electrico-tsj-morelos.xls

4
TABLERO "A" ALIMENTADO DE: MURETE DE ACOMETIDA ALIMENTADOR: 4-#2, 1-#8t PRINCIPAL: 3 x 100 AMP FASE A = 5808 % DES. MAXIMO = 0.02 SERVICIO A: ALUMBRADO , CONTACTOS Y A/A DISTANCIA: 25MTS. MONTAJE: PARED FASE B = 5760 MARCA / CAT. : SQUAR D NQOD24-4AB11 CANALIZACION: 41 mm VOLTS: 220/127 FASE C = 5880 FECHA: SEPTIEMBREDE 2009 CAIDA DE TENSION: .68% FASES: 3 F, 1 N TOTAL = 17448 CIRCUITO LUM LUM BOMBA CONT AIRE AIRE AIRE AIRE AIRE VA FACTOR CORR ACTOR AGRUP FACTOR FD AMPS. VOLTS F H L (MTS) COND. CAL. S mm CAP. DEL COND. DE TUBO (MM) CAIDA DE FASES TIPO DE 42W 13W 220W 180W 800W 1800W 2400W 1200W 3600W TEMP DEMANDA VA I nom I corr COND (AMPS) TIERRA TENSION A B C INT. C1 2 8 1 408 0.88 0.8 1 408 3.57 5.07 127 1 2 30.00 12 3.307 25 12 16 1.02 408 QO R 0.88 0.8 1 0 0.00 0.00 C3,5 1 2400 0.88 0.8 1 2400 12.12 17.22 220 2 2 30.00 10 5.26 35 10 21 1.26 1200 1200 QO C4,6 1 1200 0.88 0.8 1 1200 6.06 8.61 220 2 2 30.00 10 5.26 35 10 21 0.63 600 600 QO C7,9 1 2400 0.88 0.8 1 2400 12.12 17.22 220 2 2 30.00 10 5.26 35 10 21 1.26 1200 1200 QO C8,10 1 2400 0.88 0.8 1 2400 12.12 17.22 220 2 2 30.00 10 5.26 35 10 21 1.26 1200 1200 QO C11,13 1 3600 0.88 0.8 1 3600 18.18 25.83 220 2 2 30.00 8 8.37 50 10 21 1.18 1800 1800 QO C12,14 1 1200 0.88 0.8 1 1200 6.06 8.61 220 2 2 30.00 10 5.26 35 10 21 0.63 600 600 QO C15,17 1 2400 0.88 0.8 1 2400 12.12 17.22 220 2 2 30.00 10 5.26 35 10 21 1.26 1200 1200 QO C21 2 360 0.88 0.8 1 360 3.15 4.47 127 1 2 30.00 12 3.307 25 12 16 0.90 360 QO C23 6 1080 0.88 0.8 1 1080 9.45 13.42 127 1 2 30.00 12 3.307 25 12 16 2.70 1080 QO TOTAL 2 8 1 8 0 0 4 2 1 17448 17448 50.94 5808 5760 5880 TAB. 3F-4H 220/127 V.C.A. 24 CTOS 10,000 A.C.I. INT . PRINC 3X100 AMPS TOTAL WATTS 17448 TABLERO "B" ALIMENTADO DE: MURETE DE ACOMETIDA ALIMENTADOR: 4-#2, 1-#8t PRINCIPAL: 3 x 100 AMP FASE A = 7608 % DES. MAXIMO = 2.04 SERVICIO A: