     VERSION HISTORY

    TDMS PROGRAM

  • 8/19/2019 Manual ISA

    2/49

    DOC. RMP10167 Rev. 6.4.5 2

    VERSION 6.4.5 ............................................................................................................................ 4 

    VERSION 6.4.4 ............................................................................................................................ 5 

    VERSION 6.4.3 ............................................................................................................................ 6 

    VERSION 6.4.2 ............................................................................................................................ 7 

    VERSION 6.4.1 ............................................................................................................................ 8 

    VERSION 6.4.0 ............................................................................................................................ 9 

    VERSION 6.3.8 .......................................................................................................................... 10 

    VERSION 6.3.7 .......................................................................................................................... 11 

    VERSION 6.3.6 .......................................................................................................................... 12 

    VERSION 6.0.1 .......................................................................................................................... 13 

    VERSION 6.0.0 .......................................................................................................................... 14 

    VERSION 5.3.0 .......................................................................................................................... 16 

    VERSION 5.2.9 .......................................................................................................................... 17 

    VERSION 5.2.8 .......................................................................................................................... 18 

    VERSION 5.2.7 .......................................................................................................................... 19 

    VERSION 5.2.6 .......................................................................................................................... 20 

    VERSION 5.2.5 .......................................................................................................................... 21 

    VERSION 5.2.4 .......................................................................................................................... 22 

    VERSION 5.2.3 .......................................................................................................................... 23 

    VERSION 5.2.2 .......................................................................................................................... 24 

    VERSION 5.2.1 .......................................................................................................................... 25 

    VERSION 5.2.0 .......................................................................................................................... 26 

    VERSION 5.1.10 ........................................................................................................................ 28 

    VERSION 5.1.9 .......................................................................................................................... 29 

    VERSION 5.1.8 .......................................................................................................................... 30 

    VERSION 5.1.7 .......................................................................................................................... 31 

    VERSION 5.1.6 .......................................................................................................................... 32 

    VERSION 5.1.5 .......................................................................................................................... 33 

    VERSION 5.1.4 .......................................................................................................................... 34 

    VERSION 5.1.3 .......................................................................................................................... 35 

    VERSION 5.1.2 .......................................................................................................................... 36 

    VERSION 5.1.1 .......................................................................................................................... 37 

    VERSION 5.1.0 .......................................................................................................................... 38 

    VERSION 5.0.9 .......................................................................................................................... 39 

    VERSION 5.0.8 (RTS.3) ............................................................................................................ 40 

  • 8/19/2019 Manual ISA

    3/49

    DOC. RMP10167 Rev. 6.4.5 3

    VERSION 5.0.8 .......................................................................................................................... 41 

    VERSION 5.0.7 .......................................................................................................................... 42 

    VERSION 5.0.6 .......................................................................................................................... 43 

    VERSION 5.0.5 .......................................................................................................................... 44 

    VERSION 5.0.4 .......................................................................................................................... 45 

    VERSION 5.0.3 .......................................................................................................................... 46 

    VERSION 5.0.2 .......................................................................................................................... 47 

    VERSION 5.0.1 .......................................................................................................................... 48 

    VERSION 5.0.0 .......................................................................................................................... 49 

  • 8/19/2019 Manual ISA

    4/49

    DOC. RMP10167 Rev. 6.4.5 4

     Version 6.4.5Release date: 04/06/2012

    Comtrade Added a new menù voice under the file menu: Import from Excel.Now the user can import data reading the samples from an Excelspreadsheet.

    Diff-87 Now it is possible to test differential relais with alpha plane restraint.Now it is possible to insert a delay (setting a value in μs) before thestarting of the first cycle of a test in order to synchronize twoinstruments

    Manual Control,Sequencer,Distance 21

     Added a new voice menù on the executed test rows: Waveform Viewer. Now it is possible to plot a test cycles diagram showing thecurrents, the voltages, the auxiliary and the main contacts.

    Manual Control,Sequencer,Distance 21

    DRTS 66 instrument family only: now the user can define to tracethe contacts status during the evolution of the test. Using theWaveform Viewer program it is possible to plot the downloadedsamples

  • 8/19/2019 Manual ISA

    5/49

    DOC. RMP10167 Rev. 6.4.5 5

     Version 6.4.4Release date: 02/03/2012

    Diff-87 Now it is possible to test two synchronized relais using the sameinstrument

  • 8/19/2019 Manual ISA

    6/49

    DOC. RMP10167 Rev. 6.4.5 6

     Version 6.4.3Release date: 02/02/2012

     Advanced RelayTest Plan Editor New Release: the advanced editor of test programs has a high andpowerful number of instructions and operations; particularly,macrocommands, loop instructions, tests and graphics.It is possible to write complicated programs, for example those forthe test of distance relays. The user can also define somesubroutines to create macrocommands which involve a series ofoperations: a certain number of subroutines is available with thesoftware; for example, the subroutine which executes the researchof a threshold value and the relative reset value with the gradientmethod. Please refer to the on line help file for detailed descriptionof the program.

