 1,04 1,16 1,29 1,38

Gorbea 52CT1 Siemens Argus 51 --- --- --- --- --- --- 0,41 0,51 1,81 5,48 15,44 27,20

Gorbea 52C1 Siemens Argus Trip --- --- --- --- --- --- --- 0,04 0,11 0,23 0,41 0,61

Gorbea 52C1 Siemens Argus 51N --- --- --- --- --- --- --- 0,57 0,65 0,72 0,78 0,82

Gorbea 52C1 Siemens Argus 51 --- --- --- --- --- --- --- 0,04 0,11 0,23 0,41 0,61

Page 106: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 106 de 121

9.5.1.5. F LL 1F (R = Ω) TEMUCO B -> GORBEA 13,2 kV

62,81150,24937,68725,12412,5620,0000 [km]

5,00

4,00

3,00

2,00

1,00

0,00

Tem_66kV_ Tap Padre La..

Tap Licanco ..

Pitrufquen 6.. Cto2

Gorbea_66kV

Bushing_66kV

Gorbea_13.2k..

LMT_13.2

x-Axis: Length Tem\52B2\Tem_52B2 Gorbea_66kV\Cub_4\Gorbea_89BT1F Gorbea_13.2kV\Cub_1\Gorbea_52CT1

Gorbea_13.2kV\Cub_2\Gorbea_52C1

TD1_Tem B2 -> Gorbea MT_R25

Date: 11/7/2014

Annex:

DIg

SIL

EN

T

Page 107: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 107 de 121

Tipo Falla : 1FT RF= 25 Ohm

Ruta : Temuco B2 - Gorbea 13,2kV

Tiempos de Operación en segundos

S/E Paño Relé NEMA Temuco

66kV

LT 66kV Temuco - Gorbea

Gorbea 66kV

Gorbea Bushing 66kV T1

Gorbea Barra

13,2kV

Línea de Media Tensión 13,2 kV

Padre Las Casas 66kV

Tap Licanco

66kV

Pitrufquén 66 kV

1% 25% 50% 75% 99%

Temuco 52B2 SEL-311C Trip --- 0,01 0,01 0,02 0,38 0,38 --- --- --- --- --- ---

Temuco 52B2 SEL-311C 21-Z1 --- --- --- --- --- --- --- --- --- --- --- ---

Temuco 52B2 SEL-311C 21-Z2 --- 0,82 0,82 --- --- --- --- --- --- --- --- ---

Temuco 52B2 SEL-311C 21-Z3 --- 2,72 2,72 2,72 --- --- --- --- --- --- --- ---

Temuco 52B2 SEL-311C 21N-Z1 --- 0,02 0,02 0,02 --- --- --- --- --- --- --- ---

Temuco 52B2 SEL-311C 21N-Z2 --- 0,82 0,82 0,82 0,82 0,82 --- --- --- --- --- ---

Temuco 52B2 SEL-311C 21N-Z3 --- 2,72 2,72 2,72 2,72 2,72 --- --- --- --- --- ---

Temuco 52B2 SEL-311C 51N --- 0,26 0,26 0,32 0,38 0,38 --- --- --- --- --- ---

Temuco 52B2 SEL-311C 67N --- 0,01 0,01 --- --- --- --- --- --- --- --- ---

Gorbea 89BT1-F Fuse SMD 65E Trip --- --- --- --- --- 0,50 --- --- --- --- --- ---

Gorbea 52CT1 Siemens Argus Trip --- --- --- --- --- --- 1,70 1,71 1,76 1,81 1,89 1,94

Gorbea 52CT1 Siemens Argus 51N --- --- --- --- --- --- 1,70 1,71 1,76 1,81 1,89 1,94

Gorbea 52CT1 Siemens Argus 51 --- --- --- --- --- --- --- --- --- --- --- ---

| 52C1 Siemens Argus Trip --- --- --- --- --- --- --- 0,98 1,01 1,03 1,06 1,09

Gorbea 52C1 Siemens Argus 51N --- --- --- --- --- --- --- 0,98 1,01 1,03 1,06 1,09

