Monitor de Corriente Diferencial RGU-10 B RCM RGU-10 B RCM Residual Current Monitor CONSIDERACIONES INICIALES INSTALACIÓN Y PUESTA EN MARCHA ¡ IMPORTANTE ! ! DESCRIPCIÓN GENERAL Si se utiliza el equipo de forma no especificada por el fabricante, la protección puede resultar comprometida. Residual Current Monitor device Type B. Associated to external core balance transformer the WG-xx-TB and WGC-xx-TB families. It has 2 programmables outputs relays. Alarm signal and prealarm signal. It has one free voltage input for external TRIP/RESET. Mounting in DIN rail 466277 (En50022) or PANEL 72x72 by means of accesories M5ZFF1. Displays setting values and instantaneus earth leakage current value. GENERAL DESCRIPTION PRELIMINARY CONSIDERATIONS INSTALLATION AND START-UP ¡ IMPORTANT ! ! The unit´s protections systems might not be effective if the unit is used for purpose other than those specifications by the manufacturer. El equipo no debe ser utilizado hasta que haya finalizado por completo su instalación. El equipo debe conectarse a un circuito de alimentación protegido con fusibles acorde con el rango de alimentación y consumo del mismo. A su vez el circuito de alimentación tiene que estar provisto de un interruptor magnetotermico o dispositivo equivalente para desconectar el equipo de la red de alimentación. Durante el conexionado se 2 aconseja una sección cable permitida entre 1- 1.5 mm . Un par de apriete recomendado de 0,5-0,6 N.m y una longitud a desaislar cable de 7 mm. terminals and opening covers or removing elements, can give access to dangerous parts to touch. The equipment must not be used until it has completely finished installation. The unit must be connected to a power supply circuit protected by fuses in line with the range and power consumption. In turn, the supply circuit must be provided with a circuit breaker or equivalent device to disconnect the equipment from the mains. During the wiring cable is advisable a section permitted between 1 - 1.5 mm2. A recommended torque of 0.5-0.6 N.M. Cable Stripping Tools length 7 mm. Monitor de corriente diferencial tipo B. Se asocia a toroidales externos de las familias WG-xx-TB y WGC-xx-TB. Dispone de relés programables, 2 salidas. Señalización alarma y de señalización por prealarma. Posee entrada libre de tensión para disparo y rearme exterior. Montaje en Carril DIN 46277 (EN 50022) o en panel 72x72 mediante accesorio (M5ZZF1). Permite visualizar por display los valores de ajuste y de la corriente de fuga instantánea. RGU-10 B RCM 0,03-0,1-0,3-0,5-1-3 P 1 X X X X 0 0 X Código Code Código interno Internal code Tensión/alimentac Power supply 230 Vc.a./a.c. 0 Por ejemplo RGU-10 B alimentado a 110 Vc.a / For instance RGU-10 B supplied by 110 Va.c. P11961001 0,1-0,2-0,3-0,4-0,5-0,75-1-5 -10 COMPROBACIONES A LA RECEPCIÓN Para más información, puede descargarla de nuestra web, www.circutor.es - El equipo corresponde a las especificaciones de su pedido. - El equipo no ha sufrido desperfectos durante el transporte. Asegurarse del cumplimiento de: Para la utilización segura del equipo, es fundamental que las personas que lo instalen o manipulen, sigan las medidas de seguridad habituales, así como las advertencias en dicha guía rápida. PRECAUCIONES DE SEGURIDAD El RGU-10 B es un equipo diseñado específicamente para ser instalado dentro de un cuadro eléctrico o envolvente, con fijación en carril DIN o en panel mediante accesorio. Dispone de led luminoso (ON) indicando que hay presencia de tensión. Aunque este led no esté encendido, no exime al usuario de comprobar que el equipo está desconectado de toda de toda fuente de alimentación. You can download more information from CIRCUTOR website, www.circutor.es - The unit’s specifications are the same as those on your order. - Check that the device has not suffered any damage during transport. CHECKS ON RECEPTION On receving the instrument, check the following points: The staff using or handling the unit must follow the common safety measures and warnings included in the instruction manual. SAFETY PRECAUTIONS The RGU-10 B unit has