SEPAM - Protection Relays

Series 20 - 40

PT. Wilmar Gresik, 24 April 2012

Page 2: Sepam-Basic Presentation 240412

8/19/2019 Sepam-Basic Presentation 240412

http://slidepdf.com/reader/full/sepam-basic-presentation-240412 2/26

2

Sepam series 20:

simple solutionsfor usual applications

Sepam series 40:high-performing solutions

for demanding applications

Sepam series 80:

intelligent solutions

for custom applications

Sepam – Protection Relays

 A Range of Solution for All Applications

Page 3: Sepam-Basic Presentation 240412

8/19/2019 Sepam-Basic Presentation 240412

http://slidepdf.com/reader/full/sepam-basic-presentation-240412 3/26

3

Sepam – Protection Relay

Standard Applications

For industrial and

service sector site

networks

For public distribution

networks

For all voltage levels

Page 4: Sepam-Basic Presentation 240412

8/19/2019 Sepam-Basic Presentation 240412

http://slidepdf.com/reader/full/sepam-basic-presentation-240412 4/264

Sepam – Substation Application

Series 20 / Type : S20

Substation incomer and

feeder applications

Protection functions:

50/51, phase over

current 50N/51N, earth fault

46, negative

sequence / unbalance

Logic discrimination

4-cycle recloser 

Page 5: Sepam-Basic Presentation 240412

8/19/2019 Sepam-Basic Presentation 240412

http://slidepdf.com/reader/full/sepam-basic-presentation-240412 5/265

● Parallel incomers or closed

ring networks

● Isolated or compensatedneutral networks

● Protection functions:● 50/51,50N/51N,46,50BF● 67N/67NC,

directional earth fault● 67, directional phase

overcurrent● 32P, reverse power 

● I, U, P, E metering

Sepam – Substation Application

Series 40 / Type : S40 / S41 / S42

Page 6: Sepam-Basic Presentation 240412

8/19/2019 Sepam-Basic Presentation 240412

http://slidepdf.com/reader/full/sepam-basic-presentation-240412 6/266

Protection functions:

50/51, 50N/51N and46

49RMS, thermal

overload 38/49T, temperature

monitoring (8

sensors)

Processing of faults

detected by transformer

Buchholz or thermostat

(MES module required)

Sepam – Transformer Protection

Series 20 / Type : T20

Page 7: Sepam-Basic Presentation 240412

8/19/2019 Sepam-Basic Presentation 240412

http://slidepdf.com/reader/full/sepam-basic-presentation-240412 7/267

● Parallel transformers

● Isolated or compensatedneutral networks

● Protection functions:

● 50/51,50N/51N, 46,50BF● 49RMS and 38/49T● 67N/67NC, directional

earth fault● 67, directional phase

overcurrent

● I, U, P, E metering

Sepam – Transformer Protection

Series 40 / Type : T40 / 42

Page 8: Sepam-Basic Presentation 240412

8/19/2019 Sepam-Basic Presentation 240412

http://slidepdf.com/reader/full/sepam-basic-presentation-240412 8/26

8

Protection functions:

50/51, 50N/51N, 46

49RMS

38/49T

Specific functions:

37, phase undercurrent 48/51LR, excessive

starting time and

locked rotor 

66, starts per hour  specific motor-related

function (MES114)

Sepam – Motor Protection

Series 20 / Type : M20

Page 9: Sepam-Basic Presentation 240412

8/19/2019 Sepam-Basic Presentation 240412

http://slidepdf.com/reader/full/sepam-basic-presentation-240412 9/26

9

● Isolated or compensated

neutral networks

● All the M20 protectionfunctions, plus:● 67N/67NC, directional

earth fault● 32P, reverse power ● 27/59, 81L/81H, …

● Automatic load shedding

● I, U, P, E metering

Sepam – Motor Protection

Series 40 / Type : M41

Page 10: Sepam-Basic Presentation 240412

8/19/2019 Sepam-Basic Presentation 240412

http://slidepdf.com/reader/full/sepam-basic-presentation-240412 10/26

10

● Protection functions:● 50/51, 50N/51N,46,50BF● 49RMS and 38/49T● 27/59, 81L/81H, …