ALUMBRADO, CONTACTOS Y AIRES DISTANCIA: 30 MTS. MONTAJE: PARED FASE B = 7440 MARCA / CAT. : SQUAR D NQOD24-4AB11 CANALIZACION: 41 mm VOLTS: 220/127 FASE C = 7588 FECHA: SEPTIEMBRE DE 2009 CAIDA DE TENSION: 1.07% FASES: 3 F, 1 N TOTAL = 22636 UBICACIÓN CIRCUITO LUM LUM BOMBA CONT AIRE AIRE AIRE AIRE AIRE VA FACTOR CORR ACTOR AGRUP FACTOR FD AMPS. VOLTS F H L (MTS) COND. CAL. S mm CAP. DEL COND. DE TUBO (MM) CAIDA DE FASES TIPO DE 42W 13W 220W 280W 180W 1800W 2400W 1200W 3600W TEMP DEMANDA VA I nom I corr COND (AMPS) TIERRA TENSION A B C INT. C1R C2 24 1008 0.88 0.8 1 1008 5.09 7.23 127 1 2 30.00 12 3.307 25 10 16 1.45 1008 QO C3 8 1440 0.88 0.8 1 1440 7.27 10.33 127 1 2 30.00 12 3.307 25 10 16 2.08 1440 QO C4 8 1440 0.88 0.8 1 1440 7.27 10.33 127 1 2 30.00 12 3.307 25 10 16 2.08 1440 QO C5 7 1260 0.88 0.8 1 1260 6.36 9.04 127 1 2 30.00 12 3.307 25 10 16 1.82 1260 QO C6 3 540 0.88 0.8 1 540 2.73 3.87 127 1 2 30.00 12 3.307 25 10 16 0.78 540 QO C7 1 5 1180 0.88 0.8 1 1180 5.96 8.47 127 1 2 30.00 12 3.307 25 10 16 1.70 1180 QO C8,10 1 1200 0.88 0.8 1 1200 6.06 8.61 220 2 2 30.00 10 5.26 35 10 21 0.63 600 600 QO C9,11 1 3600 0.88 0.8 1 3600 18.18 25.83 220 2 2 30.00 10 5.26 35 10 21 1.89 1800 1800 QO C12,14 1 3600 0.88 0.8 1 3600 18.18 25.83 220 2 2 30.00 10 5.26 35 10 21 1.89 1800 1800 QO C13,15 1 1800 0.88 0.8 1 1800 9.09 12.91 220 2 2 30.00 10 5.26 35 10 21 0.94 900 900 QO C16,18 1 1800 0.88 0.8 1 1800 9.09 12.91 220 2 2 30.00 10 5.26 35 10 21 0.94 900 900 QO C17,19 1 2400 0.88 0.8 1 2400 12.12 17.22 220 2 2 30.00 10 5.26 35 10 21 1.26 1200 1200 QO C20 24 1008 0.88 0.8 1 1008 5.09 7.23 127 1 2 30.00 12 3.307 25 10 16 1.45 1008 QO C21 2 360 0.88 0.8 1 360 1.82 2.58 127 1 2 30.00 12 3.307 25 10 16 0.52 360 QO TOTAL 48 0 0 1 33 0 0 4 2 22636 22636 66.08 7608 7440 7588 TAB. 3F-4H 220/127 V.C.A. 24 CTOS 10,000 A.C.I. INT . PRINC 3X100AMPS TOTAL WATTS 22636

