Page 1: Catalogo 2011-2020 r010212 Corto Circuito

1

Coordinación de Planificación

Subdirección de ProgramaciónCoordinación de Planificación

5ª EDICIÓNEnero de 2012

_____

SISTEMA ELÉCTRICO MEXICANOCATÁLOGO DE CORTO CIRCUITO

2011-2020

SISTEMA ELÉCTRICO MEXICANOCATÁLOGO DE CORTO CIRCUITO

2011-2020

Page 2: Catalogo 2011-2020 r010212 Corto Circuito

2

Coordinación de Planificación

_____

SISTEMA ELÉCTRICO MEXICANO

CATÁLOGO DE CORTO CIRCUITO

2011-2020

Realizó:

DEPARTAMENTO DE PROGRAMACIÓN

DE LA RED DE TRANSMISIÓN

ÁREA NOROESTE

José Acosta Segura

Sergio Díaz Tello

ÁREA NORESTE

Uriel Abraham Rangel Díaz

Jorge Wilebaldo Castro González

Pascual Jaime Espinosa

Fanny L. Arenas Olvera

ÁREAS BAJA CALIFORNIA Y

BAJA CALIFORNIA SUR

Raúl Adame Ortiz

José Francisco Peñaloza Colín

ÁREA CENTRAL

Daniel Álvarez Hernández

DEPARTAMENTO DE PROGRAMACIÓN

DE REDES DE SUBTRANSMISIÓN

ÁREA NORTE

Tomasa Rodríguez Robles

Eduardo Rosales Gómez

ÁREA OCCIDENTAL

Arnulfo Arón Chávez Mújica

Mario Alberto García Domínguez

ÁREA ORIENTAL

Víctor Nolasco Miguel

Julio Castillo Trejo

Amado Flores Reyes

ÁREA PENINSULAR

Enrique López Luis

Guillermo Galicia Cano

Marco Antonio Islas Martínez

Adrián Ruiz Castillo

Aprobó:

Visto Bueno:

Gonzalo Arroyo Aguilera

Revisó:

Foto portada: Subestación Tapachula proporcionada por la Subgerencia de Difusión CFE

Subdirección de ProgramaciónCoordinación de Planificación

Enero de 2012 5ª EDICIÓN

SISTEMA ELÉCTRICO MEXICANO

CATÁLOGO DE CORTO CIRCUITO

2011-2020

Guillermo Galicia Cano

Marco Antonio Islas Martínez

Adrián Ruiz Castillo

DEPARTAMENTO DE PROGRAMACIÓN

DE LA RED DE TRANSMISIÓN

ÁREA NOROESTE

José Acosta Segura

Sergio Díaz Tello

ÁREA NORESTE

Uriel Abraham Rangel Díaz

Jorge Wilebaldo Castro González

Pascual Jaime Espinosa

Fanny L. Arenas Olvera

ÁREAS BAJA CALIFORNIA Y

BAJA CALIFORNIA SUR

Raúl Adame Ortiz

José Francisco Peñaloza Colín

ÁREA CENTRAL

Daniel Álvarez Hernández

DEPARTAMENTO DE PROGRAMACIÓN

DE REDES DE SUBTRANSMISIÓN

ÁREA NORTE

Tomasa Rodríguez Robles

Eduardo Rosales Gómez

ÁREA OCCIDENTAL

Arnulfo Arón Chávez Mújica

Mario Alberto García Domínguez

ÁREA ORIENTAL

Víctor Nolasco Miguel

Julio Castillo Trejo

Amado Flores Reyes

ÁREA PENINSULAR

Enrique López Luis

Realizó:

Aprobó:

Visto Bueno:

Gonzalo Arroyo Aguilera

Revisó:

Subdirección de ProgramaciónCoordinación de Planificación

5ª EDICIÓNEnero de 2012

Foto portada: Subestación Tapachula proporcionada por la Subgerencia de Difusión CFE

Page 3: Catalogo 2011-2020 r010212 Corto Circuito

3

Coordinación de Planificación CONTENIDO

I. INTRODUCCIÓN 4

II. LA PLANIFICACIÓN DEL SISTEMA ELÉCTRICO MEXICANO 7

III. HIPÓTESIS DEL ESTUDIO 10

IV. DESARROLLO 12

V. RESULTADOS 15

Catálogo de Corto Circuito 2011-2020

_______

_________________________________________________

_________________________________________________

_________________________________________________

_________________________________________________

_________________________________________________

Page 4: Catalogo 2011-2020 r010212 Corto Circuito

4

Coordinación de Planificación INTRODUCCIÓN

I.- INTRODUCCIÓN

Un aspecto importante a considerar en la operación y planificación de los sistemas eléctricos de potencia es su

comportamiento en condiciones normales, sin embargo también es relevante observarlo en el estado transitorio; es

decir, ante contingencia (falla o corto circuito). Esta condición transitoria en las instalaciones se debe a distintas causas

y una gran variedad de ellas está fuera del control humano.

Ante ello los equipos y/o sistemas pueden sufrir daños severos temporales o permanentes en condiciones de falla. Por

lo tanto, es necesario definir equipos y esquemas de protección adecuados al momento de diseñar las instalaciones, de

tal forma que se asegure el correcto desempeño de la red eléctrica, apoyada por los dispositivos de monitoreo,

detección y señalización.

Es necesario realizar estudios de corto circuito para determinar los niveles de corriente ante fallas, los cuales permiten

obtener información necesaria para seleccionar correctamente la capacidad de los equipos en función de los

requerimientos mínimos que deben cumplir y así soportar los efectos de las contingencias. La presencia de fallas es

una situación indeseable en un sistema eléctrico, pero lamentablemente no se pueden prever pues se presentan

eventualmente teniendo diversos orígenes, como por ejemplo: una sobretensión por descarga atmosférica, una falla de

aislamiento por envejecimiento prematuro, alguna maniobra errónea, entre otras causas, por lo que ante estas

condiciones se debe estar en posibilidad de conocer las magnitudes de las corrientes de corto circuito en todos los

puntos de la red.

____________Catálogo de Corto Circuito 2011-2020

Page 5: Catalogo 2011-2020 r010212 Corto Circuito

5

Coordinación de Planificación

El análisis del corto circuito en los sistemas eléctricos se debe realizar desde las centrales eléctricas hasta el nivel de

distribución de la energía.

El sistema eléctrico está constituido básicamente por generadores eléctricos, transformadores, líneas de transmisión,

subtransmisión y distribución, dispositivos de control de voltaje como capacitores y reactores en derivación,

Compensadores Estáticos de Vars (CEV); así como los elementos de consumo (cargas).

Eléctricamente hablando, pueden dividirse en elementos activos y pasivos, considerándose como elementos activos ó

fuentes suministradoras de las corrientes de corto circuito a:

Generadores

Motores síncronos

Motores de Inducción

Y los elementos pasivos o limitadores de las corrientes de corto circuito a:

Las impedancias de las máquinas rotatorias (generadores, motores síncronos y de inducción).

Las impedancias de las líneas de transmisión, redes de distribución, transformadores y en general todo

tipo de reactores y resistencias limitadoras.

_____ ____________Catálogo de Corto Circuito 2011-2020

INTRODUCCIÓN

Page 6: Catalogo 2011-2020 r010212 Corto Circuito

6

Coordinación de Planificación

En general, un estudio de corto circuito permite:

Determinar las capacidades interruptivas de los elementos de desconexión de las corrientes de corto

circuito como son interruptores, fusibles, restauradores y fusibles de potencia, principalmente.

Estudiar la selección y coordinación de los dispositivos de protección contra las corrientes de corto

circuito.

Realizar estudios térmicos y dinámicos que consideren los efectos de las corrientes de corto circuito

en algunos elementos de las instalaciones como son: sistemas de barras, tableros, cables, buses de

fase aislada, etc.

Obtener los equivalentes de Thevenin y su utilización en otros estudios del sistema, como estabilidad

angular y ubicación de compensación reactiva en derivación, entre otros.

_____ ____________Catálogo de Corto Circuito 2011-2020

INTRODUCCIÓN

Page 7: Catalogo 2011-2020 r010212 Corto Circuito

7

Coordinación de Planificación PLANIFICACIÓN DEL SISTEMA ELÉCTRICO MEXICANO

II. LA PLANIFICACIÓN DEL SISTEMA ELÉCTRICO MEXICANO

La planificación se realiza aprovechando las mejores opciones de inversión y producción de energía que permitan

satisfacer la demanda futura de electricidad a costo global mínimo y con un nivel adecuado de confiabilidad y calidad,

tanto en el mediano como en el largo plazo. Para ello se consideran los costos de inversión, operación y energía no

suministrada, así como las disposiciones gubernamentales en materia energética, financiera, ambiental y social. La

selección de los componentes del sistema, su programación en el tiempo y la definición de los sitios para su instalación

son actividades importantes con implicaciones técnicas, económicas, ambientales y sociales a nivel nacional.

Las decisiones sobre nuevos proyectos para expandir el Sistema Eléctrico Mexicano (SEM) se toman varios años

antes, ya que las etapas de autorización, construcción, hasta su inicio de operación son largos. Típicamente

transcurren hasta cinco años entre el análisis de la oferta para construir una nueva central generadora ó un nuevo

proyecto de transmisión y su entrada en operación comercial. Adicionalmente, formular, evaluar y autorizarlos requiere

una anticipación mínima de un año.

El programa para expandir el SEM se determina seleccionando aquéllos proyectos que minimizan los costos

actualizados de inversión, operación y energía no suministrada en el horizonte de estudio. Es decir, se elabora un plan

óptimo basado en el análisis técnico-económico de diversas alternativas, mediante modelos que optimizan el

comportamiento del sistema ante diversas condiciones de operación.

_____ ____________Catálogo de Corto Circuito 2011-2020

Page 8: Catalogo 2011-2020 r010212 Corto Circuito

8

Coordinación de Planificación

El intercambio de grandes bloques de energía entre regiones se efectúa a través de la red de transmisión troncal,

integrada por líneas con niveles de tensión de 400 kV y 230 kV, mientras que la subtransmisión de energía se atiende

con enlaces en 161, 115, 85 y 69 kV.

La red de transmisión se desarrolla tomando en cuenta la magnitud y dispersión geográfica de la demanda, así como la

localización de las centrales generadoras. En algunas áreas del país, los núcleos de generación y consumo de

electricidad se encuentran alejados entre sí, por lo que la interconexión se realiza de manera gradual, en tanto los

proyectos se van justificando técnica y económicamente.

Al planificar el SEM se efectúa un balance entre el desarrollo de la generación y la transmisión para lograr la

confiabilidad del suministro de energía eléctrica. Una red de transmisión confiable permite integrar y aprovechar

eficientemente los recursos de generación del país; por lo que al paso del tiempo se ha conformado un sistema

interconectado que cubre la mayor parte del territorio nacional, donde en 2005 se incorporó el área Noroeste.

Actualmente, sólo los sistemas de la península de Baja California se encuentran aislados.

_____ ____________Catálogo de Corto Circuito 2011-2020

PLANIFICACIÓN DEL SISTEMA ELÉCTRICO MEXICANO

Page 9: Catalogo 2011-2020 r010212 Corto Circuito

9

Coordinación de Planificación

El objetivo es diseñar un sistema que se justifique técnica y económicamente para que en condiciones normales y ante

contingencias sencillas opere con las características siguientes:

Sin sobrecargas

Dentro de los rangos de tensión establecidos

Sin problemas de estabilidad angular

Con suficiente capacidad de transferencia entre regiones para compartir la reserva de generación

Sin necesidad de interrumpir la demanda de usuarios

Con los controles apropiados para dar flexibilidad a la operación

_____ ____________Catálogo de Corto Circuito 2011-2020

PLANIFICACIÓN DEL SISTEMA ELÉCTRICO MEXICANO

Page 10: Catalogo 2011-2020 r010212 Corto Circuito

10

Coordinación de Planificación

III.- HIPÓTESIS DEL ESTUDIO

Para el cálculo del corto circuito a nivel del Sistema Eléctrico Mexicano, se consideró lo siguiente:

El caso base de flujos de potencia debe despachar toda la generación instalada, incluidas las unidades

turbogas; así como todos los elementos de transmisión y subtransmisión operando.

Se reportan las corrientes de falla que ocurren en el intervalo subtransitorio, es decir, las reactancias de

las unidades generadores corresponden a las reactancias subtransitorias X’’d.

Para las siete áreas actualmente interconectadas, el estudio se realizó en el punto de operación de la

demanda máxima a nivel Sistema Interconectado Nacional (SIN).

Para las áreas de la Península de Baja California como son el área Baja California (BC) y Baja

California Sur (BCS), el estudio se realizó en el punto de la demanda máxima de verano.

La falla aplicada en el nodo correspondiente; donde la corriente será la suma de las contribuciones de

los generadores y de los enlaces de transmisión y subtransmisión en este punto.

_____ ____________Catálogo de Corto Circuito 2011-2020

HIPÓTESIS

Page 11: Catalogo 2011-2020 r010212 Corto Circuito

11

Coordinación de Planificación

Para el modelado de los parques eólicos a instalarse en la región de La Ventosa, Oaxaca, se considera que

actualmente y a futuro en el mercado de aerogeneradores las tecnologías más utilizadas son los del tipo

generador de inducción doblemente alimentados y los síncronos con convertidor completo (full converter). El

efecto de los primeros ante fallas en el sistema es que aportan corrientes de corto circuito solo

temporalmente, sin embargo deben considerarse para determinar la capacidad interruptiva de los

alimentadores, y para los del segundo tipo no aportan corrientes de corto circuito ante falla debido a que

están aislados del sistema mediante el convertidor de potencia.

Respecto al Área Baja California, un equivalente del WECC (Western Electricity Coordinating Council).

A partir del 2014 la interconexión del SIN con el área BC por medio de un enlace asíncrono, el cual no

incrementa los niveles de falla en las subestaciones de enlace.

El Programa de Obras e Inversiones del Sector Eléctrico (POISE) de agosto de 2009.

El Programa de Requerimientos de Capacidad (PRC) y de retiros (PR) 2010-2025 del 24 de noviembre de

2010.

Se considera que se tienen voltajes 1.0 p.u. para todos los buses ante la condición de prefalla, es decir se

tienen condiciones planas de voltaje.

_____ ____________Catálogo de Corto Circuito 2011-2020

HIPÓTESIS

Page 12: Catalogo 2011-2020 r010212 Corto Circuito

12

Coordinación de Planificación

IV.- DESARROLLO

Al paso del tiempo, el sistema de transmisión troncal del SEM se ha mallado, principalmente en las regiones central,

occidental y Noreste del país. Asimismo, en las áreas Norte y Noreste se encuentra en proceso una etapa de

robustecimiento, con una red de transmisión aislada en 400 kV operando inicialmente en 230 kV.

Partiendo de la red base existente en 2011, considerando plena disponibilidad de generación y con toda la red de

transmisión, transformación y subtransmisión en servicio, se realizaron los cálculos de corto circuito trifásico y

monofásico para este año de referencia, los cuales fueron comparados con los últimos resultados obtenidos por el área

de la Subdirección de Transmisión, en particular, la Gerencia de protecciones. Cabe aclarar, sin embargo, que el área

indicada anteriormente utiliza en sus cálculos la reactancia transitoria (X’d); por lo que los resultados obtenidos en el

área de Programación resultaron ser ligeramente mayores, debido a que en este caso se utiliza la reactancia

subtransitoria (X’’d).

Para los años restantes del período de planificación, se fueron agregando las obras de generación y transmisión

correspondientes y retirando la generación programada para cada una de las nueve áreas de Control, obteniéndose así

los resultados en el intervalo 2011-2020, los cuales se reportan en el presente estudio.

_____ ____________Catálogo de Corto Circuito 2011-2020

DESARROLLO

Page 13: Catalogo 2011-2020 r010212 Corto Circuito

13

Coordinación de Planificación

En este catálogo el SEM está regionalizado de acuerdo a la siguiente numeración, que coincide con la considerada por

el área operativa:

1 CENTRAL

2 ORIENTAL

3 OCCIDENTAL

4 NOROESTE

5 NORTE

6 NORESTE

7 BAJA CALIFORNIA

8 BAJA CALIFORNIA SUR

9 PENINSULAR

_____ ____________Catálogo de Corto Circuito 2011-2020

DESARROLLO

Page 14: Catalogo 2011-2020 r010212 Corto Circuito

14

Coordinación de Planificación

Los resultados se muestran siguiendo este orden y está conformado de la siguiente manera: un diagrama unifilar base

de 2011 que muestra la red troncal del área bajo estudio, un resumen de la generación programada adicional y por

retirar en el período de análisis, donde se indica el nombre de la central generadora, la fecha de entrada ó retiro y la

capacidad máxima a considerar, así como un breve análisis de sus efectos en relación al corto circuito.

Adicionalmente, se realizan comentarios en relación al impacto que ocasionan los refuerzos de transmisión y

subtransmisión internos.

Los valores de corriente de corto circuito trifásico y monofásico obtenidos de las simulaciones se muestran en forma

tabular ordenados alfabéticamente de acuerdo al nombre de la subestación, incluido su nemotécnico. Los resultados

son presentados en kiloamperes (kA) para el periodo 2011-2020.

Todas las simulaciones fueron realizadas empleando el simulador de Sistemas de Potencia PSS/E (Power System

Simulator for Engineering), versión 32.

_____ ____________Catálogo de Corto Circuito 2011-2020

DESARROLLO

Page 15: Catalogo 2011-2020 r010212 Corto Circuito

15

Coordinación de Planificación

777

8

44

55

6

3

1

2

9

1. CENTRAL

2. ORIENTAL

3. OCCIDENTAL

4. NOROESTE

5. NORTE

6. NORESTE

7. BAJA CALIFORNIA

8. BAJA CALIFORNIA SUR

SISTEMA AISLADO GUERRERO NEGRO

SISTEMA AISLADO SANTA ROSALIA

9. PENINSULAR

_____

_______

_______

_______

_______

_______

_______

_______

_______

_______

_______

_______

ÍNDICE DE RESULTADOS POR ÁREA

_______

Catálogo de Corto Circuito 2011-2020

Page 16: Catalogo 2011-2020 r010212 Corto Circuito

16

Coordinación de Planificación

AREA CENTRAL

VALLE DE MÉXICO

AREA CENTRAL

C.F.E.

ESTUDIO DE CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

ÁREA CENTRAL

______________Catálogo de Corto Circuito 2011-2020_____

Page 17: Catalogo 2011-2020 r010212 Corto Circuito

17

Coordinación de PlanificaciónRED ELÉCTRICA PRINCIPAL 2011

ÁREA CENTRAL

TULA3X323MW, 2X300MW

2 x T421

VICTORIA3 x T421L, 4 x T28

NOPALAREMEDIOS

SAN BERNABÉ

TOPILEJO

CEV +300/-90 MVAR

STA CRUZ

3 x T2211X32MW GD

LA PAZ3 x T421L

TEXCOCO

TEOTIHUACAN

A POZA RICA II

ATLACOMULCO POT.

1 x 375 MVA

DONATO

GUERRA2 x 300 MVA

A P

ITIR

ER

A

AGUSTÍNMILLÁN II

VOLCÁN GORDO

40%

A YAUTEPECPOTENCIA

CEV +300/-90 MVAR

A TRES

ESTRELLAS

A SAN

LORENZO

POTENCIA

A SAN

MARTÍN

POTENCIA

CEV +300/-90 MVAR

APASCO

LAFARGE

JASSO3 x T28

CRUZAZUL

NOCHISTONGO

JOROBAS

PROCTER &GAMBLE

PEMEX150 MW

TIZAYUCA

KM-110

IROLO

A HÉROES DE

CARRANZA

JILOTEPEC POTENCIA1X225MVA

230/115KV

A

DAÑU

OP

. INI. 2

30K

V

A LA

MANGA

2X60MVA

230/23KV

EL VIDRIO

CARTAGENA2 x T221

CEYLAN

VALLEJOATIZAPAN

AZCAPOTZALCO

POLANCO

TECAMACHALCO

BOSQUES

CONTADERO

AGUILAS

OLIVAR

CUAJIMALPA

CONTRERAS

ODON DE BUENTAXQUEÑA

TACUBAYA

SAN ANGEL

COYOACAN

ECATEPEC3 x T222

CEV +300/-75

MVAR CERRO GORDO

CHAPINGO

AURORA

KM CERO

CUAUHTEMOC

PENSADOR

MERCED

ESMERALDA

PERALVILLO

MADERO

XALOSTOCAZTECA

AYOTLA

IZTAPALUCA

VERTIZ

MAGDALENA

JAMAICA

IZTAPALAPA

XOCHIMILCO

COAPA

MORELOS

ESTADIO

TOLUCA

ATENCO

EL CERRILLO

TOLUCA 20002 x T221

INFORMACIÓN RESERVADA DEACUERDO CON LA LEY FEDERAL DETRANSPARENCIA Y ACCESO A LA

INFORMACIÓN PÚBLICAGUBERNAMENTAL

A LÁZARO CÁRDENAS

EL SALTO2 x T28

NECAXA 10U - 109MW

PATLA 3U - 37 MW TEPEXIC 3U - 45MW

TENDIDO DEL PRIMERO

CABLE SUBTERRANEO

ALMOLOYA

40%

TOTAL 427.7 MVAR

VALLE DE MÉXICO3X150 MW,1X300MW,3X83MW

2 x T28

POTENCIA

A ZAPATA

A TUXPAN

A ZOCAC

TIANGUISTENCO

50 MVAR

6 CC - 490 MW TOTAL

50%

ARMEX

1X32 MW GD

1X32 MW GD

PUNTA NORTEMOVIL

1 x T221M

COFRADIA IIMOVIL

1X32 MW GD

COFRADIA MOVIL

1X32 MW GD

SOSATEXCOCO

HUIXQUILUCANMOVIL

PARRESMOVIL

1X32 MW GD

OCEANIA

JABON LA CORONA CARTON Y

PAPEL

FERROCARRILESNACIONALES

TRENSUBURBANO

ESTRELLA

MOVIL

3 x T221

3X28MW

1 x T221M

3 x T221

1 x T221M 3 x T221

3 x T221

3 x T28

3 x T222

2 x T282 x T221

1 x T221M

2 x T221

3 x T221

3 x T221

2 x T28

6 x T28, 3 x T221

3 x T221

3 x T421C

2 x T221

2 x T221

3 x T221

3 x T221

1 x T221M

2 x T221

3 x T221

3 x T221 2 x T221

3 x T221

3 x T221

3 x T221

4 x T28

4 x T824 x T28

3 x T221

3 x T221

3 x T28

3 x T221

3 x T221

3 x T221

3 x T221

2 x T221

3 x T221

3 x T221

2 x T221

3 x T2211 x T28

3 x T2213 x T221

3 x T421L

1 x T221M

2 x T221

2 x T421L

4 x T28

3 x T221

3 x T421L

3 x T421C

2 x T22

2 x T28

3 x T28

4 x T221

2 x T221

3 x T221

3 x T28, 3 x T221

1 x 225 MVA

1 x T211

2 x T221

1 x T221

Sust. Bco. 1 230/85 kV

Sust. Bco. 230/23 kV

2 x T22

DEPORTIVA1 x T42

TECAMAC

12.6

-1113

22

-11

13

(A

35

70

)

22

-11

13

(A

35

80

)

SUBESTACIÓN ELÉCTRICA

ENLACE 400 KV

ENLACE 230 KV

SIMBOLOGIA

NOMENCLATURA DE TRANSFORMADORES

T421L 330 MVA , 400/230 KVT421C 375 MVA , 400/230 KVT28 100 MVA , 230/85 KVT221 60 MVA , 230/23 KV

400/115 kV

400/115 kV

400/115 kV

T221M 45 MVA , 230/23 KV

4 x T421L

TOTOLTEPEC2 x T221

A QUERÉTARO MANIOBRAS

LINEA DE TRANSMISIÓN DE DOBLE CIRCUITO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 18: Catalogo 2011-2020 r010212 Corto Circuito

18

Coordinación de PlanificaciónRED ELÉCTRICA PRINCIPAL 2020

ÁREA CENTRAL

3X323MW, 2X300MW

2 x T421

VICTORIA3 x T421L, 4 x T28

NOPALAREMEDIOS

SAN BERNABÉ

TOPILEJO

CEV +300/-90 MVAR

STA CRUZ4 x T421L

1X32MW GD

LA PAZ3 x T421L

TEXCOCO

TEOTIHUACAN

A POZA RICA II

A QUERÉTARO MANIOBRAS

ATLACOMULCO POT.

1 x T41

DONATO

GUERRA2 x T411

A P

ITIR

ER

A

AGUSTÍNMILLÁN II

VOLCÁN GORDO

40%

A YAUTEPECPOTENCIA

CEV +300/-90 MVAR

A TRES

ESTRELLAS

A SAN

LORENZO

POTENCIA

A SAN

MARTÍN

POTENCIA

CEV +300/-90 MVAR

APASCO

LAFARGE

JASSO3 x T28

CRUZAZUL

NOCHISTONGO

JOROBAS

PROCTER &GAMBLE

PEMEX150 MW

TIZAYUCA

KM-110

IROLO

A HÉROES DE

CARRANZA

JILOTEPEC POTENCIA

1X225MVA

230/115KV

A

DAÑU

OP

. INI. 2

30K

V

A LA

MANGA

2X60MVA

230/23KV

EL VIDRIO

CARTAGENA2 x T221

CEYLAN

VALLEJOATIZAPAN

AZCAPOTZALCO

POLANCO

TECAMACHALCOBOSQUES

CONTADERO

AGUILAS

OLIVAR

CUAJIMALPA

CONTRERAS

ODON DE BUENTAXQUEÑA

TACUBAYA

SAN ANGEL

COYOACAN

ECATEPEC3 x T222

CEV +300/-75

MVARCERRO GORDO

CHAPINGO

AURORA

KM CERO

CUAUHTEMOC

PENSADOR

MERCED

ESMERALDA

PERALVILLO

MADERO

XALOSTOC AZTECA

AYOTLA

IZTAPALUCA

VERTIZ

MAGDALENA

JAMAICA

IZTAPALAPA

XOCHIMILCO

COAPA

MORELOS

ESTADIO

TOLUCA

ATENCO

EL CERRILLO

TOLUCA 2000

2 x T221

A LÁZARO CÁRDENAS

EL SALTO2 x T28

NECAXA 10U - 109MW

PATLA 3U - 37 MW TEPEXIC 3U - 45MW

ALMOLOYA

40%

TOTAL 427.7 MVAR

VALLE DE MÉXICOCC 2X660 MW,1X300MW,3X83MW

2 x T28

POTENCIA

A ZAPATA

A

TUXPAN

A ZOCAC

TIANGUISTENCO

50 MVAR

6 CC - 490 MW TOTAL

40%

ARMEX

1X32 MW GD

1X32 MW GD

PUNTA NORTEMOVIL

1 x T221M

COFRADIA IIMOVIL

1X32 MW GD

COFRADIA MOVIL

1X32 MW GD

CARACOL

LOMAS VERDES

EL ROSAL

1X32 MW GD

OCEANIA

JABON LA CORONA

CARTON Y PAPEL

FERROCARRILESNACIONALES

TRENSUBURBANO

ESTRELLA

3 x T221

3X28MW,1x600MW

1 x T221M

3 x T221

1 x T221M 3 x T221

3 x T221

3 x T28

3 x T222

2 x T282 x T221

1 x T221

2 x T221

3 x T221

3 x T221

2 x T28

6 x T28, 3 x T221

3 x T221

3 x T421C

2 x T221

2 x T221

3 x T221

3 x T221

1 x T221

2 x T221

3 x T221

3 x T2212 x T221

3 x T221

3 x T221

3 x T221

4 x T28

4 x T824 x T28

3 x T221

3 x T2213 x T28

3 x T221

3 x T221

3 x T221

3 x T221

2 x T221

3 x T221

3 x T221

2 x T221

3 x T2211 x T28

3 x T2213 x T221

3 x T421L

2 x 221

2 x T221

2 x T421L

4 x T28

3 x T221

3 x T421L

3 x T421C

2 x T22

2 x T28

3 x T28

4 x T221

2 x T221

3 x T221

3 x T28, 3 x T221

2 x T411

1 x T211

2 x T221

1 x T22

TECAMAC

2 x T22

83.5 KM

- 1113 AC

SR

(93110 )( A3020 )

( A3210 )

233- 1113 ACSR

ACOLMAN1 x T22

ZARAGOZA

2 x T22

3 x T221

ZUMPANGO2 x T22

1 x T421

LOMAS VERDES2 x T22

SANTA FE1 x T22

REFORMA II1 x T22

ANAHUAC2 x T221

CULHUACAN2 x T221

EL ROSAL2 x T221

CONDESA1 x T221

NARVARTE2 x T221

FISISA2 x T221

DEPORTIVA1 x T42

LAGO2 x T421L

CHIMALPA II1 x T421C

TECOMITL1 x T22

HUEHUETOCA

2 x T221

TEPOTZOTLAN

INFORMACIÓN RESERVADA DEACUERDO CON LA LEY FEDERAL DETRANSPARENCIA Y ACCESO A LA

INFORMACIÓN PÚBLICAGUBERNAMENTAL

LINEA DE TRANSMISIÓN DE DOBLE CIRCUITO

TENDIDO DEL PRIMERO

CABLE SUBTERRANEO

SUBESTACIÓN ELÉCTRICA

ENLACE 400 KV

ENLACE 230 KV

SIMBOLOGIA

NOMENCLATURA DE TRANSFORMADORES

T421L 330 MVA , 400/230 KVT421C 375 MVA , 400/230 KVT28 100 MVA , 230/85 KVT221 60 MVA , 230/23 KVT221M 45 MVA , 230/23 KV

1 x T421CCHALCO

2 x T2211 x T28

PARQUE IND. REFORMA

CEV +300/-300 MVAR

3 x T221

VERONICA2 x T221

ARAGON2 x T221

LOS REYES2 x T221

CHIMALPA

ACEROS CORSA

TOTOLTEPEC2 x T221

IXTAPANTONGO

JORGE LUQUE

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 19: Catalogo 2011-2020 r010212 Corto Circuito

19

Coordinación de PlanificaciónADICIONES Y RETIROS DE GENERACIÓN

ÁREA CENTRAL

ADICIONES:

Nombre de la Central Año Capacidad

Centro (CC) 2013 660 MW

Centro II (CC) 2015 660 MW

Valle de México II (CC) 2017 601 MW

Valle de México III (CC) 2018 601 MW

Jorge Luque (CC/NTG) 2020 601 MW

RETIROS:

Nombre de la Central Año Capacidad

Valle de México (TC) U1, U2 y U3 2013 450 MW

Francisco Pérez Ríos (Tula) U1, U2 y U5 2020 960 MW

De acuerdo con el Programa de Retiros, la CFE sugiere el retiro de todas las unidades Turbogas de Nonoalco y Valle de

México, sin embargo, debido a la importancia que tiene esta generación para el apoyo en el suministro del área ante la

condición de máxima demanda, no se contemplan estos retiros para fines del presente estudio. Las unidades térmicas

convencionales de Valle de México que son retiradas hasta el 2017 una vez que entra en operación nueva generación en este

sitio.

Los resultados reportados corresponden a la condición operativa existente, en donde no se realiza el cierre de

circuitos en 230 y 85 kV en la zona Centro del área Central; esta condición esta definida por criterios operativos en

donde ante la salida de los circuitos radiales se realiza el cierre del circuito desconectado. Adicionalmente se tiene el

objetivo de reducir los niveles de corto circuito en líneas de 230 y 85 kV construidas con cable de potencia

subterráneo.

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 20: Catalogo 2011-2020 r010212 Corto Circuito

20

Coordinación de PlanificaciónADICIONES Y RETIROS DE GENERACIÓN

ÁREA CENTRAL

Con la entrada en operación de la generación programada en el estado de Morelos (Centro y Centro II) se tiene un impacto en

el incremento del nivel de corto circuito de 5 kA en la barras de 400 kV de la subestación Topilejo y para 2012 se alcanzará un

valor de 35.34 kA trifásico.

La entrada en operación del proyecto Valle de México II (CC) no tiene impacto en el incremento del valor de corto circuito

esperado, esto es debido a que se retirarán las unidades 1, 2 y 3 en 230 kV. Sin embargo, el proyecto Valle de México II (CC)

que tiene red asociada en 400 kV para interconectar las subestaciones Teotihuacán con Victoria, si impacta en incremento de

corriente de corto circuito en subestaciones en el nivel de 400 kV como Teotihuacán con 7 kA, Victoria con 8 kA y Texcoco con

4 kA, en donde para el 2020 se esperan valores trifásicos de 44.07, 39.98 y 43.01 kA respectivamente.

En forma análoga para el nivel de 230 kV, se tendrá un impacto en la subestación Victoria con el proyecto de generación Jorge

Luque, presentando un valor actual de falla monofásica de 37 kA que llegará a un valor esperado de 54.8 kA.

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 21: Catalogo 2011-2020 r010212 Corto Circuito

21

Coordinación de PlanificaciónPRINCIPALES PROYECTOS DE TRANSMISIÓN Y TRANSFORMACIÓN

ÁREA CENTRAL

Proyecto Año Nivel de tensión

Teotihuacán Bco. 3 2011 400/230 kV

Valle de México Bco. 2 2011 230/85 kV

CS Cuauhtémoc – Kilómetro Cero (sustitución) 2012 230 kV

Repotenciación LT Tula – Nochistongo 2012 230 kV

Nochistongo – Victoria 2012 230 kV

Huejotzingo – Agua Viva 2012 115 kV

Modernización de SE Valle de México 2012 230 kV

Repotenciación Tula – Teotihuacán 2013 230 kV

La Paz, entronque LT Tuxpan – Texcoco 2013 400 kV

Repotenciación LT Apasco-Juandho-Pachuca 2013 230 kV

Suministro zona Pachuca (Parque Industrial Reforma) 2013 400/230 kV

Paquete 1620 Distribución Valle de México 2013 230, 85 kV.

S.E Lago 2014 400/230 kV

S.E. Chimalpa II 2015 400/230 kV

Red asociada de CC Valle de México II 2017 230 kV

Ixtapantongo Potencia 2017 400/115 kV

Red asociada de CC Valle de México III 2018 400 kV

Chalco 2019 400/230 kV

Red asociada de CC Jorge Luque 2020 230 kV

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 22: Catalogo 2011-2020 r010212 Corto Circuito

22

Coordinación de PlanificaciónPRINCIPALES PROYECTOS DE TRANSMISIÓN Y TRANSFORMACIÓN

ÁREA CENTRAL

La inclusión de nuevos proyectos de transmisión en el área Central y cambios en la topología de la red troncal y subtransmisión

son factores que influyen directamente en los resultados del estudio de corto circuito.

Como consideraciones de red se contempla que la subestación Donato Guerra para el nivel de 115 kV tiene actualmente barra

partida, repartiendo las cargas en cada barra con el fin de mitigar el efecto de altos niveles de corto circuito debidos a las

contribuciones del sistema de bombeo Cutzamala.

El proyecto de modernización de la subestación Valle de México en 230 kV programado para 2012 permite una redistribución

de circuitos que inciden a este punto eléctrico, con una reducción en la contribución de corrientes de corto circuito, de 52.11 kA

se reduce a 39.69 kA trifásico; este beneficio se extiende a subestaciones aledañas como Cerro Gordo de 37.54 a 31.12 kA

trifásico, Texcoco de 45.81 a 42.86 kA trifásico, Teotihuacán de 34.27 a 24.94 kA trifásico, entre otras.

Sin embargo, se tiene la adición de red troncal en 400 y 230 kV y se incrementan los valores de corto circuito esperado:

Para el nivel de tensión de 400 kV se observa el efecto del proyecto La Paz entronque Tuxpan-Texcoco (2011), en donde la

contribución de corriente de corto circuito trifásica de la generación de Tuxpan se verá reflejada en la subestación La Paz

incrementando el nivel de falla de 29.09 a 32.7 kA trifásico.

Con respecto al nivel de 230 kV, con la entrada en operación del circuito Nochistongo-Victoria en el nivel de 230 kV se tiene el

incremento de corriente de corto circuito en Nochistongo de 23.10 a 33.73 kA trifásico, en Victoria de 37.13 a 39.03 kA trifásico.

La entrada en operación de una nueva subestación en 400 kV en Parque Industrial Reforma impacta al nivel de corto circuito

esperado, en las subestaciones cercanas como es Kilometro Ciento Diez que conectará en 230 kV la subestación Parque

Industrial Reforma con un valor de 6.87 a un valor de 10.99 kA monofásico.

Para 2020 los valores máximos esperados de corto circuito son:

En 23 kV, subestación Remedios con 16.95 kA, típicamente en las subestaciones que tienen unidades de generación distribuida

En 85 kV, subestación Lechería con 32.71 kA.

En 115 kV, subestación Donato Guerra con 33.7 kA.

En 230 kV, subestación Victoria con 54.84 kA.

En 400 kV, subestación Teotihuacán con 44.07 kA.

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 23: Catalogo 2011-2020 r010212 Corto Circuito

23

Coordinación de PlanificaciónPRINCIPALES PROYECTOS DE TRANSMISIÓN Y TRANSFORMACIÓN

ÁREA CENTRAL

De acuerdo con información proporcionada por la Zona de Transmisión Metropolitana (ZTM) del inventario general de

interruptores de potencia actualizado a Julio de 2011, se observa lo siguiente:

Para la subestación Valle de México en 230 kV la mayoria de interruptores instalados tiene una capacidad interruptiva de 50 kA

excepto uno de ellos, por lo tanto, actualmente se rebasa la capacidad interruptiva considerando que se supera este valor, para

el 2012 se espera una reducción con la modernización de la subestación y la reconfiguración de red, sin embargo el interruptor

de 40 kA sigue siendo rebasado. Para 2012 se tiene en programa la instalación de una nueva subestación encapsulada con

capacidad de 63 kA.

La subestación Santa Cruz en el nivel de 400 kV tiene instalados interruptores con capacidad de 40 kA y 31.5 kA, actualmente

no se esperan valores superiores a la capacidad instalada, sin embargo, se espera un incremento marginal en su valor hasta

llegar a 31.93 kA trifásico en 2015, para 2020 se espera un valor de 33.52 kA trifásico. Los cuatro interruptores rebasados

fueron fabricados en 1978 y 1984 se espera su modernización. En forma similar para esta subestación en el nivel de 230 kA se

tiene en su mayoría interruptores con capacidad de 50 kA, excepto cinco de 40 kA, para 2015 se espera un valor de 40.29 kA

monofásico, estos interruptores tienen fecha de fabricación de 1985,1986, 2001 y 2003.

La subestación La Paz en el nivel de 400 kV tiene instalados interruptores con capacidad de 40 kA y 31.5 kA, actualmente no

se esperan valores superiores a la capacidad instalada, sin embargo, se espera para 2013 un valor de 32.7 kA trifásico y para

2020 un valor de 35.69 kA trifásico, son tres interruptores que requieren su modernización. En el nivel de 230 kA no se rebasará

la capacidad.

La subestación San Bernabé en el nivel de 400 kV todos los interruptores instalados en 400 kV tienen una capacidad de 31.5

kA de fabricación en 1985, se espera un incremento gradual del nivel de corto circuito, actualmente se espera un valor de 28.4

kA, y para 2017 se rebasaría con 31.64 kA (0.14 kA), por lo cual se requiere su modernización a 40 kA, considerando que para

2020 se espera un valor máximo de 34.15 kA.

Un caso similar a San Bernabé es la subestación Teotihuacán en 400 kV. En donde los interruptores corresponden a 31.5 kA

de capacidad, se tiene rebasada su capacidad desde 2011 con un valor de 33.85 kA trifásico, para 2020 se espera un valor de

44.07 kA trifásico, se requiere su modernización con equipamiento adecuado.

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 24: Catalogo 2011-2020 r010212 Corto Circuito

24

Coordinación de PlanificaciónPRINCIPALES PROYECTOS DE TRANSMISIÓN Y TRANSFORMACIÓN

ÁREA CENTRAL

La subestación Remedios en el nivel de 230 kV tiene instalados interruptores con capacidad de 40 kA y 50 kA, para 2011 se

tiene un valor de 41.34 kA monofásico, los interruptores de 40 kA fueron instalados en 2011.

Con respecto al resto de subestaciones registradas en la información proporcionada por la ZTM no se observa equipo que

rebase actualmente y a futuro su capacidad.

Es relevante mencionar que el área de Planificación de la extinta Luz y Fuerza del Centro realizaba una revisión de los niveles

de corto circuito, y el área de transmisión de esta, tenia en proceso el reemplazo de equipo rebasado en su capacidad en los

distintos niveles de tensión.

Adicionalmente, se recomienda confirmar la capacidad instalada de las subestaciones en donde se observan valores superiores

a la capacidad instalada, debido a que actualmente continúan los trabajos de modernización por parte de la ZTM.

