8/10/2019 SunMD Tour Presentation Bob http://slidepdf.com/reader/full/sunmd-tour-presentation-bob 1/34 Sun Modular Datacenter S20 Project Blackbox Bob Schilmoeller Global Architect Sun MD Marketing

Upload: mark-m-sibomet

Post on 02-Jun-2018

217 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: SunMD Tour Presentation Bob

8/10/2019 SunMD Tour Presentation Bob

http://slidepdf.com/reader/full/sunmd-tour-presentation-bob 1/34

Sun ModularDatacenter S20

Project Blackbox

Bob Schilmoeller Global ArchitectSun MD Marketing

Page 2: SunMD Tour Presentation Bob

8/10/2019 SunMD Tour Presentation Bob

http://slidepdf.com/reader/full/sunmd-tour-presentation-bob 2/34

2

Need to rapidly addnew data center

capacity

Want to lower energy consumption and reduce CO2 emissions

Must usehigher power

equipment inless space

Want to growcapacity

incrementallyas needed

Need flexibility tolocate and use

IT resourceswhere needed

Customer Challenges

Page 3: SunMD Tour Presentation Bob

8/10/2019 SunMD Tour Presentation Bob

http://slidepdf.com/reader/full/sunmd-tour-presentation-bob 3/34

3

What is the Sun Modular Datacenter?

 A high-density, energy efficient, datacenter configuredin an enhanced 20' x 8' shipping container for easeand speed of deployment

• Integrated, high-efficiencypower and cooling up to 25kWper rack!

• 305 RU in only 160 sq ft.

• Customizable payload> Sun and 3rd party gear

compatible

• Global deployment capabilitieswith Sun Services

Page 4: SunMD Tour Presentation Bob

8/10/2019 SunMD Tour Presentation Bob

http://slidepdf.com/reader/full/sunmd-tour-presentation-bob 4/34

4

Rapid Deployment

• Deployable in 1/10th the timevs. typical datacenter 

• Modular, self-contained, pre-integrated solution enablesfaster deployments> Standardized form-factor

 – Enhanced ISO standard 20'

shipping container> Leverages existing global

infrastructure – Transport via road, ship, or air 

>

Simply connect to network,power, and chilled water source

Build once, deploy anywhere

Page 5: SunMD Tour Presentation Bob

8/10/2019 SunMD Tour Presentation Bob

http://slidepdf.com/reader/full/sunmd-tour-presentation-bob 5/34

5

Game Changing Economics

 A better way to buy datacenter capacity• Expansion at a

fraction of the cost ofa new datacenter 

> Increase capacitywhen you need it, inthe amount you need,instead of all at once

> Can delay newbuilding investments

> Free up capital forother uses

Page 6: SunMD Tour Presentation Bob

8/10/2019 SunMD Tour Presentation Bob

http://slidepdf.com/reader/full/sunmd-tour-presentation-bob 6/34

Page 7: SunMD Tour Presentation Bob

8/10/2019 SunMD Tour Presentation Bob

http://slidepdf.com/reader/full/sunmd-tour-presentation-bob 7/347

High Density By Design

• 8 racks, 40 RU per rack for 320 RU total> 280 RU available for IT equipment

> 25 RU available for network equipment

>

15 RU reserved for Sun MD monitoring,management, and control equipment

• Up to 25kW capacity per rack> 12.5kW standard

> 200kW total input> In-line, high efficiency

heat exchangers

Page 8: SunMD Tour Presentation Bob

8/10/2019 SunMD Tour Presentation Bob

http://slidepdf.com/reader/full/sunmd-tour-presentation-bob 8/348

High Efficiency Cooling System

• Unique, closed-loop water cooling system> Self-contained, closed-loop air circulation system results in

far less area to cool>

Water can carry as much as 3,500 times more heat than airin the same volume

Innovation in action

Page 9: SunMD Tour Presentation Bob

8/10/2019 SunMD Tour Presentation Bob

http://slidepdf.com/reader/full/sunmd-tour-presentation-bob 9/349

Eco Value

• 40% lower cooling costsindependent of IT load!> Significant 5-year savings

 – 2.4 gigawatt reduction – $240,000 savings

 – 1,459 metric tons less CO2

 –  Additional savings possible with energyefficient IT load

• Locate near renewable and/orlower cost sources of energy

• Smaller footprint has less impacton local environment

Save the environment and your wallet

Page 10: SunMD Tour Presentation Bob

8/10/2019 SunMD Tour Presentation Bob

http://slidepdf.com/reader/full/sunmd-tour-presentation-bob 10/3410

Efficiency by Design

Power savings – 40% lower cooling costsSun ModularDatacenter 

TraditionalDatacenter 

Cooling Load .65W* .38W**

IT Load 1W 1W> 40%savings!