been specifically designed for its installation in a electric board, enclosure to a DIN rail or mounted in panel by means of accesories. It has a flashing green led (ON) when it is operation and, therefore, it shows that there is voltage and current in the electronic circuit. The user must make sure that the equipment is not conected to the power supply at all the times, even when the LED is not flashing. The user must take into account and observe the informations and warnings included in this instruction manual to guarantee the correct operation of the equipment and comply whit the safety specifications. The equipment must not turned on until is fully installed in the electrical panel. Disconnect the equipment from the power supply when the unit´ssafety protection systems are not working or there are signs of a problem (in case of visible damage). In this case, contact a qualified technical service or with our own technical service (TAS). INSTALLING THE EQUIPMENT DIN rail installation. Through the CBT must pass all live conductors supplyng electrical energy to loads or part of the installation which requires it to earth leakage protection with this device. In single-phase installation (phase and neutral, L and N), three phase - 3 wires (three phases, L1, L2 and L3) or three phases - 4 wires (L1, L2, L3 and N). All connections Should be inside t he electrical board. Please note that with the connected equipment, Peso / Wheight : 168 gr 52,5 85 45 43,5 67,9 Fijación carril/ Fixed by rail DIN 46277 (EN 50022) cotas en mm dimensions in mm. Optoacoplada, 0.7W /230 Vac ± 20% Corriente Nominal: 10 Ac.a. Tensión Nominal: 250 Vc.a. Carga Nominal: 2500 V·A en AC1 DESCRIPCIÓN DE BORNES CARACTERÍSTICAS Corriente Nominal: 10 Ac.a. Tensión Nominal: 250 Vc.a. Carga Nominal: 2500 V·A en AC1 1 - 2 Entrada disparo externo 3 Sin uso 4 Contacto salida relé prealarma común 5 Contacto salida relé prealarma NC 6 Contacto salida relé prealarma NA 7 Sin uso 8 Entrada toroidal 1S1 9 Entrada toroidal 1S2 10 Alimentación Aux. (fase o neutro) 11 Alimentación Aux. (neutro o fase) 12 Sin uso 13 Contacto salida relé alarma NA 14 Contacto salida relé alarma NC 15 Contacto salida relé alarma COMUN BORNES DE CONEXIONADO La presente guía rápida contiene informaciones y advertencias que el usuario tiene que respetar para garantizar el funcionamiento seguro del equipo. En su funcionamiento habitual no debe ser utilizado hasta su instalación definitiva en el cuadro eléctrico. Cuando sea probable que el equipo haya perdido la protección de seguridad (presencia de daños visibles) debe desconectarse la alimentación del equipo. En este caso póngase enc contacto con el servicio técnico cualificado, o bien, con nuestro S.A.T. (Servicio Asistencia Técnica). INSTALACIÓN DEL EQUIPO La instalación en carril DIN. Por el toroidal asociado tienen que pasar todos los conductores activos que alimentan a las cargas o parte de la instalación en la que se requiera realizar la protección diferencial con este equipo. En instalación monofásica (fase y neutro, L y N), trifásica (las tres fases, L1,L2 yL3) o trifásica mas neutro (L1, L2, L3 y N). En el interior del cuadro eléctrico. A tener en cuenta, que con el equipo conectado, los bornes y la apertura de cubiertas o eliminación de elementos, puede dar acceso a partes peligrosas al tacto. M087A01-20-20A TERMINAL CONNECTIONS TERMINAL DESCRIPCIÓN FEATURES 1 - 2 External Input Trip / Reclose 3 Not used 4 Pre-alarm output relay common 5 Pre-alarm output relay, NC 6 Pre-alarm output relay common 7 Not used 8 Input C.B.T. 1S1 9 Input C.B.T. 1S2 10 Supply 230 Va.c. (Phase or Neutral) 11 Supply 230 Va.c. (Neutral or Phase) 12 Not used 13 Alarm output relay NO 14 Alarm output relay NC 15 Alarm output relay COMMON Rated current: 10 Ac.a. Rated voltage: 250 Vc.a. Rated Load: 2.500 V·A en AC1 Rated current: 10 Ac.a. Rated voltage: 250 Vc.a. Rated Load: 2.500 V·A en AC1 Optocoupled, 0.7W /230 Vac ± 20% 8 9 1 2 4 5 6 10 11 13 14 15 Reset Test P119510000R00 Retardo disparo (s) Tripping delay Sensibilidad (A) Sensivity Código code Tipo Type