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 25: Catalogo 2011-2020 r010212 Corto Circuito

25

Coordinación de Planificación

ÁREA CENTRAL

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 1.76 1.76 1.76 1.76 1.76 1.76 1.76 1.76 1.76 1.76

1F 1.03 1.03 1.03 1.03 1.03 1.03 1.03 1.03 1.04 0.90

3F 8.21 7.62 9.24 9.24 9.26 9.26 9.27 9.31 9.32 9.36

1F 6.06 5.80 6.51 6.51 6.52 6.52 6.52 6.55 6.55 6.56

3F 13.86 13.94 14.00 13.98 14.03 14.03 14.04 14.07 14.07 14.14

1F 7.35 7.36 7.37 7.37 7.38 7.38 7.38 7.39 7.39 7.40

3F 19.37 19.88 19.97 19.93 20.17 20.17 20.19 20.24 20.25 19.38

1F 11.37 11.60 11.62 11.61 11.66 11.66 11.66 11.67 11.67 11.45

3F 26.05 26.01 26.24 26.24 26.31 26.76 26.79 27.36

1F 21.38 21.46 21.56 21.57 21.60 21.97 21.98 22.27

3F 7.85 7.85 7.85 7.85 7.85 7.86 7.86 7.86

1F 10.44 10.44 10.44 10.44 10.44 10.44 10.44 10.45

3F 2.98 2.98 3.74 3.74 3.74 3.74 3.74 3.74 3.75 3.75

1F 1.19 1.19 1.35 1.35 1.35 1.35 1.35 1.35 1.35 1.35

3F 4.47 4.48 4.83 4.83 4.83 4.83 4.83 4.83 4.83 4.83

1F 5.16 5.16 5.46 5.46 5.46 5.46 5.46 5.47 5.47 5.47

3F 4.55 4.56 4.93 4.93 4.93 4.93 4.93 4.93 4.93 4.93

1F 4.43 4.44 4.65 4.65 4.65 4.65 4.66 4.66 4.66 4.66

3F 2.34 2.35 2.35 2.35 2.35 2.35 2.35 2.35 2.35 2.35

1F 1.40 1.41 1.40 1.40 1.40 1.40 1.41 1.41 1.41 1.17

3F 3.91 4.07 4.07 4.08 4.08 4.08 4.07 4.09 4.09

1F 3.78 3.87 3.87 3.88 3.88 3.88 3.87 3.88 3.88

3F 4.71 6.55 7.24 7.23 7.24 7.24 7.24 7.21 7.29 7.29

1F 2.00 7.43 8.00 8.00 8.01 8.01 8.01 7.98 8.04 8.04

3F 4.08 4.37 4.44 4.44 4.45 4.45 4.45 4.44 4.45 4.45

1F 3.82 3.98 4.02 4.02 4.02 4.02 4.02 4.02 4.02 4.02

3F 4.15 4.45 4.53 4.52 4.53 4.53 4.53 4.52 4.53 4.53

1F 3.87 4.04 4.09 4.09 4.09 4.09 4.09 4.08 4.09 4.09

3F 26.07 26.10 28.74 28.69 29.63 29.64 29.85 30.67 30.67 31.20

1F 24.79 24.80 27.80 27.76 28.55 28.55 28.68 29.20 29.21 29.52

3F 7.56 7.56 7.58 7.58 7.58 7.58 7.58 7.59 7.59 7.59

1F 10.04 10.04 10.07 10.07 10.08 10.08 10.08 10.08 10.08 10.09

3F 7.56 7.56 7.58 7.58 7.58 7.58 7.58 7.59 7.59 7.59

1F 10.04 10.04 10.07 10.07 10.08 10.08 10.08 10.08 10.08 10.09

3F 20.00 20.01 20.31 20.31 20.51 20.53 20.69 21.22 21.21 21.39

1F 16.12 16.13 16.36 16.36 16.46 16.47 16.82 17.06 17.06 16.43

AGV

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

23-B

Agustín Millán Dos ANM2 400

Aguilas AGU

230

23-A

23-A

23-B

Agua Viva

115

85

Acambay ACA 115

230

23-B

Aculco AUO 115

Actopan AAN

85

23-A

230

23-A

Acolman ACM

85

Aceros Nacionales ACN 85

Aceros Corsa ACC

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 26: Catalogo 2011-2020 r010212 Corto Circuito

26

Coordinación de Planificación

ÁREA CENTRAL

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 17.37 17.40 17.44 17.45 17.47 17.47 17.69 17.78 17.77 17.81

1F 12.13 12.14 12.17 12.17 12.18 12.18 12.37 12.39 12.39 12.29

3F 14.72 14.71 14.91 14.91 15.05 15.05 15.14 15.60 15.60 15.73

1F 11.40 11.40 11.49 11.49 11.57 11.57 11.65 11.85 11.85 11.78

3F 21.40 21.55 21.65 21.60 23.08 23.08 23.09 23.20 23.20 14.88

1F 11.53 11.56 11.58 11.57 11.83 11.83 11.83 11.85 11.85 3.33

3F 3.00 3.07 3.07 3.07 3.07 3.07 3.11 3.11 3.11 3.11

1F 1.91 1.93 1.93 1.93 1.93 1.93 1.96 1.96 1.96 1.96

3F 8.65 8.65 8.68 8.68 8.70 8.70 8.70 8.72 8.72 8.74

1F 1.72 1.72 1.74 1.74 1.74 1.74 1.74 1.74 1.74 1.74

3F 4.82 4.82 4.82 4.82 4.83 4.83 4.83 4.83 4.83 4.83

1F 4.40 4.40 4.41 4.41 4.41 4.41 4.41 4.41 4.41 4.41

3F 4.82 4.82 4.82 4.82 4.83 4.83 4.83 4.83 4.83 4.83

1F 4.40 4.40 4.41 4.41 4.41 4.41 4.41 4.41 4.41 4.41

3F 4.82 4.82 4.82 4.82 4.83 4.83 4.83 4.83 4.83 4.83

1F 4.40 4.40 4.41 4.41 4.41 4.41 4.41 4.41 4.41 4.41

3F 28.28 28.23 29.54 29.54 29.74 30.84 30.84 31.64

1F 22.13 22.12 22.83 22.83 22.91 23.34 23.34 23.62

3F 7.76 7.76 7.77 7.77 7.77 7.78 7.78 7.78

1F 10.26 10.26 10.27 10.27 10.27 10.28 10.28 10.28

3F 7.76 7.76 7.77 7.77 7.77 7.78 7.78 7.78

1F 10.26 10.26 10.27 10.27 10.27 10.28 10.28 10.28

3F 9.01 9.01 9.03 9.03 9.05 9.05 9.06 9.08 9.08 9.09

1F 1.75 1.75 1.77 1.77 1.77 1.77 1.77 1.77 1.77 1.77

3F 17.03 18.73 21.28 21.27 21.41 21.41 21.50 21.64 21.66 21.96

1F 15.81 16.90 18.20 18.20 18.28 18.28 18.33 18.40 18.41 18.55

3F 16.20 16.68 17.63 17.63 17.66 17.66 17.68 17.72 17.72 17.79

1F 3.14 3.15 3.17 3.17 3.17 3.17 3.18 3.18 3.18 3.18

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

230

85

Apasco APA

23-B

Apaplastic AAP 85

Anáhuac ANH

230

23-A

23-B

23-C

Amomolulco AMO

85

23-A

Alpura ALP 85

Altamirano ATM 115

Agustín Millán ANM 115

Almoloya AYA 400

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 27: Catalogo 2011-2020 r010212 Corto Circuito

27

Coordinación de Planificación

ÁREA CENTRAL

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 18.61 18.80 18.94 18.94 18.90 19.15 19.18 19.26

1F 16.92 16.64 16.73 16.72 16.69 16.86 16.87 16.93

3F 9.82 9.65

1F 5.08 5.05

3F 9.20 9.18 12.30 12.30 12.30 12.30 12.30 12.31 12.31 12.31

1F 9.22 9.21 15.52 15.52 15.53 15.53 15.52 15.53 15.53 15.53

3F 4.70 4.69 7.76 7.76 7.76 7.76 7.76 7.77 7.77 7.77

1F 4.28 4.27 10.32 10.33 10.46 10.33 10.33 10.33 10.33 10.46

3F 6.28 6.26

1F 5.37 5.36

3F 6.22 6.20

1F 5.34 5.33

3F 2.56 2.59 2.59 2.59 2.59 2.59 2.61 2.61 2.61 2.61

1F 1.79 1.79 1.79 1.79 1.79 1.79 1.81 1.81 1.81 1.81

3F 2.24 2.25 2.25 2.25

1F 2.70 2.72 2.72 2.72

3F 23.33 27.23 27.47 27.46 27.73 27.74 27.90 28.23 28.26 28.83

1F 19.07 21.17 21.26 21.26 21.43 21.43 21.50 21.64 21.65 21.86

3F 17.56 17.57 17.89 17.88 18.10 18.10 18.20 18.44 18.45 18.59

1F 17.92 17.94 18.16 18.15 18.30 18.30 18.38 18.54 18.55 18.64

3F 14.50 14.51 14.58 14.57 14.62 14.62 14.65 14.70 14.70 14.73

1F 2.03 2.03 2.05 2.05 2.05 2.05 2.05 2.05 2.05 2.05

3F 12.08 12.08 12.09 12.09 12.09 12.09 12.09 12.10 12.10 12.10

1F 15.40 15.40 15.41 15.41 15.41 15.41 15.41 15.42 15.42 15.42

3F 7.54 7.54 7.55 7.55 7.55 7.55 7.55 7.56 7.56 7.56

1F 10.14 10.14 10.15 10.15 10.15 10.15 10.16 10.16 10.16 10.16

3F 8.34 8.34 8.35 8.35 8.35 8.35 8.35 8.36 8.36 8.36

1F 10.97 10.97 10.98 10.98 10.98 10.98 10.98 10.99 10.99 10.99

3F 6.55 6.55 6.56 6.55 6.56 6.56 6.56 6.56 6.56 6.56

1F 5.48 5.48 5.48 5.48 5.48 5.48 5.48 5.48 5.48 5.48

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

23-D

Atenco ATE

23-B

23-C

85

23-A

Armex ARX 230

230

115

69

Arcelia ANU

23-C

23-D

Aragón ARA

23-A

23-B

230

85

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 28: Catalogo 2011-2020 r010212 Corto Circuito

28

Coordinación de Planificación

ÁREA CENTRAL

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 21.78 21.98 22.45 22.42 22.88 22.89 23.00 23.72 23.73 24.61

1F 18.04 18.14 18.36 18.35 18.61 18.62 18.67 19.03 19.03 19.53

3F 8.19 8.19 8.19 8.19 8.20 8.20 8.20 8.21 8.21 8.22

1F 10.77 10.77 10.78 10.78 10.78 10.78 10.78 10.79 10.79 10.81

3F 8.31 8.31 8.32 8.31 8.32 8.32 8.32 8.33 8.33 8.34

1F 10.92 10.93 10.93 10.93 10.94 10.94 10.94 10.95 10.95 10.97

3F 8.31 8.31 8.32 8.31 8.32 8.32 8.32 8.33 8.33 8.34

1F 10.92 10.93 10.93 10.93 10.94 10.94 10.94 10.95 10.95 10.97

3F 7.66 7.66 7.67 7.67 7.68 7.68 7.68 7.71 7.71 7.72

1F 5.21 5.20 5.21 5.21 5.21 5.21 5.21 5.22 5.22 5.11

3F 6.58 6.58 6.59 6.59 6.59 6.59 6.59 6.61 6.61 6.62

1F 4.46 4.46 4.46 4.46 4.47 4.47 4.47 4.48 4.48 4.40

3F 9.15 9.14 9.22 9.22 9.27 9.27 9.30 9.47 9.47 9.51

1F 7.44 7.44 7.48 7.48 7.50 7.51 7.53 7.61 7.61 7.58

3F 14.80 14.79 14.84 14.84 14.88 14.88 14.89 15.00 15.00 15.04

1F 13.13 13.13 13.16 13.16 13.18 13.18 13.20 13.26 13.26 13.20

3F 1.92 1.93 2.08 2.08 2.08 2.08 2.08 2.08 2.08 2.08

1F 0.82 0.82 0.87 0.87 0.87 0.87 0.87 0.87 0.87 0.87

3F 1.19 1.19 1.20 1.20 1.20 1.20 1.20 1.20 1.20 1.20

1F 1.26 1.26 1.27 1.27 1.27 1.27 1.27 1.27 1.27 1.27

3F 34.09 34.40 35.96 34.52 35.09 35.11 35.17 35.67 37.35 37.69

1F 34.25 34.61 35.60 34.43 34.82 34.82 34.86 35.20 36.28 36.49

3F 19.20 19.95 20.87 20.75 20.83 20.83 20.84 20.78 21.19 21.23

1F 6.43 8.52 8.63 8.62 8.63 8.63 8.63 8.62 8.67 8.67

3F 8.60 8.60 8.61 8.60 8.61 8.61 8.61 8.61 8.62 8.62

1F 11.39 11.39 11.40 11.39 11.40 11.40 11.40 11.40 11.41 11.41

3F 9.29 9.29 9.30 9.29 9.30 9.30 9.30 9.30 9.31 9.31

1F 12.04 12.04 12.05 12.04 12.05 12.05 12.05 12.05 12.06 12.06

3F 7.91 7.91 7.92 7.91 7.91 7.91 7.91 7.92 7.92 7.93

1F 10.51 10.51 10.52 10.51 10.52 10.52 10.52 10.52 10.53 10.53

3F 13.81 13.90 13.96 13.94 13.99 13.99 14.00 14.03 14.03 14.08

1F 7.50 7.52 7.53 7.53 7.54 7.54 7.54 7.54 7.54 7.55

3F 7.55 7.56 7.56 7.57 7.57 7.57 7.65 7.66 7.66 7.67

1F 5.33 5.33 5.34 5.34 5.34 5.34 5.39 5.40 5.40 5.38

3F 12.69 12.69 12.75 12.74 12.78 12.78 12.80 12.84 12.84 12.87

1F 2.01 2.01 2.02 2.02 2.03 2.03 2.03 2.03 2.03 2.03

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Avante Textil AVT 85

Autometales AUM 85

Avándaro AVA 115

23-B

23-C

Aurora AUR

85

23-A

23

230

Atotonilco ANL

115

85

Atlacomulco Potencia AMP

Atlacomulco Industrial AIN 115

400

23-C

Atlacomulco ATU 115

Atizapán ATI

23-A

23-B

230

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 29: Catalogo 2011-2020 r010212 Corto Circuito

29

Coordinación de Planificación

ÁREA CENTRAL

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 21.85 22.10 22.63 22.24 22.48 22.49 22.52 18.23 23.17 23.29

1F 20.97 21.13 21.51 21.27 21.42 21.42 21.44 16.81 19.35 19.40

3F 14.40 15.78 17.75 17.67 17.72 17.73 17.73 17.46 18.05 18.07

1F 4.34 7.14 7.38 7.37 7.38 7.38 7.38 7.35 7.42 7.42

3F 9.22 9.23 9.24 9.23 9.23 9.23 9.23 9.15 9.24 9.25

1F 12.28 12.29 12.30 12.29 12.29 12.29 12.29 12.18 12.30 12.30

3F 8.31 8.31 8.32 8.31 8.32 8.32 8.32 8.24 8.32 8.33

1F 11.02 11.03 11.03 11.03 11.03 11.03 11.03 10.94 11.04 11.04

3F 7.51 7.52 7.52 7.52 7.52 7.52 7.52 7.46 7.53 7.53

1F 9.99 10.00 10.00 10.00 10.00 10.00 10.00 9.93 10.01 10.01

3F 33.33 33.41 34.65 34.58 36.56 36.57 36.87 38.57 38.58 39.84

1F 32.15 32.19 33.32 33.28 35.06 35.07 35.25 36.35 36.36 37.10

3F 9.01 9.01 9.01 9.01 9.03 9.03 9.03 9.04 9.04 9.05

1F 12.09 12.09 12.11 12.10 12.12 12.12 12.12 12.14 12.14 12.14

3F 8.96 8.96 8.97 8.97 8.98 8.98 8.98 8.99 8.99 9.00

1F 12.03 12.03 12.04 12.04 12.06 12.06 12.06 12.07 12.07 12.08

3F 8.96 8.96 8.97 8.97 8.98 8.98 8.98 8.99 8.99 9.00

1F 12.03 12.03 12.04 12.04 12.06 12.06 12.06 12.07 12.07 12.08

3F 26.64 23.25 23.98 27.09 27.40 27.41 27.30 27.62 27.69 27.86

1F 22.87 20.98 21.54 23.26 23.40 23.41 23.34 23.56 23.59 23.67

3F 8.54 8.50 8.51 8.54 8.55 8.55 8.55 8.55 8.55 8.55

1F 11.02 10.97 10.99 11.02 11.03 11.03 11.03 11.03 11.03 11.03

3F 8.55 8.51 8.52 8.55 8.55 8.55 8.55 8.56 8.56 8.56

1F 11.02 10.98 10.99 11.03 11.03 11.03 11.03 11.03 11.04 11.04

3F 22.79 23.50 23.63 23.57 23.91 23.91 23.93 24.01 24.01 22.81

1F 13.62 13.95 13.98 13.97 14.04 14.04 14.04 14.06 14.06 13.74

3F 5.30 5.31 5.32 5.32 5.32 5.32 5.32 5.32 5.32 5.30

1F 4.66 4.67 4.67 4.67 4.67 4.67 4.67 4.67 4.67 4.66

3F 5.30 5.31 5.32 5.32 5.32 5.32 5.32 5.32 5.32 5.30

1F 4.66 4.67 4.67 4.67 4.67 4.67 4.67 4.67 4.67 4.66

3F 20.96 21.11 21.21 21.16 22.64 22.64 22.66 22.76 22.76 14.74

1F 11.21 11.24 11.26 11.25 11.51 11.51 11.51 11.52 11.52 3.31

3F 22.40 22.42 23.15 23.12 24.99 25.00 25.14 25.82 25.82 26.28

1F 19.10 19.11 19.29 19.28 21.19 21.19 21.26 21.60 21.60 21.81

3F 20.83 21.42 21.53 21.47 21.76 21.76 21.77 21.84 21.84 20.84

1F 12.32 12.59 12.61 12.60 12.66 12.66 12.66 12.67 12.68 12.42

AZC

ATK

BAR

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Campo Hermanos CHE 85

Becton and Dickinson BDK 85

Bosques BOS 230

23-A

23-B

Barrientos

23-B

85

Azteca

230

23-A

23-B

23-C

Azcapotzalco

230

23-A

23-B

23-C

Ayotla AYO

85

23-A

230

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 30: Catalogo 2011-2020 r010212 Corto Circuito

30

Coordinación de Planificación

ÁREA CENTRAL

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 2.96 2.96 2.97 2.97 2.97 2.97 2.97 2.97 2.97 2.97

1F 2.00 2.00 2.00 2.00 2.00 2.00 2.00 2.00 2.00 1.98

3F 26.82 27.13 27.14 27.00 27.06 27.14 27.29

1F 25.70 25.89 25.89 25.79 25.82 25.87 25.96

3F 7.86 7.86 7.86 7.86 7.86 7.86 7.86

1F 10.45 10.45 10.45 10.45 10.45 10.45 10.45

3F 7.86 7.86 7.86 7.86 7.86 7.86 7.86

1F 10.45 10.45 10.45 10.45 10.45 10.45 10.45

3F 19.54 21.53 21.63 21.60 21.74 21.74 21.76 21.85 21.85 21.87

1F 8.37 8.99 9.00 9.00 9.01 9.01 9.02 9.03 9.03 9.02

3F 4.88 4.92 4.92 4.92 4.92 4.92 4.92 4.92 4.92 4.92

1F 4.34 4.36 4.36 4.36 4.36 4.36 4.36 4.36 4.36 4.36

3F 5.86 5.91 5.91 5.91 5.91 5.91 5.91 5.91 5.91 5.91

1F 5.10 5.12 5.12 5.12 5.12 5.12 5.12 5.13 5.13 5.13

3F 4.66 4.69 4.69 4.69 4.69 4.69 4.69 4.69 4.69 4.69

1F 4.16 4.18 4.18 4.18 4.18 4.18 4.18 4.18 4.18 4.18

3F 5.02 5.05 5.05 5.05 5.05 5.05 5.05 5.06 5.06 5.06

1F 4.45 4.47 4.47 4.47 4.47 4.47 4.47 4.47 4.47 4.47

3F 5.41 5.36 5.57 5.57 5.58 5.58 5.58 5.58 5.58 5.58

1F 2.85 2.84 2.88 2.88 2.88 2.88 2.88 2.88 2.88 2.88

3F 3.21 3.20 3.22 3.22 3.22 3.22 3.22 3.22 3.22 3.22

1F 3.07 3.07 3.08 3.08 3.08 3.08 3.08 3.08 3.08 3.08

3F 3.21 3.20 3.22 3.22 3.22 3.22 3.22 3.22 3.22 3.22

1F 3.07 3.07 3.08 3.08 3.08 3.08 3.08 3.08 3.08 3.08

3F 26.82 24.72 25.59 25.56 25.85 25.86 25.98 26.87 26.88 28.62

1F 22.59 20.75 21.11 21.10 21.27 21.27 21.33 21.85 21.86 23.15

3F 7.56 7.54 7.55 7.55 7.55 7.55 7.56 7.56 7.56 7.58

1F 10.05 10.02 10.03 10.03 10.04 10.04 10.04 10.05 10.05 10.06

3F 7.56 7.54 7.55 7.55 7.55 7.55 7.56 7.56 7.56 7.58

1F 10.05 10.02 10.03 10.03 10.04 10.04 10.04 10.05 10.05 10.06

3F 7.56 7.54 7.55 7.55 7.55 7.55 7.56 7.56 7.56 7.58

1F 10.05 10.02 10.03 10.03 10.04 10.04 10.04 10.05 10.05 10.06

3F 28.33 24.52 25.34 27.94 28.28 28.28 28.16 28.41 28.49 28.66

1F 23.95 21.86 22.47 24.19 24.35 24.35 24.27 24.42 24.46 24.54

3F 4.62 4.64 4.64 4.78 4.76 4.67 4.71 4.77 4.77 4.94

1F 3.62 3.63 3.63 3.71 3.70 3.61 3.42 3.44 3.45 1.71

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Cd. Hidalgo CDH 115

23-C

Cartón y Papel CPM 230

Cartagena CTG

23-A

23-B

23-B

230

Carmen CRM

85

23-A

23-C

23-D

Careaga CAR

23-A

23-B

23-B

85

Caracol CRO

230

23-A

Canchezda CCD 115

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 31: Catalogo 2011-2020 r010212 Corto Circuito

31

Coordinación de Planificación

ÁREA CENTRAL

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 24.64 25.50 26.12 26.06 26.39 26.39 26.53 27.61 27.63 29.68

1F 20.21 20.64 20.92 20.89 21.07 21.07 21.13 21.73 21.74 23.13

3F 9.27 9.28 9.29 9.29 9.29 9.29 9.29 9.30 9.30 9.33

1F 12.32 12.34 12.35 12.35 12.35 12.35 12.35 12.37 12.37 12.40

3F 9.27 9.28 9.29 9.29 9.29 9.29 9.29 9.30 9.30 9.33

1F 12.32 12.34 12.35 12.35 12.35 12.35 12.35 12.37 12.37 12.40

3F 7.54 7.55 7.56 7.56 7.56 7.56 7.56 7.57 7.57 7.58

1F 10.02 10.03 10.04 10.04 10.04 10.04 10.04 10.05 10.05 10.07

3F 19.84 28.04 28.31 28.30 28.61 28.62 28.79 29.17 29.21 29.90

1F 15.69 20.50 20.59 20.59 20.79 20.79 20.86 21.00 21.02 21.24

3F 20.07 20.46 20.56 20.50 20.81 20.81 20.82 20.88 20.88 19.72

1F 12.47 12.65 12.67 12.66 12.73 12.73 12.73 12.74 12.74 12.42

3F 9.58 9.77 9.99 9.99 10.00 10.00 10.00 10.02 10.02 10.04

1F 2.34 2.35 2.35 2.35 2.35 2.35 2.35 2.35 2.35 2.36

3F 9.98 10.28 10.36 10.36 10.37 10.37 10.38 10.39 10.39 10.41

1F 1.92 1.93 1.93 1.93 1.93 1.93 1.93 1.93 1.93 1.93

3F 9.07 9.26 9.40 9.40 9.41 9.41 9.41 9.42 9.43 9.45

1F 2.12 2.13 2.13 2.13 2.13 2.13 2.13 2.13 2.13 2.13

3F 3.98 4.00 4.00 4.00 4.00 4.00 4.04 4.04 4.04 4.04

1F 2.97 2.98 2.98 2.98 2.98 2.98 3.00 3.01 3.01 3.00

3F 37.54 31.12 32.44 35.74 36.31 36.32 36.10 36.37 36.51 36.79

1F 38.21 33.05 34.27 37.16 37.52 37.53 37.34 37.56 37.66 37.85

3F 30.07 27.92 29.09 28.19 29.40 29.40 29.40 29.45 29.46 28.99

1F 18.18 17.07 17.37 17.13 17.44 17.44 17.44 17.45 17.45 17.33

3F 7.92 7.89 7.90 7.92 7.92 7.92 7.92 7.92 7.92 7.92

1F 10.53 10.49 10.50 10.52 10.53 10.53 10.53 10.53 10.53 10.53

3F 7.92 7.89 7.90 7.92 7.92 7.92 7.92 7.92 7.92 7.92

1F 10.53 10.49 10.50 10.52 10.53 10.53 10.53 10.53 10.53 10.53

3F 14.61 20.49 20.44 20.41 20.52 20.52 20.53 20.60 20.61 20.64

1F 6.25 7.66 7.55 7.55 7.56 7.56 7.56 7.57 7.57 7.56

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

23-B

Cervecería Modelo CVM 85

Cerro Gordo CRG

85

23-A

Cerro del Campo (Amatepec) CCM 115

230

Cementos Hidalgo CMH 85

Cementos Tolteca TLT 85

Cementos Anáhuac CAH 85

Cementos Apasco CEA 85

23-C

Cementera Cruz Azul 230 kV CCZ 230

Ceilán CEI

23-A

23-B

230

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 32: Catalogo 2011-2020 r010212 Corto Circuito

32

Coordinación de Planificación

ÁREA CENTRAL

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 17.28 17.39

1F 12.88 12.92

3F 18.13 17.88 18.04 18.04 18.06 15.23 21.01 21.11

1F 6.03 6.01 6.02 6.02 6.02 5.79 17.31 17.35

3F 8.97 10.48 13.38 13.33 13.37 13.37 13.37 13.19 13.57 13.58

1F 3.23 6.33 6.93 6.93 6.93 6.93 6.93 6.90 6.97 6.97

3F 4.50 4.59 7.75 7.75 7.75 7.75 7.75 7.69 7.80 7.80

1F 4.13 4.18 10.23 10.22 10.23 10.23 10.23 10.16 10.37 10.37

3F 4.50 4.59 7.75 7.75 7.75 7.75 7.75 7.69 7.80 7.80

1F 4.13 4.18 10.23 10.22 10.23 10.23 10.23 10.16 10.37 10.37

3F 4.50 4.59

1F 4.13 4.18

3F 4.46 4.55

1F 4.10 4.15

3F 41.03 38.08 40.32 39.77 40.41 40.42 40.31 40.87 41.31 41.71

1F 36.50 34.78 36.08 35.35 35.69 35.69 35.62 35.98 36.21 36.40

3F 9.00 8.99 9.00 9.00 9.00 9.00 9.00 9.00 9.00 9.00

1F 11.90 11.88 11.89 11.89 11.89 11.89 11.89 11.89 11.90 11.90

3F 9.00 8.99 9.00 9.00 9.00 9.00 9.00 9.00 9.00 9.00

1F 11.90 11.88 11.89 11.89 11.89 11.89 11.89 11.89 11.90 11.90

3F 8.74 8.73 8.74 8.74 8.74 8.74 8.74 8.74 8.74 8.75

1F 11.25 11.23 11.25 11.24 11.25 11.25 11.24 11.25 11.25 11.25

3F 20.77 20.96 20.96 20.96 21.13 21.44 21.54

1F 15.86 15.93 15.93 15.93 16.00 16.12 16.16

3F 7.79 7.79 7.80 7.79 7.80 7.80 7.80

1F 10.36 10.36 10.36 10.36 10.36 10.37 10.37

3F 7.79 7.79 7.80 7.79 7.80 7.80 7.80

1F 10.36 10.36 10.36 10.36 10.36 10.37 10.37

3F 27.66 27.67 28.03 30.28 30.29 31.02

1F 25.01 25.01 25.23 26.73 26.74 27.14

3F 38.27 38.28 38.62 40.44 40.45 41.75

1F 40.66 40.66 40.92 42.41 42.42 43.39

3F 26.57 26.53 31.40 31.40 31.63 32.80 32.80 33.62

1F 22.69 22.67 29.19 29.20 29.33 30.05 30.05 30.52

3F 7.75 7.75 7.78 7.78 7.78 7.79 7.79 7.79

1F 10.24 10.24 10.29 10.29 10.29 10.30 10.30 10.30

230

23-A

Chimalpa

Chimalpa Dos

CHM

CHD

400

230

23-A

23-B

Chicoloapan CHC

23-C

230

Chapingo CPG

23-A

23-B

23-D

230

Chalco CHA

23-B

23-C

85

23-A

400

230

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 33: Catalogo 2011-2020 r010212 Corto Circuito

33

Coordinación de Planificación

ÁREA CENTRAL

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 18.75 19.01 19.65 19.52 19.75 19.76 19.81 19.95 19.99 20.10

1F 16.15 16.28 16.83 16.77 16.88 16.88 16.91 16.98 17.01 17.06

3F 12.24 12.24 12.25 12.25 12.25 12.25 12.26 12.26 12.26 12.26

1F 15.43 15.43 15.45 15.44 15.45 15.45 15.45 15.45 15.45 15.45

3F 7.54 7.55 7.56 7.55 7.56 7.56 7.56 7.56 7.56 7.56

1F 10.03 10.03 10.05 10.04 10.05 10.05 10.05 10.05 10.05 10.05

3F 7.94 7.94 7.95 7.95 7.95 7.95 7.96 7.96 7.96 7.96

1F 10.53 10.53 10.54 10.54 10.55 10.55 10.55 10.55 10.55 10.55

3F 12.03 12.03 12.08 12.08 12.12 12.12 12.13 12.17 12.17 12.19

1F 2.02 2.02 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03

3F 28.81 29.69 30.54 30.48 31.01 31.01 31.21 32.73 32.75 35.40

1F 25.50 26.05 26.50 26.47 26.82 26.82 26.92 27.93 27.94 30.19

3F 7.87 7.88 7.89 7.89 7.89 7.89 7.89 7.90 7.90 7.91

1F 10.47 10.48 10.48 10.48 10.49 10.49 10.49 10.50 10.50 10.52

3F 26.91 27.59 28.31 28.27 28.75 28.76 28.93 30.20 30.22 32.33

1F 22.92 23.31 23.66 23.64 23.94 23.94 24.02 24.79 24.79 26.39

3F 7.86 7.86 7.87 7.87 7.87 7.87 7.88 7.88 7.88 7.90

1F 10.45 10.45 10.46 10.46 10.47 10.47 10.47 10.48 10.48 10.49

3F 17.58 25.26 25.28 25.24 25.41 25.41 25.44 25.54 25.55 25.59

1F 7.04 8.65 8.64 8.64 8.65 8.65 8.66 8.66 8.66 8.66

3F 3.73 3.73 3.74 3.74 3.74 3.74 3.74 3.74 3.74 3.75

1F 2.58 2.58 2.58 2.58 2.59 2.59 2.59 2.59 2.59 2.58

3F 20.46 20.43 20.88 20.88 20.98 21.37 21.37 21.62

1F 3.08 3.08 3.09 3.09 3.09 3.10 3.10 3.10

3F 9.98 10.02

1F 4.48 4.58

3F 4.52 4.52 7.68 7.68 7.69 7.69 7.69 7.69 7.69 7.70

1F 4.13 4.13 9.95 9.95 9.95 9.95 9.96 9.96 9.96 9.97

3F 4.52 4.52 7.68 7.68 7.69 7.69 7.69 7.69 7.69 7.70

1F 4.13 4.13 9.95 9.95 9.95 9.95 9.96 9.96 9.96 9.9723-B

Condesa CDS

85

23-A

Comalco COM 115

230

23

Colgate CGT 85

Cofradía Dos CFD

23

230

Cofradía CFI

Coca Cola COK 85

230

23-B

23-C

Coapa COA

230

23-A

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 34: Catalogo 2011-2020 r010212 Corto Circuito

34

Coordinación de Planificación

ÁREA CENTRAL

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 23.47 23.49 24.93 24.89 25.96 25.97 26.13 26.80 26.80 27.25

1F 20.88 20.89 22.36 22.34 23.28 23.28 23.37 23.74 23.74 23.98

3F 8.66 8.66 8.68 8.68 8.69 8.69 8.69 8.70 8.70 8.71

1F 11.09 11.09 11.11 11.11 11.12 11.12 11.13 11.13 11.13 11.14

3F 8.57 8.57 8.59 8.59 8.60 8.60 8.60 8.61 8.61 8.61

1F 11.03 11.03 11.05 11.05 11.07 11.07 11.07 11.08 11.08 11.08

3F 8.62 8.62 8.63 8.63 8.65 8.65 8.65 8.66 8.66 8.66

1F 11.10 11.10 11.12 11.12 11.13 11.13 11.14 11.14 11.14 11.15

3F 15.87 15.91 16.38 16.35 16.53 16.53 16.59 16.75 16.75 16.86

1F 12.41 12.43 12.79 12.78 12.85 12.85 12.88 12.95 12.95 12.99

3F 8.07 8.07 8.08 8.08 8.09 8.09 8.09 8.09 8.09 8.09

1F 9.19 9.19 9.20 9.20 9.20 9.20 9.20 9.21 9.21 9.21

3F 8.07 8.07 8.08 8.08 8.09 8.09 8.09 8.09 8.09 8.09

1F 9.19 9.19 9.20 9.20 9.20 9.20 9.20 9.21 9.21 9.21

3F 7.42 7.42 7.43 7.43 7.43 7.43 7.43 7.44 7.44 7.44

1F 9.86 9.86 9.88 9.88 9.88 9.88 9.88 9.89 9.89 9.89

3F 9.25 10.48 12.61 12.57 12.60 12.60 12.60 12.45 12.77 12.79

1F 3.30 5.86 6.26 6.25 6.25 6.26 6.26 6.23 6.28 6.28

3F 4.51 4.58 4.68 4.67 4.67 4.67 4.68 4.67 4.68 4.68

1F 4.03 4.07 4.12 4.12 4.12 4.12 4.12 4.11 4.12 4.12

3F 19.79 19.81 23.77 23.73 24.32 24.32 24.46 24.98 24.98 25.32

1F 9.00 9.00 9.70 9.69 9.76 9.76 9.77 9.83 9.83 9.86

3F 8.22 8.22 8.27 8.27 8.28 8.28 8.28 8.29 8.29 8.29

1F 10.70 10.70 10.76 10.76 10.77 10.77 10.77 10.78 10.78 10.78

3F 8.32 8.32 8.38 8.38 8.39 8.39 8.39 8.39 8.39 8.40

1F 10.83 10.83 10.90 10.90 10.91 10.91 10.91 10.91 10.91 10.92

3F 8.32 8.32 8.38 8.38 8.39 8.39 8.39 8.39 8.39 8.40

1F 10.83 10.83 10.90 10.90 10.91 10.91 10.91 10.91 10.91 10.92

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

23-C

Coyoacán COY

23-A

23-B

23-A

230

Covadonga CVD

23-C

85

Contreras CRS

23-A

23-B

23-C

230

Contadero CTD

23-A

23-B

230

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 35: Catalogo 2011-2020 r010212 Corto Circuito

35

Coordinación de Planificación

ÁREA CENTRAL

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 24.74 24.75 24.87 25.52 25.54 26.51

1F 17.60 17.60 17.64 17.91 17.91 18.41

3F 10.94 10.97 10.99 10.98 14.83 14.83 14.84 14.88 14.88 12.47

1F 4.89 4.89 4.89 4.89 5.30 5.30 5.30 5.30 5.30 2.53

3F 9.49 9.49 9.49 9.49 9.67 9.67 9.67 9.67 9.67 9.57

1F 9.46 9.47 9.47 9.47 9.59 9.59 9.59 9.59 9.59 9.52

3F 9.07 9.07 9.07 9.07 9.22 9.22 9.22 9.22 9.22 9.14

1F 9.10 9.10 9.10 9.10 9.20 9.20 9.20 9.20 9.20 9.14

3F 4.47 4.47 4.47 4.47 4.60 4.60 4.60 4.60 4.60 4.53

1F 4.07 4.07 4.07 4.07 4.14 4.14 4.14 4.14 4.14 4.10

3F 24.01 24.04 24.64 24.60 25.10 25.11 25.26 25.81 25.81 26.14

1F 19.91 19.92 20.36 20.35 20.60 20.61 20.68 20.93 20.93 21.08

3F 12.93 12.93 12.94 12.94 12.96 12.96 12.96 12.97 12.97 12.98

1F 16.66 16.66 16.68 16.68 16.70 16.70 16.70 16.72 16.72 16.73

3F 12.83 12.83 12.84 12.84 12.86 12.86 12.86 12.87 12.87 12.88

1F 16.52 16.52 16.54 16.54 16.55 16.55 16.56 16.57 16.57 16.58

3F 10.89 10.89 10.90 10.90 10.91 10.91 10.92 10.93 10.93 10.93

1F 13.81 13.81 13.82 13.82 13.83 13.83 13.84 13.85 13.85 13.85

3F 21.53 20.07 20.57 21.71 21.93 21.93 21.86 21.95 22.00 22.10

1F 17.68 16.96 17.80 18.96 19.06 19.07 19.02 19.07 19.09 19.15

3F 9.22 9.19 9.20 9.22 9.22 9.22 9.22 9.22 9.23 9.23

1F 12.26 12.22 12.24 12.27 12.27 12.27 12.27 12.27 12.27 12.28

3F 9.22 9.19 9.20 9.22 9.22 9.22 9.22 9.22 9.23 9.23

1F 12.26 12.22 12.24 12.27 12.27 12.27 12.27 12.27 12.27 12.28

3F 21.09 21.23 21.32 21.27 23.84 23.84 23.85 23.96 23.96 15.78

1F 10.94 10.97 10.98 10.97 11.38 11.38 11.39 11.40 11.40 3.31

3F 9.62 9.62 9.62 9.62 9.66 9.66 9.66 9.66 9.66 9.50

1F 9.53 9.53 9.53 9.53 9.55 9.55 9.55 9.56 9.56 9.44

3F 5.07 5.08 5.08 5.08 5.11 5.11 5.11 5.11 5.11 4.96

1F 4.49 4.49 4.49 4.49 4.51 4.51 4.51 4.51 4.51 4.43

3F 5.12 5.12 5.12 5.12 5.16 5.16 5.16 5.16 5.16 5.01

1F 4.52 4.52 4.52 4.52 4.54 4.54 4.54 4.54 4.54 4.46

3F 5.12 5.12 5.12 5.12 5.16 5.16 5.16 5.16 5.16 5.01

1F 4.52 4.52 4.52 4.52 4.54 4.54 4.54 4.54 4.54 4.46

3F 4.81 4.81 4.81 4.81 4.84 4.84 4.84 4.84 4.84 4.71

1F 4.28 4.28 4.28 4.28 4.29 4.29 4.30 4.30 4.30 4.22

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

23-E

Cuautitlán CTT

23-C

23-D

23-A

23-B

23-B

85

Cuauhtémoc CMC

230

23-A

23-B

23-C

Cuajimalpa CJM

230

23-A

23-B

23-C

Coyotepec CYO

85

23-A

230

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 36: Catalogo 2011-2020 r010212 Corto Circuito

36

Coordinación de Planificación

ÁREA CENTRAL

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 5.56 5.56 5.59 5.59 5.61 5.61 5.63 5.63 5.63 5.63

1F 4.46 0.00 4.47 4.47 4.48 4.48 4.52 4.52 4.52 4.52

3F 4.45 4.45 4.46 4.46 4.46 4.46 4.47 4.47 4.47 4.47

1F 4.80 4.80 4.80 4.80 4.81 4.81 4.81 4.81 4.81 4.81

3F 4.45 4.45 4.46 4.46 4.46 4.46 4.47 4.47 4.47 4.47

1F 4.80 4.80 4.80 4.80 4.81 4.81 4.81 4.81 4.81 4.81

3F 4.16 4.16 4.17 4.17 4.17 4.17 4.17 4.17 4.17 4.17

1F 4.46 4.46 4.47 4.47 4.47 4.47 4.47 4.47 4.47 4.47

3F 20.41 20.26 20.49 20.50 20.55 20.70 20.78 20.90

1F 16.81 16.74 16.84 16.85 16.87 16.94 16.98 17.03

3F 7.68 7.68 7.68 7.68 7.68 7.68 7.69 7.69

1F 10.16 10.15 10.16 10.16 10.16 10.16 10.16 10.16

3F 7.68 7.68 7.68 7.68 7.68 7.68 7.69 7.69

1F 10.16 10.15 10.16 10.16 10.16 10.16 10.16 10.16

3F 25.77 25.85 26.06 25.92 26.60 26.60 26.62 26.70 26.70 24.08

1F 19.09 19.10 19.17 19.12 19.35 19.35 19.35 19.38 19.38 18.34

3F 16.93 16.94 17.34 17.32 17.57 17.58 17.71 18.16 18.16 18.34

1F 13.54 13.54 13.78 13.77 13.90 13.90 13.98 14.18 14.18 14.19

3F 17.62 17.63 17.92 17.91 18.08 18.09 18.17 18.43 18.43 18.56

1F 18.00 18.00 18.38 18.37 18.50 18.50 18.57 18.75 18.76 18.82

3F 7.75 7.75 7.75 7.75 7.75 7.75 7.76 7.76

1F 10.31 10.31 10.32 10.32 10.32 10.33 10.33 10.33

3F 19.08 19.25 19.25 19.20 19.27 19.30 19.38

1F 14.35 14.42 14.42 14.39 14.42 14.43 14.46

3F 7.66 7.66 7.66 7.66 7.66 7.66 7.66

1F 10.13 10.13 10.13 10.13 10.13 10.13 10.13

3F 7.66 7.66 7.66 7.66 7.66 7.66 7.66

1F 10.13 10.13 10.13 10.13 10.13 10.13 10.13

3F 21.81 21.83 22.16 22.16 22.38 22.40 22.64 23.26 23.25 23.46

1F 18.44 18.45 18.75 18.76 18.88 18.89 19.47 19.79 19.79 18.72

3F 31.18 31.27 31.41 31.43 31.52 31.52 32.14 32.41 32.41 32.51

1F 26.23 26.27 26.41 26.42 26.47 26.47 27.28 27.42 27.42 26.84

3F 32.21 32.29 32.44 32.47 32.56 32.55 33.29 33.59 33.58 33.71

1F 27.00 27.03 27.18 27.20 27.25 27.25 28.15 28.30 28.30 27.51

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

115-A

115-B

Donato Guerra DON

23-B

400

Diana DNA

230

23-A

230

23-A

Deportiva DVA

De Acero DCO 85

400

23-A

23-B

Culhuacán CHN

23-C

230

Cuernavaca CUE

23-A

23-B

85

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 37: Catalogo 2011-2020 r010212 Corto Circuito

37

Coordinación de Planificación

ÁREA CENTRAL

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 28.36 24.44 25.23 26.64 26.94 26.95 26.81 26.90 26.97 27.12

1F 23.63 21.43 21.89 22.68 22.60 22.60 22.52 22.57 22.60 22.67

3F 12.40 12.37 12.38 12.39 12.39 12.39 12.39 12.39 12.39 12.39

1F 11.65 11.62 11.63 11.64 11.64 11.64 11.64 11.64 11.64 11.64

3F 10.41 10.38 10.39 10.40 10.40 10.40 10.40 10.40 10.40 10.40

1F 7.80 7.79 7.79 7.80 7.80 7.80 7.80 7.80 7.80 7.80

3F 7.68 7.65 7.65 7.67 7.67 7.67 7.67 7.67 7.67 7.67

1F 6.21 6.19 6.20 6.20 6.20 6.20 6.20 6.20 6.20 6.20

3F 7.68 7.65 7.66 7.67 7.67 7.67 7.67 7.67 7.67 7.67

1F 6.21 6.20 6.20 6.21 6.21 6.21 6.20 6.20 6.21 6.21

3F 7.76 7.72 7.73 7.75 7.75 7.75 7.75 7.75 7.75 7.75

1F 6.26 6.25 6.25 6.26 6.25 6.25 6.25 6.25 6.25 6.26

3F 7.76 7.73 7.74 7.75 7.75 7.75 7.75 7.75 7.75 7.75

1F 6.26 6.25 6.25 6.26 6.26 6.26 6.26 6.26 6.26 6.26

3F 28.36 24.44 25.23 26.64

1F 23.63 21.43 21.89 22.68

3F 6.56 6.53 6.54 6.55

1F 8.84 8.81 8.82 8.83

3F 12.12 12.12 12.26 12.26 12.37 12.37 12.42 12.54 12.55 12.62

1F 10.82 10.82 10.90 10.89 10.96 10.96 10.98 11.05 11.05 11.09

3F 8.50 8.50 8.51 8.51 8.52 8.52 8.52 8.52 8.52 8.53

1F 11.02 11.02 11.03 11.03 11.04 11.04 11.04 11.05 11.05 11.05

3F 8.79 8.79 8.80 8.80 8.80 8.80 8.80 8.81 8.81 8.81

1F 11.48 11.48 11.49 11.49 11.50 11.50 11.50 11.51 11.51 11.51

3F 7.59 7.59 7.60 7.60 7.60 7.60 7.60 7.61 7.61 7.61

1F 10.11 10.11 10.12 10.12 10.13 10.13 10.13 10.13 10.13 10.14

3F 2.36 2.62 2.62 2.62 2.62 2.62 2.67 2.67 2.67 2.67

1F 1.37 1.43 1.43 1.43 1.43 1.43 1.47 1.47 1.47 1.47

3F 16.33 16.29 16.46 16.47 16.52 16.65 16.65 16.75

1F 13.05 13.04 13.11 13.12 13.14 13.20 13.20 13.24

3F 7.71 7.71 7.72 7.72 7.72 7.72 7.72 7.72

1F 10.26 10.26 10.27 10.27 10.27 10.27 10.27 10.27

3F 7.71 7.71 7.72 7.72 7.72 7.72 7.72 7.72

1F 10.26 10.26 10.27 10.27 10.27 10.27 10.27 10.27

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

23-B

El Rosal ROS

230

23-A

23-C

El Gallo GLL 115

El Cerrillo ECR

23-A

23-B

23

230

Ecatepec móvil ETM

23-C2

230

Ecatepec ECA

23-B2

23-C1

23-A2

23-B1

230

23-A1

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 38: Catalogo 2011-2020 r010212 Corto Circuito

38

Coordinación de Planificación

ÁREA CENTRAL

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 14.68 14.67 14.81 14.80 14.99 14.99 15.04 15.23 15.23 15.42