    UTB32 Upgrade for the DRTS 66 firmware release 1.16: maximum powergeneration for 110 V supply voltage. IRIG B signal management.Zero power option. New management of auxiliary contacts A5-A8.

    CBA New implementations (refer to the on-line help for detailedinstructions):1- New functionality: sequence. Now the user can create a singletest plan in order to store an unique result file that contains morethan one test (open, close, open/close, ...)2- A new compact, that contains only one result per page, reportlayout has been added to TDMS suite (the user can set this as

    default report clicking on Options -> Preferences -> Reports ->Breakers)3- Now the measure list can be grouped per phase (Options ->Environment)4- Added ten custom, the serial number and the number ofoperations for each phase fields that can be used to specify customparameters in the test header of the breaker parameters5- Result windows: now the user can deeply customize all the graph,changing the size of the graphs, overlapping more graphs (currentsand/or voltage transducers graphs), changing the color and saving

    layout templates in order to apply them laterENERGY METER  Added a new button “Switch Vdc on”. Line DifferentialComtrade

     Added IRIG B signal management

    Syn 25 Added two new configurations that can be used to test the relay:1. V1, V2 V3, V42. V1, V2, V3 V4, V5, V6 (DRTS66 only)

    Dir 67 Now it is possible to insert the 5051 characteristic of the relayDiff 87 Added a new test for line differential relais (test two protections

    using the same instrument).

     Added IRIG B signal synchronization (DRTS 66 instrument familyonly)

    Distance 21 Intertrip test: added IRIG B signal management

  • 8/19/2019 Manual ISA

    7/49

    DOC. RMP10167 Rev. 6.4.5 7

     Version 6.4.2Release date: 18/11/2011

    UTB32 Download COMTRADE file on USB channel: solved an issue on thedownloading of long comtrade files Added description of error number 1218 (error while downloadinguser file)

    ENERGY METER first release for the updated version 1.15 of DRTS 66added same standard files

    COMTRADE the screen width and height has been optimized for Windows 7operating systema new check for wrong or missing file has been added

    Manual Control &Sequencer

    Transcope module: when there is a fault on the test set the dataacquisition is automatically stoppedNow it is possibile to manage in the formula editor all the resultstable field in order to create more complex formula

    Distance 21 Improved testing of Power Swing. Added definition of power swingcharacteristic in Z_design

    Transcope Updated to version 1.15 of firmware

  • 8/19/2019 Manual ISA

    8/49

    DOC. RMP10167 Rev. 6.4.5 8

     Version 6.4.1Release date: 30/08/2011

     All modules The communication link (both USB and Ethernet) has been improved

  • 8/19/2019 Manual ISA

    9/49

    DOC. RMP10167 Rev. 6.4.5 9

     Version 6.4.0Release date: 02/08/2011

    Overcurrent 5051 Load current: now the user can inject a prefault currentNew test type: added zero sequence (LLL) test Added two curves: IEC generic formula and IEC/ANSI genericformula

    Differential 87 Now the program shows currents both on primary side values. Theuser can optionally choose to print primary side values (only for shotand trip time tests)

    Manual Control Now the program can manage the new boosters AMI 332 and AMI632New test added: if the user selects Delta ramp test type, now it ispossible to make a delta gradient test (in order to test frequencyrelays and voltage relays)Goose Publishing: IEC 61850-8 standard. Now the user can sendover the network imported gooses (captured during an exploringsession or imported from an SCL file). Up to 16 gooses can bepublished simultaneously. The gooses can be published repeatedlyor during the execution of the test.

     AND/OR masks (only for DRTS 34, DRTS 64, DRTS 66): now theuser can alternatively program a boolean condition, in the inputcontacts window, in order to stop the test (both for value injectionand for ramp test type)

    Distance 21 The Z-Design window has been improved: added the general starterand the load encroachment functionsWeak ground faultThe Transcope Module now can be opened from this programGoose Publishing: IEC 61850-8 standard. Now the user can sendover the network imported gooses (captured during an exploringsession or imported from an SCL file). Up to 16 gooses can bepublished simultaneously. The gooses can be published repeatedlyor during the execution of the test.

    Sequencer AND/OR masks (only for DRTS 34, DRTS 64, DRTS 66): now the

    user can alternatively program a boolean condition, in the inputcontacts window, in order to stop the test (both for value injectionand for ramp test type)

    Distance RelayLibrary

     Added P443 - P445 libraries

    Upgrade DRTS 66 Now it is possible to upgrade the firmware of the power supply unit

  • 8/19/2019 Manual ISA

    10/49

    DOC. RMP10167 Rev. 6.4.5 10

     Version 6.3.8Release date: 24/05/2011

    Manual Control Solved the following bug: during a ramp test the amplitude value ofthe currents was wrongly setSequencer Solved the following bug: the value of the frequency of the currents

    was wrongly set as that of the phase angleDistance 21 Solved a bug concerning “Switch-on-to-fault” test type 

  • 8/19/2019 Manual ISA

    11/49

    DOC. RMP10167 Rev. 6.4.5 11

     Version 6.3.7Release date: 10/05/2011

     All modules Upgrade for 64 bits processor.Manual Control New trip time measurements for voltage and frequency rate ofchange relays. When the user selects “Delta Ramp” test type now itis possible to set rate of change (amplitude, phase or frequency)parameters in order to find the ROC threshold value for voltage andfrequency relays.