Gorbea 52C1 Siemens Argus 51 --- --- --- --- --- --- --- 2,00 2,30 2,66 3,13 3,54

Page 108: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 108 de 121

10. CONCLUSIONES

A través del presente estudio, motivado por habilitación de la nueva S/E Gorbea 66/13,2 kV, se

efectuó la especificación de ajustes para las protecciones de sobrecorriente del transformador T1,

compuesto por desconectadores fusibles en 66kV y un reconectador Siemens con unidad Argus como

interruptor general de media tensión 52CT1. De igual modo, motivado por los requerimientos de la

empresa Distribuidora CODINER, se han determinado los ajustes a implementar en el alimentador 52C1,

el cual también poseerá un reconectador Siemens con unidad de control Argus.

S/E Gorbea estará conectada normalmente a la LT 66kV Temuco – Loncoche N°2. Sin embargo,

gracias a la interconexión en 66 kV, mostrada en el diagrama unilineal del punto 3.4, será posible

alimentarla desde la LT 66kV Temuco – Loncoche N°1. Esta particularidad ha hecho necesaria la revisión

del comportamiento de las protecciones para los 5 escenarios de operación que se han analizado en

este informe.

Escenario 1, 2, 3: (Alimentación en anillo de S/E Gorbea, en donde la LT66kV Temuco-

Loncoche es energizada desde los extremos Temuco y Loncoche):

En esta condición, las protecciones de distancia de los extremos Temuco y Loncoche no

detectan fallas en la barra de MT de subestación Gorbea, permitiendo despejar las fallas en

13,2 kV selectivamente en Gorbea. Se observa que las fallas ocurridas al principio del enrollado

de 66 kV del T1 de S/E Gorbea serán despejadas por los fusibles en 66kV del transformador y la

zona 1 de las protecciones de distancia los extremos Temuco y Loncoche, existiendo

coordinación vía reconexión por las reconexiones implementadas en S/E Temuco y Loncoche.

Escenario 4: (Alimentación radial de S/E Gorbea desde el extremo Loncoche):

En este escenario, se ha determinado que el paño que alimente radialmente a S/E Gorbea

(B3 o B6 de Loncoche) debe tener habilitado el set de ajustes N°2. En este grupo de ajustes

alternativo, que actualmente tienen disponibles los paños B3 y B6 de Loncoche, el alcance de la

zona 2 es menor, por lo que las fallas entre fases cercanas a la barra de 13,2 kV sólo serán

vistas en tercera zona por el extremo Loncoche, permitiendo que las fallas en MT sean

despejadas selectivamente por las protecciones de S/E Gorbea. Se observa que las fallas

ocurridas al principio del devanado de 66 kV del T1 de S/E Gorbea serán despejadas por los

fusibles en 66kV del transformador y la zona 1 de la protección de distancia del extremo

Loncoche, existiendo coordinación vía reconexión por la reconexión implementada en

Loncoche.

Escenario 5: (Alimentación radial de S/E Gorbea desde el extremo Temuco):

En este escenario, las protecciones de distancia del extremo Temuco no detectan fallas en la

barra de MT de subestación Gorbea, por lo que éstas serán despejadas selectivamente en

Gorbea. Se observa que las fallas ocurridas en el enrollado de 66 kV del T1 de S/E serán

despejadas por los fusibles en 66kV del transformador y la zona 1 de la protección de distancia

del extremo Temuco, existiendo coordinación vía reconexión por la reconexión habilitada en

S/E Temuco.

Page 109: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 109 de 121

Cabe destacar que, para realizar la incorporación de la nueva S/E Gorbea 66/13,2 kV, no se

requiere efectuar modificaciones en las protecciones del resto del sistema, por lo que se mantienen los

actuales niveles de coordinación.

Finalmente, a partir de las simulaciones presentadas y las tablas de verificación expuestas, se

concluye que los ajustes especificados para los elementos de protección mencionados, permiten

mantener una adecuada coordinación con el resto de las protecciones del sistema, brindando

protección al transformador de poder T1 de S/E Gorbea y al alimentador 52C1 propiedad de CODINER.