Upload: others

Post on 26-Sep-2020

0 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Monitor de Corriente Diferencial RGU-10 B RCM RGU-10 B …docs.circutor.com/docs/M087A01-20.pdf- CAMBIO DE CANALES: Alarma - Prealarma - CHANGING CHANNELS: Alarm - Prealarm Monitor

Monitor de Corriente Diferencial RGU-10 B RCMRGU-10 B RCM Residual Current Monitor

CONSIDERACIONES INICIALES

INSTALACIÓN Y PUESTA EN MARCHA

¡ IMPORTANTE !

!

DESCRIPCIÓN GENERAL

Si se utiliza el equipo de forma no especificada por el fabricante, la protección puede resultar comprometida.

Residual Current Monitor device Type B. Associated to external core balance transformer the WG-xx-TB and WGC-xx-TB families. It has 2 programmables outputs relays. Alarm signal and prealarm signal. It has one free voltage input for external TRIP/RESET. Mounting in DIN rail 466277 (En50022) or PANEL 72x72 by means of accesories M5ZFF1. Displays setting values and instantaneus earth leakage current value.

GENERAL DESCRIPTION

PRELIMINARY CONSIDERATIONS

INSTALLATION AND START-UP

¡ IMPORTANT !

! The unit´s protections systems might not be effective if the unit is used for purpose other than those specifications by the manufacturer.

El equipo no debe ser utilizado hasta que haya finalizado por completo su instalación. El equipo debe conectarse a un circuito de alimentación protegido con fusibles acorde con el rango de alimentación y consumo del mismo. A su vez el circuito de alimentación tiene que estar provisto de un interruptor magnetotermico o dispositivo equivalente para desconectar el equipo de la red de alimentación. Durante el conexionado se

2aconseja una sección cable permitida entre 1- 1.5 mm . Un par de apriete recomendado de 0,5-0,6 N.m y una longitud a desaislar cable de 7 mm.

terminals and opening covers or removing elements, can give access to dangerous parts to touch. The equipment must not be used until it has completely finished installation. The unit must be connected to a power supply circuit protected by fuses in line with the range and power consumption. In turn, the supply circuit must be provided with a circuit breaker or equivalent device to disconnect the equipment from the mains. During the wiring cable is advisable a section permitted between 1 - 1.5 mm2. A recommended torque of 0.5-0.6 N.M. Cable Stripping Tools length 7 mm.

Monitor de corriente diferencial tipo B. Se asocia a toroidales externos de las familias WG-xx-TB y WGC-xx-TB. Dispone de relés programables, 2 salidas. Señalización alarma y de señalización por prealarma. Posee entrada libre de tensión para disparo y rearme exterior. Montaje en Carril DIN 46277 (EN 50022) o en panel 72x72 mediante accesorio (M5ZZF1). Permite visualizar por display los valores de ajuste y de la corriente de fuga instantánea.

RGU-10 B RCM 0,03-0,1-0,3-0,5-1-3

P 1 X X X X 0 0 XCódigoCode

Código interno Internal code

Tensión/alimentacPower supply

230 Vc.a./a.c. 0

Por ejemplo RGU-10 B alimentado a 110 Vc.a / For instance RGU-10 B supplied by 110 Va.c. P11961001

0,1-0,2-0,3-0,4-0,5-0,75-1-5 -10

Retardo disparo (s) Tripping delay

Sensibilidad (A) Sensivity

Código code

COMPROBACIONES A LA RECEPCIÓN

Para más información, puede descargarla de nuestra web, www.circutor.es

- El equipo corresponde a las especificaciones de su pedido. - El equipo no ha sufrido desperfectos durante el transporte.

Asegurarse del cumplimiento de:

Para la utilización segura del equipo, es fundamental que las personas que lo instalen o manipulen, sigan las medidas de seguridad habituales, así como las advertencias en dicha guía rápida.

PRECAUCIONES DE SEGURIDAD

El RGU-10 B es un equipo diseñado específicamente para ser instalado dentro de un cuadro eléctrico o envolvente, con fijación en carril DIN o en panel mediante accesorio. Dispone de led luminoso (ON) indicando que hay presencia de tensión. Aunque este led no esté encendido, no exime al usuario de comprobar que el equipo está desconectado de toda de toda fuente de alimentación.

You can download more information from CIRCUTOR website, www.circutor.es

- The unit’s specifications are the same as those on your order. - Check that the device has not suffered any damage during transport.