  • 8/19/2019 Manual ISA

    12/49

    DOC. RMP10167 Rev. 6.4.5 12

     Version 6.3.6Release date: 11/04/2011

     All modules Fully support of the new instruments DRTS 34, DRTS 64, DRTS 66.Transcope First releaseCOMTRADE Support of Turkish language

    Impedance Locus: now the program manages up to 20 zonesNew vector form: when the user moves the mouse over the plot ofthe graphs, a vector representation of amplitudes and angles isshown

    XPRO3000 Updates for TD1000 instrument;Solved a bug of T 1000 instrument: when mixed voltage andcurrents now are correctly managedSolved a bug of current clamp ratio (only for T 2000 and T 3000firmware versions above 1.32)

    DIFF-87 Release of a new functionality: differential library

  • 8/19/2019 Manual ISA

    13/49

    DOC. RMP10167 Rev. 6.4.5 13

     Version 6.0.1Release date: 22/07/2010

    CBA Added new measure (Debounce, Wipe, Overtravel and BreakerSpeed) for the second operation in the following tests: CO, OC, OCO.XPRO3000 The software manages the new version 1.28 of the T 1000 test set

    (multiple test with the same header informations). 5051 table: addedcurves MMCO

  • 8/19/2019 Manual ISA

    14/49

    DOC. RMP10167 Rev. 6.4.5 14

     Version 6.0.0Release date: 09/12/2009

    TDMS New skin, more intuitive and user-friendly, releasedManual Control The new version of the program has been released; the program isfully compatible with the previous version of the Manual Control.New features:

    -  interface simpler and user-friendy: it is now possible to showand hide the panels with the tests and the results table, andthe graph panel; it possible to resize each panel to improvereadability. The user can now visualize in the same screen thefault parameters, the graphs and the results table

    -  the program now makes a distinction between tests andresults: it is now possible to save separately the tests or thetests plus the results generated. A single set of tests cangenerate more than one results set than can be comparedwith a previously created one (by using Test Identification it ispossible to distinguish the generated tests with differentcolors). The user can repeat the tests overwriting the existingresults or creating a new Test ID to compare the new resultsobtained

    -  the program can now create, open and managesimultaneuosly more than one file

    -  the amplitude, rate of change, phase of all currents and

    voltage values are grouped together to simplify the definitionof the test. The user can use the mouse wheel in order toincrease/decrease set values. In the Power Panel the user canset and modify the value of active and reactive power,keeping constant the value of voltage.

    -   “Set and start”: if the user clicks the “START” button theprogram transfers to the instrument the set values and startsimmediately the generation of these values.

    -  in the Formula Editor the user can set a conditional formula inorder to define if the test is “PASSED” or “FAILED”  

    it is possible to define personalized fields and formulas inorder to print and export them into TDMS program.

    -  the column layout of tests and results table can be fullypersonalized

    -  the “Measurements” window can be keep opened and can beused to calculate the Active, Reactive and Apparent Powerand the Positive, Inverse, Omopolar components.

    -  the “Vectors” window can be keep opened and can be used todrag the vectors of currents and voltages toincrease/decrease amplitude and phase. Pressing the CTRL

    key more than one vector can be moved at the same timeDifferential 87 Added Diff Library menù voice: if clicked the program opens a listwith the special differential relay characteristic that can be modified

  • 8/19/2019 Manual ISA

    15/49

    DOC. RMP10167 Rev. 6.4.5 15

    and loaded in the programCBA Fixed the bug (only for CBA1000) regarding static Resistance (results

    not saved) and dynamic Resistance (if the travel transducers wasenabled). Fixed a bug in the save of testplans on Windows 2000operating system

     All Modules Added turkish language option

  • 8/19/2019 Manual ISA

    16/49

    DOC. RMP10167 Rev. 6.4.5 16

     Version 5.3.0Release date: 06/08/2009

    BTS Improved the communication between PC and instrument (increasedthe delay time in order to read bigger results)Manual Control Improved the read process of SCL files (IEC 61850)

    Now the program manage the instrument DRTS 3 PLUSDifferential 87 Fixed various problems related to the search of the IR-Id

    characteristic (SEL387, PROTECTA and other); improvements: fromthe theory given by Protecta, the software has evolved todifferentiate the transformation matrices, Y-side, or D-side; now it ispossible to make a selection of the monitored contact; added a list ofrelays menu to simplify the selection of parameters of the protectionrelay