Upload: giovanni-cambranis-munoz

Post on 05-Dec-2015

219 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: ELECTRICO-TSJ-MORELOS.xls

TABLERO "A"ALIMENTADO DE: MURETE DE ACOMETIDA ALIMENTADOR: 4-#2, 1-#8t PRINCIPAL: 3 x 100 AMP FASE A = 5808 % DES. MAXIMO = 0.02

SERVICIO A: ALUMBRADO , CONTACTOS Y A/A DISTANCIA: 25MTS. MONTAJE: PARED FASE B = 5760

MARCA / CAT. : SQUAR D NQOD24-4AB11 CANALIZACION: 41 mm VOLTS: 220/127 FASE C = 5880FECHA: SEPTIEMBREDE 2009 CAIDA DE TENSION: .68% FASES: 3 F, 1 N TOTAL = 17448

CIRCUITO LUM LUM BOMBA CONT AIRE AIRE AIRE AIRE AIRE VA FACTOR CORR FACTOR AGRUP FACTOR FD AMPS. VOLTS F H L (MTS) COND. CAL S mm CAP. DEL COND. DE TUBO (MM) CAIDA DE FASES TIPO DEPROTEC. TERMOMAG.

42W 13W 220W 180W 800W 1800W 2400W 1200W 3600W TEMP DEMANDA VA I nom I corr COND (AMPS) TIERRA TENSION A B C INT. POLOS AMPS.C1 2 8 1 408 0.88 0.8 1 408 3.57 5.07 127 1 2 30.00 12 3.307 25 12 16 1.02 408 QO 1 10R 0.88 0.8 1 0 0.00 0.00

C3,5 1 2400 0.88 0.8 1 2400 12.12 17.22 220 2 2 30.00 10 5.26 35 10 21 1.26 1200 1200 QO 2 20C4,6 1 1200 0.88 0.8 1 1200 6.06 8.61 220 2 2 30.00 10 5.26 35 10 21 0.63 600 600 QO 2 20C7,9 1 2400 0.88 0.8 1 2400 12.12 17.22 220 2 2 30.00 10 5.26 35 10 21 1.26 1200 1200 QO 2 20

C8,10 1 2400 0.88 0.8 1 2400 12.12 17.22 220 2 2 30.00 10 5.26 35 10 21 1.26 1200 1200 QO 1 20C11,13 1 3600 0.88 0.8 1 3600 18.18 25.83 220 2 2 30.00 8 8.37 50 10 21 1.18 1800 1800 QO 1 30C12,14 1 1200 0.88 0.8 1 1200 6.06 8.61 220 2 2 30.00 10 5.26 35 10 21 0.63 600 600 QO 2 20C15,17 1 2400 0.88 0.8 1 2400 12.12 17.22 220 2 2 30.00 10 5.26 35 10 21 1.26 1200 1200 QO 2 20

C21 2 360 0.88 0.8 1 360 3.15 4.47 127 1 2 30.00 12 3.307 25 12 16 0.90 360 QO 1 10C23 6 1080 0.88 0.8 1 1080 9.45 13.42 127 1 2 30.00 12 3.307 25 12 16 2.70 1080 QO 1 15

TOTAL 2 8 1 8 0 0 4 2 1 17448 17448 50.94 5808 5760 5880TAB. 3F-4H 220/127 V.C.A. 24 CTOS 10,000 A.C.I. INT . PRINC 3X100 AMPS TOTAL WATTS 17448

TABLERO "B"ALIMENTADO DE: MURETE DE ACOMETIDA ALIMENTADOR: 4-#2, 1-#8t PRINCIPAL: 3 x 100 AMP FASE A = 7608 % DES. MAXIMO = 2.04

SERVICIO A: ALUMBRADO, CONTACTOS Y AIRES DISTANCIA: 30 MTS. MONTAJE: PARED FASE B = 7440

MARCA / CAT. : SQUAR D NQOD24-4AB11 CANALIZACION: 41 mm VOLTS: 220/127 FASE C = 7588FECHA: SEPTIEMBRE DE 2009 CAIDA DE TENSION: 1.07% FASES: 3 F, 1 N TOTAL = 22636

UBICACIÓN CIRCUITO LUM LUM BOMBA CONT AIRE AIRE AIRE AIRE AIRE VA FACTOR CORR FACTOR AGRUP FACTOR FD AMPS. VOLTS F H L (MTS) COND. CAL S mm CAP. DEL COND. DE TUBO (MM) CAIDA DE FASES TIPO DE PROTEC. TERMOMAG.

42W 13W 220W 280W 180W 1800W 2400W 1200W 3600W TEMP DEMANDA VA I nom I corr COND (AMPS) TIERRA TENSION A B C INT. POLOS AMPS.C1RC2 24 1008 0.88 0.8 1 1008 5.09 7.23 127 1 2 30.00 12 3.307 25 10 16 1.45 1008 QO 1 15C3 8 1440 0.88 0.8 1 1440 7.27 10.33 127 1 2 30.00 12 3.307 25 10 16 2.08 1440 QO 1 15C4 8 1440 0.88 0.8 1 1440 7.27 10.33 127 1 2 30.00 12 3.307 25 10 16 2.08 1440 QO 1 15C5 7 1260 0.88 0.8 1 1260 6.36 9.04 127 1 2 30.00 12 3.307 25 10 16 1.82 1260 QO 1 15C6 3 540 0.88 0.8 1 540 2.73 3.87 127 1 2 30.00 12 3.307 25 10 16 0.78 540 QO 1 10C7 1 5 1180 0.88 0.8 1 1180 5.96 8.47 127 1 2 30.00 12 3.307 25 10 16 1.70 1180 QO 1 10

C8,10 1 1200 0.88 0.8 1 1200 6.06 8.61 220 2 2 30.00 10 5.26 35 10 21 0.63 600 600 QO 2 20C9,11 1 3600 0.88 0.8 1 3600 18.18 25.83 220 2 2 30.00 10 5.26 35 10 21 1.89 1800 1800 QO 2 30