* Cooling load estimate from Lawrence Berkeley Labs & PG&E Datacenter Efficiency Report June 2005.

**Sun Modular Datacenter cooling load data derived per Sun benchmark testing

Page 11: SunMD Tour Presentation Bob

8/10/2019 SunMD Tour Presentation Bob

http://slidepdf.com/reader/full/sunmd-tour-presentation-bob 11/3411

Key Markets

 Augmentation Interim Use SpecializedLarge Scale

Network Services

• Datacenterexpansion &consolidation

• Re-purpose& re-deploy

• Disaster recovery

• Datacentermigration

• Temporarydatacenters

• Short termprojects

• Disaster relief 

• Gov’t / Military

• Oil and gas

• Extensivecustomization

• Fast growth

•  ASPs

• SPs

Page 12: SunMD Tour Presentation Bob

8/10/2019 SunMD Tour Presentation Bob

http://slidepdf.com/reader/full/sunmd-tour-presentation-bob 12/3412

Stanford Linear Accelerator Center (SLAC)

• 4X faster deployment of firstsystem and payload vs. otheralternatives (six months fromstart to finish vs. at least twoyears for a new building)

• 30% increase in processingpower  conveniently locatedoutdoors next to a powersubstation

• Purchased second Sun MD

and more compute capacity  – Deployed in half the time asthe first with Sun MDinfrastructure already in place

Sun Solution Client ResultsKey Requirements• State-of-the-art particle

physics research laboratory

• Rapidly increase computing

resources to the gridcomputing infrastructure tosupport critical particle physicsresearch.

• Overcome datacenter powerand cooling systemconstraints to address a

growing number of requestsfor computing support

• Deliver computing resourcesin an alternative form factor inless time than the 2 – 5 yearsestimated to build a newdatacenter at the site

California, United States

• Sun Modular Datacenter S20• Sun Fire X2200 M2 servers• Customer Ready Systems

Integration

Fast capacity for HPC deployment

Page 13: SunMD Tour Presentation Bob

8/10/2019 SunMD Tour Presentation Bob

http://slidepdf.com/reader/full/sunmd-tour-presentation-bob 13/3413

Hansen Transmissions

• Rapid deployment of entiresolution from Sun to India –the entire project from conceptto delivery executed in lessthan four  months

• Immediate IT capability -Production Planning andProcessing - to managebusiness development andfactory construction in Indiaand immediate ROI 

Sun Solution Client ResultsKey Requirements• Leading provider globally of

wind-turbine gearboxes

• Rapidly expanding production

in new factories in India andChina

• Want to install payload beforeshipment and installation inIndia

• Need IT services while factory

is under construction• Solution must allow 3rd party

equipment

Belgium to India

• Sun Modular Datacenter S20• Sun Fire T5120 servers• Sun Fire T5220 servers

• Sun StorageTek 6140 array• Sun StorageTek 2540 arrays• Assort. 3rd party gear enabled

Mobility Enables Rapid Deployment & Redeployment

Page 14: SunMD Tour Presentation Bob

8/10/2019 SunMD Tour Presentation Bob

http://slidepdf.com/reader/full/sunmd-tour-presentation-bob 14/3414

Mobile TeleSystems (MTS)

• Over 10x reduction in time todeploy new datacentercapacity

• Air transport - From the SunMD factory in the U.S. toMoscow in less than a week

• Only 22 days from Sun MDinstallation to operation oftelco billing solution

Currently running outdoors inMoscow during winter 

Sun Solution Client ResultsKey Requirements• Largest mobile telephone

operator in Russia and CIS.