    Distance 21 Improved the read process of SCL files (IEC 61850)In the automatic time zone test modify Zmin in Zstart and Zmax inZend so that the user can set a negative step between Zstart toZend (when Zstart > Zend)

    CBA Fixed the bug (for CBA 1000 firmware 2.13 or above) regardingThreshold voltage in the MTC test

    Energy Meter Fixed the bug (for DRTS 6 firmware 7.13 or above) regarding thepulse counter

    RELAYS CT-VT-PT  Added button "Select All", “Invert Selection”, ... in the form"Show/Hide columns"

     Added a checkbox in the Preferences in order to filter values of theCT excitation curveNow the program can be run with a monitor resolution of 800x600Now the program read from the result frame of the connectedinstrument the value of the voltage between Aux and the earth

     Added russian translation Added a control during the download of the result: now the programcheck the "200" code during the download of the result

    Libraries 7SA522: now the user can optionally consider the Inominal currentto draw the characteristic

  • 8/19/2019 Manual ISA

    17/49

    DOC. RMP10167 Rev. 6.4.5 17

     Version 5.2.9Release date: 25/02/2009

    Distance 21 Improved the “Verify blinders” test for border line zones; fixed a bugwith the “Verify R/X characteristic” released with version 5.2.8 Libraries REL670: fixed a graphical issue concerning the fourth zone with

    particular paramentersREL511: now, when the user select REL531 option the checkbox andthe label indicates that the relay selected is REL531 (the parametersare the same as REL521)

  • 8/19/2019 Manual ISA

    18/49

    DOC. RMP10167 Rev. 6.4.5 18

     Version 5.2.8Release date: 20/02/2009

    CBA The program has been updated to manage version 2.17 ofCBA1000's firmware: added the option "Full Wave" for analog input(the program manages both negative and positive values ofvoltage); the program reads second open times and flow times inthe case of Open-Close-Open test type; added "Slow Motion"measures.Now all measurements are listed in the same order as firmware(both CBA1000 and CBA2000).Graphical improvement: the trigger rappresents the start of timer;events that come before it are negative time values; events thatfollow it are with positive time values.Graphical improvement: when the user zoom an area, the programactivates an horizontal scrollbar, so that you can watch all sampleslike a film.

     Added menù voice ”Save All Files...”: by choosing this option theprogram saves all opened files (both Test Plan type and Resultstype) in the folder selected by the user.

    BTS Fixed this issues:-  if the software disconnects from the test set (usually when

    the user moves the knob inside menus), now it able to re-connect without having to unplug the cable

    the values of discharge watt setted on the test set is correctlyread by the software (multiplied by a factor of 100)

    -  inserted a delay useful to improve the reading of the resultslist (the start and end session date were wrong)

    Distance 21 Improved the “Verify the R / X characteristic” and the “Verif yblinders” tests 

  • 8/19/2019 Manual ISA

    19/49

    DOC. RMP10167 Rev. 6.4.5 19

     Version 5.2.7Release date: 11/02/2009

    CBA Fixed the bug: the program was unable to open connection with atest set serialized with “2008/20602”  code. The program now is ableto connect to instrument that have the serial number containing thestring “602” (that is the same code used by the firmware tocommunicate its parameters)

  • 8/19/2019 Manual ISA

    20/49

    DOC. RMP10167 Rev. 6.4.5 20

     Version 5.2.6Release date: 04/02/2009

    Manual Control &Sequencer Now these programs can manage the booster AMV66 (if the pilotingDRTS 6 has the 300 V option, these programs assume that also V5and V6 of the booster can reach this voltage value)

    Distance 21 Fixed these bugs: if the user modifies the value of the angle thecharacteristic diagram disappear; the default language is not storedand reloaded when the program starts; run-time error (division byzero) when the radius in the “arc” function was zero valued. Now in in initialization file the program saves also the values of Tpre,Tmax and Thold

    CBA Fixed these bugs: error when the result list was empty or the resultfile had a wrong result date; the serial number stored on the test setwas not stored by the program.Now if the result has been created with the BSG option, digitalresistance channels are graphically showed with an half levelbetween the close and the open positions.Now when opening a result or a test plan file, the user can make amultiple selection of files.

     Added a new menù voice "Save All Files...": when the user select thisoption the program automatically saves all opened files. Updated forthe release 2.17 of the firmware program: the program has beencorrected to navigate correctly to the calibration page of the travel

    transducers

  • 8/19/2019 Manual ISA

    21/49

    DOC. RMP10167 Rev. 6.4.5 21

     Version 5.2.5Release date: 09/01/2009

    TDMS Added some german translations;Fixed this bug: the menù voice of program “Differential 87” is nowenabled with different international settings

  • 8/19/2019 Manual ISA

    22/49

    DOC. RMP10167 Rev. 6.4.5 22

     Version 5.2.4Release date: 05/12/2008

    TDMS Added the new menu for turkish language translationCBA Added the new menu for turkish language translation

  • 8/19/2019 Manual ISA

    23/49

    DOC. RMP10167 Rev. 6.4.5 23

     Version 5.2.3Release date: 05/12/2008

    TDMS Fixed a bug concerning the importation process of CBA testplan andresults file (Error: ADODB.Recordset; arguments incorrect, out ofrange or in conflict).