● Specific functions:● 50V/51V, voltage restraint

overcurrent● 32P, 32Q/40, directional

active and reactiveoverpower 

● I, U, P, E measurements

Sepam – Generator Protection

Series 40 / Type : G40

Page 11: Sepam-Basic Presentation 240412

8/19/2019 Sepam-Basic Presentation 240412

http://slidepdf.com/reader/full/sepam-basic-presentation-240412 11/26

11

Voltage protection functions:

27/59, phase-to-phase

under/overvoltage

81L/81H,

under/overfrequency

59N, neutral voltage

displacement

27D/47, positive sequence

undervoltage and phase

rotation direction

27R, remanent undervoltage

27S, 3 phase-to-phase

undervoltages V1,V2,V3

Sepam – Busbar Protection

Series 20 / Type : B21

Page 12: Sepam-Basic Presentation 240412

8/19/2019 Sepam-Basic Presentation 240412

http://slidepdf.com/reader/full/sepam-basic-presentation-240412 12/26

12

Voltage protectionfunctions:

27/59, 27S, 59N 81L/81H 27D/47, 27R

Loss of mains protection

81R, rate of change offrequency (ROCOF)fast, reliable detection

of loss of mainsfor substations with

generators in parallelwith the main network

Sepam – Busbar Protection

Series 20 / Type : B22

Page 13: Sepam-Basic Presentation 240412

8/19/2019 Sepam-Basic Presentation 240412

http://slidepdf.com/reader/full/sepam-basic-presentation-240412 13/26

13

Selection criteria series 20 series 40

Measurements I U U I and U I and U I et U

Specific protection Loss of mains Directional Directional

functions (ROCOF) earth fault earth fault &

phase O/C

 Applications series 20 series 40

Substation S20 S40 S41 S42

Transformer  T20 T40 T42

Motor  M20 M41

Generator  G40

Busbar  B21 B22

Sepam – Protection Relay

Selection Guide

Page 14: Sepam-Basic Presentation 240412

8/19/2019 Sepam-Basic Presentation 240412

http://slidepdf.com/reader/full/sepam-basic-presentation-240412 14/26

14

User Machine Interfaces

Logic inputs / outputs

Communication

Temperature acquisition

 Analog output

Sepam – Protection Relay

Basic Unit and Optional Module

Page 15: Sepam-Basic Presentation 240412

8/19/2019 Sepam-Basic Presentation 240412

http://slidepdf.com/reader/full/sepam-basic-presentation-240412 15/26

15

To manage your installation

locally!

The keypad and display are used to set the Sepam parameters and protection

functions and to display measurements and alarms.

The advanced UMI does not give access to the matrix (use SFT2841).

Sepam – Protection Relay

 Advanced User Machine Interface

Page 16: Sepam-Basic Presentation 240412

8/19/2019 Sepam-Basic Presentation 240412

http://slidepdf.com/reader/full/sepam-basic-presentation-240412 16/26

16

To make the most of your

Sepam !

The SFT2841 tool may be used to set parameters and protection functions and

«customize» Sepam. It provides the alarm history, disturbance records and

parameter down and uploading.