C12,14 1 3600 0.88 0.8 1 3600 18.18 25.83 220 2 2 30.00 10 5.26 35 10 21 1.89 1800 1800 QO 2 30C13,15 1 1800 0.88 0.8 1 1800 9.09 12.91 220 2 2 30.00 10 5.26 35 10 21 0.94 900 900 QO 2 20C16,18 1 1800 0.88 0.8 1 1800 9.09 12.91 220 2 2 30.00 10 5.26 35 10 21 0.94 900 900 QO 2 20C17,19 1 2400 0.88 0.8 1 2400 12.12 17.22 220 2 2 30.00 10 5.26 35 10 21 1.26 1200 1200 QO 2 20

C20 24 1008 0.88 0.8 1 1008 5.09 7.23 127 1 2 30.00 12 3.307 25 10 16 1.45 1008 QO 1 10C21 2 360 0.88 0.8 1 360 1.82 2.58 127 1 2 30.00 12 3.307 25 10 16 0.52 360 QO 1 10

TOTAL 48 0 0 1 33 0 0 4 2 22636 22636 66.08 7608 7440 7588TAB. 3F-4H 220/127 V.C.A. 24 CTOS 10,000 A.C.I. INT . PRINC 3X100AMPS TOTAL WATTS 22636

Page 2: ELECTRICO-TSJ-MORELOS.xls

TABLERO "C"ALIMENTADO DE: TGZ ALIMENTADOR: 4-#2, 1-#8t PRINCIPAL: 3 x 70 AMP FASE A = 5880 % DES. MAXIMO = 0.02

SERVICIO A: ALUMBRADO, CONTACTOS Y AIRES DISTANCIA: 45 MTS. MONTAJE: PARED FASE B = 6060

MARCA / CAT. : SQUAR D NQOD24-4AB11 CANALIZACION: 41 mm VOLTS: 220/127 FASE C = 5916FECHA: SEPTIEMBRE DE 2009 CAIDA DE TENSION: 1.32% FASES: 3 F, 1 N TOTAL = 17856

CIRCUITO LUM LUM BOMBA CONT AIRE AIRE AIRE AIRE AIRE VA FACTOR CORR FACTOR AGRUP FACTOR FD AMPS. VOLTS F H L (MTS) COND. CAL S mm CAP. DEL COND. DE TUBO (MM) CAIDA DE FASES TIPO DEPROTEC. TERMOMAG.

42W 13W 220W 180W 800W 1800W 2400W 1200W 3600W TEMP DEMANDA VA I nom I corr COND (AMPS) TIERRA TENSION A B C INT. POLOS AMPS.R 0.88 0.8 1 0 0.00 0.00

C2 6 1080 0.88 0.8 1 1080 5.45 7.75 127 1 2 23.00 12 3.307 25 12 16 1.19 1080 QO 1 10C3 7 1260 0.88 0.8 1 1260 6.36 9.04 220 2 2 23.00 12 3.307 25 12 16 0.80 1260 QO 1 15

C4,6 1 1200 0.88 0.8 1 1200 6.06 8.61 220 2 2 23.00 10 5.26 35 10 21 0.48 600 600 QO 2 15C5,7 1 3600 0.88 0.8 1 3600 18.18 25.83 220 2 2 23.00 10 5.26 35 10 21 1.45 1800 1800 QO 2 30

C8,10 1 2400 0.88 0.8 1 2400 12.12 17.22 220 2 2 23.00 10 5.26 35 10 21 0.96 1200 1200 QO 2 20C9,11 1 1200 0.88 0.8 1 1200 6.06 8.61 220 2 2 23.00 10 5.26 35 10 21 0.48 600 600 QO 2 15

C12,14 1 2400 0.88 0.8 1 2400 12.12 17.22 220 2 2 23.00 10 5.26 35 10 21 0.96 1200 1200 QO 2 20C13,15 1 1200 0.88 0.8 1 1200 6.06 8.61 220 2 2 23.00 10 5.26 35 10 21 0.48 600 600 QO 2 15C17,18 1 1200 0.88 0.8 1 1200 10.50 14.91 127 1 2 23.00 10 5.26 35 10 21 1.45 600 600 QO 2 20C17,19 1 1200 0.88 0.8 1 1200 10.50 14.91 127 1 2 23.00 10 5.26 35 10 21 1.45 600 600 QO 2 20

C20 2 360 0.88 0.8 1 360 3.15 4.47 127 1 2 23.00 12 3.307 25 12 16 0.69 360 QO 1 10C23 18 756 0.88 0.8 1 756 6.61 9.40 127 1 2 23.00 12 3.307 25 12 16 1.45 756 QO 1 15