• Need to support rapid growth

and deploy new IT capabilityoutside main office to serve alarge geographic region

• Ability to operate outdoors indiverse climate ranges,especially 'Russian winters

• Sun Modular Datacenter S20• StorageTek 6540 arrays• Sun Fire X4600 servers

• Assorted 3rd party gearenabled

Rapid Deployments Over Large Geographic Region

Moscow, Russia

Page 15: SunMD Tour Presentation Bob

8/10/2019 SunMD Tour Presentation Bob

http://slidepdf.com/reader/full/sunmd-tour-presentation-bob 15/34

15

Standards Based Platform

• Virtually any application can bedeployed in a Sun MD

•  Any compatible Sun and 3rd partyequipment allowed> Must perform within rack

specifications to be “compatible” – 48.26 cm (19") wide; 78.1cm (30.75”)deep - including cable, bezel, andhandle depth; and front to back cooling

Page 16: SunMD Tour Presentation Bob

8/10/2019 SunMD Tour Presentation Bob

http://slidepdf.com/reader/full/sunmd-tour-presentation-bob 16/34

16

The Sun MD Suite of Services

Simplicity from procurement through production

Project Management, Datacenter Services, Training

• Key Benefits> Radically simplify &

speed deployment> Leverage Sun's

technical expertise

> Reduce complexity

and operational risk> Meet service levels

> Choice of services

Page 17: SunMD Tour Presentation Bob

8/10/2019 SunMD Tour Presentation Bob

http://slidepdf.com/reader/full/sunmd-tour-presentation-bob 17/34

17

Payload Integration:

Sun Customer Ready Systems (CRS) Program

 Actual CRS integrationinto Sun MD rack

•  Architect, integrate, and testthe entire Sun MD and

payload at the factory> Reduce risk and speed time to

deployment> Includes both Sun and

supported 3rd party gear andsoftware

• Turn it on, and it's ready to go!

Page 18: SunMD Tour Presentation Bob

8/10/2019 SunMD Tour Presentation Bob

http://slidepdf.com/reader/full/sunmd-tour-presentation-bob 18/34

18

Infrastructure Solutions

• Community of 3rd partyproviders to support Sun MDinfrastructure needs> Chiller vendors; power

equipment vendors; serviceshelters; security, etc.

> Individual sub-systemproviders or 'all in one'

solution providers• Locate reference list at:

http://www.sun.com/products/sunmd/s20/providers.jsp

Cooling

Power 

Service Structures

All-In-OneInfrastructure

ProvidersContainer Security

& Accessories

Page 19: SunMD Tour Presentation Bob

8/10/2019 SunMD Tour Presentation Bob

http://slidepdf.com/reader/full/sunmd-tour-presentation-bob 19/34

19

Sun Modular Datacenter S20

The World's First Virtualized Datacenter   Virtualize the datacenter into a modular, self-contained unit to

radically improve time to deployment; increase flexibility and

mobility; and enable higher-density and more efficient computing

Page 20: SunMD Tour Presentation Bob

8/10/2019 SunMD Tour Presentation Bob

http://slidepdf.com/reader/full/sunmd-tour-presentation-bob 20/34

20

The Possibilities Are Endless

• Take your own interactive tour of the Sun MD> www.sun.com/sunmd - click on the interactive tour icon

Please contact [email protected] for more information,or ask your local Sales representative

• We look forward to discussing your Sun MD possibilities!

Radically improve time to deployment with theSun Modular Datacenter 

Page 21: SunMD Tour Presentation Bob

8/10/2019 SunMD Tour Presentation Bob

http://slidepdf.com/reader/full/sunmd-tour-presentation-bob 21/34

Sun ModularDatacenter S20

Project Blackbox

Bob Schilmoeller Global ArchitectSun MD Marketing

Page 22: SunMD Tour Presentation Bob

8/10/2019 SunMD Tour Presentation Bob

http://slidepdf.com/reader/full/sunmd-tour-presentation-bob 22/34

22

Appendix

Page 23: SunMD Tour Presentation Bob

8/10/2019 SunMD Tour Presentation Bob

http://slidepdf.com/reader/full/sunmd-tour-presentation-bob 23/34

23

Supported Sun Equipment

• For the latest updates, see:> http://www.sun.com/products/sunmd/s20/supported_hardware.jsp