CHECKS ON RECEPTIONOn receving the instrument, check the following points:

The staff using or handling the unit must follow the common safety measures and warnings included in the instruction manual.

SAFETY PRECAUTIONS

The RGU-10 B unit has been specifically designed for its installation in a electric board, enclosure to a DIN rail or mounted in panel by means of accesories. It has a flashing green led (ON) when it is operation and, therefore, it shows that there is voltage and current in the electronic circuit. The user must make sure that the equipment is not conected to the power supply at all the times, even when the LED is not flashing.

The user must take into account and observe the informations and warnings included in this instruction manual to guarantee the correct operation of the equipment and comply whit the safety specifications. The equipment must not turned on until is fully installed in the electrical panel.

Disconnect the equipment from the power supply when the unit´ssafety protection systems are not working or there are signs of a problem (in case of visible damage). In this case, contact a qualified technical service or with our own technical service (TAS).

INSTALLING THE EQUIPMENT

DIN rail installation. Through the CBT must pass all live conductors supplyng electrical energy to loads or part of the installation which requires it to earth leakage protection with this device. In single-phase installation (phase and neutral, L and N), three phase - 3 wires (three phases, L1, L2 and L3) or three phases - 4 wires (L1, L2, L3 and N). All connections Should be inside t he electrical board. Please note that with the connected equipment,

Peso / Wheight : 168 gr

52,5

85

45

43,567,9

Fijación carril/ Fixed by rail DIN 46277 (EN 50022)

cotas en mmdimensions in mm.

Optoacoplada, 0.7W /230 Vac ± 20%

Corriente Nominal: 10 Ac.a.Tensión Nominal: 250 Vc.a. Carga Nominal: 2500 V·A en AC1

DESCRIPCIÓN DE BORNES CARACTERÍSTICAS

Corriente Nominal: 10 Ac.a.Tensión Nominal: 250 Vc.a. Carga Nominal: 2500 V·A en AC1

1 - 2 Entrada disparo externo 3 Sin uso 4 Contacto salida relé prealarma común 5 Contacto salida relé prealarma NC 6 Contacto salida relé prealarma NA 7 Sin uso 8 Entrada toroidal 1S1 9 Entrada toroidal 1S2 10 Alimentación Aux. (fase o neutro)

11 Alimentación Aux. (neutro o fase)

12 Sin uso 13 Contacto salida relé alarma NA 14 Contacto salida relé alarma NC 15 Contacto salida relé alarma COMUN

BORNES DE CONEXIONADO

La presente guía rápida contiene informaciones y advertencias que el usuario tiene que respetar para garantizar el funcionamiento seguro del equipo. En su funcionamiento habitual no debe ser utilizado hasta su instalación definitiva en el cuadro eléctrico.

Cuando sea probable que el equipo haya perdido la protección de seguridad (presencia de daños visibles) debe desconectarse la alimentación del equipo. En este caso póngase enc contacto con el servicio técnico cualificado, o bien, con nuestro S.A.T. (Servicio Asistencia Técnica).

INSTALACIÓN DEL EQUIPO

La instalación en carril DIN. Por el toroidal asociado tienen que pasar todos los conductores activos que alimentan a las cargas o parte de la instalación en la que se requiera realizar la protección diferencial con este equipo. En instalación monofásica (fase y neutro, L y N), trifásica (las tres fases, L1,L2 yL3) o trifásica mas neutro (L1, L2, L3 y N). En el interior del cuadro eléctrico. A tener en cuenta, que con el equipo conectado, los bornes y la apertura de cubiertas o eliminación de elementos, puede dar acceso a partes peligrosas al tacto.

M087A01-20-20A

TERMINAL CONNECTIONS

TERMINAL DESCRIPCIÓN FEATURES

1 - 2 External Input Trip / Reclose 3 Not used 4 Pre-alarm output relay common 5 Pre-alarm output relay, NC 6 Pre-alarm output relay common 7 Not used 8 Input C.B.T. 1S1 9 Input C.B.T. 1S2 10 Supply 230 Va.c. (Phase or Neutral) 11 Supply 230 Va.c. (Neutral or Phase) 12 Not used 13 Alarm output relay NO 14 Alarm output relay NC 15 Alarm output relay COMMON

Rated current: 10 Ac.a.

