8/17/2019 Calrsa Ejemplo
1/2
DISTRIBUCIÓN : SECUNDARIA
TIPO DE CONDUCTOR COBRE FORRADO
DISPOSICIÓN :
D 1-2 0.15
D 2-3 0.15
D 1-3 0.3
DIST. MEDIA GEOM. (mm) 188.98816
TENSIÓN (V) 220 (380/220)
FACTOR DE POTENCIA 0.9
FACTOR DE CARGA 0.35
FACTOR DE PÉRDIDAS 0.19075
TEMPERATURA DE TRABAJO oC. 45
RESISTIVIDAD (20oC) 17.9 Ohm-mm2/km
RESISTIVIDAD oC 45 19.60945 Ohm-mm2/km
POT.MÁX./CONS.(W) 900
SECCIÓN RADIO RADIO RESIST. REACTAN. FACTOR DE CAÍDA
(mm2) (mm) EQUI.(mm) Ohm/km Ohm/km DE TENSIÓN
6 1.56 1.3819766 3.2682417 0.3892554 0.0052375
10 2.025 1.7841241 1.960945 0.3700193 0.0032427
16 2.55 2.2567583 1.2255906 0.3523204 0.0021155
25 3.21 2.8209479 0.784378 0.3355147 0.001434735 3.78 3.3377906 0.56027 0.3228442 0.0010858
50 4.45 3.9894228 0.392189 0.3094129 0.0008213
70 5.35 4.7203487 0.280135 0.2967424 0.0006422
95 6.3 5.4990398 0.2064153 0.2852427 0.0005221
--------- --------- --------- --------- --------- --------- --------- --------- --------- --------- --------- --------- ---------
DISENO #1
CIRCUITO #1
PUNTO 1 2 3 4 5 6 7 8 9 10 11
Nc 5 5 15 21 8 6 5
SUM.Nc 65 60 55 40 19 11 5 0 0 0 0
f.s. 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5
POT. S.P.(kW) 29.25 27 24.75 18 8.55 4.95 2.25 0 0 0 0 POT. C.E.(kW) 2
SUM.POT.C.E.(kW) 2 2 2 0 0 0 0 0 0 0 0
POT.TOTAL (kW) 31.25 29 26.75 18 8.55 4.95 2.25 0 0 0 0
INTENSIDAD (A) 52.609428 48.821549 45.03367 30.30303 14.393939 8.3333333 3.7878788 0 0 0 0
SECCIÓN (mm2) 10 10 10 10 10 10 10
LONGITUD (m) 1 23 10 32 30 30 30
CAÍDA TENSIÓN 0.101333 2.1628521 0.8674107 1.8677704 0.8317415 0.4815345 0.2188793 #N/A #N/A #N/A #N/A
SUMAT.CAÍDA TEN. 0.101333 2.2641852 3.1315959 4.9993662 5.8311077 6.3126422 6.5315216 #N/A #N/A #N/A #N/A
--------- --------- --------- --------- --------- --------- --------- --------- --------- --------- --------- --------- ---------
PÉRD. POR TRAMO 27.207114 538.89762 199.35632 288.85336 61.099255 20.479252 4.2312503 #N/A #N/A #N/A #N/A
SUMAT. DE PÉRD.(kWh/ano) #N/A
RAMAL / PUNTO 3 3.1 3.2 3.3 3.4 3.5
Nc 10 5
SUM Nc 15 5 0 0 0 f.s. 0.5 0.5 0.5 0.5 0.5
POT. S.P.(kW) 6.75 2.25 0 0 0
POT. C.E.(kW)
SUM.POT.C.E.(kW) 0 0 0 0 0
POT.TOTAL (kW) 6.75 2.25 0 0 0
INTENSIDAD (A) 11.363636 3.7878788 0 0 0
SECCIÓN (mm2) 10 10
LONGITUD (m) 32 32