> Sun Fire V125, Sun Fire V210, Sun Fire V215, Sun Fire V245, SunFire V440/V445, Sun Fire V480/V490, Sun Fire T1000 , Sun Fire

T2000, Sun Fire V1280/E2900, Sun Fire X2100M2, Sun FireX2200M2, Sun Fire X4100 / X4100 M2 X4200 / X4200 M2, SunFire X4500, Sun Fire X4600 M2, Sun Blade 6000, Sun Blade 8000,& Sun Blade 8000P

> Sun StorageTek 2530/2540, Sun StorageTek 3120, SunStorageTek 3320, Sun StorageTek 3510, Sun StorageTek 5310,Sun StorageTek 5320, Sun StorageTek 6130, Sun StorageTek6140, Sun StorageTek 6540, Sun StorageTek CSM2, SunStorageTek D240, & StorageTek DAT 72

Page 24: SunMD Tour Presentation Bob

8/10/2019 SunMD Tour Presentation Bob

http://slidepdf.com/reader/full/sunmd-tour-presentation-bob 24/34

24

Sun Modular Datacenter Features

• What's included with the Sun MD platform> Structurally upgraded container > Internal power infrastructure provides redundant 12.5kW power per rack.

25KW option for 7 payload racks> Internal cooling system with heat exchangers, fans, & plumbing> Eight 19” racks with cable management system & rack sliding tool> Control infrastructure including internal sensor monitoring, lighting, air filters,

& dehumidifier 

•  What's not included with the Sun MD platform

> Payload (servers, disk, storage, tape, cables, network routers/switches, etc)> Chiller & external plumbing; humidification; and facility infrastructure> Power generator, transformer, UPS, external connections and infrastructure> Container pad/foundation, service shelter, leveling shims; exterior lighting &

infrastructure

Page 25: SunMD Tour Presentation Bob

8/10/2019 SunMD Tour Presentation Bob

http://slidepdf.com/reader/full/sunmd-tour-presentation-bob 25/34

25

Deployment Site Requirements

• Input Power: 200kW> Low & high voltage support

> 190 - 220 VAC, 3 Phase, 50 Hz/60 Hz

> 380 - 415 VAC, 3 Phase, 50 Hz/60 Hz

Cooling: chilled water > 18°C to 22°C (64°F to 72°F) nominal inputtemperature

• Networking: standard options> Ethernet, Fibre, or bulk pass-through

Space: flat, level area> Minimum: 9.14m x 5.49m (30ft x 18ft)

• Can be indoor or outdoor> Typical options:

 – Secure warehouse space;

 – Fenced, secure parking area with service shelter 

Page 26: SunMD Tour Presentation Bob

8/10/2019 SunMD Tour Presentation Bob

http://slidepdf.com/reader/full/sunmd-tour-presentation-bob 26/34

26

Physical & Structural Details

• Starts with ISO 1 TEU shipping container > 6.06m x 2.44m x 2.59m (20ft x 8ft x 8.5ft) (L x W x H)> Outfitted with internal structural beams, insulation and paint> Integrated cable trays and interior lighting; exterior connections

for power, water, & network> External lift points unchanged

• Less than 34,000 lbs. fully configured

• 8 racks in two rows of 4> Service access in central aisle

• Front and rear doors> Rear entry space provides

access to power distribution

Page 27: SunMD Tour Presentation Bob

8/10/2019 SunMD Tour Presentation Bob

http://slidepdf.com/reader/full/sunmd-tour-presentation-bob 27/34

27

External Connections

• Redundant water, network & power connectionslocated on each side of the platform

WatersupplyWaterreturn

Chilled water connection

Electricfeeder

entrance

Externalpowerdisconnectswitch

Networkconnectionpanel

Page 28: SunMD Tour Presentation Bob

8/10/2019 SunMD Tour Presentation Bob

http://slidepdf.com/reader/full/sunmd-tour-presentation-bob 28/34

28

Power 

• External power = 200kW> 190 to 220 VAC 3-phase 50/60Hz,

600A service (Japan and North America)

>

380 to 415 VAC 3-phase 50/60Hz,300A service (International)> Dual grid capable with redundant

power distribution panels

• Power power per rack> 12.5kW or 25kW for 7 racks> 12.5kW for control rack

Redundant powerdistribution panels with

circuit breakers

Page 29: SunMD Tour Presentation Bob

8/10/2019 SunMD Tour Presentation Bob

http://slidepdf.com/reader/full/sunmd-tour-presentation-bob 29/34

29

Rack Details

• Eight 40RU racks, 48.26cm x 78.1cm (19in x 30 !in)> Seven payload racks (servers, storage, etc.)> One network & control rack with 25RU for network switch, etc.