TOTAL 18 0 0 15 0 0 2 5 1 17856 17856 52.13 5880 6060 5916TAB. 3F-4H 220/127 V.C.A. 24 CTOS 10,000 A.C.I. INT . PRINC 3X70AMPS TOTAL WATTS 17856

TABLERO "ILUM EXT."ALIMENTADO DE: MURETE ALIMENTADOR: 2-#6, 1-#10t PRINCIPAL: 3 x 15 AMP FASE A = 800 % DES. MAXIMO = 0.00

SERVICIO A: ALUMBRADO EXTERIOR DISTANCIA: 10 MTS. 10 MONTAJE: PARED FASE B = 800

MARCA / CAT. : INTERRUPTOR TIPO FAL CON GABINETE CANALIZACION: 35 mm VOLTS: 220/127 FASE C = 800FECHA: SEPTIEMBRE DE 2009 CAIDA DE TENSION: .09% FASES: 3 F, 1 d TOTAL = 2400

CIRCUITO LUM LUM BOMBA CONT AIRE AIRE AIRE AIRE AIRE VA FACTOR CORR FACTOR AGRUP FACTOR FD AMPS. VOLTS F H L (MTS) COND. CAL S mm CAP. DEL COND. DE TUBO (MM) CAIDA DE FASES TIPO DEPROTEC. TERMOMAG.42W 13W 400W 180W 800W 1800W 2400W 1200W 3600W TEMP DEMANDA VA I nom I corr COND (AMPS) TIERRA TENSION A B C INT. POLOS AMPS.

C1,3,5 6 2400 0.88 0.8 1 2400 7.01 9.95 220 3 3 90.00 6 13.03 60 10 35 0.88 800 800 800 QO 3 15C2C4C6C7C8C9

C10C11C12

C17,19C20C23

TOTAL 0 0 6 0 0 0 0 0 0 2400 2400 7.01 800 800 800TAB. 3F-4H 220/127 V.C.A. 12 CTOS 10,000 A.C.I. INT . PRINC 3X30AMPS TOTAL WATTS 2400

BUS DE CARGA "GENERAL"ALIMENTADO DE: TGZ ALIMENTADOR: 3-#1/0, 1-#1/0, 1-#4t PRINCIPAL: 3 x 250 AMP FASE A = 20096 % DES. MAXIMO = 0.61

SERVICIO A: ALUMBRADO Y CONTACTOS EN PLANTA ALTA DISTANCIA: 80 MTS. MONTAJE: PARED FASE B = 20060

MARCA / CAT. : SQUAR D NQOD30-4AB11 CANALIZACION: 53 mm VOLTS: 220/127 FASE C = 20184FECHA: NOVIEMBRE DE 2008 CAIDA DE TENSION: 1.65% FASES: 3 F, 1 N TOTAL = 60340

UBICACIÓN CIRCUITO TAB "A" TAB "B" TAB "C" TAB "ILUM" TAB "E" TAB "F" VA FACTOR CORR FACTOR AGRUP FACTOR FD AMPS. VOLTS F H L (MTS) COND. CAL S mm CAP. DEL COND. DE TUBO (MM) CAIDA DE FASES TIPO DE PROTEC. TERMOMAG.TEMP DEMANDA VA I nom I corr COND (AMPS) TIERRA TENSION A B C INT. POLOS AMPS.

1 17448 0.88 0.8 1 17448 50.94 72.35 220 3 4 30.00 2 26.67 115 8 41 1.04 5808 5760 5880 FAL36070 3 1001 22636 0.88 0.8 1 22636 66.08 93.87 220 3 4 37.00 2 26.67 115 8 41 1.67 7608 7440 7588 FAL36030 3 70

1 17856 0.88 0.8 1 17856 52.13 74.05 220 3 4 18.00 2 26.67 115 8 41 0.64 5880 6060 5916 FAL36030 3 701 2400 0.88 0.8 1 2400 7.01 9.95 220 3 4 10.00 2 26.67 115 8 41 0.05 800 800 800 NQO30 3 15

TOTAL 1 1 1 1 0 0 60340 60340 176.15 20096 20060 20184MUERETE DE ACOMETIDA CON BUS DE CARGA CON INT . PRINC 3X250 AMPS TOTAL WATTS 60340