     Added the import/export functionality of the test plan in the testeditor program

    X-Pro3000 Fixed the following bug: with french settings in international settingsthe download of results from the T3000 test set crashed when adecimal value was set in the settings panel (Error n.13 Typemismatch)

  • 8/19/2019 Manual ISA

    24/49

    DOC. RMP10167 Rev. 6.4.5 24

     Version 5.2.2Release date: 03/12/2008

    BTS Updated for the first release of the firmwareCBAPro Added these two functionality:1) now the user can superimpose automatically coil currents graphsor transducers graphs (only for single result set and not for repeatedresults or comparing result); for transducers graphs the user canalso increase or decrease the height dimension2) Now the program automatically stores in a BLOB field the binarydata received from the test set when reading a result file. This datacan be saved in a separated binary file, enabling the propertyExtractBinaryFile (setting it to the value “1” ) in the CBA1000.ini fileand selecting the menù item “Extract Binary File” from the Resultmenù

    X-Pro3000 Fixed the following bug: when connected to T3000 test set thedownload process blocked without any warning

  • 8/19/2019 Manual ISA

    25/49

    DOC. RMP10167 Rev. 6.4.5 25

     Version 5.2.1Release date: 24/11/2008

    X-Pro3000 Fixed a problem with the downloading of results from the test set: “’Enabled’ Property can’t be set on this control”  

  • 8/19/2019 Manual ISA

    26/49

    DOC. RMP10167 Rev. 6.4.5 26

     Version 5.2.0Release date: 21/11/2008

    TDMS Now the user can import result from Line Differential, PLSynchromodule.The program has been updated for:

    1)  the implementation for Z-pro (“Stress Test” and “Power LineSynchro Test”) and X-pro (“Power Line Synchro Test”) 

    2)  the new table “Digitaltravtrans” that stores informationregarding digital travel transducers of the CBA 2000 test set

    Line Differential,PLSynchro

     Added Save in TDMS functionality; now the print function is made onthe same print report as that of TDMS

    Swing-pro In ComputeStatic0Stp routine the value of Zmin is setted to 0.0001when Zmin equals zero

    Z-pro  Added “Stress Test” and “Power Line Synchro Test”: the first testallows to define a “grid” of tests in order to verify if the protectionruns properly in the rectangle between the bounds Rmin and Rmax,and from Xmin to Xmax; the test “Power Line Synchro Test” is validonly for DRTS6, and generates faults synchronized to the mainssupply. The test will be executed with a simple click of the mouse onthe graph, as “Click and test”. Now when you press “F1” function key or click on the menù voice “?”the program loads the help file in “pdf” format. Fixed the bug of the refresh of the rows in the grids of the program.

    X-pro  Added “Power Line Synchro Test”: this test is valid only for DRTS 6,and generates faults synchronized to the mains supply. The test willbe executed by opening the preferences form from the Optionsmenù voice; if this selection is enabled, only the Shot test will beavailable.Now when you press “F1” function key or click on the menù voice “?”the program loads the help file in “pdf” format. Fixed the bug of the refresh of the rows in the grids of the program.

    Syn-25, Dir-67,Diff-87, Oc-5051

    Now when you press “F1” function key or click on the menù voice “?”the program loads the help file in “pdf” format. 

    Fixed the bug of the refresh of the rows in the grids of the program.Sequencer Recompiled to maintain compatibility with the file “Report xpro.rpt”  

    where the new parameter “lbltypePlSync”  has been addedCBAPro Added digital travel transducers management; these inputs are

    available only on the instrument CBA 2000 with the digitaltransducers board installed. In the “Analog Channels” panel of theTest Plan, now it is possible to choose digital travel transduceroption as addition input channels (the firmware version of the testset must be 1.14 or above); the user can set the nominal breakerstroke, the number of impulses per turn of the digital transducer and

    the corresponding stroke (that can be different phase per phase); asin the case of analog travel transducer, it is possible to enable datumpoints and to calibrate the test set. When the user download the

  • 8/19/2019 Manual ISA

    27/49

    DOC. RMP10167 Rev. 6.4.5 27

    results from the test set or from USB drive, the digital traveltransducers waveform are showed as usual.Now the program can download and store header information (PlantName, Feeder, Breaker Model, Breaker Serial Number, Operator,Manufacturer) from the test set (for CBA1000 the firmware version

    must be at least 2.16, for CBA2000 the firmware version must be atleast 1.14).Import from third parties format function: now the program use onlyone byte (instead of two) to interpretate the value of the digitalchannels

  • 8/19/2019 Manual ISA

    28/49

    DOC. RMP10167 Rev. 6.4.5 28

     Version 5.1.10Release date: 06/11/2008

    Sequencer Fixed this bug: when a sequence with more than ten cycles is savedand reloaded, cycles after the tenth were wrongly inserted after thefirst cycle