Sepam – Protection Relay

SFT2841 Configuration Software

Page 17: Sepam-Basic Presentation 240412

8/19/2019 Sepam-Basic Presentation 240412

http://slidepdf.com/reader/full/sepam-basic-presentation-240412 17/26

17

4 logic outputs as a

standard feature

a choice of 2 additional

input/output modules:

MES108: 4 logic

inputs/4 logic outputs

MES114: 10 logic

inputs/4 logic outputs

To enhance the

monitoring/control functions

Sepam – Protection Relay

MES – Additional Input/Output

Page 18: Sepam-Basic Presentation 240412

8/19/2019 Sepam-Basic Presentation 240412

http://slidepdf.com/reader/full/sepam-basic-presentation-240412 18/26

18

Modbus/Jbus protocol

Measurement readouts

TS status readouts

Logic input status readouts

TC remote control orders

Remote settingsControl of the optional MSA114 analog

output

Disturbance recording OPG readouts

Sepam – Protection Relay

Communication Functions

Page 19: Sepam-Basic Presentation 240412

8/19/2019 Sepam-Basic Presentation 240412

http://slidepdf.com/reader/full/sepam-basic-presentation-240412 19/26

19

Modbus communication

protocol

 ACE949-2: RS485 2-wirecommunication interface with

distributed supply

2 wires for the RS485

signal2 wires to supply the

 ACE949-2

 Auxiliary supply for the

 ACE949-2 provided by the ACE909-2 interface or the

 ACE919 or a 12 or 24 V DC

external power supply

Sepam – Protection Relay

Communication Interface

Page 20: Sepam-Basic Presentation 240412

8/19/2019 Sepam-Basic Presentation 240412

http://slidepdf.com/reader/full/sepam-basic-presentation-240412 20/26

20

Modbus communication

protocol

 ACE959: RS485 4-wirecommunication interface with

distributed supply

4 wires for the RS485

signal2 wires to supply the

 ACE959

 Auxiliary supply for the

 ACE959 provided by a 12 or 24V DC external power supply

Sepam – Protection Relay

Communication Interface

Page 21: Sepam-Basic Presentation 240412

8/19/2019 Sepam-Basic Presentation 240412

http://slidepdf.com/reader/full/sepam-basic-presentation-240412 21/26

21

Note : 1 module for Sepam series 20

1 to 2 modules for Sepam series 40

Measurementof 8 or 16 temperatures

By Pt100, Ni100 or Ni120temperature sensors

For better motor, generatorandtransformerprotection!

Sepam – Protection Relay

Temperature Acquisition

Page 22: Sepam-Basic Presentation 240412

8/19/2019 Sepam-Basic Presentation 240412

http://slidepdf.com/reader/full/sepam-basic-presentation-240412 22/26

22

 A choice of formats

(4-20mA, 0-10mA or

0-20mA)

For remote analog

measurements!

Sepam – Protection Relay

 Analogue Output

Page 23: Sepam-Basic Presentation 240412

8/19/2019 Sepam-Basic Presentation 240412

http://slidepdf.com/reader/full/sepam-basic-presentation-240412 23/26

23

Sepam – Protection Relay

 A Complete Solution

Page 24: Sepam-Basic Presentation 240412

8/19/2019 Sepam-Basic Presentation 240412

http://slidepdf.com/reader/full/sepam-basic-presentation-240412 24/26

24

Same cutout as Sepam 1000

Compact, reduced depth (< 100mm)

Universal power supply48 to 250 V DC and 110 to 240 V AC

and 24 V DC power supply

Universal logic inputs

24 to 250 V DC

Engraved terminal identification

Immunity to 10V/m radiated fields

Disconnectable I/O module

Prewired remote modules

Extended temperature range: -25°C to 70°C

<100mm

Sepam – Protection Relay

Easy To Install – Series 20

Page 25: Sepam-Basic Presentation 240412

8/19/2019 Sepam-Basic Presentation 240412

http://slidepdf.com/reader/full/sepam-basic-presentation-240412 25/26

25

● Base unit:

●new basic board

●3 resident voltage channels (3 internal transformers)

● the same size as Sepam 1000+ series 20

(same cutout dimensions and same depth)

●  Auxiliary power supply:

●universal: 24 V DC to 250 V DC and 100 V AC to

240 V AC

power line disturbance withstand: 20 ms

●consumption < 15W

<100mm

Sepam – Protection Relay

Easy To Install – Series 40

M k th t f