Page 110: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 110 de 121

ANEXO - AJUSTES ACTUALES DE PROTECCIONES CONSIDERADAS

1. TEMUCO

1.1. INTERRUPTORES DE LINEA TEMUCO - LONCOCHE, CIRCUITOS 1 Y 2 (52B6 Y 52B2)

Protección de distancia

Relé : SEL311 C

Razón TTPP : 69.000/3 : 115/3

Razón TTCC : 400/5

Parámetros de línea:

Z1MAG = 8,95 (ohm-sec)

Z1ANG = 49,57 (grados)

Z0MAG = 26,68 (ohm-sec)

Z0ANG = 71,96 (grados)

LL = 124,64 (km)

Ajustes Unidad Mho para falla entre fases

Primera Zona : 84 % Tramo Temuco-Loncoche

Alcance : 5,05 ohm-sec

Ajuste detector de falla : 1,0 A- sec

Dirección : Hacia adelante

Tiempo operación : Instantáneo

Segunda Zona : 100 % Tramo Temuco-Loncoche + 15% Tramo

Loncoche - Pullinque

Alcance : 7,3 ohm-sec

Ajuste detector de falla : 1,0 A- sec

Dirección : Hacia adelante

Tiempo operación : 0,8 seg.

Tercera Zona : 130 % de la impedancia Temuco-Pullinque

Alcance : 12,0 ohm-sec

Ajuste detector de falla : 1,0 A- sec

Dirección : Hacia adelante

Tiempo operación : 2,7 seg.

Page 111: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 111 de 121

Ajustes Unidad Mho para fallas a tierra

Primera Zona : 84 % Tramo Temuco-Loncoche

Alcance : 5,05 ohm-sec

Ajuste detector de falla : 0,5 A- sec

Dirección : Hacia adelante

K0 : 0,67 L34,97º

Tiempo operación : Instantáneo

Segunda Zona : 100 % Tramo Temuco-Loncoche + 15% Tramo

Loncoche - Pullinque

Alcance : 7,3 ohm-sec

Ajuste detector de falla : 0,5 A- sec

Dirección : Hacia adelante

K0 : 0,70 L32,88º

Tiempo operación : 0,8 seg.

Tercera Zona : 130 % de la impedancia Temuco-Pullinque

Alcance : 12,0 ohm-sec

Ajuste detector de falla : 0,5 A- sec

Dirección : Hacia adelante

K0 : 0,70 L32,88

Tiempo operación : 2,7 seg.

Protección residual direccional

Relé : SEL311 C

Razón TTPP : 69.000/3 : 115/3

Razón TTCC : 400/5

Corriente de pick up : 0,55 A-sec (44 A-prim)

Curva tiempo corriente : U4 (U.S. Extremely Inverse)

Time Dial : 6,42

Elem. Instantáneo : 11,25 A- sec (900 A-prim)

Dirección : Hacia adelante

Reconexión

Nº de reconexiones : 1

Tiempo de reconexión : 10 seg

Tiempo de reposición : 30 seg

Activación : Operación protecciones de distancia Zonas 1 y 2, sobrecorriente residual

direccional.

Page 112: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 112 de 121

Load Encrochement

Se determinará considerando la máxima carga estimada de la línea en sentido directo.

El relé no verá carga en sentido inverso.

Datos:

Máxima carga espera en sentido directo= 46MVA

Fp ind= 0,90

Fp cap= 0,90

V= 66 kV

Ajustes:

PLAF= arc cos (fp directo) = 25,84º

NLAF= -arc cos (fp directo) = -25,84º

PLAR= 180º - arc cos (fp reverso) = 154,16º

NLAR= 180 + arc cos (fp reverso) = 205,84º

ZLF= (0,9xkV^2xCTR)/MVAxPTR = 11,36 Ohm-sec

ZLR= (0,9xkV^2xCTR)/MVAxPTR = 11,36 Ohm-sec

Page 113: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 113 de 121

2. LONCOCHE

2.1.- INTERRUPTORES DE LINEA LONCOCHE - TEMUCO, CIRCUITOS 1 Y 2 (52B6 Y 52B3)