1F 11.08 11.09 11.15 11.14 11.24 11.24 11.26 11.33 11.33 11.40

3F 9.43 9.43 9.44 9.44 9.44 9.44 9.45 9.45 9.45 9.46

1F 12.23 12.23 12.24 12.24 12.25 12.25 12.25 12.26 12.26 12.27

3F 7.67 7.67 7.68 7.68 7.68 7.68 7.68 7.69 7.69 7.69

1F 10.21 10.21 10.21 10.21 10.22 10.22 10.22 10.22 10.22 10.23

3F 20.75 18.65 19.15 19.35 19.50 19.50 19.46 19.72 19.75 19.84

1F 18.39 17.20 17.99 17.66 17.75 17.75 17.71 17.90 17.92 17.98

3F 10.17 9.99 9.39 9.41 9.42 9.42 9.42 9.44 9.45 9.45

1F 5.33 5.29 5.18 5.18 5.19 5.19 5.19 5.19 5.19 5.19

3F 16.22 16.23 16.48 16.47 16.62 16.62 16.69 16.91 16.91 17.02

1F 15.24 15.25 15.49 15.48 15.57 15.57 15.62 15.75 15.75 15.80

3F 9.12 9.12 9.13 9.13 9.14 9.14 9.14 9.15 9.15 9.15

1F 12.16 12.16 12.17 12.17 12.17 12.17 12.18 12.18 12.18 12.19

3F 9.10 9.10 9.11 9.11 9.11 9.11 9.11 9.12 9.12 9.12

1F 12.12 12.12 12.13 12.13 12.14 12.14 12.14 12.15 12.15 12.15

3F 8.34 8.34 8.35 8.35 8.35 8.35 8.35 8.36 8.36 8.36

1F 10.49 10.49 10.50 10.50 10.50 10.50 10.50 10.51 10.51 10.51

3F 7.71 7.71 7.72 7.72 7.72 7.72 7.72 7.73 7.73 7.73

1F 10.27 10.27 10.27 10.27 10.28 10.28 10.28 10.29 10.29 10.29

3F 24.00 24.69 25.79 25.49 25.84 25.85 25.92 26.17 26.40 26.57

1F 19.74 20.07 20.62 20.50 20.65 20.65 20.67 20.78 20.87 20.94

3F 18.15 18.47 19.97 19.83 20.05 20.06 20.11 20.25 20.32 20.43

1F 13.97 14.11 15.26 15.21 15.29 15.30 15.31 15.37 15.40 15.44

3F 16.64 16.56 16.72 16.73 16.77 16.87 16.89 16.97

1F 13.33 13.29 13.36 13.36 13.38 13.43 13.44 13.47

3F 7.72 7.72 7.72 7.72 7.72 7.73 7.73 7.73

1F 10.27 10.27 10.27 10.27 10.27 10.28 10.28 10.28

3F 7.72 7.72 7.72 7.72 7.72 7.73 7.73 7.73

1F 10.27 10.27 10.27 10.27 10.27 10.28 10.28 10.28

3F 33.36 34.89 36.10 36.03 36.65 36.66 36.93 39.19 39.22 43.66

1F 32.96 34.18 34.97 34.93 35.48 35.49 35.66 37.65 37.68 43.08

3F 28.28 28.55 28.73 28.64 30.45 30.45 30.47 30.65 30.66 17.20

1F 16.98 17.05 17.09 17.07 17.46 17.46 17.46 17.50 17.50 3.64

3F 25.64 25.86 26.01 25.94 27.26 27.26 27.28 27.42 27.43 16.05

1F 15.74 15.79 15.83 15.81 16.11 16.11 16.11 16.15 16.15 3.58

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Fundidora México FUM 85

FNM-Lecheria FNL 230

Ford Motor Company FMC 85

23-A

23-B

Fisisa Movil FIS

ETRI 230

230

Estrella

23-D

ETRC 230

Estadio EST 23-B

23-C

230

23-A

230

85

Esmeralda ESR

23-A

23-B

El Vidrio EVD

230

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 39: Catalogo 2011-2020 r010212 Corto Circuito

39

Coordinación de Planificación

ÁREA CENTRAL

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 12.57 12.57 12.62 12.62 12.65 12.66 12.67 12.71 12.71 12.74

1F 2.15 2.15 2.16 2.16 2.16 2.16 2.16 2.16 2.16 2.16

3F 34.73 35.06 35.37 35.17 36.48 36.48 36.51 36.68 36.69 31.37

1F 31.68 31.86 32.02 31.91 32.56 32.56 32.57 32.65 32.66 29.46

3F 15.60 15.71 15.78 15.76 15.83 15.83 15.84 15.87 15.87 15.91

1F 9.20 9.23 9.24 9.24 9.25 9.26 9.26 9.26 9.26 9.27

3F 5.21 5.21 5.22 5.22 5.22 5.22 5.22 5.22 5.22 5.22

1F 4.62 4.63 4.63 4.63 4.63 4.63 4.63 4.63 4.63 4.63

3F 5.18 5.18 5.19 5.19 5.19 5.19 5.19 5.19 5.19 5.19

1F 4.60 4.60 4.60 4.60 4.60 4.60 4.60 4.60 4.60 4.61

3F 6.61 6.62 6.62 6.62 6.63 6.63 6.63 6.63 6.63 6.63

1F 5.70 5.70 5.70 5.70 5.70 5.70 5.70 5.70 5.70 5.71

3F 5.08 5.12 5.12 5.12 5.13 5.13 5.13 5.13 5.14 5.15

1F 3.57 3.59 3.58 3.58 3.59 3.59 3.60 3.60 3.60 2.79

3F 15.82 21.78 21.80 21.77 21.89 21.89 21.91 21.99 22.00 22.03

1F 5.98 7.10 7.10 7.10 7.11 7.11 7.11 7.11 7.11 7.11

3F 16.13 23.60 23.53 23.49 23.63 23.63 23.66 23.74 23.75 23.79

1F 6.46 7.99 7.87 7.87 7.88 7.88 7.88 7.89 7.89 7.88

3F 4.72 4.84 4.84 4.84 4.84 4.84 4.84 4.84 4.84 4.84

1F 4.23 4.29 4.29 4.29 4.29 4.29 4.29 4.29 4.29 4.29

3F 4.72 4.84 4.84 4.84 4.84 4.84 4.84 4.84 4.84 4.84

1F 4.23 4.29 4.29 4.29 4.29 4.29 4.29 4.29 4.29 4.29

3F 4.72 4.84 4.84 4.84 4.84 4.84 4.84 4.84 4.84 4.84

1F 4.23 4.29 4.29 4.29 4.29 4.29 4.29 4.29 4.29 4.29

3F 4.72 4.84 4.84 4.84 4.84 4.84 4.84 4.84 4.84 4.84

1F 4.23 4.29 4.29 4.29 4.29 4.29 4.29 4.29 4.29 4.29

3F 3.34 3.38 3.38 3.38 3.39 3.39 3.39 3.39 3.39 3.39

1F 1.15 1.15 1.15 1.15 1.15 1.15 1.15 1.15 1.15 1.15

3F 4.68 4.70 4.71 4.71 4.71 4.71 4.71 4.71 4.71 4.71

1F 4.49 4.50 4.50 4.50 4.50 4.50 4.50 4.50 4.50 4.50

3F 25.99 26.03

1F 23.10 23.12

3F 7.85 7.85

1F 10.44 10.44

230

23

Huixquilucan HQL

85

23

Huehuetoca HTT

23-C

23-D

Huasteca HTC

23-A

23-B

Hipódromo HIP 85

85

23-C

Hilados y Tejidos HYT 115

Guadalupe GUA

23-A

23-B

Good Year Oxo GYO 85

85

General Motor Company GMC 85

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 40: Catalogo 2011-2020 r010212 Corto Circuito

40

Coordinación de Planificación

ÁREA CENTRAL

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 2.69 2.84 2.84 2.84 2.84 2.84 2.89 2.89 2.89 2.89

1F 1.60 1.64 1.64 1.64 1.64 1.64 1.68 1.68 1.68 1.68

3F 1.85

1F 2.14

3F 10.92 18.81 18.74 18.71 18.79 18.79 18.80 18.85 18.86 18.90

1F 1.56 6.68 6.51 6.51 6.52 6.52 6.52 6.52 6.52 6.52

3F 4.41 4.62 4.62 4.62 4.62 4.62 4.62 4.62 4.62 4.62

1F 4.02 4.14 4.14 4.13 4.14 4.14 4.14 4.14 4.14 4.14

3F 4.41 4.62 4.62 4.62 4.62 4.62 4.62 4.62 4.62 4.62

1F 4.02 4.14 4.14 4.13 4.14 4.14 4.14 4.14 4.14 4.14

3F 16.18 22.47 22.49 22.46 22.59 22.59 22.61 22.69 22.70 22.74

1F 6.80 8.29 8.29 8.29 8.30 8.30 8.30 8.31 8.31 8.31

3F 8.86 9.25 9.27 9.26 9.29 9.29 9.29 9.31 9.31 9.31

1F 4.25 4.40 4.40 4.40 4.41 4.41 4.41 4.41 4.41 4.41

3F 20.58 17.79 18.99 17.91 19.11 19.11 19.10 19.12 19.12 18.99

1F 12.76 11.24 11.57 11.27 11.60 11.60 11.59 11.60 11.60 11.57

3F 9.48 9.48 9.50 9.50 9.51 9.51 9.52 9.56 9.56 9.58

1F 6.93 6.93 6.94 6.94 6.95 6.95 6.95 6.97 6.97 6.95

3F 19.76 19.71 19.90 19.82 20.01 20.01 20.02 20.04 20.05 20.02

1F 12.59 12.55 12.61 12.58 12.63 12.63 12.63 12.64 12.64 12.64

3F 5.05 5.05 5.05 5.05 5.05 5.05 5.05 5.05 5.05 5.05

1F 4.47 4.47 4.47 4.47 4.47 4.47 4.47 4.47 4.47 4.47

3F 5.14 5.14 5.15 5.14 5.15 5.15 5.15 5.15 5.15 5.15

1F 4.55 4.55 4.55 4.55 4.55 4.55 4.55 4.55 4.55 4.55

3F 4.79 4.79 4.79 4.79 4.79 4.79 4.79 4.79 4.79 4.79

1F 4.27 4.26 4.27 4.27 4.27 4.27 4.27 4.27 4.27 4.27

3F 4.79 4.79 4.79 4.79 4.79 4.79 4.79 4.79 4.79 4.79

1F 4.27 4.26 4.27 4.27 4.27 4.27 4.27 4.27 4.27 4.27

3F 8.84 8.16 9.97 9.97 10.00 10.00 10.01 10.06 10.06 10.11

1F 7.34 6.98 7.92 7.92 7.93 7.93 7.94 7.97 7.97 7.99

3F 8.60 8.53 8.70 8.70 8.70 8.70 8.70 8.71 8.71 8.71

1F 11.09 11.01 11.20 11.20 11.20 11.20 11.20 11.21 11.21 11.21

3F 7.42 7.37 7.49 7.49 7.49 7.49 7.49 7.49 7.49 7.50

1F 9.89 9.83 9.98 9.98 9.98 9.98 9.98 9.98 9.98 9.99

3F 14.23 14.22 14.27 14.27 14.30 14.30 14.32 14.42 14.42 14.45

1F 12.35 12.34 12.37 12.37 12.39 12.39 12.41 12.46 12.46 12.41

HTM

Indianilla INN

23-B

IUSA Dos IUS 115

Irolo IRO

230

23-A

23-C

23-D

Insurgentes INS

23-A

23-B

Industrias Unidas S.A de C.V IUS 115

85

Industria Militar INM 85

Industria San Cristobal ISC 85

23-B

Industria Defensa Nacional IDN 85

85

23-A

Huetamo

115

69

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 41: Catalogo 2011-2020 r010212 Corto Circuito

41

Coordinación de Planificación

ÁREA CENTRAL

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 22.31 22.53 23.00 22.60 22.84 22.85 22.88 22.36 25.54 25.69

1F 20.96 21.10 21.45 21.21 21.35 21.36 21.37 20.94 22.71 22.79

3F 7.81 7.81 7.82 7.82 7.82 7.82 7.82 7.81 7.85 7.85

1F 10.39 10.40 10.40 10.40 10.40 10.40 10.40 10.39 10.43 10.43

3F 7.81 7.81 7.82 7.82 7.82 7.82 7.82 7.81 7.85 7.85

1F 10.39 10.40 10.40 10.40 10.40 10.40 10.40 10.39 10.43 10.43

3F 7.81 7.81 7.82 7.82 7.82 7.82 7.82 7.81 7.85 7.85

1F 10.39 10.40 10.40 10.40 10.40 10.40 10.40 10.39 10.43 10.43

3F 3.88 3.89 3.89 3.89 3.89 3.89 3.92 3.92 3.92 3.92

1F 2.70 2.70 2.70 2.70 2.70 2.70 2.71 2.71 2.71 2.71

3F 17.19 17.48 17.48 17.58

1F 12.51 12.62 12.62 12.32

3F 14.88 14.95 14.97 14.98 14.99 14.99 27.06 27.22 27.22 27.28

1F 8.26 8.27 8.28 8.28 8.28 8.28 21.34 21.41 21.41 21.16

3F 9.57 9.57 9.59 9.59 9.60 9.60 9.61 9.65 9.65 9.67

1F 6.97 6.96 6.97 6.97 6.98 6.98 6.98 7.00 7.00 6.97

3F 22.42 22.92 25.28 25.04 25.40 25.41 25.49 25.71 25.84 26.02

1F 19.68 19.97 22.42 22.29 22.48 22.49 22.53 22.66 22.73 22.82

3F 13.00 13.00 13.03 13.03 13.04 13.04 13.04 13.04 13.04 13.04

1F 16.56 16.56 16.60 16.60 16.60 16.60 16.61 16.61 16.61 16.61

3F 8.27 8.27 8.30 8.30 8.30 8.30 8.30 8.31 8.31 8.31

1F 10.95 10.95 10.99 10.99 10.99 10.99 10.99 10.99 11.00 11.00

3F 9.25 9.26 9.29 9.29 9.29 9.29 9.29 9.29 9.29 9.30

1F 11.94 11.95 11.98 11.98 11.99 11.99 11.99 11.99 11.99 11.99

3F 23.61 20.91 21.52 23.34 23.58 23.58 23.50 23.74 23.79 23.91

1F 18.98 17.66 18.17 19.20 19.31 19.31 19.26 19.40 19.42 19.48

3F 20.65 22.34 23.17 22.94 23.22 23.23 23.28 23.48 23.65 23.80

1F 21.31 22.51 23.12 22.97 23.16 23.16 23.20 23.33 23.45 23.54

3F 12.01 22.38 22.27 22.23 22.34 22.34 22.36 22.43 22.45 22.50

1F 1.54 7.83 7.61 7.61 7.62 7.62 7.62 7.62 7.63 7.62

3F 4.79 5.04 5.04 5.04 5.04 5.04 5.04 5.04 5.04 5.04

1F 4.32 4.46 4.46 4.46 4.46 4.46 4.46 4.46 4.46 4.46

3F 4.79 5.04 5.04 5.04 5.04 5.04 5.04 5.04 5.04 5.04

1F 4.32 4.46 4.46 4.46 4.46 4.46 4.46 4.46 4.46 4.46

3F 5.46 5.79 5.79 5.79 5.79 5.79 5.79 5.79 5.79 5.79

1F 4.86 5.03 5.03 5.03 5.03 5.03 5.03 5.03 5.03 5.03

23-B

23-C

Jamaica JAM

85

23-A

Jabón la Corona JLC 230

230

23-B

23-C

Iztapalapa IZT

230

23-A

115

Ixtlahuaca ITD 115

Ixtapantongo IXT

Ixtapan de la Sal IXS 115

400

23-B

23-C

Ixtapaluca IXL

230

23-A

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 42: Catalogo 2011-2020 r010212 Corto Circuito

42

Coordinación de Planificación

ÁREA CENTRAL

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 21.06 27.49 27.73 27.72 27.94 27.95 28.12 28.37 28.40 28.90

1F 18.99 22.88 22.99 22.99 23.12 23.12 23.20 23.32 23.34 23.55

3F 13.98 14.56 14.72 14.72 14.74 14.74 14.76 14.79 14.79 14.84

1F 2.14 2.15 2.15 2.15 2.15 2.15 2.15 2.15 2.15 2.15

3F 5.17 5.19 5.20 5.20 5.20 5.20 5.20 5.20 5.20 5.20

1F 5.35 5.37 5.37 5.37 5.37 5.37 5.37 5.37 5.37 5.37

3F 4.96 4.98 4.99 4.99 4.99 4.99 4.99 4.99 4.99 4.99

1F 5.13 5.14 5.14 5.14 5.14 5.14 5.14 5.15 5.15 5.15

3F 8.07 8.14 8.14 8.14 8.15 8.15 8.15 8.16 8.18 8.20

1F 5.94 5.98 5.94 5.96 5.96 5.96 5.98 5.99 6.00 3.54

3F 5.54 5.57 5.57 5.57 5.58 5.58 5.58 5.58 5.59 5.60

1F 3.71 3.72 3.70 3.71 3.71 3.71 3.72 3.73 3.73 2.40

3F 5.63 5.68 5.68 5.68 5.69 5.69 5.69 5.71 5.74 5.75

1F 3.87 3.88 3.83 3.85 3.85 3.85 3.89 3.89 3.90 1.62

3F 8.44 8.50 8.51 8.51 8.52 8.52 8.52 8.54 8.56 8.57

1F 6.32 6.35 6.30 6.32 6.32 6.32 6.36 6.36 6.37 3.28

3F 40.83

1F 43.57

3F 24.24 28.48 28.74 28.73 29.03 29.03 29.21 29.57 29.61 30.23

1F 20.08 22.42 22.53 22.53 22.71 22.71 22.79 22.95 22.96 23.21

3F 8.87 8.92 8.92 8.92 8.93 8.93 8.93 8.93 8.93 8.94

1F 11.90 11.96 11.96 11.96 11.96 11.96 11.97 11.97 11.97 11.98

3F 7.83 7.87 7.87 7.87 7.88 7.88 7.88 7.88 7.88 7.88

1F 10.41 10.46 10.46 10.46 10.46 10.46 10.47 10.47 10.47 10.47

3F 3.36 3.38 6.80 6.80 6.80 6.80 6.81 6.81 6.81 6.82

1F 1.39 1.40 2.01 2.01 2.01 2.01 2.02 2.02 2.02 2.02

3F 3.62 3.62 4.19 4.19 4.19 4.19 4.19 4.19 4.19 4.19

1F 3.57 3.57 3.91 3.91 3.91 3.91 3.91 3.91 3.91 3.92

3F 3.62 3.62 4.19 4.19 4.19 4.19 4.19 4.19 4.19 4.19

1F 3.57 3.57 3.91 3.91 3.91 3.91 3.91 3.91 3.91 3.92

3F 5.34 6.55 7.40 7.38 7.39 7.40 7.40 7.35 7.45 7.45

1F 2.21 4.87 5.16 5.16 5.16 5.16 5.16 5.15 5.18 5.18

3F 5.52 5.82 5.98 5.98 5.98 5.98 5.98 5.97 5.99 5.99

1F 4.99 5.15 5.23 5.23 5.23 5.23 5.23 5.23 5.24 5.24

3F 5.52 5.82 5.98 5.98 5.98 5.98 5.98 5.97 5.99 5.99

1F 4.99 5.15 5.23 5.23 5.23 5.23 5.23 5.23 5.24 5.24

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

23-A

23-B

Juchitepec JCP

23-B

85

Juando JUA

85

23-A

23-A

23-B

Jorobas JRB

Jorge Luque JOL 230

230

230

115

Jilotepec Potencia JLP

Jilotepec JIL 115

Jilotepec Industrial JIN 115

23-A

23-B

Jasso JAS

230

85

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 43: Catalogo 2011-2020 r010212 Corto Circuito

43

Coordinación de Planificación

ÁREA CENTRAL

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 6.51 6.53 6.53 6.53 7.13 7.13 7.13 7.14 7.14 6.40

1F 3.38 3.38 3.38 3.38 3.48 3.48 3.48 3.48 3.48 2.02

3F 23.17 20.83 21.38 22.61 22.84 22.85 22.77 22.87 22.91 23.03

1F 20.42 19.09 19.90 21.07 21.21 21.21 21.16 21.22 21.24 21.31

3F 9.04 9.00 9.01 9.03 9.03 9.03 9.03 9.03 9.03 9.03

1F 11.94 11.89 11.91 11.93 11.94 11.94 11.93 11.94 11.94 11.94

3F 9.04 9.00 9.01 9.03 9.03 9.03 9.03 9.03 9.03 9.03

1F 11.94 11.89 11.91 11.93 11.94 11.94 11.93 11.94 11.94 11.94

3F 8.87 8.83 8.84 8.86 8.86 8.86 8.86 8.86 8.86 8.86

1F 11.71 11.67 11.68 11.70 11.71 11.71 11.71 11.71 11.71 11.71

3F 7.26 6.87 10.99 10.99 11.02 11.02 11.03 11.07 11.08 11.12

1F 7.48 7.19 10.83 10.83 10.85 10.85 10.86 10.89 10.89 10.92

3F 9.06 8.88 9.01 9.00 9.01 9.01 9.01 9.02 9.02 9.03

1F 2.69 2.68 2.69 2.69 2.69 2.69 2.69 2.69 2.69 2.69

3F 12.19 12.19 12.24 12.24 12.27 12.27 12.29 12.33 12.33 12.35

1F 2.11 2.11 2.12 2.12 2.12 2.12 2.12 2.12 2.12 2.12

3F 6.89 6.90 6.90 6.90 6.91 6.91 7.00 7.01 7.01 7.02

1F 4.92 4.92 4.93 4.93 4.93 4.93 5.00 5.00 5.00 4.99

3F 28.79 29.09 32.70 32.60 33.56 33.58 33.74 35.05 35.21 35.69

1F 27.15 27.36 30.35 30.41 30.97 30.99 31.09 32.07 32.18 32.44

3F 29.57 29.91 30.68 29.96 30.40 30.41 30.46 30.88 33.88 34.15

1F 31.72 32.02 32.79 32.23 32.57 32.58 32.62 32.92 35.14 35.33

3F 7.88 7.88 7.89 7.88 7.89 7.89 7.89 7.89 7.91 7.91

1F 10.48 10.48 10.49 10.48 10.49 10.49 10.49 10.49 10.51 10.51

3F 7.88 7.88 7.89 7.88 7.89 7.89 7.89 7.89 7.91 7.91

1F 10.48 10.48 10.49 10.48 10.49 10.49 10.49 10.49 10.51 10.51

3F 23.40 23.44 23.63 23.50 24.05 24.05 24.07 24.13 24.13 22.07

1F 16.52 16.51 16.57 16.53 16.69 16.69 16.69 16.71 16.71 15.97

3F 5.00 5.00 5.01 5.00 5.01 5.01 5.01 5.01 5.01 4.99

1F 4.43 4.43 4.43 4.43 4.43 4.43 4.43 4.43 4.43 4.42

3F 5.05 5.05 5.05 5.05 5.05 5.05 5.06 5.06 5.06 5.03

1F 4.46 4.46 4.46 4.46 4.46 4.46 4.46 4.47 4.47 4.45

3F 4.93 4.93 4.93 4.93 4.94 4.94 4.94 4.94 4.94 4.91

1F 4.26 4.26 4.26 4.26 4.26 4.26 4.26 4.26 4.26 4.25

3F 17.31 18.66 22.51 22.51 22.64 22.64 22.75 22.89 22.92 23.22

1F 14.05 14.69 16.51 16.51 16.57 16.57 16.61 16.66 16.67 16.77

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

23-C

Lafarge LFG 230

La Quebrada LAQ

23-A

23-B

23-B

85

La Paz LAP

230

23-A

La Estancia ETC 115

400

85

Kriher de México KDM 85

Kilómetro ciento diez KMC

23-C

230

Kilómetro Cero KCR

23-A

23-B

Jugos del Valle JDV 85

230

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 44: Catalogo 2011-2020 r010212 Corto Circuito

44

Coordinación de Planificación

ÁREA CENTRAL

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 22.42 22.71 22.72 22.78 28.10 28.13 28.59

1F 17.76 17.89 17.89 17.92 22.94 22.96 23.18

3F 22.54 22.74 22.74 22.70 23.48 23.52 23.66

1F 21.33 21.45 21.45 21.42 22.49 22.51 22.60

3F 36.39 36.74 37.09 36.88 38.32 38.32 38.35 38.53 38.54 32.71

1F 34.33 34.53 34.72 34.60 35.36 35.36 35.38 35.47 35.48 31.73

3F 10.18 10.18 10.18 10.18 10.19 10.19 10.19 10.19 10.19 10.15

1F 11.50 11.50 11.50 11.50 11.51 11.51 11.51 11.51 11.51 11.48

3F 10.18 10.18 10.18 10.18 10.19 10.19 10.19 10.19 10.19 10.15

1F 11.50 11.50 11.50 11.50 11.51 11.51 11.51 11.51 11.51 11.48

3F 5.48 5.48 5.49 5.48 5.49 5.49 5.49 5.49 5.49 5.46

1F 5.57 5.57 5.57 5.57 5.57 5.57 5.57 5.57 5.57 5.55

3F 5.48 5.48 5.49 5.48 5.49 5.49 5.49 5.49 5.49 5.46

1F 5.57 5.57 5.57 5.57 5.57 5.57 5.57 5.57 5.57 5.55

3F 2.17 2.17 2.17 2.17 2.17 2.17 2.17 2.17 2.17 2.17

1F 2.61 2.61 2.61 2.61 2.62 2.62 2.62 2.62 2.62 2.62

3F 1.67 1.67 1.67 1.67 1.67 1.67 1.67 1.67 1.67 1.67

1F 1.71 1.71 1.71 1.71 1.71 1.71 1.71 1.71 1.71 1.71

3F 12.06 11.98 12.08 12.01 12.11 12.11 12.11 12.13 12.14 12.15

1F 6.37 6.33 6.34 6.33 6.35 6.35 6.35 6.35 6.35 6.36

3F 15.06 15.68 15.73 15.71 15.81 15.81 15.82 15.86 15.86 15.65

1F 7.74 8.00 8.01 8.00 8.02 8.02 8.02 8.03 8.03 7.98

3F 5.25 5.27 5.27 5.27 5.28 5.28 5.28 5.28 5.28 5.27

1F 4.66 4.67 4.68 4.67 4.68 4.68 4.68 4.68 4.68 4.67

3F 5.25 5.27 5.27 5.27 5.28 5.28 5.28 5.28 5.28 5.27

1F 4.66 4.67 4.68 4.67 4.68 4.68 4.68 4.68 4.68 4.67

3F 6.58 6.62 6.62 6.62 6.62 6.62 6.62 6.62 6.62 6.61

1F 3.93 3.94 3.94 3.94 3.94 3.94 3.94 3.94 3.94 3.94

3F 22.84 22.99

1F 18.96 19.03

3F 7.82 7.82

1F 10.40 10.40

3F 23.51 23.47 24.08 24.08 24.21 24.98 24.99 25.83

1F 19.29 19.27 19.63 19.63 19.69 20.07 20.08 20.51

3F 7.83 7.83 7.83 7.83 7.83 7.84 7.84 7.85

1F 10.40 10.40 10.41 10.41 10.41 10.42 10.42 10.43

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

230

23-A

Lomas Verdes LVR

230

23

Lomas Verdes Móvil LVEM

23-B

23-C

Loma LOM

85

23-A

23

Linde de México LDM 85

Lerma LER

23-D

85

Lechería LEC 23-B

23-C

85

23-A

400

230

Lago LGO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 45: Catalogo 2011-2020 r010212 Corto Circuito

45

Coordinación de Planificación

ÁREA CENTRAL

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 27.78 27.12 27.48 27.49 27.53 27.87 29.84 30.05

1F 26.35 25.92 26.14 26.15 26.17 26.37 27.52 27.63

3F 15.87 16.82

1F 5.19 7.54

3F 5.14 5.17 7.76 7.75 7.75 7.75 7.75 7.76 7.77 7.77

1F 4.57 4.58 10.26 10.25 10.25 10.25 10.25 10.26 10.27 10.27

3F 5.14 5.17 7.76 7.75 7.75 7.75 7.75 7.76 7.77 7.77

1F 4.57 4.58 10.26 10.25 10.25 10.25 10.25 10.26 10.27 10.27

3F 5.18 5.21

1F 4.60 4.61

3F 6.27 6.31

1F 5.44 5.46

3F 22.30 19.88 20.42 23.16 23.38 23.38 23.31 23.68 23.73 23.86

1F 18.74 17.48 17.98 18.90 19.00 19.00 18.96 19.22 19.24 19.30

3F 8.24 8.20 8.21 8.25 8.25 8.25 8.25 8.26 8.26 8.26

1F 11.31 11.27 11.28 11.33 11.33 11.33 11.33 11.33 11.34 11.34

3F 8.25 8.22 8.23 8.27 8.27 8.27 8.27 8.27 8.27 8.27

1F 10.91 10.87 10.88 10.92 10.92 10.92 10.92 10.93 10.93 10.93

3F 8.48 8.44 8.45 8.49 8.49 8.49 8.49 8.50 8.50 8.50

1F 11.57 11.52 11.53 11.58 11.59 11.59 11.59 11.59 11.59 11.59

3F 27.43 28.34 29.80 29.39 29.86 29.87 29.96 30.29 30.62 30.86

1F 26.12 26.75 27.82 27.58 27.86 27.86 27.92 28.13 28.32 28.46

3F 19.41 19.63 19.97 19.90 19.98 19.98 19.99 20.03 20.14 20.18

1F 7.70 8.32 8.36 8.35 8.36 8.36 8.36 8.37 8.38 8.38

3F 10.37 10.38 10.39 10.38 10.39 10.39 10.39 10.39 10.39 10.39

1F 10.16 10.16 10.17 10.17 10.17 10.17 10.17 10.17 10.17 10.17

3F 5.85 5.85 5.86 5.86 5.86 5.86 5.86 5.86 5.86 5.86

1F 5.09 5.09 5.09 5.09 5.09 5.09 5.09 5.10 5.10 5.10

3F 5.90 5.91 5.91 5.91 5.91 5.91 5.91 5.91 5.92 5.92

1F 5.13 5.13 5.14 5.14 5.14 5.14 5.14 5.14 5.14 5.14

3F 5.85 5.85 5.86 5.86 5.86 5.86 5.86 5.86 5.86 5.86

1F 5.09 5.09 5.09 5.09 5.09 5.09 5.09 5.10 5.10 5.10

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

23-C

23-D

Magdalena MAG

23-A

23-B

230

85

23-B

23-C

Madero MAD

230

23-A

23-C

23-D

Los Reyes RES

23-A

23-B

230

85

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 46: Catalogo 2011-2020 r010212 Corto Circuito

46

Coordinación de Planificación

ÁREA CENTRAL

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 18.61 19.97 20.63 20.45 20.67 20.68 20.72 20.88 21.01 21.13

1F 17.70 18.51 18.91 18.81 18.93 18.94 18.96 19.05 19.12 19.19

3F 8.16 8.18 8.19 8.19 8.19 8.19 8.19 8.20 8.20 8.20

1F 10.75 10.78 10.79 10.79 10.79 10.79 10.79 10.80 10.80 10.80

3F 8.19 8.21 8.22 8.22 8.22 8.22 8.22 8.23 8.23 8.23

1F 10.74 10.77 10.78 10.78 10.78 10.78 10.78 10.78 10.79 10.79

3F 8.24 8.26 8.27 8.27 8.27 8.27 8.27 8.28 8.28 8.28

1F 10.88 10.91 10.92 10.92 10.92 10.92 10.92 10.93 10.93 10.93

3F 9.18 9.22 9.23 9.23 9.24 9.24 10.14 10.16 10.16 10.17

1F 5.97 5.98 5.99 5.99 5.99 5.99 6.75 6.76 6.76 6.74

3F 8.36 8.24 7.79 7.80 7.81 7.81 7.81 7.83 7.83 7.83

1F 4.35 4.33 4.25 4.25 4.25 4.25 4.25 4.25 4.25 4.25

3F 4.44 4.43 4.40 4.40 4.40 4.40 4.40 4.40 4.40 4.40

1F 4.09 4.09 4.07 4.07 4.07 4.07 4.07 4.07 4.07 4.07

3F 4.47 4.46 4.42 4.43 4.43 4.43 4.43 4.43 4.43 4.43

1F 4.11 4.11 4.09 4.09 4.09 4.09 4.09 4.09 4.09 4.09

3F 4.46 4.45 4.41 4.41 4.41 4.41 4.41 4.41 4.41 4.41

1F 4.10 4.10 4.08 4.08 4.08 4.08 4.08 4.08 4.08 4.08

3F 4.44 4.43 4.40 4.40 4.40 4.40 4.40 4.40 4.40 4.40

1F 4.09 4.09 4.07 4.07 4.07 4.07 4.07 4.07 4.07 4.07

3F 4.47 4.46 4.42 4.43 4.43 4.43 4.43 4.43 4.43 4.43

1F 4.02 4.01 3.99 3.99 3.99 3.99 3.99 3.99 3.99 3.99

3F 17.63 25.37 25.40 25.36 25.53 25.53 25.56 25.66 25.67 25.71

1F 7.07 8.70 8.70 8.69 8.71 8.71 8.71 8.71 8.72 8.71

3F 5.24 5.37

1F 4.63 4.70

3F 5.21 5.34

1F 4.61 4.67

3F 5.22 5.35

1F 4.62 4.69

3F 5.28 5.42

1F 4.67 4.74

3F 5.21 5.34

1F 4.48 4.55

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

23-E

Morales MOS

23-C

23-D

23-A

23-B

23-E

85

Moctezuma MZA

23-C

23-D

23-A

23-B

Minera Tizapa MTI 115

85

23-B

23-C

Merced MER

230

23-A

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 47: Catalogo 2011-2020 r010212 Corto Circuito

47

Coordinación de Planificación

ÁREA CENTRAL

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 11.42 11.48 11.97 11.94 12.03 12.04 12.06 12.12 12.12 12.16

1F 9.24 9.26 9.52 9.51 9.55 9.55 9.56 9.58 9.59 9.60

3F 7.56 7.56 7.58 7.58 7.59 7.59 7.59 7.59 7.59 7.59

1F 10.07 10.07 10.10 10.10 10.10 10.10 10.10 10.10 10.10 10.11

3F 7.56 7.56 7.58 7.58 7.59 7.59 7.59 7.59 7.59 7.59

1F 10.07 10.07 10.10 10.10 10.10 10.10 10.10 10.10 10.10 10.11

3F 12.54 12.57 12.64 12.60 12.66 12.66 12.67 12.70 12.70 12.76

1F 5.88 5.87 5.88 5.87 5.88 5.88 5.88 5.89 5.89 5.89

3F 21.90 21.87 22.36 22.37 22.49 22.92 22.92 23.21

1F 3.10 3.10 3.11 3.11 3.11 3.12 3.12 3.12

3F 11.59 11.65

1F 5.54 5.72

3F 4.79 4.79 7.70 7.70 7.71 7.71 7.71 7.71 7.71 7.71

1F 4.21 4.22 9.97 9.97 9.98 9.98 9.98 9.98 9.98 9.99

3F 4.79 4.79 7.70 7.70 7.71 7.71 7.71 7.71 7.71 7.71

1F 4.21 4.22 9.97 9.97 9.98 9.98 9.98 9.98 9.98 9.99

3F 18.17 19.19 19.27 19.25 19.35 19.36 19.37 19.42 19.42 19.43

1F 9.19 9.59 9.60 9.60 9.62 9.62 9.62 9.63 9.63 9.63

3F 5.28 5.30 5.30 5.30 5.30 5.30 5.30 5.30 5.30 5.30

1F 4.66 4.67 4.67 4.67 4.67 4.67 4.67 4.67 4.67 4.67

3F 5.28 5.30 5.30 5.30 5.30 5.30 5.30 5.30 5.30 5.30

1F 4.66 4.67 4.67 4.67 4.67 4.67 4.67 4.67 4.67 4.67

3F 5.28 5.30 5.30 5.30 5.30 5.30 5.30 5.30 5.30 5.30

1F 4.66 4.67 4.67 4.67 4.67 4.67 4.67 4.67 4.67 4.67

3F 10.52 10.34 11.52 11.52 11.53 11.53 11.53 11.54 11.54 11.55

1F 10.29 10.17 10.91 10.91 10.91 10.91 10.91 10.92 10.92 10.93

3F 13.90 14.21 14.59 14.54 14.57 14.58 14.58 14.56 14.73 14.75

1F 5.45 6.54 6.60 6.59 6.59 6.59 6.59 6.59 6.62 6.62

3F 4.81 4.82 4.83 4.83 4.83 4.83 4.83 4.83 4.83 4.83

1F 4.31 4.32 4.32 4.32 4.32 4.32 4.32 4.32 4.33 4.33

3F 4.75 4.76 4.77 4.77 4.77 4.77 4.77 4.77 4.78 4.78

1F 4.27 4.28 4.28 4.28 4.28 4.28 4.28 4.28 4.29 4.29

3F 4.79 4.80 4.81 4.81 4.81 4.81 4.81 4.81 4.82 4.82

1F 4.30 4.31 4.31 4.31 4.31 4.31 4.31 4.31 4.32 4.32

3F 4.79 4.80 4.81 4.81 4.81 4.81 4.81 4.81 4.82 4.82

1F 4.30 4.31 4.31 4.31 4.31 4.31 4.31 4.31 4.32 4.32

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

23-D

Netzahualcóyotl NET 23-B

23-C

85

23-A

23-C

Necaxa NEC 85

Naucalpan NAU

23-A

23-B

23-B

85

Narvarte NAR

85

23-A

Nacel y Nacobre NYN 85

230

23-A

23-B

Morelos MOR

230

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 48: Catalogo 2011-2020 r010212 Corto Circuito

48

Coordinación de Planificación

ÁREA CENTRAL

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 9.84 9.84 9.88 9.87 9.90 9.90 9.91 9.93 9.93 9.95

1F 1.81 1.81 1.82 1.82 1.82 1.82 1.82 1.82 1.82 1.82

3F 23.10 33.73 34.17 34.15 34.66 34.66 34.92 35.55 35.60 36.73

1F 19.51 27.45 27.63 27.63 28.08 28.08 28.20 28.50 28.52 28.96

3F 7.29 7.50 7.51 7.51 7.52 7.52 7.53 7.54 7.54 7.56

1F 6.71 6.93 6.93 6.93 6.94 6.94 6.95 6.95 6.96 6.70

3F 30.06 30.48 30.76 30.74 31.01 31.01 31.02 31.08 31.09 31.14

1F 24.13 24.39 24.52 24.51 24.62 24.62 24.62 24.65 24.65 24.67

3F 29.69 29.60 30.81 30.77 31.66 31.67 32.16 36.05 36.06 37.15

1F 29.45 29.39 30.24 30.21 31.23 31.24 31.59 34.87 34.88 35.62

3F 29.25 29.29 30.17 30.12 31.27 31.28 31.51 32.82 32.82 33.68

1F 29.78 29.79 30.47 30.43 31.39 31.39 31.55 32.57 32.57 33.15

3F 28.92 28.96 29.83 29.78 30.93 30.94 31.16 32.44 32.44 33.28

1F 29.12 29.14 29.79 29.76 30.71 30.71 30.86 31.82 31.83 32.38

3F 28.83 28.87 29.74 29.69 30.84 30.85 31.07 32.33 32.34 33.17

1F 29.66 29.68 30.35 30.31 31.30 31.31 31.46 32.41 32.41 32.98

3F 2.56 2.59 2.59 2.59 2.59 2.59 2.61 2.61 2.61 2.61

1F 1.79 1.79 1.79 1.79 1.79 1.79 1.81 1.81 1.81 1.81

3F 17.47 18.67 19.25 19.09 19.28 19.29 19.32 19.46 19.58 19.68

1F 15.80 16.43 16.74 16.66 16.76 16.76 16.78 16.85 16.91 16.96

3F 16.82 15.41 15.69 15.83 15.93 15.93 15.90 16.07 16.10 16.15

1F 12.69 12.13 12.43 12.30 12.34 12.34 12.32 12.41 12.42 12.45

3F 11.97 12.00 15.68 15.66 15.87 15.87 15.93 16.10 16.10 16.22

1F 9.97 9.98 13.46 13.45 13.56 13.56 13.58 13.67 13.67 13.73

3F 8.94 8.94 9.10 9.10 9.10 9.10 9.11 9.11 9.11 9.12

1F 11.82 11.83 12.03 12.03 12.04 12.04 12.04 12.05 12.05 12.06

3F 8.95 8.95 9.11 9.11 9.11 9.11 9.12 9.12 9.12 9.13

1F 11.84 11.84 12.05 12.05 12.06 12.06 12.06 12.06 12.06 12.07

3F 8.91 8.91 9.07 9.07 9.08 9.08 9.08 9.09 9.09 9.09

1F 11.79 11.80 12.00 12.00 12.01 12.01 12.01 12.02 12.02 12.02

3F 14.39 14.41 24.46 24.42 25.00 25.01 25.15 25.69 25.69 26.04

1F 11.25 11.26 22.51 22.49 22.86 22.87 22.95 23.25 23.25 23.44

3F 7.66 7.67 7.84 7.84 7.84 7.84 7.84 7.85 7.85 7.85

1F 10.20 10.20 10.42 10.42 10.43 10.43 10.43 10.44 10.44 10.44

3F 7.66 7.67 7.84 7.84 7.84 7.84 7.84 7.85 7.85 7.85

1F 10.20 10.20 10.42 10.42 10.43 10.43 10.43 10.44 10.44 10.4423-B

Olivar OLI

230

23-A

23-B

23-C

Odón de Buen ODB

230

23-A

OCEM 230

OCEP 230

Oceanía

NOPC 230

Nueva Arcelia ANU 115

Nopala

NOPA 230

NOPB 230

Nonoalco NON 85

NOP 400

230

115

Nochistongo NOC

Nissan NIS 85

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 49: Catalogo 2011-2020 r010212 Corto Circuito

49

Coordinación de Planificación

ÁREA CENTRAL

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 5.98 6.01 7.71 7.71 7.72 7.72 7.72 7.73 7.73 7.74

1F 1.76 1.76 1.96 1.96 1.96 1.96 1.96 1.96 1.96 1.96

3F 4.66 4.67 4.89 4.89 4.89 4.89 4.89 4.89 4.89 4.89

1F 5.01 5.01 5.18 5.18 5.18 5.18 5.18 5.18 5.18 5.18

3F 4.66 4.67 4.89 4.89 4.89 4.89 4.89 4.89 4.89 4.89

1F 5.01 5.01 5.18 5.18 5.18 5.18 5.18 5.18 5.18 5.18

3F 4.66 4.67 4.89 4.89 4.89 4.89 4.89 4.89 4.89 4.89

1F 4.35 4.36 4.48 4.48 4.48 4.48 4.48 4.48 4.48 4.48

3F 6.45 6.45 6.46 6.46 6.46 6.46 6.47 6.48 6.48 6.49

1F 4.57 4.57 4.57 4.57 4.57 4.57 4.58 4.59 4.59 4.58

3F 10.35 10.48 10.64 10.62 10.64 10.64 10.64 10.64 10.71 10.72

1F 4.51 5.03 5.06 5.05 5.06 5.06 5.06 5.06 5.07 5.07

3F 4.60 4.61 4.62 4.62 4.62 4.62 4.62 4.62 4.62 4.62

1F 4.19 4.19 4.20 4.20 4.20 4.20 4.20 4.20 4.20 4.20

3F 4.65 4.66 4.67 4.67 4.67 4.67 4.67 4.67 4.67 4.67

1F 4.23 4.23 4.24 4.24 4.24 4.24 4.24 4.24 4.24 4.24

3F 4.84 4.85 4.86 4.86 4.86 4.86 4.86 4.86 4.86 4.86

1F 4.39 4.39 4.40 4.39 4.39 4.39 4.40 4.39 4.40 4.40

3F 4.63 4.64 4.64 4.64 4.64 4.64 4.64 4.64 4.65 4.65

1F 4.21 4.21 4.22 4.22 4.22 4.22 4.22 4.22 4.22 4.22

3F 4.02 4.02 4.03 4.03 4.03 4.03 4.04 4.04 4.04 4.05

1F 2.41 2.41 2.41 2.41 2.41 2.41 2.42 2.42 2.42 2.41

3F 3.56 4.51 4.83 4.83 4.83 4.83 4.83 4.81 4.85 4.85

1F 1.61 3.88 4.04 4.03 4.04 4.04 4.04 4.03 4.05 4.05

3F 6.56 6.71 6.71 6.71 6.72 6.72 6.72 6.73 6.73 6.75

1F 5.50 5.62 5.61 5.62 5.62 5.62 5.63 5.63 5.64 5.19

Papelería San Rafael PSR 85

Parque Industrial PQI 115

23-D

Papelera El Nevado PNE 115

Pantitlán PNT 23-B

23-C

85

23-A

23-C

Palizada (Peletizadira Alzada) PLZ 115

Pachuca PAC

23-A

23-B

85

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 50: Catalogo 2011-2020 r010212 Corto Circuito

