The European Commission’sscience and knowledge service
Joint Research Centre
Results of the EU Code of Conduct for Data Centre
Energy Efficiency
Maria Avgerinou
Supervisor: Paolo Bertoldi
Ispra, 1 February 2017
2
CONTENTS
Why? (Aims)
How? (Methodology)
What? (Findings)
3
What is a data centre?
• A facility composed of networked computers and storage that businesses use to organise, process, store or distribute large amounts of data.
• All buildings, facilities and rooms which contain enterprise servers, server communication equipment, cooling and power equipment, and provide some form of data service.
4
• Data centre numbers are growing
• EU DC consume 60 TWh/year (2-3% of total)
• Up to 30% energy efficiency savings are possible at low costs.
5
EU CoC DC Energy Efficiency
• Voluntary initiative in response to growing energy consumption in data centres and the need to reduce the associated impacts.
• Improve understanding of energy demands and recommend cost-effective energy efficient best practices that do not hinder the performance of the system.
• Reference/Benchmarking for other businesses through a common set of principles.
6
Methodology
Reporting form for participants: DC information Energy/IT data Best Practices
PUE=Total DC input power/IT load power (metric to measure energy efficiency in DCs)
325 DCs have applied, 289 have been granted the Participant status
7
Results
8
Results
2009 2010 2011 2012 2013 2014 2015 20161.5
1.55
1.6
1.65
1.7
1.75
1.8
1.85
1.9
1.95
2
1.86
1.96
1.73
1.9
1.78
1.86
1.72
1.64
Average PUE Linear (Average PUE)
9
Results
2.8-3.0 2.6-2.8 2.4-2.6 2.2-2.4 2.0-2.2 1.8-2.0 1.6-1.8 1.4-1.6 1.2-1.4 1.0-1.20
10
20
30
40
50
60
70
80
10
Results - PUE/DC size (m2)
1.00 -500 500 -1,000 1,000-2,500 2,500-5,000 5,000-8,000 8,000-20,0001.72
1.74
1.76
1.78
1.8
1.82
1.84
1.86
1.76
1.77
1.81
1.84
1.77 1.77
11
Results - PUE/Construction year
1960-1980 1980-1990 1990-1995 1995-2000 2000-2005 2005-2010 2010-20151.65
1.7
1.75
1.8
1.85
1.9
1.95
1.78
1.91
1.82
1.781.77
1.74
1.88
Average PUE
12
Results - PUE/IT Rated Load (kW)
0.1-100 100-300 300-600 600-1,000 1,000-2,500 2,500-5,000 5,000-10,000 10,000-20,000
1.55
1.6
1.65
1.7
1.75
1.8
1.85
1.9
1.731.71
1.82
1.88
1.791.81
1.67
1.8
13
Results - Economizers
DA IA DW IW A None0
0.5
1
1.5
2
2.5
3
1.88 1.89 1.831.74
1.35
1.81
1.25 1.24 1.271.1
1.35
1.1
2.712.55
2.33
2.73
1.35
2.83
DA: Direct AirIA: Indirect AirDW: Direct WaterIW: Indirect WaterA: Adsorption
14
Results - Geographical Distribution
Nordic c
ountrie
s
UK and
Republ
ic of Ir
eland
Norther
n/Con
tinen
tal Eu
rope
Mediter
ranea
n/S. Eu
rope
1.55
1.6
1.65
1.7
1.75
1.8
1.85
1.9
1.95
2
2.05
1.71
1.87
1.72
2
Average PUE
15
Results – Best practices
Supplement to the CoC, provides info and support to DC operators regarding energy efficiency opportunities.
152 Best Practices in total, 81 minimum expected(2016)
Most of the top implemented practices require low capital expenditure (low hanging fruit)
Recent participants implement more BPs
16
Conclusions
PUE is decreasing since the beginning of the programme due to technological advances.
Average annual electricity consumption has decreased.
Wider ToC and RH% set point ranges.
Type of DC with the lowest PUE:• very small or very large• Built between 2005-2010• 5-10 MW• Use of Indirect Water free cooling system• Northern/Central Europe
17
Equinix - Amsterdam DC, EU CoC Winner 2013
PUE: 1.2Aquifer Thermal Energy StorageHybrid cooling towers
18