Parques Alta Diseño de placas en la dirección X Cálculo de cortante sísmico: Parámetros sísmicos; Z = 0.4 U = 1.5 C = 2.5 S = 1.2 R = 6 P = 817.49 T Vu = 245.25 T L = Vu = 10.22 m 0.53*f'c^0.5*t 0.80*L = 8.17 m Consideramos por medidas arquitectónicas: Placa 1 = 4.75 m (incluidas las columnas) Placa 2 = 3.50 m (incluidas las columnas) Total = 8.25 m Pu = 227.64 Mu = 216.95 Vu = 38.42 hm = 10.8 Lm = 4.15 F = 52.28 T As = F/fy = 12.45 cm2 8 φ 5/8" = 15.84 cm2 Acero en la placa ph min = 0.0025 As / 100t = 6.25 cm2/m espaciamiento s = L/5 = 83 cm 3*t = 75 cm As hor: 2 capas de 3/8" @25cm acero vertical: 0.0025 6.25 cm2/m As ver: 2 capas de 3/8" @25cm Vu = Vua*(Mur/Mua) = 142.04 T Vu < 2.6 t d f'c^0.5 = 312.72 T ok Vc = 0.53*t*d*f'c^0.5 = 63.75 T Vu > φVc 245.25 T Vs =Vu/φ - Vc = 103.35 T s = Avfyd/Vs = 19.16 cm 3/8 @20cm en ambos sentidos

Upload: gusacu83

Post on 23-Dec-2015

2 views

Category:

Documents


0 download

DESCRIPTION

PLANO

TRANSCRIPT

Page 1: Placas 1

Parques Alta

Diseño de placas en la dirección XCálculo de cortante sísmico:

Parámetros sísmicos;

Z = 0.4

U = 1.5

C = 2.5

S = 1.2

R = 6

P = 817.49 T

Vu = 245.25 T

L = Vu = 10.22 m

0.53*f'c^0.5*t

0.80*L = 8.17 m

Consideramos por medidas arquitectónicas:

Placa 1 = 4.75 m (incluidas las columnas)

Placa 2 = 3.50 m (incluidas las columnas)

Total = 8.25 m

Pu = 227.64

Mu = 216.95

Vu = 38.42

hm = 10.8

Lm = 4.15

F = 52.28 T

As = F/fy = 12.45 cm2

8 φ 5/8" = 15.84 cm2

Acero en la placa

ph min = 0.0025

As / 100t = 6.25 cm2/m

espaciamiento s = L/5 = 83 cm

3*t = 75 cm

As hor: 2 capas de 3/8" @25cm

acero vertical:

0.0025

6.25 cm2/m

As ver: 2 capas de 3/8" @25cm

Vu = Vua*(Mur/Mua) = 142.04 T

Vu < 2.6 t d f'c^0.5 = 312.72 T

ok

Vc = 0.53*t*d*f'c^0.5 = 63.75 T

Vu > φVc 245.25 T

Vs =Vu/φ - Vc = 103.35 T

s = Avfyd/Vs = 19.16 cm

3/8 @20cm en ambos sentidos