Rated voltage: 250 Vc.a. Rated Load: 2.500 V·A en AC1

Rated current: 10 Ac.a.

Rated voltage: 250 Vc.a. Rated Load: 2.500 V·A en AC1

Optocoupled, 0.7W /230 Vac ± 20%

8 91 2 4 5 6

10 11 13 14 15

Reset

Test

TipoType

P119510000R00

Retardo disparo (s) Tripping delay

Sensibilidad (A) Sensivity

Código code

TipoType

Page 2: Monitor de Corriente Diferencial RGU-10 B RCM RGU-10 B …docs.circutor.com/docs/M087A01-20.pdf- CAMBIO DE CANALES: Alarma - Prealarma - CHANGING CHANNELS: Alarm - Prealarm Monitor

DESCRIPCIÓN DE LOS LED Y PULSADORES.

- Indicación del estado del equipo mediante display y 2 LED.- Ajuste y programación del equipo mediante 5 pulsadores.- Operaciones de TEST y RESET del equipo mediante 2 pulsadores.

- POR ALARMA. Para volver al estado inicial del equipo se tiene que realizar un RESET manual o una señal de rearme externa.

- POR PREALARMA. Para anular este estado se tiene que realizar un RESET manual si está configurado en modo no automático.

- PULSADOR RESET / RESET BUTTON

- PULSADOR TEST / TEST BUTTON

Otros MENSAJES por display

SAVEEXITOVRERRt Mala conexión con el toroidal

Valida valores de configuración.Sale fuera modo programación.Lectura del valor fuera de escala.

Causa del disparo Mensaje display

TestSeñal remota ON/OFFCorriente de fuga

TEStEXTTRIP

DESCRIPTION LED AND BUTTONS

- BY ALARM. A manual RESET, or remote ON is required to return to the equipment's initial status. - BY PREALARM. A manual RESET has to be performed if it is in non-automatic mode to cancel this status.

MAIN RELAY PARAMETER SETTING ( t , I and std/+ )d d

PROG

Other display MESSAGES

SAVEEXITOVRERRt

Enters setting valuesExits setting modeCurrent leakage reading off scalePoor toroidal connection

Cause of trip Message display

TestRemote signal ON/OFFCurrent leakage

TEStEXTTRIP

- AJUSTE RETARDO / DELAY SETTING

- AJUSTE SENSIBILIDAD / SENSITIVITY SETTING

- AJUSTE SEGURIDAD / SAFETY SETTING

- -AJUSTE RESET PREALARMA / RESET PREALARM SETTINGAUTO

- LED VERDE: Equipo encendido / GREEN LED: Equipment on- LED ROJO: Alarma por fuga / RED LED: Leakage alarm

- LED AMARILLO: Prealarma / YELLOW LED: Prealarm Id

- CAMBIO DE CANALES: Alarma - Prealarma - CHANGING CHANNELS: Alarm - Prealarm

Monitor de corriente diferencial electrónico RGU-10 B RCMRGU-10 B RCM Residual Current Monitor

B

INDICACIONES POR LED Y DISPLAY. INDICATION BY LED AND DISPLAY

RECONEXIÓN DEL EQUIPO. RECLOSING THE EQUIPMENT

AJUSTES PARÁMETROS RELÉ PRINCIPAL ( t , I y std/+ ) .d d MAIN RELAY PARAMETER SETTING ( t , I and std/+ )d d

- SETTING ALARM DELAY The message and two values appear on the , t . d

screen after pressing the button. The lowest value indicates the current set value td

and the highest is the values to be configured which are displayed by pressing The ..selected value to be saved is displayed by showing the message SAVE.

- , I . dSENSITIVITY SETTING The same operation as above setting is carried out by pressing I . d

- , std/+. SAFETY SETTING The required safety type through changing the alarm contact polarity is selected by pressing this button. (Std) Standard nothing appears on the display and (+) Positive, the symbol appears .

AJUSTES PARÁMETROS RELÉ PREALARMA ( t , I , std/+ y Auto)d d PREALARM RELAY PARAMETER SETTING ( t , I , std/+ and Auto)d d

PROG

- AJUSTE DEL RETARDO DE ALARMA, t . Al pulsar la tecla t aparece en pantalla eld d

mensaje y dos valores. El más pequeño indica el valor actual configurado y en el más grande los valores a configurar que debemos ir visualizando pulsando . Visualizado el valor escogido se espera a que el equipo valide el valor como configurado mostrando el mensaje de SAVE.