50

Coordinación de Planificación

ÁREA CENTRAL

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 12.46 12.47 12.51 12.52 12.54 12.63 12.63 12.70

1F 9.50 9.51 9.52 9.52 9.53 9.56 9.57 9.59

3F 11.35 11.35 11.38 11.38 11.39 11.43 11.43 11.48

1F 11.80 11.80 11.82 11.82 11.82 11.85 11.86 11.89

3F 4.62 4.62 6.55 6.55 6.55 6.55 6.56 6.56 6.56 6.57

1F 1.31 1.31 1.46 1.46 1.46 1.46 1.46 1.46 1.46 1.46

3F 5.18 5.18 5.67 5.67 5.67 5.67 5.67 5.67 5.67 5.68

1F 5.76 5.76 6.15 6.15 6.15 6.15 6.15 6.15 6.15 6.15

3F 5.18 5.18 5.67 5.67 5.67 5.67 5.67 5.67 5.67 5.68

1F 5.76 5.76 6.15 6.15 6.15 6.15 6.15 6.15 6.15 6.15

3F 5.18 5.18 5.67 5.67 5.67 5.67 5.67 5.67 5.67 5.68

1F 5.76 5.76 6.15 6.15 6.15 6.15 6.15 6.15 6.15 6.15

3F 15.65 15.71

1F 12.36 12.39

3F 7.70 7.70

1F 10.24 10.24

3F 13.67 13.70 13.79 13.74 13.81 13.81 13.82 13.86 13.86 13.93

1F 6.84 6.82 6.84 6.83 6.84 6.84 6.84 6.85 6.85 6.86

3F 4.79 4.79 4.79 4.79 4.79 4.79 4.79 4.80 4.80 4.80

1F 4.30 4.30 4.31 4.31 4.31 4.31 4.31 4.31 4.31 4.31

3F 4.79 4.79 4.79 4.79 4.79 4.79 4.79 4.80 4.80 4.80

1F 4.30 4.30 4.31 4.31 4.31 4.31 4.31 4.31 4.31 4.31

3F 4.79 4.79 4.79 4.79 4.79 4.79 4.79 4.80 4.80 4.80

1F 4.30 4.30 4.31 4.31 4.31 4.31 4.31 4.31 4.31 4.31

3F 4.79 4.79 4.79 4.79 4.79 4.79 4.79 4.80 4.80 4.80

1F 4.30 4.30 4.31 4.31 4.31 4.31 4.31 4.31 4.31 4.31

3F 7.14 7.07 7.56 7.56 7.56 7.56 7.56 7.56 7.56 7.57

1F 6.34 6.30 6.55 6.55 6.56 6.56 6.56 6.56 6.56 6.56

3F 30.44 33.46 33.81 33.81 34.06 34.06 34.31 34.55 34.61 35.15

1F 25.59 27.05 27.22 27.23 27.34 27.34 27.46 27.57 27.59 27.82

3F 4.29 4.37 4.37 4.37 4.37 4.37 4.37 4.38 4.38 4.38

1F 3.43 3.49 3.49 3.49 3.49 3.49 3.50 3.50 3.50 3.44

3F 16.65 17.30 17.37 17.36 17.44 17.44 17.45 17.48 17.49 17.50

1F 8.96 9.24 9.25 9.25 9.27 9.27 9.27 9.27 9.27 9.27

3F 25.76 24.17 25.04 24.37 25.27 25.27 25.27 25.30 25.31 24.96

1F 15.28 14.49 14.70 14.53 14.75 14.75 14.75 14.76 14.76 14.68

Pemex Azcapotzalco PXA 85

Pennwalt PEW 85

230

115

Pemex PEX

23-D

Patla PTL 85

Patera PAT 23-B

23-C

85

23-A

230

23

Parres Móvil PRM

23-B

23-C

Parque Industrial Reforma PIR

85

23-A

400

230

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 51: Catalogo 2011-2020 r010212 Corto Circuito

51

Coordinación de Planificación

ÁREA CENTRAL

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 17.60 18.81 19.40 19.24 19.43 19.44 19.48 19.61 19.73 19.84

1F 15.80 16.44 16.75 16.67 16.77 16.77 16.79 16.86 16.92 16.97

3F 8.93 8.96 8.97 8.97 8.97 8.97 8.97 8.98 8.98 8.98

1F 12.01 12.05 12.06 12.06 12.07 12.07 12.07 12.07 12.07 12.08

3F 8.93 8.96 8.97 8.97 8.97 8.97 8.97 8.98 8.98 8.98

1F 12.01 12.05 12.06 12.06 12.07 12.07 12.07 12.07 12.07 12.08

3F 8.93 8.96 8.97 8.97 8.97 8.97 8.97 8.98 8.98 8.98

1F 12.01 12.05 12.06 12.06 12.07 12.07 12.07 12.07 12.07 12.08

3F 19.49 17.63 17.99 18.17 18.30 18.30 18.26 18.49 18.52 18.60

1F 16.16 15.24 15.73 15.50 15.58 15.57 15.55 15.68 15.70 15.74

3F 8.84 8.80 8.81 8.81 8.81 8.81 8.81 8.82 8.82 8.82

1F 11.87 11.81 11.83 11.83 11.83 11.83 11.83 11.84 11.84 11.84

3F 8.86 8.82 8.83 8.83 8.83 8.83 8.83 8.84 8.84 8.84

1F 11.89 11.84 11.86 11.86 11.86 11.86 11.86 11.87 11.87 11.87

3F 8.84 8.80 8.81 8.81 8.81 8.81 8.81 8.82 8.82 8.82

1F 11.87 11.82 11.83 11.83 11.84 11.84 11.83 11.84 11.84 11.84

3F 1.71 1.74 1.74 1.74 1.74 1.74 1.75 1.75 1.75 1.75

1F 1.12 1.12 1.12 1.12 1.12 1.12 1.13 1.13 1.13 1.13

3F 31.06 31.14 32.21 32.15 33.85 33.86 34.12 35.57 35.57 36.64

1F 30.24 30.28 31.29 31.25 32.81 32.81 32.97 33.93 33.93 34.58

3F 7.78 7.78 7.79 7.79 7.80 7.80 7.80 7.80 7.80 7.81

1F 10.29 10.29 10.29 10.29 10.30 10.30 10.31 10.31 10.31 10.32

3F 7.78 7.78 7.79 7.79 7.80 7.80 7.80 7.80 7.80 7.81

1F 10.29 10.29 10.29 10.29 10.30 10.30 10.31 10.31 10.31 10.32

3F 23.94 28.06 28.31 28.30 28.59 28.59 28.77 29.12 29.15 29.75

1F 19.80 22.07 22.18 22.17 22.35 22.35 22.43 22.58 22.59 22.83

3F 6.83 6.83 6.86 6.86 6.87 6.87 6.87 6.88 6.88 6.89

1F 1.89 1.89 1.89 1.89 1.89 1.89 1.89 1.89 1.89 1.89

3F 5.77 5.77

1F 5.09 5.09

3F 10.66 18.03 17.97 17.94 18.01 18.01 18.02 18.07 18.08 18.11

1F 1.49 6.19 6.03 6.03 6.03 6.03 6.04 6.04 6.04 6.04

3F 23.14 23.39 23.55 23.54 23.70 23.70 23.70 23.74 23.74 23.77

1F 13.66 13.73 13.76 13.76 13.79 13.79 13.79 13.80 13.80 13.81

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

PCC-N 85

Puesto de Control Central

23

PCC-J 85

Puerta de Hierro PTH

Procter and Gamble PYG 230

85

23-A

23-B

Polanco POO

Placeres del oro PDR 115

230

23-B

23-C

Peralvillo PEV

230

23-A

23-B

23-C

Pensador PEN

230

23-A

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 52: Catalogo 2011-2020 r010212 Corto Circuito

52

Coordinación de Planificación

ÁREA CENTRAL

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 25.01 25.58 26.20 26.16 26.59 26.59 26.74 27.81 27.83 29.58

1F 20.96 21.27 21.56 21.54 21.78 21.79 21.85 22.47 22.48 23.72

3F 7.84 7.85 7.85 7.85 7.86 7.86 7.86 7.87 7.87 7.88

1F 10.43 10.43 10.44 10.44 10.44 10.44 10.44 10.45 10.45 10.47

3F 11.74 12.43 12.46 12.45 12.50 12.50 12.51 12.54 12.54 12.54

1F 5.45 5.71 5.71 5.71 5.72 5.72 5.72 5.72 5.72 5.72

3F 4.83 4.86 4.87 4.87 4.87 4.87 4.87 4.87 4.87 4.87

1F 4.36 4.38 4.38 4.38 4.38 4.38 4.38 4.38 4.38 4.38

3F 4.83 4.86 4.87 4.87 4.87 4.87 4.87 4.87 4.87 4.87

1F 4.36 4.38 4.38 4.38 4.38 4.38 4.38 4.38 4.38 4.38

3F 4.83 4.86 4.87 4.87 4.87 4.87 4.87 4.87 4.87 4.87

1F 4.36 4.38 4.38 4.38 4.38 4.38 4.38 4.38 4.38 4.38

3F 4.80 4.83 4.83 4.83 4.83 4.83 4.83 4.83 4.83 4.83

1F 4.22 4.24 4.24 4.24 4.24 4.24 4.24 4.24 4.24 4.24

3F 37.08 37.18 38.72 38.63 41.12 41.13 41.52 43.68 43.69 45.32

1F 41.34 41.40 42.93 42.86 46.03 46.04 46.37 48.35 48.36 49.74

3F 32.20 38.01 38.30 38.21 38.66 38.67 38.73 39.01 39.02 39.05

1F 12.26 13.65 13.67 13.66 13.70 13.70 13.70 13.72 13.73 13.71

3F 13.19 13.19 13.19 13.19 13.21 13.21 13.21 13.22 13.22 13.22

1F 16.91 16.91 16.92 16.92 16.94 16.94 16.94 16.95 16.95 16.95

3F 8.59 8.59 8.60 8.60 8.61 8.61 8.61 8.62 8.62 8.63

1F 11.47 11.47 11.48 11.48 11.50 11.50 11.50 11.51 11.51 11.52

3F 8.52 8.52 8.53 8.53 8.54 8.54 8.54 8.55 8.55 8.56

1F 11.29 11.29 11.30 11.30 11.32 11.32 11.32 11.33 11.33 11.33

3F 4.54 4.56 4.56 4.71 4.71 4.68 4.68 4.71 4.71 4.77

1F 3.26 3.27 3.27 3.36 3.36 3.34 3.27 3.27 3.28 2.42

3F 11.90 11.90 11.95 11.95 11.98 11.98 12.00 12.04 12.04 12.06

1F 2.07 2.07 2.08 2.08 2.08 2.08 2.08 2.08 2.08 2.08

3F 12.61 12.61 12.67 12.67 12.70 12.70 12.72 12.76 12.76 12.79

1F 2.01 2.01 2.02 2.02 2.02 2.02 2.03 2.03 2.03 2.03

3F 5.25 5.07 6.65 6.65 6.66 6.66 6.66 6.68 6.68 6.69

1F 5.71 5.56 6.85 6.85 6.85 6.85 6.85 6.86 6.87 6.88

3F 10.70 10.52 11.75 11.75 11.76 11.76 11.76 11.77 11.77 11.79

1F 10.35 10.23 10.98 10.98 10.98 10.98 10.99 10.99 10.99 11.00

3F 6.03 6.02 6.12 6.12 6.12 6.12 6.12 6.12 6.12 6.12

1F 6.36 6.34 6.42 6.42 6.42 6.42 6.42 6.42 6.42 6.42

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

23

Salto SAO

230

85

Roberto Bosch RBS 85

Safimex SFM 85

23-C

Resistol RRS 115

Remedios REM 23-A

23-B

230

85

23-C

23-D

Reforma REF

23-A

23-B

23

85

Punta Norte móvil PNN

230

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 53: Catalogo 2011-2020 r010212 Corto Circuito

53

Coordinación de Planificación

ÁREA CENTRAL

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 13.51 13.62 13.78 13.75 13.79 13.79 13.79 13.81 13.86 13.88

1F 5.82 6.16 6.18 6.18 6.18 6.18 6.18 6.19 6.19 6.20

3F 4.71 4.71 4.71 4.71 4.71 4.71 4.72 4.72 4.72 4.72

1F 4.24 4.24 4.24 4.24 4.24 4.24 4.24 4.24 4.24 4.24

3F 4.71 4.71 4.71 4.71 4.71 4.71 4.72 4.72 4.72 4.72

1F 4.24 4.24 4.24 4.24 4.24 4.24 4.24 4.24 4.24 4.24

3F 4.67 4.68 4.68 4.68 4.68 4.68 4.68 4.68 4.69 4.69

1F 4.21 4.21 4.22 4.22 4.22 4.22 4.22 4.22 4.22 4.22

3F 4.80 4.81 4.81 4.81 4.81 4.81 4.81 4.81 4.81 4.81

1F 4.32 4.32 4.32 4.32 4.32 4.32 4.32 4.32 4.32 4.32

3F 20.92 20.94 25.41 25.37 26.04 26.04 26.20 26.80 26.80 27.19

1F 18.58 18.59 23.95 23.93 24.39 24.40 24.49 24.84 24.84 25.06

3F 8.25 8.26 8.31 8.31 8.32 8.32 8.32 8.33 8.33 8.33

1F 10.82 10.82 10.89 10.89 10.90 10.90 10.90 10.91 10.91 10.91

3F 8.23 8.23 8.29 8.29 8.30 8.30 8.30 8.31 8.31 8.31

1F 10.79 10.79 10.87 10.87 10.87 10.87 10.88 10.88 10.88 10.89

3F 8.08 8.09 8.14 8.14 8.15 8.15 8.15 8.15 8.15 8.16

1F 10.72 10.72 10.79 10.79 10.80 10.80 10.80 10.81 10.81 10.81

3F 28.40 28.44 30.08 30.02 31.16 31.17 31.64 33.38 33.41 34.15

1F 26.98 27.01 28.05 28.02 28.99 29.00 29.30 30.53 30.59 31.00

3F 29.91 29.96 30.99 30.93 31.63 31.64 31.89 32.73 32.74 33.25

1F 31.90 31.93 32.82 32.78 33.34 33.35 33.54 34.21 34.23 34.59

3F 6.84 6.84

1F 1.89 1.89

3F 5.77 5.77

1F 5.09 5.09

3F 5.17 5.16 5.17 5.17 5.18 5.18 5.18 5.19 5.19 5.19

1F 3.79 3.79 3.79 3.79 3.79 3.79 3.80 3.80 3.80 3.80

3F 11.30 11.30 11.33 11.33 11.35 11.36 11.37 11.40 11.40 11.42

1F 2.12 2.12 2.12 2.12 2.12 2.12 2.12 2.12 2.12 2.12

3F 6.43 6.43 6.43 6.43 6.43 6.43 6.44 6.44 6.44 6.44

1F 5.44 5.44 5.45 5.45 5.45 5.45 5.45 5.45 5.45 5.45

3F 1.83 1.83 1.83 1.83 1.83 1.83 1.83 1.83 1.83 1.83

1F 1.23 1.23 1.23 1.23 1.23 1.23 1.23 1.23 1.23 1.22

3F 10.58 17.79 17.72 17.69 17.76 17.76 17.77 17.82 17.83 17.86

1F 1.49 6.17 6.02 6.01 6.02 6.02 6.02 6.02 6.02 6.02

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

San Lázaro LAZ 85

23

San Francisco de los Reyes SFR 115

San Francisco SSO

San Felipe del Progreso SFP 115

85

85

23

San Diego SDI

400

230

San Bernabé BRN

23-B

23-C

San Ángel SNG

230

23-A

23-C

23-D

San Ándres ANS

23-A

23-B

85

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 54: Catalogo 2011-2020 r010212 Corto Circuito

54

Coordinación de Planificación

ÁREA CENTRAL

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 4.85 4.85 4.86 4.86 4.86 4.86 4.87 4.88 4.88 4.88

1F 2.84 2.84 2.84 2.84 2.84 2.84 2.85 2.85 2.85 2.85

3F 4.23 4.23 4.23 4.23 4.23 4.23 4.23 4.24 4.24 4.24

1F 2.88 2.88 2.88 2.88 2.88 2.88 2.89 2.89 2.89 2.65

3F 9.96 10.00 10.00 10.01 10.01 10.01 13.99 14.04 14.04 14.05

1F 5.47 5.47 5.48 5.48 5.48 5.48 9.15 9.16 9.16 9.11

3F 27.76 28.09 31.04 30.89 31.93 31.95 32.17 33.05 33.08 33.52

1F 26.61 26.87 29.11 29.07 29.69 29.70 29.85 30.51 30.57 30.82

3F 33.10 34.44 36.63 36.01 36.72 36.73 36.87 37.38 37.86 38.23

1F 36.75 38.01 40.21 39.71 40.29 40.30 40.42 40.87 41.27 41.56

3F 12.82 12.83 12.84 12.84 12.84 12.84 12.85 12.85 12.85 12.85

1F 16.33 16.34 16.35 16.35 16.35 16.35 16.35 16.36 16.36 16.36

3F 8.31 8.32 8.33 8.33 8.34 8.34 8.34 8.34 8.34 8.34

1F 11.08 11.09 11.10 11.10 11.11 11.11 11.11 11.11 11.11 11.11

3F 8.49 8.50 8.52 8.51 8.52 8.52 8.52 8.52 8.52 8.52

1F 11.38 11.39 11.40 11.40 11.41 11.41 11.41 11.41 11.41 11.41

3F 25.69 25.65 26.63 26.63 26.80 27.49 27.49 27.95

1F 23.37 23.35 24.17 24.17 24.26 24.66 24.66 24.90

3F 7.85 7.85 7.86 7.86 7.86 7.86 7.86 7.87

1F 10.44 10.44 10.45 10.45 10.45 10.45 10.46 10.46

3F 43.27 34.91 36.59

1F 41.87 35.28 36.47

3F 7.95 7.91 7.92

1F 10.56 10.52 10.53

3F 12.46 12.46 12.48 12.49 12.50 12.50 12.58 12.62 12.62 12.63

1F 5.22 5.22 5.23 5.23 5.23 5.23 7.52 7.53 7.53 7.48

3F 27.61 27.65 27.75 27.77 27.84 27.83 28.32 28.53 28.53 28.61

1F 20.73 20.74 20.82 20.83 20.86 20.86 21.29 21.37 21.37 20.98

3F 15.26 15.29 15.32 15.32 15.34 15.34 17.25 17.32 17.32 17.34

1F 9.20 9.21 9.23 9.23 9.23 9.23 10.94 10.96 10.96 10.87

3F 14.28 14.29 14.32 14.32 14.34 14.34 14.46 14.51 14.51 14.53

1F 7.52 7.52 7.53 7.53 7.54 7.54 8.99 9.00 9.00 8.93

3F 6.56 6.58 6.59 6.59 6.59 6.59 7.04 7.05 7.05 7.05

1F 4.07 4.08 4.08 4.08 4.08 4.08 4.42 4.42 4.42 4.42

3F 22.81 23.16 23.23 23.24 23.29 23.28 23.62 23.76 23.76 23.81

1F 16.06 16.17 16.22 16.23 16.25 16.25 16.50 16.55 16.55 16.31

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Subestación Tres de Bombeo PB3 115

Subestación Seis de Bombeo PB6 115

Subestación Siete de Bombeo PB7 115

Subestación Cuatro de Bombeo PB4 115

Subestación Dos de Bombeo PB2 115

23

Subestación Cinco de Bombeo PB5 115

Sosa Texcoco Movil SOX

23-A

230

Santa Fé SFE

23-C

230

Santa Cruz CRU 23-A

23-B

400

230

San Sebastián SSE 115

Santa Bárbara BBR 115

San Mateo SMT 115

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 55: Catalogo 2011-2020 r010212 Corto Circuito

55

Coordinación de Planificación

ÁREA CENTRAL

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 11.76 11.79 11.80 11.80 11.81 11.81 13.71 13.75 13.75 13.76

1F 6.66 6.67 6.67 6.67 6.67 6.67 8.33 8.34 8.34 8.29

3F 18.17 18.62 18.71 18.70 18.80 18.80 18.80 18.84 18.84 18.85

1F 10.85 11.06 11.08 11.07 11.10 11.10 11.10 11.10 11.11 11.11

3F 4.78 4.79 4.79 4.79 4.79 4.79 4.79 4.79 4.79 4.79

1F 4.27 4.27 4.27 4.27 4.27 4.27 4.27 4.27 4.27 4.27

3F 4.78 4.79 4.79 4.79 4.79 4.79 4.79 4.79 4.79 4.79

1F 4.27 4.27 4.27 4.27 4.27 4.27 4.27 4.27 4.27 4.27

3F 4.89 4.90 4.90 4.90 4.90 4.90 4.90 4.90 4.90 4.90

1F 4.35 4.36 4.36 4.36 4.36 4.36 4.36 4.36 4.36 4.36

3F 4.82 4.83 4.83 4.83 4.83 4.83 4.83 4.83 4.83 4.83

1F 4.30 4.30 4.30 4.30 4.30 4.30 4.30 4.30 4.30 4.30

3F 19.54 19.55 22.38 22.34 22.88 22.88 23.00 23.47 23.47 23.78

1F 16.97 16.97 19.89 19.87 20.20 20.21 20.27 20.52 20.52 20.67

3F 8.97 9.36 9.38 9.37 9.40 9.40 9.41 9.42 9.42 9.43

1F 4.29 4.45 4.45 4.45 4.46 4.46 4.46 4.46 4.46 4.46

3F 8.15 8.15 8.19 8.19 8.20 8.20 8.20 8.20 8.20 8.21

1F 10.76 10.76 10.81 10.81 10.82 10.82 10.82 10.83 10.83 10.83

3F 8.13 8.13 8.17 8.17 8.18 8.18 8.18 8.19 8.19 8.19

1F 10.74 10.74 10.80 10.80 10.81 10.81 10.81 10.81 10.81 10.82

3F 8.27 8.27 8.32 8.32 8.32 8.32 8.33 8.33 8.33 8.34

1F 10.84 10.84 10.89 10.89 10.90 10.90 10.90 10.91 10.91 10.91

3F 4.67 4.70 4.70 4.70 4.71 4.71 4.71 4.71 4.71 4.71

1F 4.27 4.29 4.29 4.29 4.29 4.29 4.29 4.29 4.29 4.29

3F 11.59 11.62 14.27 14.25 14.41 14.41 14.46 14.59 14.59 14.68

1F 9.51 9.53 12.16 12.15 12.23 12.23 12.25 12.32 12.32 12.36

3F 12.70 12.77 12.96 12.94 12.97 12.97 12.98 12.99 13.03 13.04

1F 6.29 6.55 6.58 6.58 6.58 6.58 6.58 6.59 6.59 6.60

3F 5.28 5.28 7.66 7.66 7.67 7.67 7.67 7.67 7.67 7.67

1F 4.71 4.71 10.20 10.20 10.21 10.21 10.21 10.21 10.21 10.21

3F 5.28 5.28 7.66 7.66 7.67 7.67 7.67 7.67 7.67 7.67

1F 4.71 4.71 10.20 10.20 10.21 10.21 10.21 10.21 10.21 10.21

3F 5.28 5.28

1F 4.71 4.71

3F 6.40 6.40

1F 5.58 5.58

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

23-D

Taxqueña TAX

23-B

23-C

85

23-A

23-D

230

Tacubaya TYA

23-B

23-C

85

23-A

23-D

230

Tacuba TAC 23-B

23-C

85

23-A

Subestación Uno de Bombeo PB1 115

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 56: Catalogo 2011-2020 r010212 Corto Circuito

56

Coordinación de Planificación

ÁREA CENTRAL

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 11.27 11.36 16.27 16.26 16.35 16.35 16.38 16.51 16.52 16.70

1F 8.65 8.68 11.63 11.64 11.66 11.67 11.68 11.74 11.75 11.81

3F 7.56 7.56 7.71 7.71 7.71 7.71 7.71 7.72 7.72 7.72

1F 10.06 10.06 10.25 10.25 10.25 10.25 10.25 10.26 10.26 10.26

3F 7.56 7.56 7.71 7.71 7.71 7.71 7.71 7.72 7.72 7.72

1F 10.06 10.06 10.25 10.25 10.25 10.25 10.25 10.26 10.26 10.26

3F 33.11 17.68 19.41 19.39 19.53 19.53 19.59 19.87 19.88 20.47

1F 27.47 13.51 14.29 14.30 14.36 14.36 14.38 14.51 14.52 14.82

3F 7.90 7.74 7.77 7.77 7.77 7.77 7.77 7.78 7.78 7.79

1F 10.50 10.29 10.33 10.33 10.33 10.33 10.33 10.34 10.34 10.35

3F 21.97 22.00 22.70 22.67 24.47 24.47 24.61 25.26 25.26 25.70

1F 17.84 17.85 18.01 18.00 19.63 19.63 19.69 19.98 19.98 20.16

3F 8.49 8.49 8.50 8.50 8.52 8.52 8.52 8.53 8.53 8.53

1F 11.25 11.25 11.26 11.26 11.29 11.29 11.29 11.30 11.30 11.31

3F 8.50 8.50 8.51 8.51 8.53 8.53 8.53 8.54 8.54 8.54

1F 11.07 11.07 11.08 11.08 11.11 11.11 11.11 11.12 11.12 11.12

3F 17.55 20.31 20.40

1F 15.02 16.29 16.33

3F 7.74 7.79 7.79

1F 10.30 10.35 10.35

3F 10.67 10.72 10.74 10.74 10.75 10.75 11.11 11.14 11.14 11.15

1F 8.28 8.29 8.30 8.30 8.31 8.31 8.61 8.63 8.63 8.61

3F 1.24 1.24 1.25 1.25 1.25 1.25

1F 0.85 0.85 0.85 0.85 0.85 0.85

3F 0.85 0.85 0.85 0.85

1F 0.62 0.62 0.62 0.62

3F 33.85 33.35 34.55 35.58 36.29 36.32 36.52 43.01 43.12 44.07

1F 29.38 28.60 29.67 31.64 32.03 32.04 32.16 39.50 39.57 40.15

3F 34.27 24.94 36.26 36.19 36.62 36.63 36.75 37.69 37.75 38.69

1F 34.27 25.72 35.44 35.72 36.00 36.01 36.08 37.33 37.38 38.02

3F 7.91 7.84 7.92 7.92 7.92 7.92 7.92 7.93 7.93 7.93

1F 10.51 10.43 10.52 10.52 10.53 10.53 10.53 10.53 10.53 10.54Tepexic TEP 3F 8.78 8.66 9.46 9.46 9.46 9.46 9.46 9.47 9.47 9.48

1F 7.72 7.66 8.06 8.06 8.06 8.06 8.07 8.07 8.07 8.07

23-A

85

Teotihuacan TTH

400

230

115

69

Teloloapan TLP

23-A

Tejupilco TJP 115

Tecomitl TCT

23-B

230

Tecamachalco TEH

230

23-A

230

23

Tecamac Móvil TKM

23-A

23-B

Tecamac TCM

230

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 57: Catalogo 2011-2020 r010212 Corto Circuito

57

Coordinación de Planificación

ÁREA CENTRAL

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 16.35 16.43 16.49 16.46 18.08 18.08 18.09 18.16 18.16 13.10

1F 8.13 8.14 8.15 8.14 8.38 8.38 8.39 8.39 8.39 3.01

3F 4.95 4.95 4.95 4.95 4.99 4.99 4.99 4.99 4.99 4.85

1F 4.30 4.30 4.30 4.30 4.32 4.32 4.32 4.32 4.32 4.25

3F 5.26 5.27 5.28 5.28 5.28 5.28 5.33 5.34 5.34 5.34

1F 4.04 4.04 4.04 4.04 4.04 4.04 4.07 4.07 4.07 4.07

3F 36.32 36.44 37.60 37.79 38.76 38.80 38.93 42.21 42.38 43.01

1F 33.82 33.82 34.81 35.43 36.02 36.04 36.14 39.19 39.31 39.68

3F 45.81 42.86 47.03 46.82 47.64 47.67 47.57 48.69 49.01 49.61

1F 47.66 45.46 49.10 49.06 49.70 49.72 49.63 50.84 51.08 51.51

3F 10.36 10.37 10.51 10.51 10.60 10.61 10.67 10.73 10.74 10.78

1F 8.63 8.66 8.70 8.70 8.74 8.74 8.80 8.83 8.83 8.85

3F 8.85 8.85 8.86 8.86 8.87 8.87 8.87 8.88 8.88 8.88

1F 10.33 10.33 10.33 10.33 10.34 10.34 10.35 10.35 10.35 10.35

3F 8.65 8.65 8.66 8.66 8.67 8.67 8.67 8.68 8.68 8.68

1F 10.11 10.11 10.12 10.12 10.12 10.12 10.13 10.13 10.13 10.13

3F 7.71 7.84 7.84 7.84 7.84 7.84 8.71 8.72 8.72 8.73

1F 3.88 3.90 3.90 3.90 3.90 3.90 4.59 4.59 4.59 4.58

3F 2.54 2.72 2.72 2.72 2.72 2.72 2.77 2.78 2.78 2.78

1F 1.48 1.52 1.52 1.52 1.52 1.52 1.56 1.56 1.56 1.56

3F 10.47 10.53 10.54 10.54 10.55 10.55 11.74 11.77 11.77 11.78

1F 6.98 7.00 7.00 7.00 7.01 7.01 8.07 8.08 8.08 8.06

3F 11.27 11.60 13.56 13.55 13.61 13.61 13.64 13.71 13.71 13.83

1F 9.32 9.48 10.14 10.14 10.17 10.17 10.18 10.21 10.21 10.25

3F 7.90 7.92 8.00 8.00 8.00 8.00 8.00 8.00 8.00 8.01

1F 10.34 10.36 10.45 10.45 10.45 10.45 10.45 10.45 10.45 10.46

3F 7.90 7.92 8.00 8.00 8.00 8.00 8.00 8.00 8.00 8.01

1F 10.34 10.36 10.45 10.45 10.45 10.45 10.45 10.45 10.45 10.46

3F 7.56 7.57 7.64 7.64 7.64 7.64 7.64 7.64 7.64 7.65

1F 10.06 10.08 10.16 10.16 10.17 10.17 10.17 10.17 10.17 10.17

3F 8.74 8.74 8.75 8.75 8.76 8.78 8.78 8.79

1F 1.94 1.94 1.94 1.94 1.94 1.94 1.94 1.94

3F 6.19 6.19 6.19 6.19 6.19 6.20 6.20 6.20

1F 5.34 5.34 5.34 5.34 5.34 5.34 5.34 5.34

3F 6.19 6.19 6.19 6.19 6.19 6.20 6.20 6.20

1F 5.34 5.34 5.34 5.34 5.34 5.34 5.34 5.34

23-A

23-B

Tlatelulco TTL

23-C

85

Tizayuca TIZ

23-A

23-B

Tizapa Maniobras TMA 115

230

Tingambato TIN 115

Tiquicheo TQC 115

23-A

23-B

Tianguistengo TIA

230

230

Texcoco TEX

Texcaltitlán TTT 115

400

85

23-A

Tepotzotlán TZN

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 58: Catalogo 2011-2020 r010212 Corto Circuito

58

Coordinación de Planificación

ÁREA CENTRAL

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 7.32 7.32

1F 1.26 1.26

3F 5.97 5.97

1F 5.22 5.22

3F 2.66 2.71 2.71 2.71 2.71 2.71 2.74 2.74 2.74 2.74

1F 1.76 1.78 1.78 1.78 1.78 1.78 1.80 1.80 1.80 1.80

3F 15.63 15.64 15.88 15.87 16.03 16.03 16.10 16.29 16.30 16.41

1F 15.28 15.29 15.46 15.45 15.55 15.55 15.60 15.72 15.73 15.79

3F 14.57 14.57 14.64 14.64 14.68 14.68 14.71 14.76 14.76 14.79

1F 2.31 2.31 2.31 2.31 2.31 2.31 2.31 2.31 2.31 2.31

3F 5.12 5.12 5.12 5.12 5.12 5.12 5.12 5.13 5.13 5.13

1F 4.56 4.56 4.56 4.56 4.56 4.56 4.56 4.56 4.56 4.56

3F 5.19 5.19 5.19 5.19 5.19 5.19 5.20 5.20 5.20 5.20

1F 4.62 4.62 4.62 4.62 4.62 4.62 4.62 4.62 4.62 4.62

3F 6.55 6.55 6.56 6.56 6.56 6.56 6.56 6.57 6.57 6.57

1F 5.48 5.48 5.48 5.48 5.48 5.48 5.48 5.48 5.48 5.49

3F 10.87 10.88 10.99 10.98 11.09 11.09 11.13 11.24 11.24 11.31

1F 8.90 8.90 8.95 8.95 9.00 9.00 9.02 9.07 9.07 9.10

3F 7.54 7.54 7.54 7.54 7.55 7.55 7.55 7.55 7.55 7.56

1F 10.04 10.04 10.05 10.05 10.05 10.05 10.05 10.06 10.06 10.06

3F 7.54 7.54 7.54 7.54 7.55 7.55 7.55 7.55 7.55 7.56

1F 10.04 10.04 10.05 10.05 10.05 10.05 10.05 10.06 10.06 10.06

3F 28.28 28.46 31.42 31.32 33.18 33.21 33.85 34.63 34.79 35.34

1F 27.29 27.43 29.31 29.26 30.39 30.40 30.89 31.94 32.34 32.65

3F 24.62 24.88 27.32 27.17 27.66 27.67 27.81 28.10 28.10 28.34

1F 26.47 26.68 29.07 28.95 29.33 29.34 29.45 29.70 29.72 29.90

3F 16.00 23.32 23.26 23.22 23.36 23.36 23.38 23.46 23.47 23.52

1F 6.16 7.54 7.43 7.43 7.44 7.44 7.44 7.44 7.44 7.44

3F 15.41 22.48 22.12 22.09 22.21 22.21 22.23 22.31 22.32 22.36

1F 6.30 7.80 7.56 7.56 7.57 7.57 7.57 7.58 7.58 7.58

3F 14.19 14.19 14.39 14.39 14.53 14.54 14.60 14.76 14.77 14.86

1F 13.20 13.20 13.32 13.31 13.40 13.40 13.44 13.53 13.53 13.59

3F 7.66 7.66 7.67 7.67 7.67 7.67 7.67 7.68 7.68 7.68

1F 10.20 10.20 10.21 10.21 10.21 10.21 10.22 10.22 10.22 10.23

3F 7.66 7.66 7.67 7.67 7.67 7.67 7.67 7.68 7.68 7.68

1F 10.20 10.20 10.21 10.21 10.21 10.21 10.22 10.22 10.22 10.23

PEX-H

23-A

23-B

Totoltepec TTC

85

230

Torre Pemex

230

85

Topilejo TOP

23-B

400

Toluca Dos Mil TDK

230

23-A

23-B

23-C

Toluca TOL

85

23-A

Tlapehuala TPA 115

230

85

23

Tlaltelulco móvil TTM

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 59: Catalogo 2011-2020 r010212 Corto Circuito

59

Coordinación de Planificación

ÁREA CENTRAL

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 22.91 23.65 24.18 24.14 24.41 24.42 24.53 25.45 25.46 27.18

1F 13.82 13.99 14.11 14.10 14.17 14.17 14.19 14.40 14.40 14.76

3F 34.47 33.94 34.68 34.79 35.24 35.25 37.05 36.91 36.97 37.80

1F 33.26 32.89 33.67 33.81 34.11 34.12 35.53 35.39 35.43 35.97

3F 37.68 42.78 43.39 43.38 43.82 43.83 44.27 44.71 44.80 45.78

1F 42.92 47.52 48.07 48.08 48.47 48.47 48.87 49.23 49.31 50.09

3F 5.67 5.62 4.52 4.52 4.52 4.52 4.52 4.53 4.53 4.53

1F 1.82 1.82 1.73 1.73 1.73 1.73 1.73 1.73 1.73 1.73

3F 4.15 4.14 3.95 3.95 3.95 3.95 3.95 3.95 3.95 3.95

1F 4.44 4.43 4.29 4.29 4.29 4.29 4.29 4.29 4.29 4.29

3F 4.15 4.14 3.95 3.95 3.95 3.95 3.95 3.95 3.95 3.95

1F 4.44 4.43 4.29 4.29 4.29 4.29 4.29 4.29 4.29 4.29

3F 4.15 4.14 3.95 3.95 3.95 3.95 3.95 3.95 3.95 3.95

1F 4.44 4.43 4.29 4.29 4.29 4.29 4.29 4.29 4.29 4.29

3F 4.29 4.32 4.32 4.44 4.43 4.38 4.39 4.42 4.42 4.50

1F 3.15 3.16 3.16 3.23 3.23 3.19 3.09 3.10 3.10 2.04

3F 37.32 37.36 38.26

1F 35.17 35.20 35.82

3F 52.11 39.69 41.85 43.89 44.71 44.72 44.30 44.27 44.51 44.90

1F 59.05 45.80 47.82 49.67 50.34 50.35 49.93 49.86 50.06 50.38

3F 52.11 39.69 41.85 43.89 44.71 44.72 44.30 44.27 44.51 44.90

1F 59.05 45.80 47.82 49.67 50.34 50.35 49.93 49.86 50.06 50.38

3F 24.39 15.37 18.24 15.49 18.34 18.34 18.34 18.34 18.35 18.31

1F 22.19 12.60 13.90 12.66 13.94 13.94 13.93 13.94 13.94 13.92

3F 5.39 5.21 5.28 5.21 5.29 5.29 5.29 5.29 5.29 5.28

1F 4.72 4.62 4.67 4.63 4.67 4.67 4.67 4.67 4.67 4.67

3F 5.32 5.15 5.22 5.15 5.22 5.22 5.22 5.22 5.22 5.22

1F 4.67 4.58 4.62 4.58 4.62 4.62 4.62 4.62 4.62 4.62

3F 6.89 6.60 6.72 6.60 6.72 6.72 6.72 6.72 6.72 6.72

1F 5.84 5.69 5.75 5.69 5.76 5.76 5.76 5.76 5.76 5.76

3F 4.59 4.55 4.06 4.06 4.06 4.06 4.06 4.06 4.06 4.06

1F 1.65 1.64 1.60 1.60 1.60 1.60 1.60 1.60 1.60 1.60

3F 5.28 5.26 5.07 5.07 5.07 5.07 5.07 5.07 5.07 5.07

1F 4.86 4.85 4.74 4.74 4.74 4.74 4.74 4.74 4.74 4.74

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

85

23-A

Valle Tulancingo VTG

23-C

Valle de México VAE

23-A

23-B

230-B

85

400

230-A

23-C

Tuxpan TUX 115

Tulancingo TLG

23-A

23-B

230

85

Tula TUL

Tren Suburbano TSU 230

400

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 60: Catalogo 2011-2020 r010212 Corto Circuito

60

Coordinación de Planificación

ÁREA CENTRAL

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 23.39 24.17 24.72 24.67 24.96 24.96 25.08 26.04 26.06 27.86

1F 14.02 14.19 14.32 14.31 14.37 14.37 14.40 14.61 14.61 14.98

3F 17.30 17.42 17.53 17.47 17.57 17.57 17.58 17.65 17.65 17.80

1F 8.14 8.14 8.16 8.15 8.17 8.17 8.17 8.18 8.18 8.20

3F 13.05 13.06 13.07 13.07 13.07 13.07 13.07 13.08 13.08 13.10

1F 16.40 16.41 16.42 16.42 16.42 16.42 16.43 16.44 16.44 16.46

3F 8.44 8.45 8.46 8.46 8.46 8.46 8.46 8.47 8.47 8.49

1F 11.15 11.16 11.17 11.17 11.17 11.17 11.17 11.18 11.18 11.20

3F 8.48 8.49 8.50 8.49 8.50 8.50 8.50 8.51 8.51 8.53

1F 11.20 11.21 11.22 11.22 11.22 11.22 11.22 11.23 11.23 11.26

3F 19.84 20.90 21.10 21.10 21.04 21.12 21.16 21.26

1F 16.41 17.52 17.61 17.61 17.58 17.62 17.64 17.68

3F 16.30 24.42 24.00 23.96 24.11 24.11 24.13 24.22 24.23 24.28

1F 6.54 8.17 7.91 7.91 7.92 7.92 7.92 7.93 7.93 7.93

3F 4.59 4.71 7.67 7.69 7.69 7.69 7.69 7.69 7.69 7.69

1F 4.12 4.19 10.15 10.17 10.17 10.17 10.17 10.17 10.17 10.17

3F 4.59 4.71 7.67 7.69 7.69 7.69 7.69 7.69 7.69 7.69

1F 4.12 4.19 10.15 10.17 10.17 10.17 10.17 10.17 10.17 10.17

3F 4.59 4.71

1F 4.12 4.19

3F 4.59 4.71

1F 4.12 4.19

3F 19.96 21.54 22.31 22.09 22.35 22.36 22.41 22.59 22.75 22.89

1F 19.76 20.79 21.30 21.17 21.33 21.34 21.37 21.48 21.58 21.66

3F 8.39 8.41 8.42 8.42 8.42 8.42 8.43 8.43 8.43 8.43

1F 10.91 10.94 10.95 10.95 10.95 10.95 10.95 10.95 10.96 10.96

3F 8.39 8.41 8.42 8.42 8.42 8.42 8.43 8.43 8.43 8.43

1F 10.91 10.94 10.95 10.95 10.95 10.95 10.95 10.95 10.96 10.96

3F 8.39 8.41 8.42 8.42 8.42 8.42 8.43 8.43 8.43 8.43

1F 10.91 10.94 10.95 10.95 10.95 10.95 10.95 10.95 10.96 10.96

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

23-B

23-C

Vértiz VER

230

23-A

23-C

23-D

Verónica VRN

23-A

23-B

85

23-C

230

Vallejo VAJ 23-A

23-B

230

85

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 61: Catalogo 2011-2020 r010212 Corto Circuito

61

Coordinación de Planificación

ÁREA CENTRAL

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 28.12 27.86 28.70 28.68 29.23 29.24 29.77 38.57 38.60 39.98