    CBA Added the images of help explanation (Recording Options andDatum Points) for spanish and deutch languages. Implementationfor firmware release 2.15 of CBA 1000 test set: now the programcan manage the command with code 416 that enables the softwareto download the header informations written on the test set (thiscommand is executed evety time the user downloads testplans fromthe test set)

     Added the menù voice “Notes” that enables to link text notes to theTest Plan or the Results file

  • 8/19/2019 Manual ISA

    29/49

    DOC. RMP10167 Rev. 6.4.5 29

     Version 5.1.9Release date: 31/10/2008

    CBA Updated for release of firmware version 2.14 (CBA 1000 only): nowthe program can read, store and print the session date; with thenew firmware command (code 248) header informations (Plantname, Feeder, Manufacturer, Breaker Model, Breaker Serial Number,Operator) can be uploaded on the test set.

     Added two new menù voice in the Result menù: Extract Test Planand Save Test Plan; with the first option the program opens the TestPlan that generated the result file in a new window so that the usercan repeat the test or save it in TDMS; with the second option theprogram saves the test plan in a separated file on the local disk.

    Now the user can sort, ordering for name or date field, the Test Planand the Results list read from the connected test set.

  • 8/19/2019 Manual ISA

    30/49

    DOC. RMP10167 Rev. 6.4.5 30

     Version 5.1.8Release date: 21/10/2008

    Xpro3000,Upgrade, Set-comm

    Now these programs manage T1000 PLUS test set with USB port

  • 8/19/2019 Manual ISA

    31/49

    DOC. RMP10167 Rev. 6.4.5 31

     Version 5.1.7Release date: 13/10/2008

    CBA Fixed the bug with the program crashing when a Test Plan wasopened by TDMS program

  • 8/19/2019 Manual ISA

    32/49

    DOC. RMP10167 Rev. 6.4.5 32

     Version 5.1.6Release date: 09/10/2008

    Comm-Port Added two new tabs for settings connection property (USB or COMport): one for T1000, T2000 and T3000 family and one for CircuitBreakers Analyzer (CBA1000 and CBA2000)

    CBA The program is able to communicate with firmware version 1.12:MTC, Pressure Transducers, Travel Transducers (calibrationfunctionality and different values for actual stroke), Full Wave in

     Analog Channels, Static and Dynamic Resistance Test

    Datum Points are now plotted on each transition in multipletransition tests (Open-Close, Close-Open and Open-Close-Open).Now you can define if the Datum Point is referred to Close Position(default), Open Position or at Transition

    Improvement of the communication between the PC and the test set(USB port only)

    Graphic plots: cursors T1 and T2 can be moved only over samplepoints. The zoom function is now implemented with three buttons.The first button initializes the zoom functionality; when pressed theuser can zoom a graphic area pressing the left button of the mouseand then holding the mouse over the graphic area (like in Comtrade

    program); the second button zooms the graphic area inside the twocursors T1 and T2; the third button restores the graphic bounds.

     A Test Plan created for CBA1000 instrument can be downloaded alsoon CBA2000 test set

    Now the currently opened Test Plan can be directly uploaded on thetest set

  • 8/19/2019 Manual ISA

    33/49

    DOC. RMP10167 Rev. 6.4.5 33

     Version 5.1.5Release date: 19/09/2008

    Manual,Sequencer,Distance 21

    Fixed a bug with the parser of the GOOSE packet: the length in TLVwas misinterpreted when greater than 255

  • 8/19/2019 Manual ISA

    34/49

    DOC. RMP10167 Rev. 6.4.5 34

     Version 5.1.4Release date: 02/09/2008

    CBA Fixed this bug: opening time of C1, ..., C6 phases was wronglyinitialize to the same value of B1, ..., B6 phasesThe "Two Recordings" check in Test Option panel is now hidden forCBA2000 test planThe menù voice "Save in TDMS" is enabled only when a test plan ora result file is openedThe minimum value of nominal breaker stroke can now be setted to1 mm (the previous minimum value was 20 mm)

  • 8/19/2019 Manual ISA

    35/49

    DOC. RMP10167 Rev. 6.4.5 35

     Version 5.1.3Release date: 08/08/2008

    Manual Fixed a bug with delta frequency tests: negative gradient was notrecorded in result gridCBA Fixed a bug with the datum points plot of travel transducers phase B

    and phase C, that were wrongly the same of the travel transducerphase A.Changes: the Test Plan saved locally on PC is now automaticallylinked to the result downloaded from the test set, when the name ofthe test plan file (saved in C:\xtest\CBA\Testplans folder) is thesame of that memorized on the test set

  • 8/19/2019 Manual ISA

    36/49

    DOC. RMP10167 Rev. 6.4.5 36

     Version 5.1.2Release date: 23/07/2008

    Distance 21 Added "Multiple Contacts Test"; if you select this kind of test, youcan register trip times of different contacts of the connected test set,regardless of fault.Operative steps:1) Define or load the characterist of the protection relay2) Select "Multiple Contacts Test" in the Advanced Function Panel3) Click on the icon near the label of the contact name to enable oneor more contacts, changing its default status (from not operative tonormally open or normally close).4) Click on the graph (like in "Click and Test" option). The test willend when all enabled contacts trip.5) Under the column named " T[s] " the program will report all thetrip times of the enabled contacts (if the trip time of a contact isgreater than Tmax the program writes "No Trip")

    CBA Fixed this bug: when the user download the result file from the testset, then when closing the program and clicking "Cancel" button atthe question "Save results?" the application wrongly closes.