2.1.1. GRUPO DE AJUSTES N°1

Este grupo se utiliza para la condición normal de operación: Pitrufquén alimentada en forma

simultánea desde Temuco y Loncoche

Protección de distancia

Relé : SEL311 C

Razón TTPP : 69.000/3 : 115/3

Razón TTCC : 300/5

Parámetros de línea:

Z1MAG = 4,51 (ohm-sec)

Z1ANG = 47,50 (grados)

Z0MAG = 13,09 (ohm-sec)

Z0ANG = 71,07 (grados)

LL = 80,98 (km)

Ajustes Unidad Mho para falla entre fases

Primera Zona : 84 % Tramo Loncoche-Temuco

Alcance : 3,79 ohm-sec

Ajuste detector de falla : 1,0 A- sec

Dirección : Hacia adelante

Tiempo operación : Instantáneo

Segunda Zona

Alcance : 9,35 ohm-sec

Ajuste detector de falla : 0,8 A- sec

Dirección : Hacia adelante

Tiempo operación : 0,7 seg.

Tercera Zona

Alcance : 11,24 ohm-sec

Ajuste detector de falla : 1,0 A- sec

Dirección : Hacia adelante

Tiempo operación : 2,0 seg.

Page 114: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 114 de 121

Ajustes Unidad Mho para fallas a tierra

Primera Zona : 84 % Tramo Loncoche-Temuco

Alcance : 3,79 ohm-sec

Ajuste detector de falla : 0,5 A- sec

Dirección : Hacia adelante

K0 : 0,67 L34,97º

Tiempo operación : Instantáneo

Segunda Zona

Alcance : 6,66 ohm-sec

Ajuste detector de falla : 0,5 A- sec

Dirección : Hacia adelante

K0 : 0,67 L34,97º

Tiempo operación : 0,7 seg.

Tercera Zona

Alcance : 11,4 ohm-sec

Ajuste detector de falla : 0,5 A- sec

Dirección : Hacia adelante

K0 : 0,67 L34,97º

Tiempo operación : 2,0 seg.

Protección de sobrecorriente residual direccional

Relé : SEL311 C

Razón TTPP : 69.000/3 : 115/3

Razón TTCC : 300/5

Corriente de pick up : 0,55 A-sec (33 A-prim)

Curva tiempo corriente : U4 (U.S. Extremely Inverse)

Time Dial : 6,42

Elem. Instantáneo : Inop

Dirección : Hacia adelante

Reconexión

Nº de reconexiones : 1

Tiempo de reconexión : 10 seg

Tiempo de reposición : 30 seg

Page 115: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 115 de 121

Load Encrochement

Se determinará considerando la máxima carga soportada por la línea

Se considera que el aporte normal es de Temuco hacia Loncoche.

Datos:

Conductor mínima sección= Cu1/0 AWG ; In=310 A

Máxima carga espera en sentido directo= 35 MVA

Fp ind= 0,90

Fp cap= 0,90

V= 66 kV

Ajustes:

PLAF= arc cos (fp directo) = 25,84º

NLAF= -arc cos (fp directo) = -25,84º

PLAR= 180º - arc cos (fp reverso) = 154,16º

NLAR= 180 + arc cos (fp reverso) = 205,84º

ZLF= (0,9xkV^2xCTR)/MVAxPTR = 11,2 Ohm-sec

ZLR= (0,9xkV^2xCTR)/MVAxPTR = 11,2 Ohm-sec

Alarma Sobrecarga

Se determina de acuerdo a la máxima carga permisible por la instalación.

Conductor de salida Cu 1/0 AWG

TTCC 300/5

Interruptor Delle

Protección de Fase

TTCC 300/5 (RTC: 60)

Relé SEL-311C

Instantánea Pick up 5,17 A-sec (310 A-prim; 35 MVA 66kV)

Curva Tiempo definido

Tiempo 30 seg.