1F 25.71 25.57 26.08 26.07 26.51 26.51 26.82 35.68 35.70 37.03

3F 37.13 39.03 40.56 40.47 41.26 41.27 41.61 44.50 44.54 50.35

1F 39.43 41.19 42.34 42.28 43.09 43.10 43.35 46.34 46.37 54.85

3F 32.11 32.45 32.70 32.57 34.69 34.69 34.72 34.95 34.96 18.35

1F 20.50 20.59 20.66 20.62 21.14 21.14 21.15 21.20 21.20 3.78

3F 8.89 8.90 8.91 8.91 8.91 8.91 8.91 8.92 8.92 8.94

1F 11.94 11.95 11.96 11.96 11.96 11.96 11.96 11.98 11.98 12.00

3F 13.09 13.10 13.11 13.11 13.11 13.11 13.11 13.12 13.13 13.14

1F 16.72 16.73 16.74 16.74 16.74 16.74 16.75 16.76 16.76 16.78

3F 9.12 9.13 9.14 9.14 9.14 9.14 9.15 9.16 9.16 9.18

1F 11.96 11.98 11.99 11.99 11.99 11.99 11.99 12.01 12.01 12.03

3F 10.87 10.92 10.96 10.94 10.98 10.98 10.98 11.01 11.01 11.07

1F 5.35 5.35 5.36 5.35 5.36 5.36 5.36 5.36 5.36 5.37

3F 13.48 13.49 13.55 13.55 13.59 13.59 13.61 13.66 13.66 13.69

1F 2.02 2.02 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.04

3F 12.05 11.99 12.08 12.02 12.11 12.11 12.11 12.14 12.14 12.16

1F 6.34 6.30 6.32 6.31 6.33 6.33 6.33 6.33 6.33 6.33

3F 9.36 8.35 8.77 8.38 8.79 8.79 8.79 8.79 8.79 8.78

1F 5.29 4.80 4.90 4.81 4.90 4.90 4.90 4.90 4.90 4.90

3F 8.85 8.77 8.81 8.78 8.81 8.81 8.81 8.81 8.81 8.81

1F 8.90 8.84 8.87 8.84 8.87 8.87 8.87 8.87 8.87 8.87

3F 4.34 4.28 4.31 4.28 4.31 4.31 4.31 4.31 4.31 4.31

1F 3.96 3.92 3.94 3.92 3.94 3.94 3.94 3.94 3.94 3.94

3F 2.46 2.46 2.46 2.46 2.46 2.46 2.47 2.48 2.48 2.48

1F 1.69 1.69 1.69 1.69 1.69 1.69 1.69 1.69 1.69 1.69

3F 9.33 9.54 9.70 9.70 9.71 9.71 9.71 9.72 9.72 9.75

1F 2.20 2.21 2.21 2.21 2.21 2.21 2.21 2.21 2.21 2.21

3F 4.54 4.55 4.56 4.56 4.56 4.56 4.56 4.57 4.57 4.57

1F 4.05 4.06 4.07 4.07 4.07 4.07 4.07 4.07 4.07 4.07

3F 4.54 4.55 4.56 4.56 4.56 4.56 4.56 4.57 4.57 4.57

1F 4.05 4.06 4.07 4.07 4.07 4.07 4.07 4.07 4.07 4.07

3F 12.08 12.03 12.12 12.06 12.15 12.15 12.15 12.18 12.18 12.20

1F 6.33 6.29 6.31 6.30 6.31 6.31 6.31 6.32 6.32 6.32

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Vitro Fibra VFI 85

23-A

23-B

Vito VIT

Villa Guerrero VGO 115

85

23-A

23-B

Villa de las Flores VDF

Vidrio Plano de México VPM 85

85

Vidriera Los Reyes VLR 85

Vidriera Toluca VDT 85

23-B

23-C

Victoria VIC

85

23-A

400

230

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 62: Catalogo 2011-2020 r010212 Corto Circuito

62

Coordinación de Planificación

ÁREA CENTRAL

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 8.75 8.76 8.81 8.81 8.85 8.85 8.87 8.96 8.96 8.99

1F 6.77 6.78 6.81 6.81 6.82 6.83 6.87 6.91 6.91 6.86

3F 13.70 13.78 13.81 13.81 13.83 13.83 14.19 14.25 14.25 14.27

1F 14.40 14.46 14.48 14.48 14.50 14.50 14.87 14.91 14.91 14.88

3F 22.37 19.93 20.48 21.95 22.16 22.16 22.09 22.33 22.38 22.49

1F 18.01 16.84 17.35 18.13 18.22 18.22 18.18 18.32 18.34 18.39

3F 8.40 8.36 8.37 8.40 8.40 8.40 8.40 8.40 8.40 8.40

1F 6.66 6.64 6.65 6.66 6.66 6.66 6.66 6.66 6.66 6.66

3F 8.41 8.37 8.38 8.40 8.40 8.40 8.40 8.41 8.41 8.41

1F 6.66 6.64 6.65 6.66 6.66 6.66 6.66 6.66 6.66 6.67

3F 8.32 8.28 8.29 8.31 8.31 8.31 8.31 8.32 8.32 8.32

1F 6.61 6.59 6.60 6.61 6.61 6.61 6.61 6.61 6.61 6.61

3F 8.32 8.28 8.29 8.31 8.32 8.32 8.32 8.32 8.32 8.32

1F 6.61 6.59 6.60 6.61 6.61 6.61 6.61 6.61 6.61 6.61

3F 8.32 8.28 8.29 8.31 8.31 8.31 8.31 8.32 8.32 8.32

1F 6.61 6.59 6.60 6.61 6.61 6.61 6.61 6.61 6.61 6.61

3F 8.32 8.28 8.29 8.31 8.32 8.32 8.32 8.32 8.32 8.32

1F 6.61 6.59 6.60 6.61 6.61 6.61 6.61 6.61 6.61 6.61

3F 8.18 8.07 8.76 8.76 8.77 8.77 8.77 8.78 8.78 8.78

1F 6.92 6.87 7.20 7.20 7.20 7.20 7.20 7.20 7.20 7.20

3F 1.36 1.36 1.37 1.37 1.37 1.37 1.37 1.37 1.37 1.37

1F 1.38 1.38 1.38 1.38 1.38 1.38 1.38 1.38 1.38 1.38

3F 20.68 21.07 21.74 21.57 21.83 21.84 21.90 22.07 22.16 22.29

1F 18.15 18.37 19.31 19.22 19.36 19.36 19.39 19.49 19.54 19.61

3F 9.12 9.13 9.14 9.14 9.15 9.15 9.15 9.15 9.15 9.15

1F 11.88 11.89 11.91 11.90 11.91 11.91 11.91 11.91 11.91 11.92

3F 9.12 9.13 9.14 9.14 9.15 9.15 9.15 9.15 9.15 9.15

1F 11.88 11.89 11.91 11.90 11.91 11.91 11.91 11.91 11.91 11.92

3F 9.12 9.13 9.14 9.14 9.15 9.15 9.15 9.15 9.15 9.15

1F 11.88 11.89 11.91 11.90 11.91 11.91 11.91 11.91 11.91 11.92

3F 6.30 6.30 6.30 6.30 6.31 6.31 6.31 6.33 6.33 6.33

1F 4.48 4.48 4.48 4.48 4.48 4.48 4.49 4.49 4.49 4.48

3F 22.10 22.26 22.37 22.31 24.54 24.54 24.56 24.67 24.67 15.81

1F 11.78 11.81 11.83 11.82 12.20 12.20 12.20 12.22 12.22 3.37

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Yebucibi YBB 115

Zapata Envases ZAE 85

23-B

23-C

Xochimilco XOC

230

23-A

85

23

Xicotepec XIP

23-C1

23-C2

Xalostoc XAL 23-B1

23-B2

23-A1

23-A2

115

230

Volcán Gordo VLG

400

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 63: Catalogo 2011-2020 r010212 Corto Circuito

63

Coordinación de Planificación

ÁREA CENTRAL

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 27.79 29.03 28.46 28.88 28.89 28.96 29.28 29.82 30.04

1F 25.31 26.09 25.76 25.99 26.00 26.03 26.22 26.51 26.62

3F 7.76 7.77 7.76 7.77 7.77 7.77 7.77 7.77 7.77

1F 10.25 10.27 10.26 10.26 10.26 10.26 10.27 10.27 10.27

3F 7.76 7.77 7.76 7.77 7.77 7.77 7.77 7.77 7.77

1F 10.25 10.27 10.26 10.26 10.26 10.26 10.27 10.27 10.27

3F 4.53 4.54 4.39 4.39 4.39 4.39 4.39 4.40 4.40 4.40

1F 1.08 1.08 1.38 1.38 1.38 1.38 1.38 1.38 1.38 1.38

3F 3.96 3.96 3.93 3.93 3.94 3.94 3.94 3.94 3.94 3.94

1F 4.30 4.30 4.27 4.27 4.28 4.28 4.28 4.28 4.28 4.28

3F 3.96 3.96 3.93 3.93 3.94 3.94 3.94 3.94 3.94 3.94

1F 4.30 4.30 4.27 4.27 4.28 4.28 4.28 4.28 4.28 4.28

3F 2.15 2.15 2.15 2.15 2.15 2.17 2.18 2.18 2.18

1F 1.23 1.23 1.23 1.23 1.23 1.25 1.25 1.25 1.25

3F 1.21

1F 1.11

3F 4.58 4.60 4.60 4.76 4.75 4.72 4.72 4.75 4.75 4.81

1F 3.29 3.30 3.30 3.40 3.39 3.37 3.30 3.30 3.31 2.44

3F 4.88 4.90 4.90 5.09 5.09 5.06 5.07 5.09 5.09 5.14

1F 3.47 3.48 3.48 3.61 3.61 3.58 3.53 3.54 3.54 2.77

3F 7.41 7.52 7.70 7.70 7.71 7.71 7.71 7.72 7.72 7.74

1F 2.20 2.21 2.22 2.22 2.22 2.22 2.22 2.22 2.22 2.22

3F 4.38 4.39 4.40 4.40 4.40 4.40 4.40 4.41 4.41 4.41

1F 4.06 4.06 4.07 4.07 4.07 4.07 4.07 4.07 4.07 4.07

3F 4.38 4.39 4.40 4.40 4.40 4.40 4.40 4.41 4.41 4.41

1F 4.06 4.06 4.07 4.07 4.07 4.07 4.07 4.07 4.07 4.07

3F 4.38 4.38 4.40 4.40 4.40 4.40 4.40 4.40 4.40 4.40

1F 4.06 4.06 4.07 4.07 4.07 4.07 4.07 4.07 4.07 4.07

3F 13.72 13.71 13.77 13.77 13.80 13.86 13.87 13.99

1F 9.92 9.92 9.94 9.94 9.95 9.98 9.98 10.02

3F 7.64 7.64 7.65 7.65 7.65 7.65 7.65 7.65

1F 10.17 10.17 10.17 10.17 10.17 10.17 10.17 10.18

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

230

23-A

Zumpango Dos ZMD

23-B

23-C

Zumpango ZUM

85

23-A

Zitácuaro ZIT 115

Zitácuaro Dos ZID 115

Zirándaro ZIR

115

69

23-A

23-B

Zictepec ZIC

23-B

85

Zaragoza ZAR

230

23-A

_______Catálogo de Corto Circuito 2011-2020_____

Page 64: Catalogo 2011-2020 r010212 Corto Circuito

64

Coordinación de Planificación

ÁREA ORIENTAL

ÁREAORIENTAL

ESTUDIO DE CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

______________Catálogo de Corto Circuito 2011-2020 _______Catálogo de Corto Circuito 2011-2020_____

Page 65: Catalogo 2011-2020 r010212 Corto Circuito

65

Coordinación de PlanificaciónRED ELÉCTRICA PRINCIPAL 2011

ÁREA ORIENTAL

_______Catálogo de Corto Circuito 2011-2020_____ _____

Pie de la Cuesta

Ixtapa Potencia

Peñitas

Manuel Moreno Torres

Angostura

Tapachula Pototencia

Tabasco Potencia

Km.20

Temascal II

Juile

Tecali

Poza Rica II

Cruz Azul Maniobras

Texcoco

A Tamos(Área Noreste)

Teotihuacán

Topilejo

Zapata

Mezcala

Los Ríos

Conejos

Oaxaca Potencia

La Ciénega

Ejutla

Temascal I

Caracol

Chilpancingo Potencia

Cementos Moctezuma

Zocac

El Castillo

Jalacingo

Mazatepec

Pantepec

CYCNA

Cerro de Oro

SuchiateA los Brillantes(Guatemala)

Ojo de Agua

Simec Int.

HYLSA

Tula

La Paz

O c e á n o P a c í f i c o

Golfo de TehuantepecS i m b o l o g í a

Subestación a 400 kV

Subestación a 230 kV

Subestación a 115 kV

Enlace a 400 kV

Enlace a 230 kV

Enlace a 115 kV

Reactor

CEV

Ciclo Combinado

Eólica

Hidroeléctrica

Térmica ConvencionalEstructura de doble circuito

Tendido del primero

Nuclear

Burlington

150 MVAr

75 MVAr

100 MVAr

150 MVAr

100 MVAr

75 MVAr75

MVAr

70 MVAr

62 MVAr

50 MVAr

50 MVAr

50 MVAr

50 MVAr

55 MVAr

55 %

47 %

50 MVAr

62 MVAr

+150 MVAr-50 MVAr

21 MVAr

25 %

A Santa Lucía(Área Peninsular)

Sta. Cruz

Estado de Veracruz

Estado de Hidalgo

Esta

do d

e H

idalg

o

3x200 MW

1x100 MVA 230/115kV

Esta

do d

e Méx

ico

Estado de Tlaxcala

Estado de Puebla

Estado de Morelos

Esta

do d

e M

ore

los

Estado d

e Guer

rero

Esta

do d

e G

uerre

ro

Esta

do d

e O

axaca

Estado de Puebla

Estado de Oaxaca

Estado de

Tabasco

Estado de

Veracruz

Estado

de

Taba

sco

Estado de Chiapas

Esta

do d

e V

era

cru

z

Esta

do d

e

México

Distr

ito F

edera

l

Estado de México

62 MVAr

San MartínPotencia

A Santiago Tianguistenco(Área Central)

A Lázaro Cárdenas(Área Centro Occidente)

Est

ado d

e C

hia

pas

República

de G

uate

mala

A Escárcega(Área Peninsular)

1X100 MVA 230/115kV

2x330 MVA 400/230kV

4x55 MW

1x100 MVA 230/115kV

2x100 MVA 230/115kV

2x100 MVA 230/115kV

2x100 MVA 230/115kV

70 MVAr

21 MVAr

1x100 MVA 230/115kV

1x225 MVA 230/115kV

Op.inic. 230kV

2x100 MVA 230/115kV O

p.in

ic.

115kV

1x225 MVA 230/115kV

2x100 MVA 230/115kV

2x225 MVA 400/230kV

2X100 MW 4x38.5 MW

2x225 MVA 400/230kV

G o l f o d e

M é x i c o

INFORMACIÓN RESERVADA

DE ACUERDO CON LA LEY

FEDERAL DE TRANSPARENCIA

Y ACCESO A LA INFORMACIÓN

PÚBLICA GUBERNAMENTAL

Comalcalco Potencia

Veracruz II

Jardìn1x225 MVA 230/115kV

2x225 MVA 230/115kV

Laguna Verde2x810 MW1X330 MVA 400/230kV

Minatitlán II

TAMSA II

75 MVAr

Tuxpan PV6X350 MW

75 MVAr

A Minera Autlán(Área Noreste)

1X375 MVA 400/115kV

4x105 MW2x375 MVA 400/230kV

1x225 MVA 230/115kV

1x225 MVA 230/115kV

1x225 MVA 230/115kV

1x375 MVA 400/115kV

1x100 MVA 230/115kV2x225 MVA

400/115kV

1x375 MW 400/115kV

Chinameca Potencia

1x375 MVA 400/115kV

Coatzacoalcos II

Dos Bocas

37%32%

47%

82%Tolteca

Cementos

62 MVAr

Macuspana II

Op.inic. 115kV

Villahermosa Norte

1x100 MVA 230/115kV

Cintalapa El Sabino1x375 MVA 400/115kV

Malpaso 6x180 MW1x50 MVA

400/115kV

1x225 MVA1x375 MVA 400/230kV

Cárdenas II

1x225 MVA 230/115kV

1x375 MVA 400/115kV

70 MVAr

8x300 MW1x225 MVA 400/115kV

1x375 MVA400/115kV1x225 MW400/230kV

230/115kV2x100 MVA

230/85 kV2x100 MVA

53-2X1113

34.4

-1113

71.3-900

113.

2-11

13

134-

900207.7-1113

24-1113

143-

900

114-9

00

124-7

95

47.9-795

28-795

25.8-900

14.9-9008-900

17.8-795

99-795

116.9-1113

42-900

37-1113

1x225 MW

Puebla II2x375 MVA400/115kV

400/230kV

San Lorenzo Pot.2x375 MVA400/115kV2x133 MW1x123 MW

124.5-1113

225-1113

30.7

1113

226-

1113

178-

1113

80-9

00

50-900

49-900123-900

89-9

00

69-795

150-1113

242-3x1113

203-1113

238-3x1113

255-1113

55-1

113

68-1

113

202-1

113

198-1

113

59-9

00

151-9

00

92-900

2.7

-900

23-900

12.3-3x1113

78-1113

47-3x1113

80-1113

53.5-1113

29.5-1113

120-1

113

142-1113

192.7-1113

4-900

102-1113

106.7

-795

90-79514-900

14.8

-900

225-1113

181.3-1113

7-1113

144-1113

137-1113

37.7-1113

37-900

152-1113

69.4

-900

84-900

110-900

243-1113241.9-1113

80-111367-1113

88-1

11371.3-1113

31.7-1113

193.5

-1113

53.5-1113

27-1113

155-1113

154.2-1113

26.4

-1113

42-1

113

35-1113

Jalapa de Díaz1x20 MVA

230/13.8kV

163.3

-900

50-1113

ETZ 1x495 MWFET 2x491.5 MWEAT 1x495 MWTres Estrellas

2x100 MVA 230/115kV

Poza Rica I

2.6-900

7.7-1113

5-9

00

275.5-1113

26.7

-900

109.2-900

43-1113

48-900

Yautepec

1x375 MW400/115kV

2x375 MVA400/230kV

Los Amates2x100 MVA 230/115kV

El Quemado

±300 MVAr

±300 MVAr

Op.inic. 230kV78.8-1113

84.7

-1113

74-1113

128-1113

Parques eólicos en el Istmo de Tehuantepec

Amatlán II2x100MVA 230/115kV Manlio Fabio

Altamirano2x375 MVA 400/230kV

Oaxaca IV

Ixtepec Potencia

100 MVAr

75 MVAr

Estado de Oaxaca

Parque Ecológicos de México

135.8

-1113

Juchitán IIEurus

2x100 MVA 230/115kV

80 MW

85 MW

250 MW

±300 MVAr

3x375 MVA 400/230kV2x375 MVA 400/115kV

17.8-1113

16-1113

2.5-1113

45-1

113

Matías Romero Potencia 1x225 MVA 230/115kV

La Venta II

Oaxaca I

2-1113

9.8-1113

101 MWOaxaca II

101 MW

101 MWOaxaca III

101 MW

31-1113

25-1

113

157-1113

5x180 MW1x225 MVA 400/115kV

209.3

-1113

145-9

00102-1

113

147-1

113

100 MVAr

Op.inic. 115kV

Ixtepec Potencia

Juchitán II

2x100 MVA 230/115kV

±300 MVAr

La Venta II83.3 MW

16-1113

135.8-3X1113

Eurus

250 MW

3x375 MVA 400/230kV

2x375 MVA 400/115kV

Golfo de Tehuantepec

A Juile

A M

atía

s R

. Pot.

A Conejos

A Juile

A Juile

25-1113

2.7

-1113

Parques Ecológicos de México79.9 MW

17.8-1113

Oaxaca II101 MW

Oaxaca IV101 MW

Oaxaca III101 MW

Oaxaca I101 MW

9.8-1

113

31-1113

2-1113

145-9

00

Op.inic.

115kV

157-1

113

45-1

113

147-1

113

Page 66: Catalogo 2011-2020 r010212 Corto Circuito

66

Coordinación de PlanificaciónRED ELÉCTRICA PRINCIPAL 2020

ÁREA ORIENTAL

_______Catálogo de Corto Circuito 2011-2020_____ _____

Pie de la Cuesta

Ixtapa Potencia

Peñitas

Manuel Moreno Torres

Tapachula Pototencia

Tabasco Potencia

Km.20

Manlio Fabio Altamirano

Temascal II

Juile

Tecali

Cruz Azul Maniobras

Texcoco

A Tamos(Área Noreste)

Teotihuacán

Topilejo

Zapata

Mezcala

Los Ríos

Oaxaca Potencia

La Ciénega

Ejutla

Temascal I

Caracol

Chilpancingo Potencia

Cementos Moctezuma

Zocac

El Castillo

Jalacingo

Mazatepec

Pantepec

CYCNA

Cerro de Oro

SuchiateA los Brillantes(Guatemala)

Ojo de Agua

Simec Int.

HYLSA

Tula

La Paz

O c e á n o P a c í f i c o

Golfo de TehuantepecS i m b o l o g í a

Subestación a 400 kV

Subestación a 230 kV

Subestación a 115 kV

Enlace a 400 kV

Enlace a 230 kV

Enlace a 115 kV

Reactor

CEV

Ciclo Combinado

Eólica

Hidroeléctrica

Térmica ConvencionalEstructura de doble circuito

Tendido del primero

Nuclear

Burlington

150 MVAr

75 MVAr

100 MVAr

150 MVAr

100 MVAr

75 MVAr

75 MVArR

75 MVAr

70 MVAr

62 MVAr

50 MVAr

50 MVAr

50 MVAr

55 MVAr

55 %

47 %

50 MVAr

62 MVAr

+150 MVAr-50 MVAr

21 MVAr

25 %

A Santa Lucía(Área Peninsular)

Sta. Cruz

Estado de Veracruz

Estado de Hidalgo

Esta

do d

e H

idalg

o

3x200 MW

1x100 MVA 230/115kV

Esta

do d

e Méx

ico

Estado de Tlaxcala

Estado de Puebla

Estado de Morelos

Estado de Morelos

Estado d

e Guer

rero

Esta

do d

e G

uerre

ro

Esta

do d

e O

axaca

Estado de Puebla

Estado de Oaxaca

Estado de Oaxaca

Estado de

Tabasco

Estado de

Veracruz

Estado

de

Taba

sco

Estado de Chiapas

Esta

do d

e V

era

cru

z

Esta

do d

e

México

Distr

ito F

edera

l

Estado de México

62 MVAr

San MartínPotencia

A Santiago Tianguistenco(Área Central)

A Lázaro Cárdenas(Área Centro Occidente)

Est

ado d

e C

hia

pas

República

de G

uate

mala

A Escárcega(Área Peninsular)

2X100 MVA 230/115kV

4x55 MW

1x100 MVA 230/115kV

2x100 MVA 230/115kV

2x100 MVA 230/115kV

2x100 MVA 230/115kV

70 MVAr

21 MVAr

1x100 MVA 230/115kV

1x225 MVA 230/115kV

Op.inic. 230kV

2x100 MVA 230/115kV O

p.in

ic.

115kV

1x225 MVA 230/115kV

2x100 MVA 230/115kV

2x225 MVA 400/230kV

2X100 MW 4x38.5 MW

2x225 MVA 400/230kV

G o l f o d e

M é x i c o

INFORMACIÓN RESERVADA

DE ACUERDO CON LA LEY

FEDERAL DE TRANSPARENCIA

Y ACCESO A LA INFORMACIÓN

PÚBLICA GUBERNAMENTAL

Comalcalco Potencia

Veracruz II

Jardìn1x225 MVA 230/115kV

2x225 MVA 230/115kV

Laguna Verde2x810 MW1X330 MVA 400/230kV

Minatitlán II

TAMSA II

75 MVAr

Tuxpan PV6X350 MW

75 MVAr

A Minera Autlán(Área Noreste)

1X375 MVA 400/115kV

4x105 MW2x375 MVA 400/230kV

2x225 MVA 230/115kV

1x225 MVA 230/115kV

1x225 MVA 230/115kV

1x375 MVA 400/115kV

2x100 MVA 230/115kV2x225 MVA

400/115kV

1x375 MW 400/115kV

Chinameca Potencia

1x225 MVA 230/115kV

1x375 MVA 400/115kV

Olmeca

Coatzacoalcos II

Mezcalapa

Tagolaba

Huatulco Potencia

Alpuyeca

La Malinche

Dos Bocas

37%32%

47%

82%Tolteca

Cementos

62 MVAr

Macuspana II

Op.inic. 115kV

225 MW

Villahermosa Norte

2x100 MVA 230/115kV

Cintalapa El Sabino1x375 MVA 400/115kV

Malpaso 6x180 MW1x50 MVA

400/115kV

1x225 MVA1x375 MVA 400/230kV

Cárdenas II

1x225 MVA 230/115kV

1x225 MVA 230/115kV

1x225 MVA 230/115kV

1x375 MVA 400/115kV

1x375 MVA 400/115kV

1x225 MVA 230/115kV

1x225 MVA 230/115kV

2x375 MVA 400/230kV

70 MVAr

8x300 MW1x225 MVA 400/115kV

1x375 MVA400/115kV

230/115kV2x100 MVA

230/85 kV2x100 MVA

53-2X1113

34.4

-1113

71.3-900

113.

2-11

13

134-

900207.7-1113

24-1113

19-900

36.5-900

143-

900

101-9

00

110-7

95

47.9-795

28-795

25.8-900

14.9-9008-900

17.8-795

99-795

116.9-1113

118-1113

42-900

37-1113

2x225 MW

Puebla II2x375 MVA400/115kV

400/230kV

San Lorenzo Pot.2x375 MVA400/115kV2x133 MW1x123 MW

124.5-1113

225-1113

30.7

1113

226-

1113

178-

1113

80-9

00

50-900

49-900123-900

89-9

00

69-795

131.5-1113

242-3x1113

203-1113

238-3x1113

255-1113

55-1

113

68-1

113

202-1

113

198-1

113

59-9

00

151-9

00

92-900

2.7

-900

23-900

12.3-3x1113

78-1113

47-3x1113

80-1113

53.5-1113

29.5-1113

120-1

113

142-1113

192.7-1113

4-900

102-1113

106.7

-795

90-795 14-900

14.8

-900

225-1113

181.3-1113

7-1113

144-1113

137-1113

37.7-1113

37-900

152-1113

69.4

-900

84-900

84-900

241.9-1113

80-111367-1113

88-1

11371.3-1113

31.7-1113

193.5

-1113

53.5-1113

27-1113

155-1113

154.2-1113

26.4

-1113

42-1

113

35-1113

Jalapa de Díaz1x20 MVA

230/13.8kV

159.

4-11

13

163.

3-90

0

50-1113

ETZ 1x495 MWFET 2x491.5 MWEAT 1x495 MWTres Estrellas

2x100 MVA 230/115kV

Poza Rica I

2.6-900

7.7-1113

5-9

00

El Eden1x225 MVA 230/115kV

275.5-1113

26.7

-900

109.2-900

43-1113

48-900

Yautepec

1x375 MW400/115kV

2x375 MVA400/230kV

La Parota450 MW

Los Amates2x100 MVA 230/115kV

El Quemado

100 MVAr

±300 MVAr

±300 MVAr

Op.inic. 230kV78.8-1113

Centro1320 MW

14-795

17-1113

209.

3-11

13

28-900

84.7

-1113

74-1113

128-1113

Parques eólicos en el Istmo de Tehuantepec

Poza Rica II2x330 MVA 400/230kV

14-900

Amatlán II3x100MVA 230/115kV

Chicoasén II

239-1113

12-1113

Oaxaca IV

Oaxaca II

Juchitán IIEurus

2x100 MVA 230/115kV 250 MW

±300 MVAr

3x375 MVA 400/230kV2x375 MVA 400/115kV

17.8-1113

16-1113

2.5-1113

45-1

113

Matías Romero Potencia 1x225 MVA 230/115kV

Oaxaca I

2-1113

9.8-1113

101 MW

101 MW

101 MWOaxaca III

101 MW

31-111325-1113

Parque Ecológicos de México80 MW

101 MWLa Venta III

La Venta II85 MWIxtepec Potencia

26.5-1113

1x225 MVA 230/115kV

100 MVAr

1x225 MW400/230kV

50 MVAr

Papantla

400/115kV1x375 MVA

18.5-1113

114-1113

38-1

113

34-1113 Barra Vieja1x225 MVA 230/115kV

Angostura5x180 MW2x225 MVA 400/115kV

145-9

00102-1

113

147-1

113

135.8

-3X1113

1100 MWSureste I-IV

Laguna Superior3x375 MVA 400/230kV

100 MVAr

100 MVAr

250-1

113

Ixtepec Potencia

Juchitán II

2x100 MVA 230/115kV

±300 MVAr

La Venta II83.3 MW

17.8-1113

16-1113

135.8-3X1113

Eurus

250 MW

3x375 MVA 400/230kV

2x375 MVA 400/115kV

Golfo de Tehuantepec

A Juile

A M

atía

s R

. Pot.

A Juile

A Juile

Oaxaca II101 MW

Oaxaca IV101 MW

Oaxaca III101 MW

La Venta III

101 MW

Oaxaca I101 MW

9.8-1

113

31-1113

25-1113

2-1113

2.7

-1113

Parques Ecológicos de México79.9 MW

Tagolaba1x225 MVA 230/115kV

145-9

00

A Huatulco

Potencia

114-111345-1

113

147-1

113

38-1113

Page 67: Catalogo 2011-2020 r010212 Corto Circuito

67

Coordinación de PlanificaciónADICIONES Y RETIROS DE GENERACIÓN

ÁREA ORIENTAL

ADICIONES:

Nombre de la Central Año Capacidad Bruta

Oaxaca I /1 2010 101 MW

Oaxaca II, III y IV /2 2011 304 MW

Humeros Fase A 2011 27 MW

La Venta III /1 2011 101 MW

Proyectos de Autoabastecimiento de Temporada Abierta /2 2011-2014 1521 MW

Humeros Fase B 2012 27 MW

RM CC Poza Rica I /4 2012 161 MW

Proyecto de autoabastecimiento Nuevo Pemex 2013 300 MW

Sureste I y II /2 /3 2013 608 MW

Sureste III /3 2015 304 MW

Sureste IV /3 2016 304 MW

/ 1 Proyectos Eólicos interconectados en SE Juchitán II

/ 2 Proyectos Eólicos interconectados en SE Ixtepec Potencia

/ 3 Proyectos Eólicos interconectados en SE Laguna Superior

/ 4 Proyectos de Rehabilitación y Modernización (RM) de la Subdirección de Generación _______Catálogo de Corto Circuito 2011-2020

_____ _____

Page 68: Catalogo 2011-2020 r010212 Corto Circuito

68

Coordinación de PlanificaciónADICIONES Y RETIROS DE GENERACIÓN

ÁREA ORIENTAL

ADICIONES:

Nombre de la Central Año Capacidad Bruta

Chicoasén II 2017 225 MW

La Parota 2017 450 MW

El Pescado 2019 17 MW

Sistema Pescados 2019 120 MW

Xúchiles 2019 54 MW

RETIROS:

Nombre de la Central Año Capacidad Bruta

Dos Bocas, Paquete 2 2011 226 MW

Dos Bocas, Paquete 1 2012 226 MW

Humeros 2012 15 MW

Humeros 2015 25 MW

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 69: Catalogo 2011-2020 r010212 Corto Circuito

69

Coordinación de PlanificaciónMODELADO DE LA GENERACIÓN EÓLICA

ÁREA ORIENTAL

Para simplificar los modelos, se realizó un equivalente para cada uno de los desarrolladores que integran cada parque.

Cada equivalente tiene tres componentes principales.

1. El aerogenerador equivalente

2. El transformador de unidad equivalente

3. El sistema colector equivalente

Sistema equivalente de un parque eólico

Los parámetros de estos equivalentes son particulares para cada desarrollador y están en función de la capacidad de

generación instalada, del tipo y marca de aerogeneradores emplazados, así como de su distribución geográfica,

principalmente.

Eolo

Transformador de unidad equivalente

Punto de interconexión

Línea de transmisión de interconexión

Transformador de subestación

Sistema colector equivalente

Aerogenerador equivalente

Representan la capacidad total de generación y la

compensación reactiva de todos los aerogeneradores

Efecto agregado de los transformadores de cada aerogenerador

Efecto agregado del sistema colector y debe representar una aproximación de

las pérdidas y caída de voltaje

BTMTMTAT

MAT

ATMAT

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 70: Catalogo 2011-2020 r010212 Corto Circuito

70

Coordinación de PlanificaciónMODELADO DE LA GENERACIÓN EÓLICA

ÁREA ORIENTAL

El tipo de aerogeneradores, la marca, la capacidad y el numero de aerogeneradores de cada desarrollador que integran

los proyectos Inmediatos, la Nueva Temporada y la Temporada Abierta, se tomaron con base a información disponible

de las áreas operativas, de la Asociación Mexicana de Energía Eólica (AMDEE) y de internet.

Para los proyectos eólicos Sureste I Fase II a Sureste IV (1,100 MW), interconectados en la subestación Laguna

Superior se utilizó el mismo modelado que el de sureste I Fase I, esto es, se hicieron 11 equivalentes de 100 MW.

Para los aerogeneradores del tipo doblemente alimentados (DFIG), se consideró una reactancia subtransitoria Xd’’ =

0.2 p.u. en base a la capacidad del aerogenerador equivalente, para tener una contribución de 5 veces la corriente

nominal.

Para los del tipo Full Converter (FC) la reactancia subtransitoria Xd’’ = 0.91 p.u. en base a la capacidad del

aerogenerador equivalente, para tener una contribución de 1.1 veces la corriente nominal.

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 71: Catalogo 2011-2020 r010212 Corto Circuito

71

Coordinación de PlanificaciónMODELADO DE LA GENERACIÓN EÓLICA

ÁREA ORIENTAL

Dado que no se cuenta con el detalle del sistema colector de los parques eólicos, se hizo la siguiente consideración

para la impedancia equivalente del sistema colector.

Z= 0.02 p.u.

X/R=4

X/Y=0.5

Para el banco elevador de la subestación colectora se consideró un transformador de dos devanados con conexión

Delta – Estrella aterrizada y una impedancia Z=12% con base a la capacidad del banco y una relación X/R = 40.

En las siguientes figuras se muestran los equivalentes utilizados para el estudio de corto circuito de los parques eólicos

conectados a las subestaciones Juchitán II e Ixtepec Potencia.

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 72: Catalogo 2011-2020 r010212 Corto Circuito

72

Coordinación de PlanificaciónMODELADO DE LA GENERACIÓN EÓLICA

ÁREA ORIENTAL

Equivalentes de los parques eólicos interconectados en la subestación Juchitán II

Subestación Juchitán II

Juile

2X100 MVA

145-900

115KV115KV 34.5 KV 34.5 KV 690 V

230KV

18.5-1113

Punto de Interconexión

4.87-795

Z=0.0227+j0.227pu

Z=0.005+j0.02 puY=j0.04 pu

Z=0.01+j0.4 pu

Bíi Nee Stipa (26 MW, ±9 MVAr)

31 aerogeneradores Gamesa de 0.85 MW cada uno del tipo DFIG

Z=0.005+j0.02 puY=j0.04 pu

115KV 34.5 KV 34.5 KV 690 V5-795

Z=0.0272+j0.272 pu

Z=0.005+j0.02 puY=j0.04 pu

Z=0.01+j0.4 pu

Eoliatec del Istmo (22 MW, ±7 MVAr)

11 aerogeneradores Gamesa de 2.0 MW cada uno del tipo DFIG

30 MVA

30 MVA

Eurus (250 MW, ±82 MVAr)

167 aerogeneradores Acciona de 1.5 MW cada uno del tipo DFIG

12.0 KV

Z=0.0012+j0.048 pu

230KV 12.0 KV

250 MVA

34.5 KV 34.5 KV 690 V

Z=0.00751+j0.0751 pu

Z=0.005+j0.02 puY=j0.04 pu

Parques Ecológicos de México(79.9 MW, ±26 MVAr)

94 aerogeneradores Gamesa de 0.85 MW cada uno tipo DFIG

100 MVA

2.7-1113

230KV

Z=0.003+j0.12 pu

34.5 KV 34.5 KV 690 V

Z=0.0072+j0.072 pu

Z=0.005+j0.02 puY=j0.04 pu

La Venta II(83.3 MW, ±27 MVAr)

98 aerogeneradores Gamesa de 0.85 MW cada uno tipo DFIG

100 MVA

17.8-1113

230KV

Z=0.003+j.12 pu

34.5 KV 34.5 KV 690 V

Z=0.00593+j0.0593 pu

Z=0.005+j0.02 puY=j0.04 pu

La Venta III(101 MW, ±33 MVAr)

119 aerogeneradores Gamesa de 0.83 MW cada uno del tipo DFIG

125 MVA

9.8-1113

230KV

Z=0.0024+j.096 pu

34.5 KV 34.5 KV 690 V

Z=0.00588+j0.0588 pu

Z=0.005+j0.02 puY=j0.04 pu

Oaxaca I(101 MW, ±33 MVAr)

51 aerogeneradores Vestas de 2.0 MW cada uno tipo DFIG

125 MVA

9.8-1113

230KV

Z=0.0024+j.096 pu

9.28-795Eléctrica del Valle de México

(67.5 MW, ±22 MVAr)

27 aerogeneradores Clipper de 2.5 MW cada uno del tipo Full converter

115KV 13.2 kV

Z=0.005+j0.02 puY=j0.04 pu

Z=0.003+j0.12pu

13.2 kV

100 MVA

Punto de Interconexión

147-1113

58-1113103-1113

Matías Romero Potencia

Punto de Interconexión

Inmediatos

Nueva Temporada

Servicio Público

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 73: Catalogo 2011-2020 r010212 Corto Circuito

73

Coordinación de PlanificaciónMODELADO DE LA GENERACIÓN EÓLICA

ÁREA ORIENTAL

Equivalentes de los parques eólicos interconectados en la subestación Ixtepec Potencia

Subestación Ixtepec Potencia

SE Juile

3X375 MVAZ=0.0224 pu

2X375 MVAZ=0.0224 pu

136-1113 3C/F

115KV 115KV 34.5 KV 34.5 KV 690 V400KV

31-1113

230KV12.0 KV

25-1113

Punto de Interconexión

Z=0.00264+j0.00264 pu

Z=0.005+j0.02 puY=j0.04 pu

Z=0.0012+j0.048 pu

Fuerza y Energía Bíi Hioxo (227 MW, ±75 MVAr)

267 aerogeneradores Vestas o Gamesa de 0.85 MW cada uno del tipo DFIG

Z=0.005+j0.02 puY=j0.04 pu

Z=0.0026+j0.107 pu

Z=0.005+j0.02 puY=j0.04 pu

115KV 13.2 kV

16-795 Z=0.005+j0.02 puY=j0.04 pu

Z=0.0033+j0.133 pu

Fuerza Eólica del Istmo (80 MW, ±17 MVAr)

32 aerogeneradores Clipper de 2.5 MW cada uno del tipo Full converter

13.2 kV

115KV 34.5 KV 34.5 KV 690 V

26-795

Z=0.0049+j0.049 pu

Z=0.005+j0.02 puY=j0.04 pu

Z=0.0009+j0.0375 pu

Gamesa (Bíi Nee Stipa) (288 MW, ±95 MVAr)

144 aerogeneradores Gamesa de 2.0 MW cada uno del tipo DFIG

320 MVA

250 MVA

90 MVA

Oaxaca III (101 MW, ±33 MVAr)

68 aerogeneradores Acciona de 1.5 MW cada uno del tipo DFIG

Oaxaca IV (101 MW, ±33 MVAr)

68 aerogeneradores Acciona de 1.5 MW cada uno del tipo DFIG

230KV 12.0 KV 12.0 KV

Z=0.005+j0.02 puY=j0.04 pu

112 MVA

Oaxaca II (101 MW, ±33 MVAr)

68 aerogeneradores Acciona de 1.5 MW cada uno del tipo DFIG

12.0 KV

Z=0.0026+j0.107 pu

Z=0.0026+j0.107 pu

230KV 12.0 KV

112 MVA

230KV 12.0 KV

112 MVA

2-1113

34.5 KV 34.5 KV 690 V

Z=0.00422+j0.0422 pu

Z=0.005+j0.02 puY=j0.04 pu

Eoliatec del Istmo (142 MW, ±47 MVAr)

71 aerogeneradores Gamesa de 2.0 MW cada uno del tipo DFIG

160 MVA

15-1113

230KV

Z=0.0018+j0.075 pu

34.5 KV 34.5 KV 690 V

Z=0.00375+j0.0375 pu

Z=0.005+j0.02 puY=j0.04 pu

Eoliatec del Pacífico (160 MW, ±53 MVAr)

80 aerogeneradores Gamesa de 2.0 MW cada uno del tipo DFIG

180 MVA

27-1113

230KV

Z=0.0016+j0.066 pu

34.5 KV 34.5 KV 690 V

Z=0.00263+j0.0263 pu

Z=0.005+j0.02 puY=j0.04 pu

Desarrollos Eólicos Mexicanos (227.5 MW, ±75

MVAr)

114 aerogeneradores Gamesa de 2.0 MW cada uno del tipo DFIG

250 MVA

20-1113

230KV

Z=0.0012+j0.048 pu

34.5 KV 34.5 KV 690 V

Z=0.00227+j0.0227 pu

Z=0.005+j0.02 puY=j0.04 pu

FEMSA (Preneal) (396 MW, ±130 MVAr)

132 aerogeneradores Vestas de 3.0 MW cada uno del tipo DFIG

440 MVA

50-1113230KV

Z=0.0006+j0.0272 pu

36-1113

Punto de Interconexión

40-1113 Z=0.005+j0.02 puY=j0.04 pu

Sureste I Fase I (101 MW, ±33 MVAr)

68 aerogeneradores Acciona de 1.5 MW cada uno del tipo DFIG

12.0 KV

Z=0.0026+j0.107 pu

230KV 12.0 KV112 MVA

Temporada Abierta

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 74: Catalogo 2011-2020 r010212 Corto Circuito

74

Coordinación de PlanificaciónADICIONES Y RETIROS DE GENERACIÓN

ÁREA ORIENTAL

Con la instalación de generación eólica del proyecto denominado Temporada Abierta para 2011-2014 se impactará el

nivel de corto circuito en la zona Tehuantepec en los voltajes de 400 kV. Considerando los valores de 2011 para 2014

en la barra de 400 kV de la subestación Juile se incrementará el valor de corto circuito de 16.6 kA a 19.4 kA.

Debido a los proyectos eólicos Sureste I, II, III y IV para el 2013-2016, el corto circuito se incrementa igualmente en los

niveles de transmisión, siendo el cambio más notorio el valor de las subestaciones Cerro de Oro y Tecali en la barra de

400 kV al pasar de 20.6 kA a 24.8 kA y 22.6 kA a 26.4 kA, respectivamente de 2012 a 2016.

Para 2012, con la puesta en operación de la repotenciación de la Central Poza Rica I, se producen incrementos en los

niveles de corto circuito para las subestaciones adyacentes en 230 kV y 115 kV de la zona de distribución Poza Rica.

Finalmente, para el 2017 se tiene programada la entrada en operación de 225 MW de generación que se ubicará sobre

la cuenca del río Grijalva en el municipio de Chicoasén en el estado de Chiapas con el consecuente incremento del

valor de corto circuito en la subestación Manuel Moreno Torres en la barra de 400 kV al pasar de 27.9 kA a 29.8 kA.

También en este año con la entrada en operación de la Parota en la zona Acapulco, se producen incrementos en los

niveles de corto circuito para las subestaciones adyacentes en 230 kV y 115 kV de dicha zona de distribución.

En general en la mayoría de las subestaciones se mantienen los valores de corto circuito, esto es debido a la poca

adición de nuevas fuentes de generación.

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 75: Catalogo 2011-2020 r010212 Corto Circuito

75

Coordinación de PlanificaciónPRINCIPALES PROYECTOS DE TRANSMISIÓN Y TRANSFORMACIÓN

ÁREA ORIENTAL

Proyecto Año Nivel de tensión

Comalcalco Potencia Bco. 1 2012 230/115 kV

Cárdenas II – Comalcalco Potencia 2012 230 kV

Cerro de Oro Bco. 1 2013 400/115 kV

Papantla Bco. 1 2013 400/115 kV

La Malinche Bco. 1 2015 230/115 kV

Barra Vieja Bco. 1 2016 230/115 kV

Jalapa de Díaz – La Ciénega 2016 230 kV

Tagolaba Potencia Bco. 1 2017 230/115 kV

Alpuyeca Bco. 1 2017 230/115 kV

Dos Bocas Bco. 7 (SF6) 2017 230/115 kV

Tecali – Yautepec Potencia 2017 400 kV

Huatulco Potencia Bco. 1 2018 230/115 kV

Manlio Fabio Altamirano – Dos Bocas 2018 230 kV

Olmeca Bco. 1 2020 230/115 kV

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 76: Catalogo 2011-2020 r010212 Corto Circuito

76

Coordinación de PlanificaciónPRINCIPALES PROYECTOS DE TRANSMISIÓN Y TRANSFORMACIÓN

ÁREA ORIENTAL

Los principales proyectos de transmisión en el Área Oriental son redes asociadas a centrales y redes que tienen como

objetivo reforzar el troncal para transportar grandes magnitudes de potencia y proporcionar el suministro de la demanda

a los centros de consumo con la calidad y confiabilidad requerida.