 –  Also includes alarm control box, EPO control box, and de-humidifier 

> Each rack includes an overhead articulated cable-management arm

Slide mechanism

for maintenance

Shock mounts

Rated up to 9 G (vertical plane)

Racks lock to floor for transportation

Page 30: SunMD Tour Presentation Bob

8/10/2019 SunMD Tour Presentation Bob

http://slidepdf.com/reader/full/sunmd-tour-presentation-bob 30/34

Sun ModularDatacenter S20

Bob Schilmoeller Global ArchitectSun Modular Datacenter 

Page 31: SunMD Tour Presentation Bob

8/10/2019 SunMD Tour Presentation Bob

http://slidepdf.com/reader/full/sunmd-tour-presentation-bob 31/34

31

When You Can't Afford to Wait

"We increased our compute capacity over 30% in a matter ofmonths with Sun MD. Including design, approvals, site prep,install and start-up it was much faster than the two to five!

years required to build a satellite center or a major building."

Chuck Boeheim Assistant Director of ComputingStanford Linear Accelerator Center 

Sun Modular Datacenter 

http://www.sun.com/SLACvideo

http://today.slac.stanford.edu/feature/2007/blackbox1.asp

http://today.slac.stanford.edu/feature/2007/blackbox2.asp

http://www.slac.stanford.edu/~boeheim/blackboxsite.html

Page 32: SunMD Tour Presentation Bob

8/10/2019 SunMD Tour Presentation Bob

http://slidepdf.com/reader/full/sunmd-tour-presentation-bob 32/34

32

“The Sun Modular Datacenter S20 is a great solution for us -- cost

effective and easy-to deploy. Using the Sun Modular Datacenter,we'll be able to offer IT services in a semi-finished factory and startseeing ROI almost immediately.”

Marnix MaesDirector of ITHansen Transmissions

What Customers Are Saying

Sun Modular Datacenter 

Page 33: SunMD Tour Presentation Bob

8/10/2019 SunMD Tour Presentation Bob

http://slidepdf.com/reader/full/sunmd-tour-presentation-bob 33/34

33

Financing Solutions

• Lease the datacenter and equipment with a single,combined payment for both the Sun MD & payload!>  Attractive rates and flexible terms from 12 to 60 months>

Standard end-of-lease options available, allowing flexibility torenew, return or buyout the entire solution> Structures available that may classify Sun MD as an operating

expense

 Available in select countries world-wide> Subject to credit approval and acceptable financing terms

Sun Microsystems Global Financial Services

Please contact your Sun Microsystems GlobalFinancial Services account executive for further detailsor visit http://www.sun.com/sales/leasing/index.jsp

>

Page 34: SunMD Tour Presentation Bob

8/10/2019 SunMD Tour Presentation Bob

http://slidepdf.com/reader/full/sunmd-tour-presentation-bob 34/34

Radboud University Nijmegen Medical Centre

• Large, immediate increasein compute power  – Large,immediate increase incompute power – added 250+

CPUs; room for more

• Reduced datacentercomplexity and cost with7 x 24 Sun Services supportand energy costs savings

• Rapid time to deployment –

Sun MD unit delivered in lessthan 45 days; project fromconcept to reality in 4 months

Sun Solution Client ResultsKey Requirements• Leading academic center and

teaching hospital in theNetherlands

•Existing two server farmscompletely full – need newserver space fast to maintainsupport for university andmedical research IT needs

• Looking for future flexibility tolocate near less expensive

power sources• Need 3rd party support for

existing equipment

• Sun Modular Datacenter S20• Sun Blade 6000 systems• Assorted 3rd party gear

enabled

Rapid Expansion of Energy Efficient Datacenter Capacity

The Netherlands