Page 116: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 116 de 121

2.1.2. GRUPO DE AJUSTES N°2

Este grupo se utiliza cuando Pitrufquén quede alimentada en forma radial desde Loncoche

Protección de distancia

Relé : SEL311 C

Razón TTPP : 69.000/3 : 115/3

Razón TTCC : 300/5

Parámetros de línea:

Z1MAG = 4,51 (ohm-sec)

Z1ANG = 47,50 (grados)

Z0MAG = 13,09 (ohm-sec)

Z0ANG = 71,07 (grados)

LL = 80,98 (km)

Ajustes Unidad Mho para falla entre fases

Primera Zona : 84 % Tramo Loncoche-Temuco

Alcance : 3,79 ohm-sec

Ajuste detector de falla : 1,0 A- sec

Dirección : Hacia adelante

Tiempo operación : Instantáneo

Segunda Zona

Alcance : 5,41 ohm-sec

Ajuste detector de falla : 0,8 A- sec

Dirección : Hacia adelante

Tiempo operación : 0,7 seg.

Tercera Zona

Alcance : 11,24 ohm-sec

Ajuste detector de falla : 1,0 A- sec

Dirección : Hacia adelante

Tiempo operación : 2,0 seg.

Page 117: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 117 de 121

Ajustes Unidad Mho para fallas a tierra

Primera Zona : 84 % Tramo Loncoche-Temuco

Alcance : 3,79 ohm-sec

Ajuste detector de falla : 0,5 A- sec

Dirección : Hacia adelante

K0 : 0,67 L34,97º

Tiempo operación : Instantáneo

Segunda Zona

Alcance : 6,66 ohm-sec

Ajuste detector de falla : 0,5 A- sec

Dirección : Hacia adelante

K0 : 0,67 L34,97º

Tiempo operación : 0,7 seg.

Tercera Zona

Alcance : 11,4 ohm-sec

Ajuste detector de falla : 0,5 A- sec

Dirección : Hacia adelante

K0 : 0,67 L34,97º

Tiempo operación : 2,0 seg.

Protección de sobrecorriente residual direccional

Relé : SEL311 C

Razón TTPP : 69.000/3 : 115/3

Razón TTCC : 300/5

Corriente de pick up : 0,55 A-sec (33 A-prim)

Curva tiempo corriente : U4 (U.S. Extremely Inverse)

Time Dial : 6,42

Elem. Instantáneo : Inop

Dirección : Hacia adelante

Reconexión

Nº de reconexiones : 1

Tiempo de reconexión : 10 seg

Tiempo de reposición : 30 seg

Page 118: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 118 de 121

Load Encrochement

Se determinará considerando la máxima carga soportada por la línea

Se considera que el aporte normal es de Temuco hacia Loncoche.

Datos:

Conductor mínima sección= Cu1/0 AWG ; In=310 A

Máxima carga espera en sentido directo= 35 MVA

Fp ind= 0,90

Fp cap= 0,90

V= 66 kV

Ajustes:

PLAF= arc cos (fp directo) = 25,84º

NLAF= -arc cos (fp directo) = -25,84º

PLAR= 180º - arc cos (fp reverso) = 154,16º

NLAR= 180 + arc cos (fp reverso) = 205,84º

ZLF= (0,9xkV^2xCTR)/MVAxPTR = 11,2 Ohm-sec

ZLR= (0,9xkV^2xCTR)/MVAxPTR = 11,2 Ohm-sec

Alarma Sobrecarga

Se determina de acuerdo a la máxima carga permisible por la instalación.

Conductor de salida Cu 1/0 AWG

TTCC 300/5

Interruptor Delle

Protección de Fase

TTCC 300/5 (RTC: 60)

Relé SEL-311C

Instantánea Pick up 5,17 A-sec (310 A-prim; 35 MVA 66kV)

Curva Tiempo definido

Tiempo 30 seg.