En 2012 está programada la operación a 230 kV del doble circuito Cárdenas II – Comalcalco Potencia que actualmente

está operando en 115 kV. El corto circuito de la zona Chontalpa se verá incrementado en su valor para el caso de la

barra de 115 kV de la subestación Comalcalco Oriente de 4.9 kA a 7.3 kA .

En 2013 se incrementará el valor de corto circuito en la red eléctrica de las zonas Jalacingo y Poza Rica, con la entrada

en operación del Proyecto Papantla Bco 1. El valor de corto circuito trifásico en la subestación Tajín en 115 kV se

incrementa de 6.6 kA a 12.3 kA.

Las subestaciones que presentarán en el 2020 el mayor valor de corto circuito son: Yautepec Potencia con 30.3 kA

trifásico en 400 kV y 21.5 kA trifásico en 230 kV. En el nivel de 115 kV, San Lorenzo Potencia 53.5 kA monofásico.

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 77: Catalogo 2011-2020 r010212 Corto Circuito

77

Coordinación de Planificación

ÁREA ORIENTAL

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 3.26 3.26 3.26 3.26 3.26 3.46 3.46 3.46 3.46 3.46

1F 2.20 2.20 2.21 2.21 2.21 2.28 2.28 2.28 2.28 2.28

3F 1.25 1.25 1.25 1.26 1.26 1.26 1.28 1.28 1.28 1.28

1F 0.91 0.91 0.91 0.91 0.91 0.91 0.91 0.91 0.91 0.91

3F 7.81 7.79 7.83 7.83 7.83 9.22 9.25 9.25 9.25 9.25

1F 5.94 5.93 5.95 5.95 5.95 6.80 6.81 6.81 6.81 6.81

3F 6.19 6.19 6.23 6.40 6.36 6.42 8.09 8.09 8.11 8.11

1F 5.91 5.91 5.94 6.04 6.01 6.06 6.97 6.97 6.98 6.98

3F 2.87 2.87 2.87 3.18 3.24 3.25 3.26 3.27 3.27 3.27

1F 1.78 1.78 1.79 1.97 2.01 2.01 2.02 2.02 2.03 2.03

3F 3.31 3.31 3.90 5.26 5.27 5.27 5.28 5.27 5.29 5.28

1F 2.04 2.04 2.42 3.23 3.23 3.23 3.24 3.23 3.24 3.24

3F 10.99 11.00 11.09 11.09 11.12 11.12 11.13 11.13 11.14 11.11

1F 8.47 8.47 8.51 8.51 8.52 8.53 8.53 8.53 8.53 8.52

3F 4.17 4.14 4.16 4.16 4.16 4.16 4.17 4.17 4.47 4.47

1F 2.88 2.87 2.87 2.87 2.87 2.88 2.88 2.88 3.04 3.04

3F 10.36 10.37 10.41 10.41 10.95 10.95 10.94 10.93 10.97 10.95

1F 6.50 6.50 6.51 6.51 6.84 6.84 6.84 6.83 6.84 6.84

3F 5.90 5.90 5.94 6.10 6.06 6.12 7.63 7.63 7.64 7.64

1F 5.46 5.46 5.49 5.57 5.56 5.59 6.37 6.37 6.38 6.38

3F 6.21 6.21 6.23 6.23 6.24 6.24 6.24 6.24 6.25 6.24

1F 4.18 4.18 4.18 4.19 4.19 4.19 4.19 4.19 4.19 4.19

3F 6.37 6.37 6.39 6.39 6.40 6.40 6.41 6.41 6.41 6.40

1F 4.29 4.30 4.30 4.30 4.30 4.30 4.31 4.31 4.31 4.30

3F 8.48 8.49 8.52 8.56 7.99 7.99 8.11 8.38 8.40 8.39

1F 5.43 5.43 5.44 5.46 5.04 5.05 5.13 5.31 5.32 5.32

3F 1.20 1.20 1.20 1.46 1.46 1.61 1.66 1.69 1.68 1.68

1F 0.78 0.78 0.78 0.94 0.94 1.04 1.06 1.08 1.08 1.08

3F 13.91 13.80 13.99 14.00

1F 12.87 12.81 12.92 12.92

3F 16.51 16.43 16.56 16.57

1F 18.66 18.59 18.70 18.71

3F 3.77 3.71 3.73 3.73 5.16 5.16 5.17 5.16 5.18 5.18

1F 2.48 2.43 2.43 2.43 3.37 3.37 3.38 3.38 3.38 3.38

3F 19.00 19.02 19.20 19.30 19.45 19.46 19.46 19.41 19.52 19.40

1F 13.70 13.71 13.78 13.83 13.89 13.89 13.92 13.19 13.94 13.89

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Acacoyahua AYA 115

Acahuizotla ACH 69

Acala ALA 115

Acapulco APC 115

Acatlán ACA 115

Acatzingo ACZ 115

Acayucan ACY 115

Actopan AOC 115

Acuitlapilco AUL 115

Adolfo Ruiz Cortinez ARC 115

Agronitrogenados ARG 115

Agua Dulce II ADD 115

Agua Santa AGA 115

Agua Zarca AZA 115

Alumex AMX 115

Alpuyeca APY

230

115

Altzayanca AZY 115

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 78: Catalogo 2011-2020 r010212 Corto Circuito

78

Coordinación de Planificación

ÁREA ORIENTAL

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 12.66 11.55 11.70 11.69 11.75 11.75 12.21 12.19 12.29 12.29

1F 13.12 12.07 12.18 12.17 12.21 12.21 13.12 13.11 13.18 13.18

3F 2.32 2.31 2.46 2.46 2.46 2.46 2.46 2.46 2.47 2.47

1F 1.62 1.62 1.68 1.68 1.68 1.68 1.68 1.68 1.68 1.68

3F 8.02 8.24 8.30 8.35 8.39 8.39 8.41 8.40 8.51 8.47

1F 7.52 8.29 8.33 8.37 8.39 8.40 8.42 8.41 8.49 8.46

3F 16.24 16.76 16.90 17.10 17.18 17.19 17.23 17.20 17.54 17.35

1F 17.17 18.57 18.68 18.85 18.91 18.92 18.96 18.94 19.22 19.07

3F 5.59 5.59 5.61 6.02 6.03 6.03 6.04 6.03 6.04 6.03

1F 3.50 3.50 3.51 3.73 3.73 3.73 3.73 3.70 3.74 3.73

3F 13.40 13.44 13.52 13.53 13.54 13.57 13.75 13.75 13.75 13.74

1F 16.56 16.60 16.69 16.69 16.71 16.84 17.03 17.03 17.03 17.02

3F 12.09 12.09 12.22 12.23 12.23 17.80 17.89 17.89 17.89 17.89

1F 12.14 12.13 12.25 12.25 12.25 18.88 18.95 18.95 18.95 18.94

3F 19.52 19.56 19.72 19.76 19.90 19.91 19.91 19.86 19.97 19.86

1F 13.57 13.58 13.64 13.66 13.71 13.71 13.73 13.47 13.75 13.71

3F 3.41 3.41 3.42 4.39 4.40 4.40 4.70 4.70 4.72 4.70

1F 2.14 2.14 2.15 2.81 2.81 2.81 3.01 3.00 3.01 3.00

3F 10.26 10.27 10.31 10.31 11.53 11.54 11.57 11.55 11.61 11.60

1F 7.09 7.09 7.11 7.11 8.04 8.04 8.06 8.05 8.07 8.06

3F 2.41 2.42 2.42 2.42 2.42 2.43 2.43 2.43 2.43 2.43

1F 1.52 1.53 1.53 1.53 1.53 1.54 1.54 1.54 1.54 1.54

3F 1.77 1.77 1.78 2.29 2.25 2.25 2.26 2.28 2.28 2.28

1F 1.10 1.10 1.10 1.41 1.38 1.38 1.39 1.40 1.40 1.40

3F 14.00 14.04 14.11 14.11 18.96 18.96 19.00 18.94 19.08 19.03

1F 9.92 9.94 9.96 9.96 13.97 13.97 13.99 13.96 14.02 14.00

3F 14.71 14.73 14.82 14.84 14.93 14.93 14.93 14.90 14.96 14.91

1F 9.80 9.81 9.84 9.85 9.88 9.88 9.89 9.81 9.90 9.88

3F 7.71 7.72 7.74 7.88 7.24 7.24 7.38 7.68 7.69 7.69

1F 4.90 4.90 4.91 4.99 4.53 4.53 4.63 4.83 4.83 4.83

3F 1.91 1.91 1.91 2.05 2.05 2.05 2.05 2.05

1F 1.38 1.38 1.38 1.45 1.45 1.46 1.46 1.46

3F 4.14 5.89 6.70 5.91 5.91

1F 4.74 6.24 7.15 6.26 6.26

3F 7.27 10.27 10.83 10.30 10.30

1F 9.21 12.38 13.10 12.42 12.42

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Aluminio II ALD 230

Alvarado II AVD 115

Amatlán II ATD

230

115

Amozoc II AMZ 115

Angostura ANG

400

115

Antuñano AUN 115

Apecsa PEC 115

Apizaco API 115

Arriaga ARR 115

Atencingo AEN 115

Atlihuetzía ATZ 115

Atlixcáyotl AXT 115

Barra Vieja BJA

230

115

Atlixco ATC 115

Balancán BCA 115

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 79: Catalogo 2011-2020 r010212 Corto Circuito

79

Coordinación de Planificación

ÁREA ORIENTAL

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 6.05 6.05 6.06 6.06 6.06 7.27 7.28 7.28 7.29 7.28

1F 5.39 5.39 5.40 5.40 5.40 6.11 6.12 6.12 6.12 6.12

3F 5.66 5.57 8.83 8.83 8.86 8.90 8.92 8.92 8.97 8.95

1F 4.46 4.42 6.13 6.13 6.14 6.16 6.17 6.17 6.19 6.18

3F 7.77 8.01 8.03 8.03 8.03 8.04 7.90 7.93 7.93 7.93

1F 7.85 8.04 8.05 8.06 8.06 8.06 7.99 8.01 8.01 8.00

3F 12.29 9.40 9.76 9.76 9.78 9.78 13.32 13.31 13.37 13.37

1F 10.26 6.84 6.98 6.98 6.98 6.98 11.68 11.67 11.70 11.70

3F 3.55 3.55 3.64 3.64 3.64 3.69 3.69 3.69 3.69 3.69

1F 2.57 2.57 2.63 2.63 2.63 2.65 2.66 2.66 2.66 2.66

3F 5.26 4.94 4.97 5.07 5.05 6.19 9.28 9.54 9.30 9.30

1F 4.63 4.20 4.21 4.26 4.25 6.30 8.92 9.14 8.94 8.94

3F 9.13 9.14 9.30 11.00 11.05 11.05 11.05 11.04 11.08 11.04

1F 5.96 5.96 6.05 7.22 7.24 7.24 7.24 7.09 7.25 7.24

3F 6.06 6.77 6.98 6.98 6.98 6.98 6.99 6.98 6.98 6.98

1F 4.85 5.23 5.36 5.36 5.36 5.35 5.35 5.34 5.35 5.35

3F 16.20 16.22 16.34 16.38 16.48 16.49 16.49 16.45 16.53 16.47

1F 10.94 10.95 10.99 11.00 11.05 11.05 11.05 10.96 11.07 11.05

3F 9.27 9.27 9.50 9.50 9.65 9.65 9.70 9.64 9.72 9.73

1F 6.77 6.77 6.90 6.90 6.97 6.97 7.00 6.98 7.01 7.01

3F 1.47 1.48 1.48 1.50 1.60 2.61 2.61 2.61

1F 0.95 0.96 0.96 0.96 1.03 2.35 2.35 2.35

3F 4.75 4.71 6.13 6.13 6.13 6.13 6.14 6.14 6.14 6.33

1F 4.31 4.27 5.43 5.43 5.43 5.43 5.44 5.44 4.72 4.81

3F 3.13 3.14 3.14 3.14 3.16 3.16 3.16 3.16 3.17 3.16

1F 1.97 1.97 1.97 1.97 1.98 1.98 1.98 1.98 1.98 1.98

3F 11.72 11.74 11.81 11.81 11.84 11.84 11.86 11.85 11.86 11.82

1F 9.00 9.01 9.04 9.04 9.05 9.05 9.06 9.05 9.06 9.04

3F 8.20 8.20 8.23 8.27 8.27 8.28 8.89 8.88 8.95 8.95

1F 9.54 9.54 9.57 9.61 9.60 9.62 10.15 10.15 10.21 10.21

3F 2.00 2.00 2.99 3.00 3.00 3.00 3.09 3.09 3.51 3.51

1F 1.37 1.37 2.16 2.16 2.16 2.16 2.20 2.20 2.93 2.93

3F 3.02 2.98 2.99 2.99 2.99 2.99 3.00 3.00 3.06 3.06

1F 1.93 1.91 1.92 1.92 1.92 1.92 1.92 1.92 1.95 1.95

3F 7.34 8.31 10.19 10.19 10.19 10.19 10.17 10.17 10.17 10.49

1F 6.01 7.08 9.23 9.24 9.24 9.24 9.23 9.24 9.23 9.41

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Belisario Domínguez BDZ 115

Benito Juárez BJU 115

BII NEE Stipa BNS 115

Boca del Río BDR 115

Bochil BCH 115

Bonfil BOF 115

Bosques BOS 115

Buenavista BVI 115

Bugambilias BGB 115

Burlington Yecapixtla YCP 230

Cacaluta CCT 115

Cactus CAX 115

Calpulalpan CPL 115

Cánticas CIC 115

Cárdenas I CDN 115

Caracol CRL

230

115

Cardel CAE 115

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 80: Catalogo 2011-2020 r010212 Corto Circuito

80

Coordinación de Planificación

ÁREA ORIENTAL

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 6.27 7.80 8.37 8.38 8.38 8.38 8.34 8.34 8.34 8.75

1F 5.38 7.64 8.08 8.08 8.09 8.09 8.08 8.09 8.08 8.34

3F 9.47 10.88 12.10 12.11 12.11 12.11 12.08 12.08 12.08 12.53

1F 8.95 11.16 12.22 12.22 12.23 12.23 12.22 12.23 12.21 12.54

3F 5.65 5.97 8.90 8.90 8.90 8.90 8.89 8.89 8.89 9.12

1F 4.35 4.66 7.54 7.54 7.55 7.55 7.54 7.55 7.54 7.66

3F 3.46 3.42 4.02 4.02 4.02 4.02 4.04 4.04 4.05 4.05

1F 2.38 2.37 2.63 2.62 2.62 2.63 2.63 2.63 2.64 2.64

3F 2.83 2.83 2.87 2.87 2.87 2.87 2.87 2.87 2.87 2.87

1F 2.65 2.65 2.68 2.68 2.68 2.68 2.68 2.68 2.68 2.68

3F 7.77 7.78 7.84 8.12 8.06 8.19 11.49 11.55 11.53 11.54

1F 8.79 8.79 8.85 9.08 9.04 9.19 11.93 11.98 11.96 11.96

3F 7.29 8.94 10.50 10.50 10.51 10.51 10.53 10.50 10.52 10.52

1F 5.94 6.88 7.90 7.90 7.90 7.90 7.91 7.89 7.90 7.90

3F 3.01 3.02 3.02 3.02 3.05 3.05 3.05 3.05 3.05 3.05

1F 1.89 1.90 1.90 1.90 1.91 1.91 1.90 1.90 1.91 1.91

3F 1.83 1.83 1.83 1.83 1.83 1.85 1.85 1.85 1.85 1.85

1F 2.25 2.25 2.25 2.25 2.25 2.27 2.27 2.27 2.27 2.27

3F 10.16 10.17 10.23 10.23 10.25 10.25 10.26 10.26 10.27 10.24

1F 8.10 8.11 8.13 8.13 8.14 8.14 8.15 8.14 8.15 8.14

3F 7.64 7.64 7.70 7.98 7.93 8.03 11.05 11.08 11.09 11.09

1F 8.38 8.38 8.43 8.66 8.62 8.73 11.02 11.04 11.05 11.05

3F 4.68 5.09 5.25 5.25 5.25 5.33 5.34 5.34 5.34 5.34

1F 3.77 4.04 4.10 4.10 4.10 4.14 4.15 4.15 4.14 4.14

3F 5.36 5.41 5.42 5.42 5.42 5.42 5.42 5.43 5.43 5.42

1F 4.46 4.47 4.48 4.48 4.48 4.48 4.48 4.49 4.49 4.49

3F 9.43 9.42 9.64 9.64 9.92 9.93 9.92 9.87 9.96 9.96

1F 6.41 6.41 6.50 6.51 6.63 6.64 6.64 6.62 6.65 6.65

3F 7.31 7.32 7.40 7.40 7.46 7.47 7.59 7.56 7.60 7.60

1F 5.65 5.65 5.69 5.69 5.73 5.73 5.79 5.78 5.79 5.79

3F 13.27 13.29 13.75 13.75 14.10 14.11 14.34 14.20 14.40 14.41

1F 11.27 11.28 11.59 11.60 11.80 11.79 12.33 12.26 12.36 12.36

3F 10.07 10.12 10.17 10.31 10.34 10.35 10.36 10.35 10.47 10.34

1F 7.26 7.28 7.30 7.35 7.36 7.37 7.37 7.37 7.41 7.35

3F 4.12 4.18 4.45 4.45 4.45 4.49 4.49 4.48 4.48 4.48

1F 2.95 2.97 3.14 3.14 3.14 2.72 2.72 2.71 2.72 2.72

Cárdenas Sur CDS 115

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Cárdenas II CDD

230

115

Carlos A. Carrillo CAC 115

Catemaco CTO 115

Cayaco CAY 115

Cazones CZN 115

Cebadas y Maltas CBM 115

Cecilio del Valle CCL 69

Celanece CLS 115

Cementos Apasco, Acapulco CAP 115

Cementos Apasco, Tabasco CEM 115

Cementos Cruz Azul, Oaxaca CCA 115

Cementos Cruz Azul, Puebla CZC 400

Cementos de Oriente TOC 230

Cerro Azul II CDO 115

Cementos Moctezuma CUM 230

Cementos Veracruz CVE 115

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 81: Catalogo 2011-2020 r010212 Corto Circuito

81

Coordinación de Planificación

ÁREA ORIENTAL

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 20.25 20.62 23.39 23.48 24.50 24.81 24.90 24.77 25.10 24.07

1F 16.83 17.01 21.08 21.13 21.71 21.88 21.94 21.85 22.05 21.18

3F 22.27 22.26 22.43 22.50 22.63 22.60 22.95 22.82

1F 21.77 21.76 21.88 21.93 22.02 22.00 22.25 22.10

3F 5.10 5.02 7.73 7.73 7.75 7.78 7.80 7.80 7.84 7.82

1F 3.88 3.84 5.26 5.26 5.26 5.28 5.29 5.28 5.30 5.29

3F 12.43 12.54 12.63 12.79 12.84 12.84 12.87 12.85 13.24 13.08

1F 11.95 12.04 12.09 12.20 12.22 12.23 12.24 12.23 12.53 12.43

3F 7.83 7.84 7.87 7.91 7.56 7.56 7.64 7.80 7.82 7.81

1F 5.01 5.01 5.02 5.04 4.79 4.79 4.84 4.95 4.96 4.96

3F 20.70 20.69 20.71 20.65

1F 17.75 17.75 18.71 18.68

3F 2.52 2.54 2.65 2.65 2.65 2.66 2.66 2.66 2.66 2.66

1F 1.70 1.70 1.76 1.76 1.76 1.52 1.52 1.52 1.52 1.52

3F 2.70 2.70 2.70 2.70 2.72 2.72 2.72 2.72 2.73 2.73

1F 1.71 1.71 1.71 1.71 1.73 1.73 1.73 1.73 1.73 1.73

3F 2.49 2.49 2.49 2.50 2.50 2.50 2.59 2.59 2.60 2.60

1F 1.97 2.48 1.98 1.98 1.98 1.98 2.02 2.02 2.02 2.02

3F 1.99 1.99 1.99 1.99 1.99 1.99 2.03 2.03 2.03 2.03

1F 1.87 1.21 1.87 1.87 1.87 1.87 1.89 1.89 1.89 1.89

3F 2.81 2.81 2.85 2.85 2.85 2.85 2.86 2.86 2.86 2.86

1F 2.74 2.74 2.77 2.77 2.77 2.77 2.77 2.77 2.77 2.77

3F 6.19 6.22 6.24 6.29 6.28 6.30 6.95 6.95 7.01 7.01

1F 6.55 6.34 6.35 6.39 6.38 6.39 6.82 6.82 6.86 6.86

3F 2.21 2.22 2.22 2.22 2.22 2.22 2.26 2.26 2.27 2.27

1F 2.83 2.82 2.83 2.83 2.83 2.83 2.88 2.88 2.88 2.88

3F 7.58 7.58 7.62 7.68 7.67 7.70 8.62 8.62 8.71 8.71

1F 9.43 9.42 9.45 9.52 9.51 9.54 10.46 10.46 10.55 10.55

3F 5.19 5.19 5.22 5.28 5.27 5.30 6.18 6.19 6.25 6.25

1F 6.36 6.36 6.40 6.45 6.44 6.47 7.33 7.33 7.39 7.40

3F 8.02 8.02 8.06 8.13 8.11 8.15 9.18 9.18 9.28 9.28

1F 11.68 11.68 11.74 11.84 11.82 11.87 13.33 13.33 13.46 13.46

3F 18.62 18.66 18.83 18.84 18.91 18.93 18.96 18.95 18.98 18.87

1F 19.76 19.78 19.92 19.93 19.98 19.99 20.01 20.01 20.03 19.95

Cervecería del Trópico CVT 115

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Cerro de Oro EDO

400

115

Cervecería Moctezuma CMA 115

Chachapa CHA 115

Chicoasén II CPN 400

Chicontepec CHI 115

Chignahuapan CHH

115

115

Chilapa CIP 69

Chilapan CHP

115

115

Chilpancingo CHG 69

Chinameca II CHD 115

Chilpancingo II CCS

115

230

Chilpancingo Potencia CNP 115

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 82: Catalogo 2011-2020 r010212 Corto Circuito

82

Coordinación de Planificación

ÁREA ORIENTAL

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 11.21 11.26 11.54 11.56 11.66 11.69 11.73 11.71 11.75 11.58

1F 10.42 10.45 10.64 10.65 10.71 10.72 10.75 10.74 10.76 10.65

3F 20.95 21.00 21.22 21.24 21.32 21.35 21.39 21.37 21.41 21.27

1F 26.63 26.68 26.93 26.94 27.03 27.06 27.10 27.09 27.12 26.97

3F 9.02 9.03 9.13 12.06 12.10 12.07

1F 5.48 5.48 5.56 7.63 7.65 7.64

3F 3.38 3.58 3.89 3.89 3.89 3.89 3.88 3.88 3.88 3.93

1F 2.32 2.47 2.68 2.68 2.68 2.68 2.68 2.68 2.68 2.70

3F 13.00 13.01 13.09 13.12 13.19 13.20 13.20 13.18 13.23 13.19

1F 8.61 8.61 8.64 8.65 8.68 8.68 8.69 8.60 8.69 8.68

3F 4.73 4.74 4.74 4.75 4.75 4.84 4.84 4.84 4.84 4.84

1F 3.11 3.12 3.12 3.12 3.12 3.19 3.19 3.19 3.19 3.19

3F 1.54 1.54 1.54 1.54 1.54 1.62 1.62 1.62 1.62 1.62

1F 1.04 1.04 1.04 1.04 1.04 1.07 1.07 1.07 1.07 1.07

3F 11.30 11.36 13.43 13.43 13.44 13.44 13.47 13.48 13.48 13.73

1F 10.47 10.54 11.76 11.76 11.76 11.76 12.32 12.33 12.33 12.61

3F 5.81 6.82 7.16 7.16 7.16 7.18 7.19 7.20 7.20 7.19

1F 5.87 6.77 7.00 7.00 7.00 7.01 7.02 7.02 6.30 6.30

3F 10.78 10.79 10.94 10.94 11.06 11.06 11.97 11.92 11.99 12.00

1F 9.22 9.22 9.32 9.32 9.38 9.38 9.98 9.95 9.99 9.99

3F 12.75 12.76 12.84 12.83 13.53 13.53 13.63 13.59 13.69 13.68

1F 9.74 9.74 9.77 9.77 10.72 10.73 10.78 10.76 10.80 10.80

3F 12.79 12.80 12.89 12.89 12.92 12.93 12.94 12.94 12.95 12.90

1F 9.96 9.97 10.00 10.01 10.02 10.02 10.03 10.03 10.03 10.01

3F 4.41 4.42 4.44 6.22 6.24 6.24 6.87 6.86 6.90 6.86

1F 2.80 2.81 2.82 4.08 4.08 4.08 4.51 4.51 4.52 4.51

3F 4.64 4.63 4.66 4.66 4.67 4.67 4.67 4.67 5.89 5.89

1F 3.78 3.77 3.79 3.79 3.79 3.79 3.79 3.79 5.58 5.58

3F 12.77 12.83 13.12 13.14 13.23 13.26 13.33 13.31 13.35 13.20

1F 12.33 12.36 12.56 12.57 12.63 12.64 12.68 12.68 12.70 12.60

3F 22.20 22.25 22.50 22.51 22.60 22.62 22.67 22.66 22.69 22.56

1F 21.60 21.63 21.80 21.80 21.86 21.87 21.91 21.90 21.92 21.83

3F 11.24 11.24 11.24 11.24 11.27 11.24 11.26 11.26

1F 8.48 8.48 8.48 8.48 8.49 8.47 8.48 8.48

3F 1.71 1.71 1.71 1.72 1.72 1.72 1.74 1.74 1.74 1.74

1F 1.98 1.90 1.98 1.98 1.98 1.98 2.00 2.00 2.00 2.00

Cholula II CHO 115

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Chinameca Potencia CHM

400

115

Chontalpa CHT 115

Cinco de Mayo CIY 115

Cintalapa CIT 115

Ciudad Hidalgo CGO 115

Ciudad Industrial CIH 115

Ciudad Pemex CPX 115

Civac CIV 115

Clemex CLX 115

Cloro CLO 115

Coapan CPA 115

Coatepec COP 115

Coatzacoalcos II CTS

400

115

Coatzintla CZT 115

Colotlipa CLT 69

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 83: Catalogo 2011-2020 r010212 Corto Circuito

83

Coordinación de Planificación

ÁREA ORIENTAL

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 0.94 0.94 0.94 0.94 0.94 0.96 0.96 0.96 0.96 0.96

1F 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.63

3F 4.86 6.62 6.89 6.89 6.90 6.90 6.88 6.88 6.88 7.02

1F 3.55 6.09 6.27 6.27 6.27 6.27 6.26 6.26 6.26 6.34

3F 4.94 7.33 7.62 7.62 7.62 7.62 7.60 7.60 7.60 7.77

1F 3.63 8.08 8.32 8.32 8.32 8.32 8.31 8.31 8.31 8.44

3F 5.12 5.38 5.38 5.38 5.38 5.36 5.36 5.36 5.53

1F 5.37 5.56 5.56 5.56 5.56 5.55 5.56 5.55 5.67

3F 7.76 8.07 8.07 8.08 8.08 8.06 8.06 8.06 8.25

1F 9.52 9.84 9.84 9.84 9.84 9.83 9.83 9.83 10.01

3F 4.44 5.49 5.75 5.75 5.75 5.75 5.74 5.74 5.74 5.84

1F 3.19 4.35 4.52 4.52 4.52 4.52 4.52 4.52 4.52 4.56

3F 2.65 2.65 2.66 2.66 2.66 2.85 2.58 2.58 2.58 2.58

1F 1.76 1.76 1.76 1.76 1.76 1.85 1.67 1.67 1.67 1.67

3F 2.57 2.57 2.57 2.57

1F 1.66 1.66 1.66 1.66

3F 6.93 6.93 6.95 6.96 6.96 6.97 6.97 6.97 6.97 6.96

1F 4.72 4.72 4.73 4.73 4.73 4.73 4.73 4.73 4.73 4.73

3F 1.56 1.56 1.58 1.60 1.60 1.61 1.75 3.33 3.33 3.33

1F 1.02 1.02 1.02 1.03 1.03 1.04 1.14 3.99 3.99 3.99

3F 17.40 17.45 17.55 17.55 18.14 18.14 18.13 18.09 18.19 18.12

1F 11.93 11.95 11.98 11.98 12.38 12.38 12.38 12.36 12.40 12.38

3F 11.62 11.78 11.85 11.98 12.02 12.03 12.05 12.03 12.20 12.07

1F 9.30 9.49 9.52 9.58 9.60 9.60 9.61 9.60 9.67 9.61

3F 13.46 13.77 13.86 14.01 14.06 14.07 14.10 14.08 14.30 14.17

1F 12.11 12.66 12.72 12.80 12.83 12.84 12.85 12.84 12.97 12.89

3F 4.58 4.60 4.61 4.63 4.64 4.64 4.64 4.64 4.67 4.64

1F 3.37 3.38 3.39 3.40 3.40 3.40 3.40 3.40 3.41 3.40

3F 3.66 3.63 4.24 4.24 4.24 4.24 4.25 4.25 5.01 5.01

1F 2.54 2.53 2.74 2.74 2.74 2.74 2.74 2.74 3.66 3.66

3F 6.69 6.69 6.71 6.72 6.72 6.73 6.73 6.73 6.73 6.72

1F 4.26 4.26 4.27 4.27 4.27 4.27 4.27 4.27 4.27 4.27

3F 6.57 6.58 6.62 6.80 6.77 6.89 9.17 9.24 9.20 9.20

1F 6.73 6.74 6.77 6.89 6.87 6.99 8.52 8.57 8.54 8.54

3F 3.22 3.22 3.23 3.74 3.72 3.75 4.25 4.25 4.26 4.26

1F 2.40 2.40 2.40 2.74 2.74 2.75 2.92 2.92 2.93 2.93

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Comalapa COA 115

Comalcalco COM 115

Comalcalco Oriente CAO 115

Comalcalco Potencia CMP

230

115

Comalcalco Sur COS 115

Comitán CJT 115

Comitán Oriente CJO 115

Complejo Petroquímico

CangrejeraCGJ 115

Conejos CNJ 115

Contla CNU 115

Córdoba COR 115

Córdoba II CBS 115

Coscomatepec CSE 115

Cosolapa CSL 115

Coyuca CYC 115

Cosoleacaque CPQ 115

Costa Azul CAZ 115

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 84: Catalogo 2011-2020 r010212 Corto Circuito

84

Coordinación de Planificación

ÁREA ORIENTAL

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 9.80 10.29 10.34 10.35 10.51 10.51 10.49 10.47 10.52 10.50

1F 6.49 6.93 6.94 6.94 7.00 7.00 7.00 6.99 7.01 7.00

3F 7.93 7.93 8.00 8.29 8.24 8.36 11.71 11.75 11.75 11.75

1F 9.00 9.00 9.06 9.32 9.27 9.41 12.18 12.21 12.21 12.21

3F 12.52 12.51 12.89 12.90 13.40 13.42 13.41 13.32 13.48 13.49

1F 8.90 8.90 9.08 9.09 9.33 9.34 9.35 9.31 9.37 9.37

3F 1.10 1.10 1.13 1.13 1.13 1.13 1.13 1.13 1.13 1.13

1F 0.73 0.74 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75

3F 1.60 1.60 1.61 1.80 1.80 2.15 2.30 2.33 2.32 2.32

1F 1.06 1.06 1.06 1.17 1.17 1.46 1.51 1.52 1.52 1.52

3F 7.03 7.92 9.61 9.61 9.61 9.61 9.59 9.59 9.59 9.87

1F 5.67 6.62 8.46 8.46 8.47 8.47 8.46 8.46 8.46 8.61

3F 10.78 10.79 10.85 10.86 10.88 10.88 10.89 10.89 10.90 10.87

1F 7.84 7.85 7.87 7.87 7.88 7.88 7.88 7.88 7.89 7.87

3F 4.83 4.79 4.81 4.81 7.89 7.89 7.93 7.92 7.95 7.95

1F 3.16 3.13 3.14 3.14 5.35 5.35 5.36 5.35 5.36 5.36

3F 10.15 10.16 10.35 10.35 10.50 10.58 10.75 10.72 10.77 10.77

1F 7.60 7.60 7.76 7.76 7.85 7.92 8.01 7.99 8.02 8.02

3F 7.15 7.15 7.24 7.24 7.32 7.77 7.87 7.85 7.88 7.88

1F 4.99 4.99 5.05 5.05 5.09 5.46 5.50 5.50 5.51 5.51

3F 4.98 4.98 5.02 5.02 5.06 5.20 5.24 5.23 5.24 5.24

1F 3.31 3.31 3.34 3.34 3.36 3.46 3.48 3.47 3.48 3.48

3F 1.86 1.87 1.88 1.88 1.92 1.92 1.92 1.92 1.92 1.92

1F 1.41 1.41 1.41 1.41 1.44 1.44 1.44 1.44 1.44 1.44

3F 1.46 1.46 1.46 1.69 1.71 1.77 1.77 1.78 1.78 1.78

1F 1.08 1.08 1.08 1.27 1.28 1.30 1.30 1.30 1.30 1.30

3F 8.33 8.34 8.38 8.38 8.39 8.39 8.40 8.40 8.40 8.38

1F 5.82 5.82 5.83 5.83 5.84 5.84 5.84 5.84 5.84 5.83

3F 4.59 4.62 4.64 4.65 4.66 4.66 4.66 4.66 4.68 4.67

1F 3.14 3.19 3.19 3.19 3.20 3.20 3.20 3.20 3.20 3.20

3F 4.99 5.66 5.92 5.92 5.92 5.92 5.91 5.91 5.91 6.02

1F 3.57 4.15 4.26 4.26 4.26 4.26 4.26 4.26 4.25 4.29

3F 7.84 8.75 8.85 8.86 8.86 8.87 8.87 8.87 8.86

1F 8.25 8.93 9.00 9.00 9.00 9.01 9.01 9.01 9.00

3F 3.36 3.37 3.37 3.37 3.37 3.37 3.38 3.38 3.38 3.38

1F 2.34 2.34 2.35 2.35 2.35 2.35 2.35 2.35 2.35 2.35

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Crisol Textil CTX 115

Cruces CUG 115

Cruz Azul Maniobras CZM 400

Cruz de Ataque CRA 115

Cruz Grande CGN 115

Cryoinfra, Cárdenas Tabasco ICD 115

Cryoinfra, Puebla CRY 115

Cuauhtémoc CTM 115

Cuautla CUA 115

Cuautla II CUS 115

Cuautla Industrial CIL 115

Cuetzalan CTN 115

Cuicatlán CUX 115

Cuichapa CCP 115

Cuitláhuac CTH 115

Cunduacán II CUD 115

Desarrollos Eólicos Mexicanos DEM 230

Donaji DOJ 115

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 85: Catalogo 2011-2020 r010212 Corto Circuito

85

Coordinación de Planificación

ÁREA ORIENTAL

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 2.82 4.16 4.25 4.25 4.25 4.25 4.25 4.25 4.25 4.30

1F 1.90 3.41 3.45 3.45 3.45 3.45 3.45 3.45 3.45 3.47

3F 10.65 9.85 9.96 9.95 9.99 9.99 12.37 12.35 12.44 12.44

1F 10.12 9.45 9.52 9.51 9.54 9.54 13.96 13.94 14.02 14.02

3F 17.26 11.73 12.17 12.10 12.13 12.13 19.58 19.56 19.69 19.69

1F 17.99 9.06 9.24 9.20 9.21 9.21 24.12 24.10 24.23 24.23

3F 11.72 12.45 12.53 12.53 12.72 12.72 12.69 12.66 12.73 12.70

1F 7.79 8.46 8.49 8.49 8.56 8.56 8.55 8.54 8.56 8.55

3F 3.25 3.25 3.26 3.50 3.51 3.86 3.90 4.05 4.06 4.05

1F 2.55 2.55 2.56 2.71 2.71 2.87 2.89 3.03 3.03 3.03

3F 5.12 5.18 5.26 5.26 5.27 5.28 5.28 5.27 5.90 5.90

1F 4.90 4.93 4.98 4.98 4.99 4.99 5.00 4.99 5.53 5.53

3F 7.73 7.72 7.82 7.82 7.84 7.84 7.85 7.84 9.64 9.64

1F 8.72 8.70 8.79 8.79 8.81 8.81 8.81 8.81 10.72 10.72

3F 6.59 6.53 6.61 6.61 6.63 6.63 6.63 6.63 7.71 7.71

1F 6.17 6.10 6.15 6.15 6.16 6.16 6.16 6.16 6.91 6.91

3F 15.01 15.04 15.13 15.15 15.22 15.22 15.22 15.20 15.26 15.20

1F 10.09 10.10 10.13 10.14 10.16 10.16 10.17 10.08 10.18 10.16

3F 9.48 9.49 9.49 9.42

1F 9.33 9.33 9.33 9.36

3F 15.48 15.49 15.49 15.49

1F 17.67 17.68 17.68 17.75

3F 3.84 3.89 4.26 4.26 4.27 4.27 4.27 4.27 4.31 4.31

1F 3.05 3.07 3.29 3.29 3.29 3.29 3.29 3.29 3.31 3.31

3F 3.49 3.55 3.87 3.87 3.87 3.88 3.88 3.87 3.88 3.88

1F 2.63 2.65 2.88 2.88 2.88 2.85 2.85 2.85 2.85 2.85

3F 9.94 10.22 10.26 10.26 10.47 10.47 10.46 10.44 10.48 10.46

1F 6.71 6.93 6.94 6.94 7.02 7.02 7.02 7.01 7.03 7.02

3F 3.23 3.32 3.56 3.56 3.58 3.58 3.58

1F 2.65 2.70 2.81 2.82 2.82 2.82 2.82

3F 2.56 2.56

1F 2.37 2.37

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Dos Bocas, Tabasco DBX 115

Dos Bocas, Veracruz DBC

230

115

Draexlmaier DXM 115

Ejutla EJT 115

El Castillo ELC

230

115

El Cerro CEO 115

El Conde ECN 115

El Edén EED

230

115

El Encanto ECT 115

El Esfuerzo ESF 115

El Pescado EPS 115

El Moral MOA 115

El Moral Switcheo MOR 115

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 86: Catalogo 2011-2020 r010212 Corto Circuito

86

Coordinación de Planificación

ÁREA ORIENTAL

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 5.06 5.06 5.11 5.28 5.23 5.28 8.03 8.04 8.07 8.07

1F 6.12 6.12 6.18 6.33 6.29 6.38 8.99 9.00 9.03 9.03

3F 9.09 9.09 9.18 9.61 9.53 9.67 14.19 14.21 14.25 14.25

1F 11.95 11.95 12.06 12.55 12.46 12.69 17.81 17.82 17.87 17.88

3F 10.36 10.36 10.43 10.74 10.69 10.79 13.56 13.57 13.59 13.59

1F 13.47 13.47 13.55 13.91 13.84 13.98 17.03 17.04 17.06 17.06

3F 14.31 14.39 14.52 14.54 14.56 14.57 14.90 14.89 14.90 14.88

1F 12.67 12.71 12.78 12.79 12.80 12.81 12.98 12.98 12.99 12.98

3F 20.37 20.40 20.50 20.51 20.52 20.66 20.84 20.84 20.84 20.83

1F 20.51 20.53 20.60 20.61 20.62 20.69 20.82 20.82 20.82 20.81

3F 17.08 11.87 12.32 12.25 12.28 12.28 18.92 18.90 19.02 19.02

1F 17.13 9.19 9.38 9.33 9.34 9.34 21.70 21.68 21.78 21.79

3F 3.74 3.72 3.75 3.82 3.85 4.26 4.26 4.29 4.30 4.29

1F 3.23 3.22 3.24 3.27 3.29 3.49 3.49 3.51 3.51 3.51

3F 5.22 5.75 5.95 5.95 5.95 6.05 6.06 6.06 6.06 6.06

1F 4.38 4.75 4.84 4.84 4.84 4.90 4.90 4.90 4.90 4.90

3F 6.38 6.53 6.54 6.55 6.55 6.55 6.46 6.48 6.48 6.48

1F 5.42 5.51 5.52 5.52 5.52 5.53 5.49 5.50 5.50 5.50

3F 26.99 27.17 27.34 27.37 27.42 27.43 27.80 27.30 27.54 27.56

1F 27.65 27.79 27.97 27.99 28.02 27.96 28.25 27.88 28.05 28.06

3F 26.99 27.17 27.34 27.37 27.42 27.43 27.80 27.30 27.54 27.56

1F 27.65 27.79 27.97 27.99 28.02 27.96 28.25 27.88 28.05 28.06

3F 2.34 2.34 2.34 2.34 2.34 2.34 2.35 2.35 2.35 2.34

1F 1.48 1.48 1.48 1.48 1.48 1.48 1.48 1.48 1.48 1.48

3F 2.84 2.97 6.07 6.07 6.07 6.07 6.08 6.07 6.07 6.08

1F 1.86 1.91 4.06 4.06 4.07 4.06 4.07 4.06 4.06 4.06

3F 8.32 9.49 9.62 9.63 9.63 9.64 9.64 9.64 9.63

1F 8.36 9.16 9.25 9.25 9.25 9.26 9.26 9.26 9.25

3F 7.97 7.99 7.99 7.99 8.00 7.86 7.89 7.89 7.89

1F 7.97 7.98 7.98 7.99 7.99 7.92 7.94 7.94 7.94

3F 7.28 7.35 7.36 7.36 7.36 7.36 7.36 7.36

1F 7.16 7.20 7.21 7.21 7.21 7.21 7.21 7.21

3F 12.67 12.76 12.84 13.05 13.10 13.11 13.13 13.11 13.35 13.14

1F 10.30 10.35 10.39 10.49 10.51 10.51 10.53 10.52 10.63 10.51

3F 6.09 6.09 6.25 9.21 9.24 9.24 9.31 9.30 9.37 9.29

1F 3.91 3.92 4.02 6.11 6.12 6.12 6.19 6.18 6.21 6.18

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

El Quemado QMD

230

115

69

El Sabino SAB

400

115

El Tejar TJR 115

El Tule TUE 115

El Zopo ZOP 115

Eléctrica del Valle de México EVM 115

Electricidad Águila de Tuxpan EAT 400

Electricidad Sol de Tuxpan ETS 400

Emiliano Zapata EMZ 115

Entabladero ETD 115

Eoliatec del Istmo EOI 230

Eoliatec del Istmo EDI 115

Eoliatec del Pacífico EDP 230

Escamela ECM 115

Esperanza ERZ 115

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 87: Catalogo 2011-2020 r010212 Corto Circuito

87

Coordinación de Planificación

ÁREA ORIENTAL

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 3.69 3.68 3.70 3.87 3.93 4.33 4.33 4.36 4.36 4.36