CAÍDA TENSIÓN 3.1315959 0.7004139 0.2334713 #N/A #N/A #N/A
SUMAT.CAÍDA TEN. 3.1315959 3.8320097 4.065481 #N/A #N/A #N/A
--------- --------- --------- --------- --------- --------- --------- ---------
PÉRD. POR TRAMO 40.620003 4.5133337 #N/A #N/A #N/A
SUMAT. DE PÉRD.(kWh/ano) #N/A
RAMAL / PUNTO 4 4.1 4.2 4.3 4.4 4.5 Nc 3
SUM Nc 3 0 0 0 0
f.s. 0.5 0.5 0.5 0.5 0.5
POT. S.P.(kW) 1.35 0 0 0 0
POT. C.E.(kW)
SUM.POT.C.E.(kW) 0 0 0 0 0
POT.TOTAL (kW) 1.35 0 0 0 0
INTENSIDAD (A) 2.2727273 0 0 0 0
SECCIÓN (mm2) 10
LONGITUD (m) 30
CAÍDA TENSIÓN 4.9993662 0.1313276 #N/A #N/A #N/A #N/A
SUMAT.CAÍDA TEN. 4.9993662 5.1306938 #N/A #N/A #N/A #N/A
--------- --------- --------- --------- --------- --------- --------- ---------
PÉRD. POR TRAMO 1.5232501 #N/A #N/A #N/A #N/A
SUMAT. DE PÉRD.(kWh/ano) #N/A
RAMAL / PUNTO 0.1 0.2 0.3 0.4 0.5
Nc
SUM Nc 0 0 0 0 0
f.s. 0.5 0.5 0.5 0.5 0.5
POT. S.P.(kW) 0 0 0 0 0
-
8/17/2019 Calrsa Ejemplo
2/2
POT. C.E.(kW)
SUM.POT.C.E.(kW) 0 0 0 0 0
POT.TOTAL (kW) 0 0 0 0 0
INTENSIDAD (A) 0 0 0 0 0
SECCIÓN (mm2)
LONGITUD (m)
CAÍDA TENSIÓN #N/A #N/A #N/A #N/A #N/A #N/A
SUMAT.CAÍDA TEN. #N/A #N/A #N/A #N/A #N/A #N/A
--------- --------- --------- --------- --------- --------- --------- ---------
PÉRD. POR TRAMO #N/A #N/A #N/A #N/A #N/A
SUMAT. DE PÉRD.(kWh/ano) #N/A
RAMAL / PUNTO 0.1 0.2 0.3 0.4 0.5
Nc
SUM Nc 0 0 0 0 0
f.s. 0.5 0.5 0.5 0.5 0.5
POT. S.P.(kW) 0 0 0 0 0
POT. C.E.(kW)
SUM.POT.C.E.(kW) 0 0 0 0 0
POT.TOTAL (kW) 0 0 0 0 0
INTENSIDAD (A) 0 0 0 0 0
SECCIÓN (mm2) LONGITUD (m)
CAÍDA TENSIÓN #N/A #N/A #N/A #N/A #N/A #N/A
SUMAT.CAÍDA TEN. #N/A #N/A #N/A #N/A #N/A #N/A
--------- --------- --------- --------- --------- --------- --------- ---------
PÉRD. POR TRAMO #N/A #N/A #N/A #N/A #N/A
SUMAT. DE PÉRD.(kWh/ano) #N/A
RAMAL / PUNTO 0.1 0.2 0.3 0.4 0.5
Nc
SUM Nc 0 0 0 0 0
f.s. 0.5 0.5 0.5 0.5 0.5
POT. S.P.(kW) 0 0 0 0 0
POT. C.E.(kW)
SUM.POT.C.E.(kW) 0 0 0 0 0
POT.TOTAL (kW) 0 0 0 0 0 INTENSIDAD (A) 0 0 0 0 0
SECCIÓN (mm2)
LONGITUD (m)
CAÍDA TENSIÓN #N/A #N/A #N/A #N/A #N/A #N/A
SUMAT.CAÍDA TEN. #N/A #N/A #N/A #N/A #N/A #N/A
--------- --------- --------- --------- --------- --------- --------- ---------
PÉRD. POR TRAMO #N/A #N/A #N/A #N/A #N/A
SUMAT. DE PÉRD.(kWh/ano) #N/A