Page 119: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 119 de 121

3. PULLINQUE

3.1. INTERRUPTORES DE LINEA PULLINQUE – LONCOCHE, CIRCUITOS 1 Y 2 (52B2 Y 52B4)

Protección de distancia

Relé : SEL311 C

Razón TTPP : 69.000/3 : 115/3

Razón TTCC : 300/5

Parámetros de línea:

Z1MAG = 2,21 (ohm-sec)

Z1ANG = 53,81 (grados)

Z0MAG = 6,92 (ohm-sec)

Z0ANG = 73,64 (grados)

LL = 43,66 (km)

Ajustes Unidad para falla entre fases (Mho)

Primera Zona : 80 % Tramo Pullinque-Loncoche

Alcance : 1,77 ohm-sec

Ajuste detector de falla : 1,0 A- sec

Dirección : Hacia adelante

Tiempo operación : Instantáneo

Segunda Zona : 100 % Tramo Pullinque-Loncoche + 15% Tramo

Loncoche - Temuco

Alcance : 4,21 ohm-sec

Ajuste detector de falla : 1,0 A- sec

Dirección : Hacia adelante

Tiempo operación : 0,8 seg.

Page 120: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 120 de 121

Tercera Zona : 100 % Tramo Pullinque-Temuco

Alcance : 9,54 ohm-sec

Ajuste detector de falla : 1,0 A- sec

Dirección : Hacia adelante

Tiempo operación : 1,8 seg.

Ajustes Unidad para fallas a tierra (Poligonal y Mho)

Primera Zona : 80 % Tramo Pullinque-Loncoche

Alcance Mho : 1,77 ohm-sec

Alcance XG : 1,77 ohm-sec

Alcance RG : 1,77 ohm-sec

Ajuste detector de falla : 0,5 A- sec

Dirección : Hacia adelante

K0 : 0,74 L28,61º

Tiempo operación : Instantáneo

Segunda Zona : 100 % Tramo Pullinque-Loncoche + 15% Tramo

Loncoche – Temuco

Alcance Mho : 4,34 ohm-sec

Alcance XG : 4,34 ohm-sec

Alcance RG : 4,34 ohm-sec

Ajuste detector de falla : 0,5 A- sec

Dirección : Hacia adelante

K0 : 0,74 L28,61º

Tiempo operación : 0,8 seg.

Tercera Zona : 100 % Tramo Pullinque-Temuco

Alcance Mho : 10,1 ohm-sec

Alcance XG : 10,1 ohm-sec

Alcance RG : 10,1 ohm-sec

Ajuste detector de falla : 0,5 A- sec

Dirección : Hacia adelante

K0 : 0,74 L28,61º

Tiempo operación : 1,8 seg.

Reconexión

Nº de reconexiones : 1

Tiempo de reconexión : 10 seg

Tiempo de reposición : 30 seg

Activación : Operación protecciones de distancia Zonas 1 y 2.

Page 121: INFORME IEP AR-010/2014 · 2015-01-09 · 52C1 propiedad de CODINER, el cual tendrá un reconectador Siemens y unidad de control Argus como equipos de protección 2. OBJETIVOS El

Mantenimiento Araucanía TRANSNET

IEP AR-010/2014 JNG/Octubre 2014

Página 121 de 121

Load Encrochement

Se determinará considerando la máxima carga estimada de la línea en sentido directo.

El relé no verá carga en sentido inverso.

Datos:

Máxima carga espera en sentido directo= 41MVA

Fp ind= 0,90

Fp cap= 0,90

V= 66 kV

Ajustes:

PLAF= arc cos (fp directo) = 25,84º

NLAF= -arc cos (fp directo) = -25,84º

PLAR= 180º - arc cos (fp reverso) = 154,16º

NLAR= 180 + arc cos (fp reverso) = 205,84º

ZLF= (0,9xkV^2xCTR)/MVAxPTR = 9,56 Ohm-sec

ZLR= (0,9xkV^2xCTR)/MVAxPTR = 9,56 Ohm-sec

Alarma Sobrecarga

Se determina de acuerdo a la máxima carga permisible por la instalación.

Conductor de salida Cu 2/0 AWG

TTCC 300/5

Interruptor Delle

Protección de Fase

TTCC 300/5 (RTC: 60)

Relé SEL-311C

Instantánea Pick up 5,83 A-sec (350 A-prim; 40 MVA 66kV)

Curva Tiempo definido

Tiempo 30 seg.