1F 3.39 3.38 3.40 3.60 3.64 3.88 3.88 3.90 3.90 3.90

3F 5.50 5.58 5.60 5.60 5.61 5.61 5.64 5.67 5.67 5.67

1F 6.28 6.35 6.37 6.37 6.37 6.38 6.43 6.46 6.46 6.46

3F 14.63 14.65 14.74 14.76 14.84 14.84 14.84 14.81 14.88 14.83

1F 9.74 9.75 9.78 9.78 9.81 9.82 9.82 9.75 9.83 9.81

3F 5.33 5.32 5.36 5.37 5.39 5.40 5.40 5.40 5.41 5.38

1F 3.70 3.70 3.72 3.73 3.73 3.74 3.74 3.74 3.74 3.73

3F 6.88 6.89 6.91 6.91 6.92 6.93 6.93 6.93 6.93 6.92

1F 4.40 4.40 4.41 4.41 4.41 4.41 4.41 4.41 4.42 4.41

3F 10.23 10.30 10.36 10.47 10.50 10.51 10.52 10.51 10.77 10.66

1F 8.61 8.65 8.68 8.73 8.75 8.75 8.75 8.75 8.90 8.85

3F 3.91 3.65 3.80 3.73 3.73 3.73 3.98 3.98 3.98 3.98

1F 2.56 2.37 2.42 2.36 2.36 2.36 2.57 2.57 2.57 2.57

3F 5.46 5.46 5.49 5.49 5.49 6.38 6.34 6.34 6.34 6.34

1F 4.00 4.00 4.02 4.02 4.02 4.53 4.49 4.49 4.50 4.49

3F 10.84 10.85 10.90 10.90 13.82 13.83 13.96 13.92 14.02 14.00

1F 7.64 7.65 7.66 7.66 11.67 11.67 11.75 11.73 11.78 11.77

3F 13.90 14.06 14.15 14.37 14.44 14.44 14.47 14.45 14.69 14.48

1F 11.55 11.71 11.76 11.87 11.90 11.90 11.92 11.91 12.02 11.90

3F 1.46 1.56 1.58 1.58 1.58 1.58 1.58 1.58 1.58 1.58

1F 1.04 1.12 1.12 1.12 1.12 1.12 1.12 1.12 1.12 1.13

3F 16.67 16.69 16.82 16.89 16.99 17.00 17.00 16.96 17.05 16.96

1F 11.54 11.55 11.60 11.63 11.67 11.67 11.69 11.29 11.70 11.67

3F 6.04 6.47 6.63 6.80 6.80 6.80 6.80 6.80 6.80 6.80

1F 6.13 6.44 6.55 6.67 6.67 6.67 6.67 6.67 6.67 6.67

3F 27.29 27.48 27.65 27.68 27.73 27.74 28.12 27.61 27.85 27.87

1F 28.39 28.53 28.72 28.74 28.77 28.71 29.01 28.63 28.80 28.81

3F 5.18 5.10 8.51 8.50 8.52 8.54 8.58 8.58 8.62 8.61

1F 3.82 3.78 5.82 5.82 5.82 5.83 5.85 5.85 5.87 5.86

3F 11.32 11.70 12.12 12.13 12.13 12.13 12.13 12.13 12.13

1F 12.87 13.20 13.57 13.58 13.58 13.58 13.58 13.58 13.58

3F 7.38 7.39 7.45 7.71 7.66 7.75 10.35 10.36 10.39 10.39

1F 7.89 7.89 7.94 8.14 8.10 8.18 10.00 10.00 10.02 10.02

3F 2.64 2.55 2.68 2.66 2.66 2.66 2.74 2.74 2.74 2.74

1F 1.70 1.64 1.68 1.66 1.67 1.67 1.72 1.72 1.73 1.73

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Etla ETX 115

Eurus, S. A. de C. V. EUR 230

Exelopolis EXE 115

Fábrica de Papel Tuxtepec PTU 230

Fenoquimia FNQ 115

Fermex FEM 115

Fisisa FIS 115

Flores Magón FLM 115

Forjamex FJM 115

Fortín FOR 115

Frontera FRT 115

Fuertes FUE 115

Fuerza Eólica del Istmo FEO 115

Fuerza y Energía de Tuxpan FET 400

Gabino Barreda GBA 115

Gamesa Energía GAE 115

Garita GAR 115

Gas Matapionche MPH 115

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 88: Catalogo 2011-2020 r010212 Corto Circuito

88

Coordinación de Planificación

ÁREA ORIENTAL

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 10.31 11.91 11.91 11.91 11.94

1F 7.53 9.74 9.74 9.74 9.78

3F 13.31 13.32 13.40 13.40 14.10 14.10 14.21 14.17 14.28 14.27

1F 10.32 10.32 10.36 10.36 11.35 11.35 11.41 11.39 11.44 11.43

3F 5.68 4.97 5.87 5.87 5.87 5.87 5.88 5.88 5.88 5.99

1F 4.21 3.68 4.36 4.36 4.36 4.36 4.36 4.36 4.35 4.40

3F 10.43 10.45 10.49 10.49 12.99 12.99 13.11 13.07 13.16 13.15

1F 7.32 7.32 7.33 7.33 10.64 10.64 10.70 10.68 10.72 10.72

3F 17.67 18.10 18.23 18.23 19.03 19.04 19.01 18.95 19.09 19.02

1F 13.61 13.96 14.01 14.02 14.43 14.43 14.42 14.39 14.45 14.43

3F 11.14 11.16 11.20 11.20 12.45 12.46 12.46 12.43 12.49 12.46

1F 7.22 7.23 7.24 7.24 8.08 8.08 8.08 8.07 8.09 8.08

3F 6.51 6.41 6.42 6.42 6.43 6.64 6.65 6.65 6.65 6.65

1F 4.45 4.39 4.39 4.39 4.39 4.49 4.49 4.49 4.49 4.49

3F 17.28 17.30 17.45 17.52 17.65 17.65 17.66 17.62 17.71 17.64

1F 11.98 11.99 12.04 12.07 12.13 12.13 12.14 11.93 12.16 12.14

3F 3.38 3.52 5.98 5.98 5.99 5.99 6.00 5.98 6.00 6.00

1F 2.27 2.32 3.99 3.99 3.99 3.98 3.99 3.98 3.99 3.99

3F 1.82 1.82 1.82 1.95 2.11 2.13 2.13 2.14 2.14 2.14

1F 1.15 1.15 1.15 1.23 1.33 1.34 1.34 1.34 1.34 1.34

3F 4.46 4.42 4.44 4.44 8.57 8.57 8.61 8.59 8.63 8.63

1F 2.91 2.88 2.89 2.88 5.85 5.85 5.86 5.86 5.87 5.87

3F 0.97 0.97 0.97 0.97 0.97 0.97 0.98 0.98 0.98 0.98

1F 0.68 0.72 0.68 0.68 0.68 0.68 0.68 0.68 0.68 0.68

3F 1.56 1.56 1.57 1.59 1.59 1.61 1.73 2.98 2.98 2.98

1F 1.01 1.02 1.02 1.03 1.03 1.04 1.12 2.93 2.93 2.93

3F 1.95 1.95 1.95

1F 2.40 2.40 2.40

3F 3.50 3.50 3.50

1F 4.68 4.68 4.68

3F 3.38 3.38 3.39 3.40 3.41 3.41 3.41 3.41 3.42 3.41

1F 2.45 2.46 2.46 2.46 2.46 2.46 2.46 2.46 2.47 2.46

3F 0.63 0.71 0.71 0.72 0.72 0.72 0.73 0.73 0.73 0.73

1F 0.53 0.62 0.62 0.65 0.65 0.65 0.65 0.65 0.65 0.65

3F 12.55 13.54 13.64 13.65 13.90 13.90 13.87 13.84 13.91 13.88

1F 8.50 9.46 9.49 9.50 9.60 9.60 9.59 9.57 9.60 9.59

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Gaviotas GAV 115

General Cable TLM 115

Giraldas GIR 115

Glicomex GLI 115

Global Denim TKN 115

Gress GRE 115

Grijalva GIA 115

Guadalupe Analco GAN 115

Gutiérrez Zamora II GZD 115

Huajuapan HJP 115

Huamantla HUA 115

Huamuxtitlán HUU 115

Huatulco HCO 115

Huatulco Potencia HUP

230

115

Huejotzingo II HJO 115

Huatusco HTU 115

Huautla HUJ 69

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 89: Catalogo 2011-2020 r010212 Corto Circuito

89

Coordinación de Planificación

ÁREA ORIENTAL

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 19.11 19.09 23.24 23.25 23.25 22.78 23.43 23.48

1F 18.12 18.10 24.06 23.10 24.09 23.74 24.22 24.25

3F 3.14 3.16 3.23 3.23 3.27 3.27 3.28 3.27 3.29 3.29

1F 2.25 2.25 2.28 2.28 2.30 2.30 2.30 2.30 2.31 2.31

3F 3.37 3.37 3.40 3.40 3.40 3.40 3.40 3.40 3.40 3.40

1F 2.68 2.68 2.69 2.69 2.69 2.69 2.69 2.69 2.69 2.69

3F 4.66 4.66 4.67 4.66

1F 2.97 2.97 2.97 2.97

3F 5.19 5.30 8.38 8.38 8.38 8.38 8.37 8.37 8.37 8.57

1F 3.93 4.04 6.85 6.85 6.85 6.86 6.86 6.86 6.85 6.95

3F 1.98 1.98 1.98 1.99 1.99 1.99 2.03 2.03 2.04 2.04

1F 1.36 1.36 1.36 1.36 1.36 1.36 1.37 1.37 1.38 1.38

3F 3.41 3.41 3.42 3.42 3.42 3.68 3.68 3.68 3.68 3.68

1F 2.40 2.40 2.40 2.40 2.40 2.50 2.50 2.50 2.50 2.50

3F 5.60 5.60 5.75 5.74 6.11 6.11 6.12 6.11 6.16 6.16

1F 5.62 5.55 5.64 5.62 6.12 6.12 6.13 6.12 6.15 6.15

3F 5.43 5.56 5.55 5.93 5.93 5.93 5.93 5.97 5.97

1F 5.37 5.45 5.44 5.87 5.87 5.87 5.87 5.89 5.89

3F 6.27 6.28 6.32 6.32 6.36 6.36 7.15 7.13 7.17 7.14

1F 4.57 4.57 4.59 4.59 4.62 4.62 5.12 5.11 5.13 5.12

3F 17.37 17.39 17.54 17.62 17.74 17.75 17.75 17.71 17.80 17.70

1F 12.30 12.31 12.37 12.41 12.46 12.46 12.48 11.90 12.50 12.46

3F 2.65 2.65 2.66 2.66 2.66 2.66 2.74 2.74 2.77 2.77

1F 1.88 1.88 1.89 1.89 1.89 1.89 1.91 1.91 1.92 1.92

3F 3.42 3.42 3.43 3.43 3.43 3.70 3.70 3.70 3.71 3.70

1F 2.30 2.30 2.30 2.30 2.30 2.43 2.43 2.43 2.43 2.43

3F 21.54 21.58 21.78 21.89 22.07 22.08 22.08 22.01 22.16 22.01

1F 15.53 15.55 15.63 15.69 15.76 15.76 15.79 15.14 15.81 15.75

3F 13.40 13.70 13.79 13.94 13.99 14.00 14.03 14.01 14.23 14.10

1F 12.02 12.56 12.61 12.70 12.73 12.73 12.75 12.74 12.86 12.78

3F 14.86 13.53 13.68 13.66 13.70 13.70 14.02 14.00 14.07 14.08

1F 13.89 12.96 13.05 13.04 13.06 13.07 13.48 13.48 13.52 13.52

3F 10.59 10.64 12.44 12.44 12.45 12.45 12.48 12.48 12.48 12.70

1F 9.48 9.54 10.53 10.53 10.53 10.53 10.98 10.98 10.98 11.21

3F 10.56 10.57 10.62 10.63 10.65 10.65 10.66 10.66 10.67 10.64

1F 7.63 7.63 7.65 7.66 7.66 7.66 7.67 7.67 7.67 7.66

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Huexca HUX 400

Hueyapan HYN 115

Hueyapan de Ocampo HOC 115

Hueyotlipan HYT 115

Huimanguillo HMG 115

Huitzuco HZO 115

Huixtla HUX 115

Humeros II HMD 115

Humeros III HMT 115

Hylsa HSA 230

Idesa IDE 115

Iguala IGU 115

Independencia IPD 115

Industrial INT 115

Industrias Patrona IPA 115

Infonavit IFN 115

Infra, Villahermosa Tabasco IVH 115

Iquisa IQU 115

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 90: Catalogo 2011-2020 r010212 Corto Circuito

90

Coordinación de Planificación

ÁREA ORIENTAL

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 2.28 2.27 2.44 2.44 2.44 2.44 2.44 2.44 2.44 2.44

1F 1.45 1.44 1.52 1.52 1.52 1.52 1.52 1.52 1.52 1.52

3F 0.80 0.80 0.80 0.83 0.91 0.92 0.92 0.92 0.92 0.92

1F 0.55 0.55 0.55 0.57 0.62 0.63 0.63 0.63 0.63 0.63

3F 2.15 2.17 2.28 2.28 2.28 2.29 2.29 2.28 2.29 2.29

1F 1.48 1.49 1.55 1.55 1.55 1.54 1.55 1.54 1.54 1.54

3F 7.79 7.79 8.36 8.42 7.86 8.59 9.21 9.26 9.23 9.23

1F 6.37 6.37 6.81 6.86 6.36 7.59 7.91 7.93 7.91 7.91

3F 6.27 6.27 6.39 6.77 6.64 9.30 9.64 9.67 9.66 9.66

1F 6.93 6.93 7.07 7.41 7.26 10.58 10.88 10.90 10.89 10.89

3F 4.18 4.25 4.26 4.26 4.26 4.26 4.19 4.19 4.19 4.19

1F 3.17 3.20 3.20 3.20 3.20 3.20 3.16 3.17 3.17 3.16

3F 7.34 9.06 10.61 11.11 11.14 11.15 11.17 11.17 11.18 11.14

1F 8.54 10.40 11.94 12.44 12.47 12.48 12.50 12.50 12.51 12.47

3F 10.30 13.16 16.77 17.23 17.26 17.27 17.29 17.29 17.30 17.26

1F 12.85 16.29 20.46 20.97 21.00 21.01 21.03 21.02 21.03 21.00

3F 15.84 19.67 21.35 23.44 23.48 23.49 23.51 23.51 23.52 23.48

1F 17.41 21.50 23.01 25.11 25.14 25.15 25.17 25.16 25.17 25.14

3F 3.00 3.01 3.01 3.01 3.01

1F 1.97 1.97 1.97 1.97 1.97

3F 2.76 2.76 2.76 4.23 4.10 4.11 4.14 4.21 4.21 4.21

1F 1.70 1.70 1.70 2.62 2.53 2.53 2.55 2.60 2.60 2.60

3F 3.08 3.08 3.08 3.88 3.76 3.76 3.79 3.85 3.85 3.85

1F 1.90 1.90 1.90 2.40 2.31 2.31 2.33 2.37 2.37 2.37

3F 7.97 8.18 8.37 8.37 8.41 8.41 8.43 8.40 9.00 9.00

1F 7.39 7.51 7.62 7.62 7.65 7.65 7.66 7.65 8.04 8.04

3F 8.95 9.06 9.52 9.52 9.61 9.61 9.62 9.61 10.00 10.00

1F 9.67 9.75 10.11 10.11 10.19 10.19 10.20 10.19 10.50 10.50

3F 5.47 5.46 5.50 5.51 5.53 6.16 6.16 6.17 6.18 6.16

1F 3.82 3.82 3.84 3.84 3.85 4.42 4.42 4.43 4.43 4.42

3F 4.85 4.84 4.88 4.88 4.89 4.89 4.89 4.89 6.00 6.00

1F 4.05 4.05 4.07 4.07 4.07 4.07 4.07 4.07 5.23 5.23

3F 4.03 4.91 5.06 5.06 5.06 5.06 5.06 5.06 5.06 5.13

1F 2.81 3.74 3.81 3.81 3.81 3.81 3.81 3.81 3.81 3.83Jalpa JAA 115

Jalapa de Díaz JDD 230

Jalapa II JLD 115

Izúcar de Matamoros II IZD 115

Jalacingo JAL

230

115

Ixtlán IXL 115

Izúcar de Matamoros IZM 115

Ixtepec IXP 115

Ixtepec Potencia IPO

400

230

115

Ixhuatlán IXH 115

Ixtapa Potencia ITP

230

115

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Isla ISL 115

Itundujia ITJ 115

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 91: Catalogo 2011-2020 r010212 Corto Circuito

91

Coordinación de Planificación

ÁREA ORIENTAL

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 12.96 11.80 11.95 11.95 12.00 12.01 12.49 12.47 12.56 12.56

1F 13.66 12.52 12.64 12.63 12.67 12.68 13.66 13.65 13.73 13.73

3F 19.37 17.17 17.41 17.39 17.44 17.45 17.97 17.95 18.06 18.06

1F 21.79 19.59 19.80 19.78 19.83 19.83 20.82 20.80 20.90 20.90

3F 14.40 13.15 13.29 13.27 13.31 13.31 13.61 13.60 13.66 13.66

1F 13.23 12.39 12.47 12.46 12.48 12.48 12.87 12.86 12.90 12.90

3F 9.54 9.55 9.69 9.69 9.80 9.80 10.13 10.10 10.15 10.15

1F 6.93 6.93 7.01 7.01 7.06 7.06 7.21 7.20 7.22 7.22

3F 5.97 5.98 6.03 6.03 6.07 6.07 12.53 12.48 12.55 12.56

1F 4.06 4.06 4.09 4.09 4.10 4.10 10.43 10.41 10.44 10.44

3F 7.39 7.61 7.63 7.63 7.63 7.64 7.41 7.43 7.43 7.43

1F 7.01 7.17 7.18 7.18 7.19 7.19 6.98 6.99 6.99 6.99

3F 7.81 8.00 8.04 8.05 8.06 8.06 8.13 8.20 8.21 8.20

1F 9.22 9.41 9.45 9.46 9.47 9.47 9.79 9.89 9.89 9.88

3F 10.31 10.73 10.77 10.78 10.79 10.79 10.54 10.59 10.59 10.58

1F 12.69 13.23 13.26 13.27 13.28 13.29 13.09 13.15 13.15 13.14

3F 16.58 17.74 19.15 19.38 19.63 19.69 19.86 19.83 19.91 19.63

1F 14.75 15.40 16.35 16.47 16.59 16.62 16.62 16.61 16.66 16.49

3F 12.22 12.53 12.82 12.86 12.91 12.92 12.96 12.98 12.99 12.94

1F 13.71 13.98 14.26 14.30 14.34 14.35 14.38 14.39 14.40 14.35

3F 0.82 0.82 0.82 0.84 0.85 0.85 0.85 0.85 0.85 0.85

1F 0.53 0.53 0.53 0.54 0.55 0.55 0.55 0.55 0.55 0.55

3F 12.19 11.93 13.83 13.84 13.86 13.86 13.89 13.91 13.91 13.92

1F 12.35 12.24 13.66 13.66 13.68 13.68 13.88 13.89 13.88 14.03

3F 15.96 15.75 19.40 19.41 19.42 19.43 19.63 19.65 19.65 20.04

1F 16.95 16.79 19.78 19.78 19.79 19.80 20.19 20.20 20.19 20.77

3F 12.89 12.97 13.05 13.28 13.33 13.34 13.37 13.35 13.55 13.33

1F 10.33 10.38 10.42 10.53 10.55 10.55 10.57 10.56 10.65 10.52

3F 13.71 13.72 13.81 13.81 14.36 14.36 14.48 14.43 14.55 14.53

1F 10.90 10.90 10.94 10.94 11.75 11.75 11.81 11.79 11.85 11.84

3F 12.52 12.84 12.91 12.91 13.02 13.02 12.96 12.94 12.99 12.96

1F 8.02 8.27 8.29 8.29 8.33 8.33 8.30 8.29 8.31 8.30

3F 3.55 3.62 3.95 3.95 3.95 3.96 3.96 3.96 3.96 3.96

1F 2.69 2.72 2.96 2.96 2.96 2.93 2.93 2.93 2.93 2.93

3F 11.62 11.70 15.02 15.02 15.03 15.03 15.14 15.15 15.15 16.95

1F 10.83 10.91 13.30 13.30 13.31 13.31 13.54 13.54 13.52 16.64

JB Lobos JBL 115

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Jardín JDN

230

115

Jiutepec JIU 115

Jojutla JJT 115

Juchitán I JUC 115

Juchitán II JUD

230

115

Juile JUI

400

230

Juxtlahuaca TCX 115

Kilómetro Veinte KLV

230

115

Kimberly Clarck, Orizaba KIM 115

Kimberly Clarck, Tlaxcala KIC 115

Krupp KRU 115

La Barra LBR 115

La Choca LCH 115

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 92: Catalogo 2011-2020 r010212 Corto Circuito

92

Coordinación de Planificación

ÁREA ORIENTAL

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 3.03 3.03 3.05 3.14 3.17 4.11 4.12 4.17 4.17 4.16

1F 3.16 3.16 3.18 3.25 3.27 4.03 4.04 4.08 4.08 4.07

3F 5.38 5.35 5.39 5.61 5.66 6.85 6.87 6.99 7.00 6.99

1F 5.92 5.90 5.93 6.12 6.16 7.21 7.23 7.34 7.34 7.33

3F 9.08 9.15 9.11 9.11

1F 8.40 8.44 8.41 8.41

3F 5.84 6.86 7.21 7.21 7.21 7.23 7.24 7.24 7.24 7.24

1F 5.80 6.69 6.91 6.91 6.92 6.93 6.93 6.94 6.37 6.37

3F 1.89 1.89 1.89 1.89 1.89 1.93 1.93 1.93 1.93 1.93

1F 1.21 1.21 1.21 1.21 1.21 1.24 1.24 1.24 1.24 1.24

3F 7.61 7.32 11.31 11.22 11.26 11.27 11.54 11.54 11.66 11.64

1F 6.45 6.24 8.32 8.26 8.27 8.27 8.49 8.49 8.55 8.54

3F 1.33 1.34 1.41 1.41 1.41 1.41 1.41 1.41 1.41 1.41

1F 0.88 0.88 0.92 0.92 0.92 0.92 0.92 0.92 0.92 0.92

3F 11.96 11.97 12.43 12.36 12.52 12.49

1F 10.54 10.54 10.85 10.81 10.90 10.88

3F 18.25 18.25 18.51 18.44 18.61 18.58

1F 19.62 19.62 19.86 19.81 19.94 19.92

3F 5.09 5.10 5.10 6.52 6.52 6.55 6.52

1F 3.29 3.29 3.29 4.25 4.25 4.26 4.25

3F 5.42 5.42 5.46 5.57 5.55 5.59 6.94 6.95 6.95 6.95

1F 4.96 4.96 4.98 5.04 5.03 5.05 5.73 5.73 5.73 5.73

3F 9.19 9.25 9.22 9.23

1F 11.60 11.67 11.64 11.64

3F 4.37 4.32 5.23 5.36 5.36 5.36 5.36

1F 3.64 3.60 4.21 4.27 4.27 4.27 4.27

3F 2.41 2.33 2.44 2.42 2.42 2.42 2.48 2.48 2.49 2.49

1F 1.54 1.49 1.53 1.51 1.51 1.51 1.56 1.56 1.56 1.56

3F 4.65 4.65 4.66 4.72 4.71 5.00 5.04 5.05 5.05 5.05

1F 3.28 3.28 3.29 3.31 3.30 3.44 3.45 3.46 3.46 3.46

3F 3.64 3.64 3.64 3.67 3.66 3.67 3.90 3.90 3.90 3.90

1F 3.93 3.93 3.93 3.96 3.95 3.96 4.13 4.13 4.13 4.13

3F 5.71 5.72 5.73 5.73 5.74 5.74 5.74 5.74 5.75 5.74

1F 3.81 3.81 3.81 3.81 3.81 3.81 3.81 3.81 3.82 3.81

3F 6.97 7.10 7.13 7.14 7.14 7.15 7.19 7.24 7.25 7.24

1F 8.01 8.13 8.16 8.16 8.17 8.17 8.28 8.34 8.34 8.33

La Cima LCM 115

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

La Ciénega CIG

230

115

La Curva LVA 115

La Garza LGZ 115

La Granja III GRT 115

La Guadalupe LGP 115

La Malinche MCH

230

115

La Meseta MTA 115

La Mira MRA 115

La Parota PTA 230

La Puerta LPR 115

La Tinaja LTN 115

La Unión UNO 115

La Venta VEN 69

La Venta II VED 115

La Venta II (Eoloeléctrica) LVD 230

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 93: Catalogo 2011-2020 r010212 Corto Circuito

93

Coordinación de Planificación

ÁREA ORIENTAL

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 5.85 5.93 5.95 5.96 5.96 5.96 5.99 6.03 6.03 6.02

1F 6.27 6.34 6.35 6.35 6.36 6.36 6.41 6.44 6.44 6.43

3F 0.75 0.75 0.67 0.67 0.67 0.69 0.69 0.69 0.69 0.69

1F 0.53 0.53 0.48 0.48 0.48 0.49 0.49 0.49 0.49 0.49

3F 6.42 6.42 6.47 6.61 6.57 6.63 8.35 8.36 8.37 8.37

1F 6.77 6.77 6.80 6.91 6.88 6.92 8.08 8.09 8.09 8.09

3F 5.93 5.93 7.07 7.98 7.98 7.98 7.99 7.95

1F 8.86 8.86 10.58 11.94 11.94 11.94 11.95 11.90

3F 9.26 9.27 12.10 14.46 14.46 14.46 14.47 14.43

1F 13.85 13.85 18.11 21.63 21.63 21.62 21.64 21.58

3F 15.85 15.45 15.61 15.61 15.73 15.74 15.78 15.71 15.84 15.83

1F 19.71 19.28 19.45 19.46 19.58 19.59 19.64 19.57 19.70 19.69

3F 11.24 10.91 10.97 10.97 11.01 11.01 11.06 11.04 11.09 11.08

1F 12.03 11.77 11.82 11.82 11.84 11.85 11.89 11.88 11.92 11.92

3F 17.95 18.23 18.35 18.36 19.25 19.25 19.22 19.16 19.31 19.24

1F 14.09 14.29 14.34 14.34 14.81 14.82 14.81 14.78 14.84 14.82

3F 12.91 13.38 13.46 13.46 13.81 13.81 13.79 13.76 13.83 13.80

1F 9.05 9.45 9.47 9.48 9.63 9.63 9.62 9.61 9.63 9.62

3F 17.19 15.43 15.63 15.61 15.65 15.66 16.07 16.06 16.15 16.15

1F 17.61 16.14 16.28 16.27 16.30 16.31 16.97 16.95 17.02 17.02

3F 3.20 3.20 3.21 3.21 3.21 3.21 3.21 3.21 3.21 3.21

1F 2.04 2.04 2.04 2.04 2.04 2.04 2.04 2.04 2.04 2.04

3F 8.15 8.15 8.20 8.39 8.35 8.42 10.02 10.03 10.04 10.04

1F 8.47 8.47 8.50 8.64 8.61 8.67 9.75 9.76 9.77 9.77

3F 34.30 34.62 34.35

1F 27.97 28.19 28.06

3F 1.75 1.75 1.75 1.88 2.07 2.10 2.10 2.10 2.10 2.10

1F 1.11 1.11 1.11 1.18 1.31 1.32 1.32 1.32 1.32 1.32

3F 10.97 10.98 11.04 11.05 11.07 11.07 11.08 11.08 11.09 11.06

1F 7.68 7.68 7.70 7.70 7.71 7.71 7.71 7.71 7.72 7.70

3F 2.53 2.53 2.53 2.97 2.98 2.98 2.99 3.01 3.01 3.01

1F 1.57 1.57 1.57 1.83 1.84 1.84 1.84 1.85 1.86 1.86

3F 6.24 6.22 6.28 6.28 6.29 6.29 6.30 6.29 7.77 7.77

1F 5.64 5.63 5.66 5.66 5.67 5.67 5.67 5.67 7.02 7.02

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

La Venta III LVT 230

Lacanjá LCJ 115

Laguna de Coyuca LCY 115

Laguna Superior LSP

400

230

Laguna Verde LAV

400

230

Lamosa LOA 115

Lapsolite LSL 115

Las Brisas BRS 115

Las Choapas II LHD 115

Las Cruces CRC 69

Las Fuentes LFU 115

Las Juntas LJU 115

Las Trancas TRN 115

Las Matas MAS 115

Las Palomas LPA 115

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 94: Catalogo 2011-2020 r010212 Corto Circuito

94

Coordinación de Planificación

ÁREA ORIENTAL

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 5.34 5.44 5.44 5.46 5.46 5.47 5.46 5.77 5.77

1F 4.11 4.16 4.15 4.16 4.16 4.17 4.16 4.30 4.30

3F 1.56

1F 1.41

3F 2.20 2.19 2.27 2.27 2.27 2.28 2.28 2.28 2.28 2.28

1F 1.65 1.64 1.68 1.68 1.68 1.68 1.68 1.68 1.68 1.68

3F 3.09 3.09 3.10 3.10 3.10 3.13 3.13 3.13 3.13 3.13

1F 1.96 1.97 1.97 1.97 1.97 1.99 1.99 1.99 1.99 1.99

3F 3.72 3.60 3.63 3.63 4.31 4.31 4.32 4.32 4.33 4.33

1F 2.54 2.43 2.44 2.44 2.89 2.89 2.89 2.89 2.89 2.89

3F 2.68 2.67 3.08 3.08 3.08 3.08 3.08 3.08 3.09 3.09

1F 1.74 1.74 1.93 1.93 1.93 1.93 1.93 1.93 1.93 1.93

3F 8.22 8.22 8.34 8.34 8.44 11.75 11.97 11.92 11.99 11.99

1F 5.87 5.87 5.97 5.97 6.02 9.05 9.17 9.15 9.18 9.18

3F 6.57 6.58 6.62 6.80 6.77 6.89 9.17 9.24 9.20 9.20

1F 6.73 6.74 6.77 6.89 6.87 6.99 8.52 8.57 8.54 8.54

3F 9.67 9.68 9.72 9.72 9.74 9.75 9.75 9.75 9.76 9.73

1F 6.92 6.92 6.94 6.94 6.94 6.95 6.95 6.95 6.95 6.94

3F 4.88 4.88 4.94 5.08 5.04 4.88 7.22 7.39 7.25 7.25

1F 5.64 5.65 5.69 5.82 5.78 5.63 7.67 7.83 7.69 7.69

3F 8.12 8.12 8.20 8.48 8.42 8.61 12.48 12.60 12.53 12.53

1F 9.98 9.98 10.05 10.33 10.27 10.55 14.49 14.62 14.53 14.53

3F 1.97 1.97 1.97 1.97 2.64 2.65 2.65 2.65 2.65

1F 1.64 1.64 1.64 1.64 1.99 1.99 1.99 1.99 1.99

3F 5.36 5.26 5.39 5.38 5.71 5.71 5.72 5.72 5.75 5.75

1F 5.49 5.18 5.27 5.25 5.75 5.75 5.75 5.75 5.77 5.77

3F 5.01 4.92 5.07 5.07 5.07 5.10 5.15 5.18 5.18 5.19

1F 4.89 4.85 4.94 4.94 4.94 5.44 5.48 5.51 5.51 5.51

3F 5.59 5.57 5.67 5.67 5.67 7.16 7.20 7.23 7.23 7.24

1F 6.54 6.53 6.62 6.62 6.62 8.81 8.86 8.89 8.89 8.90

3F 9.11 8.67 8.69 8.69 8.70 8.73 8.76 8.76 8.76 8.76

1F 6.70 6.32 6.32 6.32 6.33 6.31 6.32 6.32 6.32 6.32

3F 4.65 5.92 6.45 6.45 6.45 6.45 6.44 6.44 6.44 6.52

1F 3.64 4.84 5.08 5.08 5.08 5.08 5.11 5.11 5.11 5.17

3F 5.81 6.69 7.00 7.00 7.00 7.04 7.06 7.06 7.06 7.06

1F 5.41 6.18 6.35 6.35 6.35 6.38 6.39 6.39 6.37 6.37

Lerdo LRD 115

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Las Vigas VGA

115

69

Liberación Mexicana LMX 115

Libres LIB 115

Loma Bonita II LBD 115

Lomas de Cocoyoc LOC 115

Lomas del Mar LMM 115

López Mateos LME 115

Los Amates LAT

230

115

Los Brillantes LBI 400

Los Humeros HMS 115

Los Ríos LRS

230

115

Macuspana MCP 115

Mactumatza MTZ 115

Macultepec MCL 115

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 95: Catalogo 2011-2020 r010212 Corto Circuito

95

Coordinación de Planificación

ÁREA ORIENTAL

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 9.60 9.51 10.02 10.02 10.03 10.04 10.08 10.10 10.10 10.13

1F 9.65 10.52 10.94 10.94 10.95 10.96 11.01 11.03 11.01 11.06

3F 8.41 10.70 11.56 11.57 11.57 11.62 11.65 11.66 11.66 11.66

1F 9.91 13.38 14.32 14.32 14.32 14.37 14.41 14.42 14.30 14.30

3F 1.56 1.58 1.58 1.60 1.73 3.31 3.31 3.31

1F 1.01 1.02 1.02 1.03 1.12 4.00 4.00 4.00

3F 23.07 23.13 23.78 23.82 23.92 23.94 24.28 24.28 24.30 24.22

1F 27.87 27.94 28.57 28.60 28.70 28.72 29.05 29.05 29.07 29.00

3F 15.21 15.20 15.51 15.51 15.53 15.54 15.60 15.60 15.60 15.62

1F 17.22 17.22 17.48 17.48 17.50 17.50 17.55 17.55 17.56 17.57

3F 5.96 5.86 6.34 6.34 6.34 6.35 6.35 6.35 6.35 6.37

1F 6.83 6.74 7.19 7.19 7.19 7.20 7.20 7.20 7.20 7.22

3F 9.35 9.36 9.37 12.33 12.32 12.37 12.37

1F 6.60 6.61 6.61 10.31 10.30 10.33 10.33

3F 10.29 9.89 9.99 9.99 10.04 10.05 10.09 10.07 10.14 10.14

1F 10.32 10.00 10.07 10.07 10.11 10.11 10.30 10.28 10.33 10.33

3F 16.99 15.80 16.00 16.01 16.11 16.12 16.29 16.25 16.41 16.41

1F 19.49 18.30 18.49 18.50 18.58 18.60 19.24 19.20 19.35 19.35

3F 26.88 27.20 27.77 27.83 27.93 27.95 29.76 29.75 29.78 29.69

1F 31.54 31.83 32.36 32.41 32.50 32.53 34.37 34.36 34.58 34.49

3F 15.21 15.22 15.41 15.42 15.42 15.64 15.74 15.74 15.74 15.74

1F 17.79 17.80 17.98 17.99 17.99 18.19 18.28 18.28 18.28 18.28

3F 4.40 4.40 4.41 4.41 4.41 4.75 4.76 4.76 4.76 4.76

1F 3.04 3.04 3.04 3.04 3.04 3.19 3.19 3.19 3.19 3.19

3F 3.94 4.04 4.44 4.44 4.48 4.48 4.48 4.48 4.50 4.50

1F 2.75 2.78 3.01 3.01 3.02 3.02 3.02 3.02 3.03 3.03

3F 5.24 5.33 5.59 5.50 7.21 7.41 7.43 7.42 7.42

1F 5.10 5.17 5.35 5.27 6.83 6.95 6.96 6.95 6.95

3F 3.17 3.22 3.68 3.68 3.68 3.68 3.69 3.68 3.71 3.71

1F 2.28 2.30 2.57 2.57 2.57 2.57 2.57 2.57 2.58 2.58

3F 2.99 3.05 3.61 3.61 3.61 3.61 3.62 3.61 3.63 3.63

1F 2.09 2.11 2.44 2.44 2.45 2.45 2.45 2.44 2.45 2.45

3F 8.35 8.45 8.48 8.49 8.49 8.50 8.49 8.51 8.51 8.50

1F 8.83 8.91 8.93 8.93 8.93 8.94 8.94 8.95 8.95 8.95

Mandinga MAN 115

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Macuspana II MCD

230

115

Magueyitos MGY 115

Malpaso II MPD

400

230

115

Manlio Fabio Altamirano MFA

400

230

Manuel Moreno Torres MMT

400

115

Mapastepec MAP 115

Margaritas MGS 115

Marina Ixtapa MAI 115

Martínez de la Torre II MDD 115

Martínez de la Torre III MTT 115

Matías Romero MRO 115

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 96: Catalogo 2011-2020 r010212 Corto Circuito

96

Coordinación de Planificación

ÁREA ORIENTAL

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 5.74 5.83 5.86 5.86 5.87 5.87 5.88 5.90 5.90 5.90

1F 5.93 5.99 6.01 6.02 6.02 6.02 6.04 6.05 6.06 6.05

3F 9.23 9.35 9.38 9.39 9.40 9.40 9.39 9.42 9.42 9.41

1F 11.10 11.21 11.25 11.25 11.26 11.26 11.27 11.29 11.29 11.29

3F 4.39 4.39 4.39 4.39 4.39 5.13 5.13 5.13 5.13 5.13

1F 3.57 3.57 3.57 3.57 3.57 3.94 3.94 3.94 3.94 3.94

3F 9.00 9.21 9.31 9.30 9.32 9.32 9.34 9.32 9.51 9.51

1F 8.80 8.94 9.00 9.00 9.02 9.02 9.03 9.02 9.14 9.14

3F 11.63 11.64 11.70 11.72 11.76 11.76 11.76 11.75 11.79 11.75

1F 7.61 7.61 7.63 7.63 7.65 7.65 7.66 7.57 7.66 7.65

3F 10.17 10.29 10.34 10.44 10.48 10.48 10.49 10.48 10.61 10.51

1F 7.81 7.94 7.96 8.00 8.01 8.01 8.02 8.02 8.07 8.02

3F 6.84 6.85 6.87 6.95 6.43 6.44 6.54 6.79 6.80 6.79

1F 4.32 4.32 4.32 4.38 4.01 4.01 4.08 4.24 4.25 4.25

3F 0.85 0.85 0.85 0.85 0.85 0.85 0.86 0.86 0.86 0.86

1F 0.61 0.65 0.61 0.61 0.61 0.61 0.62 0.62 0.62 0.62

3F 9.99 9.99 10.13 10.13 10.23 10.23 11.00 10.96 11.02 11.02

1F 8.30 8.30 8.37 8.37 8.42 8.42 8.90 8.89 8.91 8.91

3F 4.72 4.64 6.74 6.73 6.74 6.75 6.79 6.79 6.82 6.81

1F 3.42 3.39 4.49 4.48 4.49 4.49 4.51 4.51 4.52 4.52

3F 8.30 8.30 8.37 8.46 8.46 8.50 10.08 10.07 10.27 10.27

1F 8.74 8.74 8.79 8.86 8.86 8.89 10.03 10.03 10.19 10.20

3F 8.73 8.73 8.77 8.83 8.82 8.85 9.71 9.70 10.11 10.11

1F 10.29 10.29 10.33 10.38 10.38 10.40 11.19 11.19 11.63 11.63

3F 6.04 5.68 7.59 7.59 7.59 7.59 7.59 7.60 7.60 7.73

1F 4.69 4.43 6.04 6.04 6.04 6.04 6.04 6.04 6.03 6.10

3F 8.36 8.68 8.69 8.69 8.69 8.69 8.69 8.69 8.83

1F 6.85 7.00 7.01 7.01 7.01 7.02 7.02 7.02 7.09

3F 2.18 2.18 2.19 2.21 2.22 2.33 2.36 2.54 2.54 2.53

1F 1.51 1.51 1.51 1.52 1.52 1.56 1.58 1.74 1.74 1.74

3F 2.05 2.05 2.07 2.07 2.07 2.07 2.07 2.07 2.08 2.08

1F 2.19 2.19 2.20 2.20 2.21 2.21 2.21 2.21 2.21 2.21

3F 9.15 9.16 9.21 9.21 9.22 9.23 9.23 9.23 9.24 9.21

1F 6.68 6.68 6.70 6.70 6.70 6.71 6.71 6.71 6.71 6.70Minatitlán I MIU 115

Miahuatlán MHT 115

Minas MIS 69

Mezcalapa MEZ 115

Mezcalapa Maniobras MEZ 230

Mexpape MPP 115

Mezcala MZL

230

115

Metlatanoc MTL 115

Mexama MXA 115

Metalúrgica Veracruzana MVE 115

Metepec MEC 115

Mazatepec MZT 230

Metaloides MET 115

Mazatán MAZ 115

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Matías Romero Potencia MSP

230

115

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 97: Catalogo 2011-2020 r010212 Corto Circuito

97

Coordinación de Planificación

ÁREA ORIENTAL

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 13.95 14.02 14.39 14.41 14.53 14.56 14.64 14.62 14.66 14.47

1F 13.86 13.91 14.17 14.19 14.27 14.29 14.34 14.32 14.35 14.22

3F 25.52 25.59 25.93 25.94 26.06 26.09 26.16 26.14 26.19 26.00

1F 28.33 28.38 28.67 28.69 28.78 28.80 28.86 28.85 28.88 28.73

3F 5.53 5.53 5.55 5.57 5.57 5.58 5.91 5.90 6.05 6.05

1F 4.81 4.81 4.82 4.83 4.83 4.84 5.00 5.00 5.08 5.08

3F 1.88 1.90 2.04 2.04 2.05 2.05 2.05 2.05 2.05 2.05

1F 1.27 1.27 1.35 1.35 1.35 1.35 1.35 1.35 1.35 1.35

3F 2.40 2.39 2.40 2.43 2.44 2.60 2.60 2.61 2.61 2.61

1F 1.80 1.79 1.80 1.81 1.81 1.87 1.87 1.88 1.88 1.88

3F 11.58 8.94 9.24 9.25 9.26 9.26 12.50 12.49 12.55 12.55

1F 9.46 6.43 6.54 6.54 6.55 6.55 10.67 10.67 10.69 10.69

3F 1.43 1.43 1.43 1.43 1.43 1.48 1.48 1.48 1.48 1.48

1F 0.94 0.94 0.94 0.94 0.94 0.95 0.95 0.95 0.95 0.95

3F 6.22 6.22 6.26 6.44 6.40 6.46 8.17 8.17 8.19 8.19

1F 5.94 5.94 5.96 6.07 6.05 6.09 7.02 7.02 7.03 7.03

3F 3.72 3.72 3.72 3.72 3.72 3.72 3.76

1F 2.63 2.63 2.63 2.63 2.63 2.63 2.64

3F 13.01 13.03 13.12 13.12 13.15 13.16 13.18 13.17 13.18 13.14

1F 10.18 10.19 10.23 10.23 10.24 10.24 10.25 10.25 10.25 10.24

3F 1.90 1.90 1.90 2.19 2.32 2.41 2.41 2.42 2.42 2.42

1F 1.32 1.32 1.32 1.52 1.65 1.69 1.69 1.69 1.69 1.69

3F 10.08 10.14 10.19 10.31 10.34 10.35 10.36 10.35 10.55 10.44

1F 7.97 8.00 8.03 8.08 8.09 8.09 8.10 8.09 8.19 8.14

3F 21.04 21.09 21.26 21.30 21.45 21.45 21.45 21.40 21.53 21.41

1F 14.86 14.88 14.95 14.96 15.02 15.02 15.04 14.86 15.06 15.02

3F 3.51 3.52 3.52 3.53 3.53 3.53 3.53 3.53 3.53 3.53

1F 2.38 2.38 2.38 2.38 2.38 2.38 2.38 2.38 2.38 2.38

3F 7.69 7.57 12.05 12.05 12.05 12.05 12.11 12.11 12.11 12.87

1F 7.02 6.92 11.65 11.65 11.65 11.65 11.69 11.69 10.82 11.35

3F 9.74 9.56 17.94 17.94 17.95 17.95 18.07 18.08 18.08 19.82

1F 8.73 8.55 19.52 19.53 19.53 19.53 19.65 19.65 19.21 20.96

3F 3.96 3.95 3.98 4.07 4.11 4.62 4.63 4.67 4.67 4.67

1F 3.59 3.59 3.60 3.66 3.68 3.96 3.97 3.99 3.99 3.99

3F 5.85 5.93 5.95 5.96 5.96 5.96 5.99 6.03 6.03 6.02

1F 6.27 6.34 6.35 6.35 6.36 6.36 6.41 6.44 6.44 6.43

Minera Nukay MNK 115

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Minatitlán II MID

400

115

Misantla II MSD 115

Mitla MTX 115

Mocambo MCB 115

Motozintla MTO 115

Mozimba MOZ 115

Nacajuca NJA 115

Nanchital NND 115

Nochixtlán NCH 115

Nogales NGL 115

Norte NOR 115

Nuevo Morelos NMO 115

Nuevo Pemex NPX 115

Oaxaca I (Eoloeléctrica) OXU 230

Nuevo Pemex CC CAX 115

Oaxaca I OAX 115

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 98: Catalogo 2011-2020 r010212 Corto Circuito