- AJUSTE DE LA SENSIBILIDAD, I . Al pulsar la tecla I realizamos la operación con eld d

mismo modus operandi que el anterior ajuste.

+

- AJUSTE DE SEGURIDAD, std/+ . Al pulsar esta tecla seleccionamos el tipo de seguridad que queremos variando la polaridad de los contactos de alarma. (Std) Standard, no aparece nada en el display. (+) Positiva, aparece el símbolo . +

Para entrar en el canal de prealarma se realiza una pulsación corta en PROG,activando el mensaje de Alarm en el display.

A short press on PROG enters the prealarm channel activating the Alarm message on the display.

- AJUSTE DEL RETARDO, t seleccionamos el retardo de tiempo en dar la señal ded

prealarma. - DELAY SETTING . Select the time delay for giving the prealarm signal, t . d

- , I . SdSENSITIVITY SETTING elect the equipment's prealarm threshold. Selected sensitivity stated as % in the main channel (OFF-50-60-70-80-MAIN).

- , std/+. SPOLARITY SETTING elect the prealarm output signal polarity.

REC- , Auto. ASETTING OF RESET OF PREALARM ctivating , the equipment automatically resets the prealarm when the leakage current drops below the preset alarm threshold.

- AJUSTE DE LA SENSIBILIDAD, I seleccionamos el umbral de prealarma del equipo. d

Referidos en % a la sensibilidad escogida en el canal principal ( OFF-50-60-70-80-MAIN).

- AJUSTE DE POLARIDAD, std/+ . Seleccionamos la polaridad de la salida de señalización de la prealarma.

REC- AJUSTE DE RESET DE PREALARMA, Auto. Al activar el equipo realiza un reset de la prealarma de forma automática cuando la corriente de fuga vuelva a estar por debajo del umbral de prealarma programado.

M087A01-20-20A

Shows equipment status via a display and 2 LED's.- 5 button equipment setup and setting.

- 2 button equipment TEST and RESET.

- . ALARM SIGNAL LED and display signals achange of status by changing from green to red. Display event type messages or values.

- . PREALARM SIGNAL. The yellow LED only comes on when current leakage exceeds the preset prealarm threshold.

- SEÑALIZACIÓN ALARMA. Señaliza por un cambio de estado de color verde a rojo, tanto del LED como del display. Se visualizan los mensajes o valores concernientes al tipo evento que lo produce.

- SEÑALIZACIÓN PREALARMA.Cuando la corriente de fuga supera el umbral de prealarma programado solo se enciende el LED amarillo.

0.2s 30mA

0 mA

Page 3: Monitor de Corriente Diferencial RGU-10 B RCM RGU-10 B …docs.circutor.com/docs/M087A01-20.pdf- CAMBIO DE CANALES: Alarma - Prealarma - CHANGING CHANNELS: Alarm - Prealarm Monitor

Monitor de corriente diferencial electrónico RGU-10 B RCMRGU-10 B RCM Residual Current Monitor

CARACTERÍSTICAS TÉCNICAS. TECHNICAL FEATURES

- Tipo de relé: Electrónico, clase B- Tipo de reconexión: Manual, mediante pulsador de RESET o corte de alimentación.- Tensión de alimentación nominal: 230 (± 20%) 50/60 Hz, 6 V·A- Temperatura de trabajo: -10ºC / +50ºC- Humedad (sin condensación) : 5% .... 95%- IP Protección Equipo montado (frontal) : IP 41 Equipo sin montar (laterales y tapa posterior : IP 20- Altitud máxima funcionamiento : 2000 m.