     Added auxiliary channels close and open time calculation. Added the definition of the Datum Point A reference position: atClose Position (default), at Open Position and at Transition (TestPlan and Result file)

  • 8/19/2019 Manual ISA

    37/49

    DOC. RMP10167 Rev. 6.4.5 37

     Version 5.1.1Release date: 14/07/2008

    CBA

  • 8/19/2019 Manual ISA

    38/49

    DOC. RMP10167 Rev. 6.4.5 38

     Version 5.1.0Release date: 26/06/2008

    Distance 21 Now the program can manage up to 20 zones (the previousmaximum value was 8 zones)BTS Program released.

    This program provides connectivity to BTS200 instruments. Thesoftware performs various tasks, such as:

    1.  Create, save, open and print Testplans for the test set2.  Upload created Testplans to the test set3.  Download Results from the test set4.  Save, open and print downloaded results5.  Display channels (Voltage, Current and Ah) waveform

  • 8/19/2019 Manual ISA

    39/49

    DOC. RMP10167 Rev. 6.4.5 39

     Version 5.0.9Release date: 22/05/2008

    TDMSManual, 5051, syn-25, dir-67, diff-87Xpro3000CBA

  • 8/19/2019 Manual ISA

    40/49

    DOC. RMP10167 Rev. 6.4.5 40

     Version 5.0.8 (RTS.3)Release date: 22/04/2008

    X_pro/5051/utb32.dll Improvement for managing RTS.3 test set

  • 8/19/2019 Manual ISA

    41/49

    DOC. RMP10167 Rev. 6.4.5 41

     Version 5.0.8Release date: 09/04/2008

     All Libraries Added integration in TDMS functionality: now the user can link alibrary to a relay defined in the network tree. Right-clicking the nodethe user can recall library program, print settings

    Utb For voltages above 120V added a fixed correction of -0.1 degree(voltages/currents)

  • 8/19/2019 Manual ISA

    42/49

    DOC. RMP10167 Rev. 6.4.5 42

     Version 5.0.7Release date: 09/04/2008

    Sequencer/TDMS Integration of saving from Sequencer to TDMS, printing andexecuting test from TDMS

  • 8/19/2019 Manual ISA

    43/49

    DOC. RMP10167 Rev. 6.4.5 43

     Version 5.0.6Release date: 02/04/2008

    Sequencer Program released.This tool is a sequence editor that allows to build and run asequence defined by consecutive cycles or steps. It is useful tosearch trip and reset thresholds, trip and reset times, control tripcontacts and auxiliary contacts, display the waveform created by thecycles definition… When uploaded to the instrument, all the cycles of the definedsequence will be executed step by step.Each cycle is defined by the output values of currents and voltages,the state of auxiliary contacts, by a condition for the timing start anda condition for the timing stop of the cycle itself.The user can define the condition of transition from one cycle to thenext one: this may take place after a fixed timeout time, a trigger(trip or reset) condition of the main contacts of the connectedinstrument or by pressing a button by the user himself.In every cycle the user defines if the output condition is a “ValueInjection”, a “Ramp” or if the instrument must hold values of theprevious cycle.For each cycle of value injection type the user defines amplitude,phase, frequency values of currents and voltages.For each cycle of ramp type the user defines initial value and rate of

    change values for amplitude, phase and frequency of currents andvoltages.The waveform viewer displays graphically the time signals ofvoltages, currents, auxiliary contacts and main contacts and is usefulto study the reaction of the protection relay.

  • 8/19/2019 Manual ISA

    44/49

    DOC. RMP10167 Rev. 6.4.5 44

     Version 5.0.5Release date: 14/03/2008

    TDMS Now the program manages two different reports for the CBA results:the standard one and the compact one. A new page is added to thePreferences window to allow to decide which of the available reportsbecomes the default for each report type. The list of reports isdefined in an external .ini file named Reports.ini

    CBA Now the program can connect to the new CBA2000 instrument. Thesoftware automatically recognizes if the instrument connected is aCBA1000 or CBA2000. Communication USB driver is the same.Before creating a new testplan, the user must choose if the testplanwill be uploaded to a CBA1000 or a CBA2000 instrument.The testplan editor allows now to manage up to twelve auxiliaryinputs (four for CBA1000) and up to three breakers and pressure ortravel transducers (only one for CBA1000).The number of analogic channels is two (one for CBA1000).