- Conexionado:2 Sección cable permitida: 0,127 - 2,082 mm

Par de apriete recomendado: 0,5-0,6 N.m Longitud de cable a desaislar: 7 mm Destornilladores recomendado: Varilla: 0,4 x 2,5 x 80 mm, longitud 160 mm

Tipo A / Type A

Tipo B / Type B

CORRIENTE / CURRENT

Tipo AC (senoidal) / Type AC (sine)Onda senoidal rectificada / Sine half wave

Onda senoidal rectificada controlada por fase / Sine half wave phase controlled (90º-135º)

Onda senoidal a1000Hz / Sine current at 1000HzOnda senoidal a 400Hz / Sine current at 400HzOnda senoidal a 150Hz / Sine current at 150Hz

Corriente DC / Smooth DC current

Límite inferior / Lower limit

0,8xldn0,8xldn

1xldn0,8xldn0,8xldn0,8xldn1,2xldn

Límite superior / Upper limit

1xldn1,4xldn

1,3xldn1xldn1xldn

1,7xldn1,4xldn

- Tipo Relay type: Electronic class B- Reclosing type: Manual via RESET button or by cutting power supply.- Rated power supply voltage: 230 (± 20%) 50/60 Hz, 6 VA- : -10ºC / +50ºCOperating temperature- Humidity (without condensation) : 5% .... 95%- IP Protection Assembled equipment (front) : IP 41 Non assembled equipment (sides and rear cove) : IP 20- Maximum operating height : 2000 m.

- :Connections2 0,127 - 2,082 mmPermissible cable section:

Recommended tightening torque: 0.5-0.6 Nm Length of cable to strip: 7 mm Recommended screwdrivers length : Bar 0.4 x 2.5 x 80 mm, 160 mm

- Características contactos conmutados de salida 13-14-15 y 4-5-6: Corriente Nominal/Máxima corriente instantánea: 10 / 15 A c.a. Tensión Nominal / tensión conmutación 250 / 400 V c.a. Carga Nominal en AC1: 2 500 V·A

- 13-14-15 and 4-5-6Switch Output contact features : 10 / 15 A a.c.Rated current/Maximum instant current : 250 / 400 V a.c.Rated voltage/Maximum switching voltage AC1: 2,500 V·ARated load in

NL1 L2 L3

1S

11S

2

Typ

e W

G

1S

11S

2

ON

/ O

FF

ext

ern

oE

xte

rna

l ON

/OF

F

Disparo por BOBINA DE MÍNIMA- Rearme manual.

Trip by UNDERVOLTAGE COIL.- Manual reclose.

Reset

Test

CARGA

LOAD

1 2 4 5 6 8 9

10 11 13 14 15

ESQUEMAS DE CONEXIÓN / WIRING DIAGRAM

RG

U -

10 C

NL1 L2 L3

CARGA

1S

11S

2

LOAD

Typ

e W

G

1S

11

S2

ON

/ O

FF

ext

ern

oE

xtern

al O

N/O

FF

Disparo por BOBINA DE EMISIÓN- Rearme manual.

Trip by SHUNT COIL.- Manual reclose.

8 91 2 4 5 6

10 11 13 14 15

Reset

Test

MENU SETUP / SETUP MENU

Márgenes de disparo según tipo de fuga medida / Tripping range according to leakage current measured

M087A01-20-20A

Servicio de Asistencia Técnica (S.A.T.)

En caso de cualquier duda de funcionamiento o averia del equipo avisar al servicio de asistencia tecnicaTel: 902 449 459 (España)Tel: (+34) 93 745 29 00 (Fuera de España)Fax: (+34) 93 742 29 14email: [email protected]

Vial Sant Jordi s/n08232 Viladecavalls (Bacelona) SPAIN

Technical Assistance Service (T.A.S)

If you have any doubts about the running of the equipment or any faults, contact the service staff.

Tel: (+34) 93 745 29 00Fax: (+34) 93 745 29 14email: [email protected]

Vial Sant Jordi s/n08232 Viladecavalls (Bacelona) SPAIN

NORMATIVA STANDARD

Meet with standard IEC62020 and Trip conditions for Type B waveforms specified in IEC60755.

Cumple con la Normativa IEC62020 y con las condiciones de disparo para formas de onda Tipo B especificadas en la Norma IEC60755.

NL1 L2 L3

CARGA

S1

S2

LOAD

Typ

e W

GC

S1

S2

ON

/ O

FF

ext

ern

oE

xte

rna

l ON

/OF

F

Aux. Supply230 V a.c.

8 91 2 4 5 6

10 11 13 14 15

Reset

TestB

30 mA

Sensibilidad / Sensivity

WGC-80 TB, WGC-110 TB, WGC-140 TB, WGC-180 TB

Tipo de transformador según sensibilidad IDn/ Type transformer according sensivity IDn

300 mA

500 mA

WGC-55 TB,

WGS-20 TB, WGC-25 TB, WGC-35 TB

Transformador / Transformer