     Analogic channels, travel or pressure transducers can be enabledsimultaneously.Results management (download and/or delete) is transparent to theconnected instrument. The results and waveform viewer formsupports the major number of analog and digital channels.

     Added a new menu voice: import from Pen Drive. The userdownloads results from the instrument into a USB pen drive. If the

    user presses this menu voice, the program opens a window thatshows a grid containing files loaded in the USB pen drive source.These files can be loaded in the results and waveform viewerwindow.

    Upgrade Now the program manages epg files that can be downloaded onCBA2000 instrument

    Energy Now the program allows the connect in parallel the currents ofDRTS.6 instrument

  • 8/19/2019 Manual ISA

    45/49

    DOC. RMP10167 Rev. 6.4.5 45

     Version 5.0.4Release Date: 14/03/2008

    TDMSManual5051Dir 67Diff 87Syn 25Distance 21

    These programs can now load customized reports. Each programloads the following printing modules (built with Crystal Reportseditor):Manual -> Report xproman.rpt5051 -> Report 5051.rptDir 67 -> Report 67.rptDiff 87 -> Report 87.rptSyn 25 -> Report 25.rptDistance 21 -> Report Zpro.rptThe programs first of all search these files into

     “C:\xtest\TDMS\Reports\Custom”  folder. If the file is missed fromthis folder, the program loads standard module installed in

     “C:\xtest\TDMS\Reports\ ”  folder.

  • 8/19/2019 Manual ISA

    46/49

    DOC. RMP10167 Rev. 6.4.5 46

     Version 5.0.3Release Date: 14/03/2008

    General notes USB drivers for DRTS family instruments and CBA family instrumentsare now preinstalled by the setup program. The operating system(Windows 2000, XP or Vista32bit only) will install them automaticallyat the first connection of the instrument into a USB port

  • 8/19/2019 Manual ISA

    47/49

    DOC. RMP10167 Rev. 6.4.5 47

     Version 5.0.2Release Date: 22/10/07

    Manual +Distance 21 Now the user can set boolean condition on virtual contacts defined inthe read goose.In the “Exploring Goose” window, a new menu voice has been added(Open substation file). By selecting this menu the user can importfiles written with stadard SCL language (with extension SCD and/orICD).Data loaded from these files are shown in a third tab, so that theuser can compare them with acquired goose packets.

  • 8/19/2019 Manual ISA

    48/49

    DOC. RMP10167 Rev. 6.4.5 48

     Version 5.0.1Release Date: 03/10/2007

    Manual +Distance 21 By means of a dedicated module, DRTS.6 instruments can expandtheir testing capabilities by handling IEC61850 messages. One suchmessage coming from a device connected to the substation network(such a relay) is also called Goose.When the user presses the “IEC 61850” button, the software opensthe “Goose Explorer” form. In this mask the user can activate Gooseexploration of the IEC61850 messages on the network; the softwarewill interpretate the goose packet read by the instrument. MACsource address, MAC destination address, Goose univoque identifier,Dataset univoque identifier associated to Goose and timestamp (dateand hour) of sending goose packet will be shown in a grid. When theuser selects goose describing row, the program will show in an othergrid the goose’s details. Captured data can be saved in a databasefile in Access format, that stores the result of a session of exploringof the IEC61850 network.

    Comtrade Now program loads data even when the number of analogic ordigital channels doesn’t match with that of the file header

    Relays CT-VT-PT Now during diagram’s axis definition the user can’t set a negativevalue as minimum value

  • 8/19/2019 Manual ISA

    49/49

    DOC. RMP10167 Rev. 6.4.5 49

     Version 5.0.0Release Date: 12/09/2007

    General Notes Setup program, communication drivers for USB port with instrumentsof DRTS family and CBA family, all programs have been adapted tobe fully compatible with Windows Vista (32 bit only) operatingsystem

    TDMS Testplans for Multifunction Relay: now the user can create and run aTestPlan, which is a list of macro functions to be run on the samedevice. Each function is associated with a program (Manual, Distance21, etc…). When the user runs the testplan, TDMS handles thesoftware execution for all the steps and the results are automaticallysaved in TDMS

    CBA  Added “Test repetitions” option for “Open-Close” and “Close-Open”test option types. The user can set the number of tests and the timeinterval between every test. The program will repeat the setted testfor the number of times

    Manual5051Dir 67Diff 87Syn 25Distance 21

    The print preview is done on the same reports (Crystal Reportsformat) loaded also by the TDMS software. This report previewallows to export into PDF, Excel or Word formats.

     Added in the menu File a new voice that allows the saving of resultsdirectly into TDMS: by clicking on this menu item a form opens toshow the Network tree defined into the TDMS Software. It ispossible to select the device where data is to be saved.

    In the show/hide columns form added “Select All” button Distance 21 In the print preview added graphs of SHOT and SOTF test typesDir 67 Added verify test of Vo-Io characteristic, added pass-fail criteria for

     Vo-Io and angular sector