98

Coordinación de Planificación

ÁREA ORIENTAL

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 4.86 4.82 4.87 5.00 5.05 5.77 5.78 5.84 5.84 5.83

1F 4.83 4.80 4.83 4.92 4.95 5.43 5.43 5.47 5.47 5.47

3F 6.10 6.72 7.29 7.35 7.35 7.35 7.36 7.36 7.36 7.35

1F 6.44 6.90 7.30 7.34 7.35 7.35 7.35 7.35 7.35 7.35

3F 5.95 6.67 7.37 7.44 7.45 7.45 7.45 7.45 7.46 7.45

1F 5.81 6.29 6.71 6.75 6.75 6.76 6.76 6.76 6.76 6.75

3F 5.91 6.48 7.00 7.06 7.06 7.06 7.07 7.07 7.07 7.06

1F 6.20 6.62 6.98 7.02 7.02 7.02 7.02 7.02 7.02 7.02

3F 4.21 4.20 4.23 4.33 4.38 4.95 4.96 5.00 5.01 5.00

1F 3.99 3.99 4.01 4.07 4.10 4.44 4.45 4.47 4.47 4.47

3F 3.09 3.08 3.10 3.19 3.23 3.89 3.90 3.94 3.95 3.94

1F 3.33 3.33 3.34 3.42 3.44 3.97 3.98 4.01 4.02 4.01

3F 5.44 5.42 5.47 5.64 5.71 6.68 6.70 6.76 6.77 6.76

1F 6.54 6.53 6.57 6.73 6.81 7.75 7.77 7.83 7.84 7.83

3F 1.05 1.05 1.30 1.30 1.30 1.34 1.34 1.34 1.34 1.34

1F 0.69 0.69 0.84 0.84 0.84 0.85 0.85 0.85 0.85 0.85

3F 3.98 3.97 3.99 4.15 4.18 4.76 4.78 4.87 4.87 4.87

1F 3.54 3.54 3.55 3.65 3.66 3.99 4.01 4.07 4.07 4.07

3F 6.35 6.35 6.36 6.36 6.37 6.86 6.88 6.88 6.88 6.88

1F 4.53 4.53 4.54 4.54 4.54 5.06 5.07 5.07 5.07 5.07

3F 16.44 16.49 17.01 17.05 17.42 17.46 17.50 17.37 17.73 14.96

1F 14.94 14.98 15.31 15.34 15.56 15.58 15.65 15.48 15.77 13.52

3F 21.91 22.14 22.40 23.06 23.23 23.25 23.33 23.27 23.90 23.24

1F 23.00 23.24 23.44 23.99 24.12 24.14 24.22 24.15 24.65 23.97

3F 11.01

1F 11.00

3F 19.69

1F 22.27

3F 3.31 3.29 3.65 3.65 3.66 3.66 3.66 3.66 4.76 4.76

1F 2.22 2.21 2.33 2.33 2.33 2.33 2.33 2.33 3.86 3.86

3F 1.12 1.12 1.12 1.43 1.43 1.54 1.59 1.62 1.61 1.61

1F 0.73 0.73 0.73 0.92 0.92 1.00 1.01 1.03 1.03 1.03

3F 17.21 17.23 17.38 17.43 17.56 17.56 17.57 17.53 17.62 17.53

1F 12.11 12.12 12.18 12.20 12.25 12.25 12.27 11.77 12.29 12.25

3F 16.27 16.44 16.60 16.89 16.97 16.98 17.02 16.99 17.68 17.40

1F 17.76 17.96 18.08 18.32 18.38 18.39 18.42 18.40 19.09 18.85

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Oaxaca II OXD 115

Oaxaca II (Eoloeléctrica) OAX-II 230

Oaxaca III (Eoloeléctrica) OAX-III 230

Oaxaca IV (Eoloeléctrica) OAX-IV 230

Oaxaca Poniente OAP 115

Oaxaca Potencia OXP

230

115

Ocosingo OCO 115

Ocotlán OCL 115

Ocozocuautla OCZ 115

Ojo de Agua Potencia OJP

400

115

Olmeca OLM

230

115

Omealca OME 115

Orizaba ORI 115

Ometepec OMT 115

Oriente ORT 115

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 99: Catalogo 2011-2020 r010212 Corto Circuito

99

Coordinación de Planificación

ÁREA ORIENTAL

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 1.39 1.39 1.86 1.86 1.86 1.93 1.93 1.93 1.93 1.93

1F 0.89 0.89 1.20 1.20 1.20 1.23 1.23 1.23 1.23 1.23

3F 10.25 8.05 8.26 8.25 8.26 8.26 10.99 10.98 11.02 11.03

1F 8.11 5.67 5.75 5.74 5.75 5.75 9.07 9.06 9.08 9.08

3F 11.88 11.02 11.11 11.10 11.13 11.13 11.33 11.32 11.37 11.37

1F 9.92 9.45 9.49 9.49 9.50 9.50 9.71 9.71 9.73 9.73

3F 12.48 12.50 12.57 12.58 12.61 12.61 12.63 12.62 12.63 12.59

1F 9.37 9.38 9.41 9.41 9.42 9.42 9.43 9.43 9.43 9.42

3F 2.36 2.36 2.38 2.38 2.38 2.60 2.61 2.61 2.61 2.61

1F 1.80 1.80 1.80 1.80 1.80 1.93 1.93 1.93 1.93 1.93

3F 3.69 3.69 3.90 5.73 5.75 5.75 5.77 5.76 5.78 5.76

1F 2.29 2.30 2.43 3.51 3.51 3.51 3.52 3.52 3.53 3.52

3F 8.31 10.51 11.87 11.87 11.87 11.87 11.90 11.86 11.89 11.89

1F 7.12 8.52 9.40 9.40 9.40 9.40 9.41 9.39 9.40 9.40

3F 11.19 11.23 11.27 11.27 12.74 12.74 12.74 12.71 12.78 12.75

1F 8.19 8.21 8.22 8.22 8.26 8.26 8.26 8.26 8.28 8.27

3F 5.48 5.73 5.91 5.91 5.91 5.93 5.94 5.92 5.93 5.93

1F 4.45 4.58 5.32 5.32 5.32 5.03 5.03 5.02 5.03 5.03

3F 7.04 7.31 8.87 8.87 8.87 8.91 8.93 8.90 8.91 8.91

1F 7.28 7.49 9.74 9.74 9.74 9.49 9.50 9.47 9.48 9.48

3F 2.71 2.71 2.72 2.88 2.87 4.50 5.51 5.65 5.52 5.52

1F 1.90 1.90 1.90 2.00 1.99 3.86 4.33 4.41 4.34 4.34

3F 18.30 18.35 18.46 18.47 18.74 18.74 18.74 18.70 18.80 18.72

1F 12.74 12.76 12.79 12.80 12.96 12.96 12.97 12.94 12.99 12.96

3F 1.27 1.28 1.29 2.03 2.02 2.10 2.15 2.15 2.15 2.15

1F 0.87 0.88 0.88 1.35 1.35 1.38 1.39 1.39 1.39 1.39

3F 17.53 17.54 17.57 17.58 18.11 17.46 17.61 17.61

1F 14.03 14.03 14.04 13.82 14.15 13.77 13.83 13.83

3F 19.15 19.15 19.18 19.18 19.32 19.14 19.22 19.22

1F 17.11 17.11 17.12 17.04 17.15 17.02 17.06 17.06

3F 3.54 5.94 6.12 6.12 6.12 6.13 6.11 6.11 6.11 6.22

1F 2.45 5.75 5.87 5.87 5.87 5.87 5.86 5.86 5.86 5.93

3F 4.10 4.73 4.89 4.89 4.89 4.89 4.89 4.89 4.89 4.96

1F 2.82 3.37 3.43 3.43 3.43 3.43 3.43 3.43 3.43 3.45

3F 7.34 7.50 7.54 7.54 7.55 7.56 7.61 7.68 7.68 7.67

1F 8.29 8.45 8.48 8.48 8.49 8.49 8.72 8.80 8.80 8.79

Parque Industrial PRQ 115

Parques Ecológicos de México PEM 230

Papantla PAP

400

115

Paraíso PSO 115

Papalotla PPL 115

Papanoa PPN 115

Pantepec PPC

230

115

Papagayo PPG 115

Palmas PMM 115

Panotla PNA 115

Palenque PLQ 115

Palmar de Bravo PLB 115

Pages-2 PAG 115

Pajaritos II PJD 115

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Oxchuc OXC 115

Pages-1 PAG 115

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 100: Catalogo 2011-2020 r010212 Corto Circuito

100

Coordinación de Planificación

ÁREA ORIENTAL

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 13.31 13.19 15.69 15.69 15.70 15.70 15.85 15.86 15.86 16.08

1F 12.23 12.16 13.66 13.66 13.67 13.67 13.93 13.94 13.93 14.17

3F 2.64 2.64 2.64 2.64 2.63 2.63 2.63 2.63 2.63 2.63

1F 1.62 1.62 1.62 1.62 1.84 1.84 1.84 1.84 1.84 1.84

3F 11.21 9.03 9.61 9.02 9.03 9.04 11.16 11.16 11.21 11.21

1F 8.81 6.50 6.73 6.22 6.23 6.23 8.58 8.58 8.60 8.60

3F 11.77 11.78 11.85 11.85 11.88 11.88 11.90 11.89 11.90 11.87

1F 8.92 8.93 8.96 8.96 8.97 8.97 8.97 8.97 8.98 8.96

3F 2.54 2.48 8.21 8.21 8.22 8.22 8.21 8.21 8.21 8.40

1F 1.82 1.78 6.61 6.61 6.61 6.61 6.61 6.61 6.61 6.70

3F 13.39 13.33 13.78 13.79 13.80 13.81 13.82 13.83 13.83 13.96

1F 14.39 14.44 14.80 14.80 14.81 14.81 14.83 14.83 14.84 14.94

3F 4.07 3.97 4.47 4.47 4.47 4.47 4.47 4.47 4.47 4.50

1F 3.15 3.08 3.42 3.42 3.42 3.42 3.42 3.42 3.42 3.43

3F 3.74 3.59 3.64 3.64 3.64 3.64 3.65 3.64 3.80 3.80

1F 2.68 2.55 2.56 2.56 2.56 2.56 2.56 2.56 2.63 2.63

3F 1.97 1.98 1.99 2.57 2.56 2.76 2.82 2.82 2.82 2.82

1F 1.40 1.41 1.41 1.79 1.78 1.87 1.89 1.89 1.89 1.89

3F 9.38 12.29 8.43 8.43 8.43 8.43 8.44 8.42 8.43 8.44

1F 8.51 10.59 5.97 5.97 5.97 5.97 5.97 5.97 5.97 5.97

3F 9.55 9.61 9.64 9.64 9.84 9.85 9.84 9.82 9.86 9.84

1F 10.18 10.23 10.25 10.25 10.41 10.41 10.41 10.40 10.42 10.41

3F 11.17 11.18 11.24 11.25 11.27 11.27 11.29 11.29 11.29 11.26

1F 8.30 8.31 8.33 8.33 8.34 8.34 8.35 8.34 8.35 8.34

3F 2.14 2.14 2.72 2.72 2.72 2.72 2.72 2.72 2.72 2.72

1F 1.40 1.40 1.74 1.74 1.74 1.74 1.74 1.74 1.74 1.74

3F 5.43 5.43 5.51 5.65 5.58 5.61 8.32 8.58 8.36 8.36

1F 6.83 6.83 6.92 7.06 6.99 7.01 9.73 10.10 9.76 9.76

3F 8.42 8.42 8.51 8.74 8.67 8.76 11.95 12.02 12.00 12.00

1F 13.07 13.07 13.21 13.59 13.47 13.62 18.83 18.94 18.90 18.90

3F 5.63 5.23 5.82 5.70 5.71 5.71 6.09 6.08 6.10 6.10

1F 3.86 3.57 3.78 3.69 3.70 3.70 4.01 4.01 4.02 4.02

3F 2.70 2.70 2.70 2.70 2.70 2.83 2.83 2.83 2.83 2.83

1F 1.76 1.76 1.76 1.76 1.76 1.82 1.82 1.82 1.82 1.82

3F 0.99 0.99 0.99 1.58 1.58 1.66 1.69 1.75 1.75 1.75

1F 0.65 0.65 0.65 1.01 1.01 1.06 1.07 1.12 1.12 1.12

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Parrilla PLL 115

Paso de Cortés PDC 115

Paso del Toro PDT 115

Pemex Cavernas CVN 115

Pemex Paredón PPX 115

Peñitas PEA

230

115

Perote PEE 115

Petatlán PTT 115

Petroquímica Escolín PQS 115

Petroquímica Independencia PEI 115

Petroquímica Morelos PMO 115

Pichucalco PCO 115

Pie de la Cuesta PIC

230

115

Piedras Negras PNS 115

Pijijiapan PJJ 115

Pinotepa PIN 115

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 101: Catalogo 2011-2020 r010212 Corto Circuito

101

Coordinación de Planificación

ÁREA ORIENTAL

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 5.71 4.86 4.89 4.99 4.96 5.70 7.40 7.52 7.42 7.42

1F 5.33 4.16 4.18 4.22 4.21 5.22 6.22 6.29 6.23 6.23

3F 13.74 12.59 12.72 12.71 12.74 12.74 13.02 13.01 13.06 13.07

1F 12.32 11.58 11.66 11.65 11.67 11.67 12.00 12.00 12.03 12.03

3F 1.58 1.57 1.71 1.71 1.71 1.71 1.71 1.71 1.71 1.71

1F 1.01 1.01 1.07 1.07 1.07 1.07 1.07 1.07 1.07 1.07

3F 5.34 5.35 5.38 5.49 5.47 5.51 6.83 6.83 6.84 6.84

1F 4.80 4.80 4.82 4.88 4.86 4.89 5.52 5.52 5.53 5.53

3F 1.70 1.70 1.72 1.75 1.75 1.79 1.86 2.38 2.38 2.38

1F 1.11 1.11 1.11 1.14 1.14 1.16 1.20 1.80 1.80 1.80

3F 10.05 10.06 10.10 10.10 12.41 12.41 12.52 12.48 12.56 12.55

1F 7.00 7.01 7.02 7.02 9.99 9.99 10.05 10.03 10.07 10.06

3F 18.56 18.86 19.00 19.00 19.96 19.96 19.93 19.87 20.02 19.95

1F 14.73 14.94 15.00 15.00 15.52 15.52 15.51 15.48 15.55 15.52

3F 12.68 12.77 15.62 15.62 15.63 15.63 15.57 15.58 15.58 16.14

1F 13.41 13.55 15.78 15.78 15.79 15.79 16.09 16.09 16.09 16.91

3F 24.07 24.13 24.37 24.40 24.61 24.63 24.62 24.54 24.72 24.57

1F 17.30 17.33 17.42 17.43 17.52 17.52 17.54 17.32 17.57 17.52

3F 16.55 16.59 16.68 16.69 17.21 17.22 17.21 17.17 17.26 17.20

1F 11.27 11.28 11.31 11.31 11.67 11.67 11.67 11.65 11.69 11.67

3F 6.36 6.44 6.46 6.49 6.50 6.50 6.50 6.50 6.55 6.52

1F 4.59 4.68 4.69 4.70 4.70 4.70 4.70 4.70 4.72 4.71

3F 14.08 16.40 16.70 16.70 16.71 16.72 16.88 16.67 16.83 16.83

1F 14.60 16.99 17.31 17.31 17.32 17.23 17.38 17.19 17.30 17.30

3F 13.53 20.55 21.84 21.84 21.85 21.86 21.94 21.83 21.91 21.91

1F 15.91 25.24 26.58 26.58 26.59 26.57 26.66 26.54 26.62 26.62

3F 12.09 23.76 24.26 24.26 24.27 24.27 24.30 24.26 24.29 24.29

1F 16.89 33.19 33.87 33.87 33.88 33.87 33.91 33.86 33.89 33.90

3F 27.19 27.83 28.27 28.28 28.34 28.38 30.25 28.03 28.38 28.40

1F 21.79 22.28 23.53 23.53 23.54 22.36 23.70 22.21 22.36 22.37

3F 15.53 17.76 18.03 18.03 18.05 18.06 18.26 17.99 18.20 18.20

1F 16.83 19.01 19.35 19.35 19.36 19.22 19.43 19.17 19.33 19.33

3F 3.26 3.26 3.27 3.41 3.40 3.67 4.38 4.47 4.38 4.38

1F 2.39 2.39 2.39 2.47 2.46 3.00 3.31 3.35 3.31 3.31

3F 8.54 8.62 8.62 8.62 8.63 8.63 8.63 8.62

1F 9.55 9.62 9.63 9.63 9.63 9.63 9.63 9.63

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Playa Diamante PDI 115

Playa Norte PYN 115

Playa Vicente PVC 115

Playas PYS 115

Pochutla POC 115

Polidesa PLS 115

Polifil POF 115

Pomoca PMC 115

Poniente PON 115

Porcel POR 115

Potrero II PTD 115

Poza Rica I PRI

230

115

69

Preneal México PRM 230

Poza Rica II PRD

400

230

Pozos Ranney PZR 115

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 102: Catalogo 2011-2020 r010212 Corto Circuito

102

Coordinación de Planificación

ÁREA ORIENTAL

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 7.42 7.43 7.45 7.45 9.20 9.20 9.24 9.22 9.26 9.25

1F 4.95 4.95 4.96 4.96 6.56 6.56 6.57 6.57 6.58 6.58

3F 22.90 22.93 23.19 23.33 23.55 23.56 23.57 23.49 23.66 23.48

1F 17.24 17.25 17.37 17.44 17.54 17.54 17.58 16.44 17.62 17.54

3F 19.49 19.52 19.69 19.75 19.89 19.90 19.90 19.85 19.96 19.85

1F 13.66 13.67 13.74 13.76 13.82 13.82 13.84 13.44 13.86 13.82

3F 24.59 24.69 25.79 25.82 26.72 26.79 26.91 26.54 27.37 26.14

1F 24.84 24.92 25.75 25.79 26.49 26.54 27.01 26.00 27.32 26.37

3F 13.83 13.85 14.05 14.04 14.27 14.28 18.93 18.80 19.06 18.85

1F 13.51 13.53 13.66 13.66 13.94 13.95 19.89 19.68 19.99 19.82

3F 39.13 39.23 39.99 40.59 41.22 41.27 41.29 41.05 41.58 40.98

1F 36.89 36.96 37.48 38.00 38.44 38.47 38.68 32.96 38.85 38.43

3F 4.44 4.44 4.46 4.46 5.85 5.84 5.86 5.86

1F 3.05 3.05 3.06 3.06 4.06 4.06 4.06 4.06

3F 3.50 3.50

1F 2.57 2.57

3F 1.17 1.17 1.18 1.29 1.29 1.32 1.35 1.50 1.50 1.50

1F 0.76 0.76 0.76 0.84 0.84 0.85 0.87 1.01 1.01 1.01

3F 9.58 9.59 9.63 9.64 9.65 9.66 9.66 9.66 9.67 9.64

1F 6.63 6.63 6.64 6.64 6.65 6.65 6.65 6.65 6.66 6.65

3F 2.97 2.97 2.98 2.98 2.98 3.29 3.30 3.30 3.30 3.30

1F 2.18 2.18 2.18 2.18 2.18 2.31 2.31 2.31 2.31 2.31

3F 7.25 7.25 7.31 7.53 7.48 7.63 9.76 9.84 9.79 9.79

1F 8.00 8.01 8.05 8.23 8.19 8.37 9.41 9.46 9.43 9.43

3F 5.19 5.22 5.33 5.31 5.92 7.50 7.60 7.52 7.52

1F 4.61 4.62 4.68 4.67 5.43 6.30 6.36 6.31 6.31

3F 4.50 5.09 5.17 5.41 5.33 6.92 7.11 7.12 7.12 7.12

1F 4.20 4.86 4.93 5.09 5.02 6.41 6.52 6.52 6.52 6.52

3F 2.61 2.59 2.59 2.59 2.59 2.59 2.60 2.60 2.64 2.64

1F 1.65 1.64 1.65 1.65 1.65 1.65 1.65 1.65 1.67 1.67

3F 16.08 16.50 16.61 16.61 17.24 17.25 17.22 17.17 17.29 17.23

1F 12.00 12.35 12.39 12.39 12.70 12.70 12.69 12.67 12.71 12.69

3F 7.30 7.32 7.32 7.32 7.37 7.39 7.39 7.39 7.39

1F 5.14 5.14 5.15 5.15 5.16 5.17 5.17 5.17 5.17

3F 8.59 8.60 8.63 8.63 8.65 8.65 8.66 8.66 8.66 8.64

1F 6.04 6.04 6.05 6.05 6.06 6.06 6.06 6.06 6.06 6.06

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Procter & Gamble PGC 115

Puebla 2000 PDM 115

Puebla I PBU 115

Puebla II PBD

400

230

115

Puente de Ixtla PIX

115

85

Puerto Escondido PUE 115

Puerto Franco PFR 115

Puerto Madero PTM 115

Puerto Marqués PUM 115

Punta Diamante PUT 115

Punta Ixtapa PUI 115

Punta Limón PLI 115

Refinería Minatitlán RMN 115

Rassini Frenos AMF 115

Real del Bosque RDB 115

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 103: Catalogo 2011-2020 r010212 Corto Circuito

103

Coordinación de Planificación

ÁREA ORIENTAL

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 2.87 2.91 2.91 2.87 2.87 2.87 4.01 3.95 3.95 3.95

1F 2.02 2.04 2.04 2.03 2.03 2.03 3.38 3.36 3.36 3.36

3F 8.69 7.44 9.91 9.91 9.91 9.92 9.96 9.96 9.96 10.23

1F 6.83 5.65 7.21 7.21 7.21 7.21 7.23 7.23 7.20 7.33

3F 8.10 8.10 8.17 8.49 8.43 8.54 12.04 12.06 12.08 12.08

1F 9.35 9.35 9.42 9.70 9.64 9.79 12.76 12.78 12.79 12.79

3F 8.77 8.78 8.82 8.82 8.83 8.84 8.84 8.84 8.85 8.83

1F 6.24 6.25 6.26 6.26 6.26 6.27 6.27 6.27 6.27 6.26

3F 13.99 14.01 14.09 14.12 14.19 14.20 14.20 14.17 14.23 14.17

1F 9.35 9.35 9.38 9.39 9.42 9.42 9.43 9.28 9.44 9.42

3F 4.49 4.52 4.66 4.70 5.44 5.46 5.52 5.53 5.52

1F 4.27 4.29 4.38 4.40 4.87 4.88 4.92 4.92 4.92

3F 6.21 6.21 6.23 6.23 6.24 6.24 6.24 6.24 6.25 6.24

1F 4.18 4.18 4.18 4.19 4.19 4.19 4.19 4.19 4.19 4.19

3F 10.24 10.29 10.35 10.48 10.51 10.51 10.53 10.52 10.69 10.57

1F 7.94 7.97 8.00 8.05 8.06 8.07 8.07 8.07 8.15 8.09

3F 0.84 0.84 0.84 0.97 0.98 1.00 1.01 1.06 1.06 1.06

1F 0.56 0.56 0.56 0.64 0.64 0.65 0.66 0.70 0.70 0.70

3F 10.83 9.95 10.05 10.04 10.06 10.06 10.34 10.33 10.37 10.37

1F 8.03 7.54 7.58 7.58 7.58 7.58 7.91 7.91 7.93 7.93

3F 2.33 2.33 2.43 2.43 2.43 2.43 2.43 2.43 2.43 2.43

1F 1.47 1.47 1.52 1.52 1.52 1.52 1.52 1.52 1.52 1.52

3F 11.52 8.86 9.13 9.13 9.14 9.15 12.45 12.44 12.50 12.50

1F 9.44 6.36 6.46 6.46 6.46 6.46 10.72 10.72 10.75 10.75

3F 3.22 3.26 3.26 3.21 3.21 3.21 4.71 4.63 4.63 4.63

1F 2.31 2.32 2.32 2.32 2.32 2.32 4.26 4.23 4.23 4.23

3F 11.23 11.30 14.13 14.14 14.14 14.14 14.22 14.22 14.22 15.46

1F 10.35 10.43 12.34 12.34 12.35 12.35 12.55 12.55 12.53 14.46

3F 5.32 5.33 5.97 5.97 5.97 5.97 6.00 6.00 6.00 7.67

1F 3.66 3.67 3.93 3.93 3.93 3.93 3.95 3.95 3.95 5.63

3F 2.60 2.60 2.64 2.64 2.64 2.64 2.65 2.65 2.65 2.65

1F 2.31 2.31 2.34 2.34 2.34 2.34 2.34 2.34 2.34 2.34

3F 3.85 3.85 3.87 3.97 4.00 4.52 4.53 4.57 4.58 4.57

1F 3.41 3.41 3.42 3.47 3.49 3.77 3.78 3.80 3.80 3.80

3F 4.50 4.50 5.37 5.37 5.37 5.82 5.83 5.83 5.83 5.83

1F 3.13 3.13 3.81 3.81 3.81 4.04 4.04 4.04 4.04 4.04

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Refinería Salina Cruz RSC 115

Reforma RFA 115

Renacimiento REN 115

Resirene RSR 115

Resurrección RNS 115

Reyes Mantecón RMT 115

Rhodia Fosfatados TOY 115

Río Blanco RBO 115

Río Grande RGD 115

Río Medio RMD 115

Rodríguez Clara RDC 115

Sacrificios SCF 115

Salina Cruz SAC 115

Saloya SYA 115

Samaria SMI 115

San Andrés ADS 115

San Bartolo Coyotepec BTO 115

San Cristóbal CRI 115

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 104: Catalogo 2011-2020 r010212 Corto Circuito

104

Coordinación de Planificación

ÁREA ORIENTAL

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 2.32 2.32 4.06 4.06 4.06 4.38 4.39 4.39 4.39 4.39

1F 1.51 1.51 2.76 2.76 2.76 2.91 2.92 2.92 2.92 2.92

3F 4.42 4.41 4.44 4.55 4.60 5.23 5.24 5.28 5.29 5.28

1F 4.36 4.36 4.38 4.45 4.48 4.89 4.90 4.93 4.93 4.92

3F 1.17 1.17 1.17 1.68 1.69 1.76 1.77 1.82 1.82 1.82

1F 0.80 0.80 0.80 1.11 1.11 1.14 1.15 1.18 1.18 1.18

3F 1.50 1.50 1.50 2.18 2.17 2.20 2.32 2.32 2.32 2.32

1F 1.01 1.01 1.01 1.45 1.45 1.46 1.49 1.49 1.49 1.49

3F 37.88 38.19 38.70 38.75 39.27 39.30 38.44 38.29 38.70 38.37

1F 31.72 31.93 32.18 32.22 32.49 32.50 31.69 31.54 31.81 31.65

3F 41.90 42.18 42.79 42.84 43.39 43.42 43.43 43.23 43.75 43.32

1F 38.08 38.27 38.62 38.66 39.00 39.02 39.08 38.85 39.27 39.02

3F 23.98 24.08 25.01 25.04 25.77 25.82 25.85 25.49 26.32 25.45

1F 24.03 24.11 24.78 24.81 25.36 25.39 25.59 25.02 25.91 25.28

3F 50.57 50.95 51.84 51.92 52.70 52.75 52.76 52.47 53.23 52.60

1F 51.78 52.11 52.77 52.84 53.45 53.48 53.61 53.17 53.96 53.49

3F 1.15 1.15 1.15 1.20 1.21 1.21 1.21 1.21 1.21 1.21

1F 0.73 0.73 0.73 0.76 0.76 0.76 0.76 0.76 0.76 0.76

3F 20.08 20.35 20.50 20.50 21.47 21.48 21.44 21.37 21.54 21.46

1F 17.47 17.66 17.74 17.75 18.33 18.34 18.33 18.28 18.38 18.34

3F 17.69 17.77 18.18 18.19 18.58 18.60 18.53 18.33 18.88 18.65

1F 14.97 15.04 15.25 15.27 15.52 15.52 15.51 15.39 15.69 15.58

3F 25.90 26.40 26.66 26.66 28.64 28.65 28.59 28.46 28.78 28.63

1F 23.80 24.24 24.40 24.40 25.84 25.85 25.82 25.73 25.93 25.85

3F 12.64 13.20 13.28 13.29 13.60 13.60 13.58 13.55 13.62 13.59

1F 8.76 9.26 9.29 9.29 9.42 9.42 9.41 9.40 9.43 9.42

3F 4.43 4.43 4.43 4.42 4.43 4.42

1F 3.09 3.09 3.10 3.09 3.10 3.09

3F 2.02 2.05 2.22 2.22 2.22 2.22 2.22 2.22 2.23 2.23

1F 1.37 1.38 1.47 1.47 1.47 1.47 1.47 1.47 1.47 1.47

3F 1.69 1.70 1.70 1.70 1.70 1.70 1.70 1.70 1.70 1.70

1F 1.10 1.10 1.10 1.10 1.10 1.10 1.10 1.10 1.10 1.10

3F 12.40 12.42 12.47 12.47 14.25 14.25 14.25 14.22 14.29 14.26

1F 8.26 8.27 8.29 8.29 9.54 9.54 9.55 9.53 9.56 9.55

3F 11.10 11.12 11.17 11.16 15.61 15.62 15.72 15.67 15.79 15.76

1F 7.83 7.84 7.85 7.85 12.81 12.81 12.87 12.85 12.90 12.89

Santa Ana Chiautempan ANC 115

Santa Anita STN 115

San Rafael II RFD 115

Sánchez Taboada SNT 115

San Miguel SMG 115

San Nicolás de los Ranchos SNR 115

San Martín MAR 115

San Martín Potencia MPT

400

115

San Lorenzo Potencia LRP

400

115

San Luis Morelia SSM 115

San Lorenzo Almecatla LML 115

San Lorenzo Distribución LRZ 115

San Jacinto Tlacotepec JTL 115

San Jerónimo JRN 115

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

San Cristóbal Oriente SCO 115

San Felipe SFO 115

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 105: Catalogo 2011-2020 r010212 Corto Circuito

105

Coordinación de Planificación

ÁREA ORIENTAL

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 10.98 10.18 10.26 10.25 10.27 10.28 10.53 10.52 10.61 10.61

1F 8.00 7.57 7.61 7.60 7.61 7.61 7.90 7.89 7.94 7.94

3F 1.15 1.14 1.15 1.28 1.29 1.33 1.33 1.33 1.33 1.33

1F 0.81 0.81 0.81 0.90 0.91 0.92 0.92 0.92 0.92 0.92

3F 13.65 13.76 13.87 14.08 14.14 14.15 14.17 14.16 14.54 14.33

1F 20.47 20.63 20.77 21.11 21.20 21.21 21.25 21.22 21.79 21.48

3F 1.01 1.01 1.02 1.26 1.26 1.29 1.31 1.40 1.40 1.40

1F 0.66 0.66 0.66 0.81 0.81 0.83 0.84 0.92 0.92 0.92

3F 2.97 3.05 4.06 4.06 4.06 4.06 4.07 4.06 4.08 4.08

1F 2.01 2.04 2.67 2.67 2.67 2.67 2.67 2.67 2.67 2.67

3F 4.87 4.95 4.96 4.96 4.96 4.96 4.92 4.93 4.93 4.93

1F 3.69 3.72 3.73 3.73 3.73 3.73 3.72 3.72 3.72 3.72

3F 8.16 9.19 9.20 9.20 9.20 9.17 9.17 9.17 9.34

1F 7.26 7.82 7.82 7.82 7.83 7.89 7.90 7.90 8.05

3F 4.94 4.96 4.97 4.97 4.98 4.98 4.98 4.98 4.98 4.98

1F 3.78 3.79 3.79 3.80 3.80 3.80 3.80 3.80 3.80 3.80

3F 5.18 5.20 5.18

1F 3.29 3.30 3.29

3F 3.28 3.28 3.29 3.29 3.29 3.59 3.49 3.49 3.49 3.49

1F 2.22 2.22 2.22 2.22 2.22 2.37 2.29 2.29 2.29 2.29

3F 8.12 8.13 8.20 8.20 8.25 8.26 8.34 8.30 8.39 8.38

1F 5.66 5.67 5.69 5.69 5.97 5.97 6.00 5.99 6.02 6.02

3F 10.85 10.87 10.92 10.91 13.65 13.65 13.78 13.74 13.84 13.82

1F 7.66 7.67 7.68 7.68 11.39 11.39 11.46 11.44 11.49 11.48

3F 6.50 6.50

1F 9.75 9.75

3F 12.30 12.40 12.49 12.65 12.70 12.70 12.72 12.71 13.09 12.93

1F 11.77 11.86 11.91 12.01 12.04 12.04 12.05 12.04 12.34 12.24

3F 12.87 13.38 13.46 13.46 13.80 13.80 13.78 13.75 13.82 13.79

1F 8.98 9.43 9.46 9.46 9.60 9.60 9.60 9.58 9.61 9.60

3F 2.81 2.75 2.76 2.76 2.76 2.76 2.78 2.78 2.78 2.78

1F 1.79 1.76 1.77 1.77 1.77 1.77 1.78 1.78 1.78 1.78

3F 7.75 7.76 7.93 7.93 7.94 8.05 8.08 8.08 8.08 8.08

1F 6.39 6.40 6.53 6.53 6.53 6.60 6.61 6.61 6.61 6.61

3F 5.66 5.70 5.70 5.70 5.70 5.70 5.70 5.70

1F 5.22 5.24 5.24 5.24 5.25 5.25 5.25 5.24

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Santa Fe SNF 115

Santa Flor SFL 115

Santa Gertrudis PSG 115

Santa Rosa RSO 115

Santa Sofía SNS 115

Santo Domingo, Oaxaca STD 115

Santo Domingo, Tabasco SND 115

Sarabia SRB 115

Serdán SRD 115

Shpoiná SCH 115

Simec International ATX 230

Sintesis Orgánica SIA 115

Sistema Pescados SPS 115

Sivesa SIV 115

Skytex SKY 115

Soledad de Doblado SOD 115

Soyaló SYO 115

Sureste I Fase I (Eoloeléctrica) STE-IFI 230

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 106: Catalogo 2011-2020 r010212 Corto Circuito

106

Coordinación de Planificación

ÁREA ORIENTAL

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 8.38 8.38 10.47 12.08 12.09 12.08 12.09 12.06

1F 10.58 10.58 12.73 14.27 14.27 14.26 14.27 14.25

3F 8.60 8.61 10.75 12.40 12.40 12.39 12.40 12.38

1F 10.98 10.98 13.23 14.85 14.86 14.85 14.86 14.84

3F 10.75 12.40 12.40 12.39 12.40 12.38

1F 13.23 14.85 14.86 14.85 14.86 14.84

3F 12.40 12.40 12.39 12.40 12.38

1F 14.85 14.86 14.85 14.86 14.84

3F 10.56 10.47 11.24 11.27 11.30 11.30 11.35 11.36 11.36 11.64

1F 9.88 9.88 10.34 10.37 10.39 10.39 10.47 10.47 10.47 10.89

3F 13.82 13.64 15.36 15.38 15.40 15.41 15.44 15.45 15.46 16.40

1F 15.47 15.44 16.89 16.91 16.93 16.94 17.08 17.09 17.09 18.52

3F 2.32 2.59 2.64 2.64 2.64 2.64 2.64 2.64 2.64 2.66

1F 1.68 1.90 1.91 1.91 1.91 1.91 1.92 1.92 1.92 1.93

3F 2.43 2.42 4.65 4.65 4.65 4.66 4.67 4.67 4.67 4.67

1F 1.73 1.73 3.37 3.37 3.37 3.37 3.37 3.38 3.37 3.38

3F 5.35 5.43 5.43 5.43

1F 5.85 6.04 6.05 6.04

3F 7.30 7.12 7.12 7.11

1F 9.17 9.03 9.03 9.02

3F 5.99 6.63 12.33 12.33 12.34 12.34 12.39 12.32 12.35 12.36

1F 4.32 4.60 8.96 8.96 8.96 8.94 8.97 8.94 8.95 8.95

3F 9.81 9.86 9.91 10.04 10.07 10.07 10.09 10.08 10.19 10.07

1F 7.04 7.06 7.08 7.13 7.14 7.14 7.15 7.15 7.19 7.13

3F 4.43 4.36 4.37 4.37 4.37 4.37 4.40 4.40 4.53 4.53

1F 2.90 2.87 2.87 2.87 2.87 2.87 2.89 2.89 2.95 2.95

3F 1.69 1.69 1.70 1.84 2.12 2.17 2.17 2.18 2.18 2.18

1F 1.09 1.09 1.09 1.18 1.39 1.40 1.40 1.41 1.41 1.41

3F 12.26 11.62 11.73 11.74 11.79 11.80 11.88 11.87 11.95 11.95

1F 11.21 10.80 10.87 10.87 10.90 10.91 11.12 11.11 11.16 11.16

3F 9.52 9.53 13.42 13.42 13.42 13.42 13.55 13.55 13.55 18.14

1F 8.09 8.10 10.92 10.92 10.92 10.92 11.04 11.04 10.99 17.32

3F 9.46 9.44 13.87 13.87 13.87 13.88 14.01 14.02 14.02 16.10

1F 7.89 7.88 11.27 11.27 11.27 11.27 11.38 11.38 11.31 13.46

3F 6.76 6.77 6.77 6.77 6.78 8.51 8.53 8.53 8.53 8.53

1F 6.59 6.59 6.60 6.60 6.60 7.84 7.85 7.85 7.85 7.85

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Sureste I Fase II (Eoloeléctrica) STE-IF2 230

Sureste II (Eoloeléctrica) STE-II 230

Sureste III (Eoloeléctrica) STE-III 230

Sureste IV (Eoloeléctrica) STE-IV 230

Tabasco TSP

400

230

Tabasquillo TBO 115

Tacotalpa TCT 115

Tagolaba Potencia TGP

230

115

Tajín TAJ 115

Talleres y Aceros TAL 115

Tamarindo II TDD 115

Tamazulapan TMZ 115

Tamsa II TSA 230

Tamulte TAT 115

Tamulte Switcheo TAT-SW 115

Tapachula Aeropuerto TAE 115

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 107: Catalogo 2011-2020 r010212 Corto Circuito

107

Coordinación de Planificación

ÁREA ORIENTAL

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 4.92 4.92 4.93 4.93 4.93 5.71 5.72 5.72 5.72 5.72

1F 4.14 4.14 4.15 4.15 4.15 4.55 4.56 4.56 4.56 4.56

3F 5.04 5.04 5.05 5.05 5.05 5.86 5.87 5.87 5.87 5.87

1F 4.30 4.30 4.30 4.30 4.30 4.74 4.74 4.74 4.74 4.74

3F 1.97 1.97 1.97 1.97 1.97 2.00 2.01 2.01 2.01 2.01

1F 2.24 2.24 2.24 2.24 2.24 2.27 2.27 2.27 2.27 2.27

3F 5.02 5.02 5.03 5.03 5.03 5.87 5.88 5.88 5.88 5.88

1F 4.23 4.23 4.23 4.23 4.23 4.68 4.68 4.68 4.68 4.68

3F 2.86 2.86 2.86 2.86 2.86 4.54 4.56 4.56 4.56 4.56

1F 2.96 2.96 2.96 2.96 2.96 4.39 4.40 4.40 4.40 4.40

3F 7.58 7.58 7.59 7.59 7.59 10.08 10.11 10.11 10.11 10.11

1F 8.29 8.30 8.30 8.30 8.31 10.61 10.63 10.63 10.63 10.63

3F 18.34 18.56 18.68 18.68 20.02 20.03 20.00 19.93 20.09 20.02

1F 15.12 15.27 15.33 15.33 14.89 14.89 14.88 14.85 14.92 14.89

3F 2.49 2.49 2.49 2.49 2.49 2.50 2.56 2.56 2.59 2.59

1F 1.75 1.75 1.75 1.75 1.75 1.75 1.77 1.77 1.78 1.78

3F 3.22 3.21 4.72 4.72 4.72 4.73 4.74 4.74 4.74 4.75

1F 2.34 2.34 3.46 3.46 3.46 3.46 3.47 3.47 3.47 3.48

3F 15.05 15.07 15.19 15.20 15.23 15.24 15.27 15.26 15.28 15.22

1F 12.20 12.21 12.27 12.27 12.29 12.29 12.30 12.30 12.30 12.28

3F 22.45 22.55 24.08 24.13 26.34 26.43 26.40 25.99 26.69 26.72

1F 19.56 19.61 20.72 20.79 22.48 22.51 22.58 22.29 22.72 22.74

3F 12.52 12.53 12.76 12.77 12.96 12.97 13.34 13.27 13.38 13.37

1F 12.14 12.15 12.34 12.34 12.52 12.53 12.80 12.75 12.83 12.82

3F 26.73 26.77 27.21 28.71 29.02 29.05 29.12 29.09 29.35 29.25

1F 24.00 24.02 24.34 25.52 25.78 25.79 25.88 25.78 26.03 25.98

3F 8.52 8.53 8.57 8.75 8.78 8.79 8.84 8.84 8.86 8.85

1F 5.63 5.64 5.65 5.76 5.77 5.77 5.81 5.80 5.81 5.81

3F 8.17 8.17 8.21 8.36 8.38 8.39 8.42 8.42 8.44 8.43

1F 5.40 5.40 5.41 5.49 5.50 5.50 5.52 5.52 5.53 5.52

3F 3.37 3.42 3.42 3.39 3.39 3.39 5.93 5.81 5.81 5.81

1F 2.44 2.46 2.46 2.46 2.46 2.46 6.18 6.11 6.11 6.11

3F 0.88 0.88 0.88 1.94 1.93 1.97 2.04 2.04 2.04 2.04

1F 0.60 0.61 0.61 1.28 1.27 1.29 1.31 1.31 1.31 1.31

3F 5.01 5.01 5.05 6.15 6.16 6.17 6.83 6.82 6.86 6.82

1F 3.18 3.18 3.20 3.96 3.97 3.97 4.45 4.45 4.46 4.44

Tecpan TCA 115

Tehuacán THN 115

Tecamachalco II TLD 115

Tecnológico TNL 115

Tecamachalco TML 115

Teapa, Tabasco TTB 115

Teapa, Veracruz TEA 115

Tecali TCL

400

230

115

Tarrant TRR 115

Taxco TXO 115

Tapachula Oriente TOE 115

Tapachula Potencia THP

400

115

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Tapachula I TCH 115

Tapachula Norte TNE

115

69

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 108: Catalogo 2011-2020 r010212 Corto Circuito

108

Coordinación de Planificación

ÁREA ORIENTAL

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 3.35 3.39 3.39 3.29 3.29 3.29 5.07 4.99 4.99 4.99

1F 2.42 2.43 2.44 2.43 2.43 2.43 4.79 4.75 4.75 4.75

3F 10.78 10.79 10.94 10.94 11.06 11.06 11.97 11.92 11.99 12.00

1F 9.24 9.24 9.34 9.34 9.40 9.40 10.00 9.98 10.01 10.01

3F 13.71 13.68 13.91 13.97 14.09 14.13 14.14 14.14 14.20 14.06

1F 13.83 13.81 14.04 14.08 14.16 14.20 14.21 14.21 14.25 14.12

3F 8.19 8.00 17.62 17.58 17.67 17.70 17.86 17.85 18.28 18.23

1F 9.25 9.07 17.81 17.78 17.84 17.86 17.99 17.98 18.38 18.33

3F 21.69 22.01 24.25 24.34 25.26 25.51 25.60 25.45 25.81 24.16

1F 19.19 19.37 22.05 22.10 22.64 22.79 22.86 22.75 22.97 21.38

3F 17.69 17.62 18.06 18.13 18.35 18.46 18.49 18.48 18.58 18.33

1F 19.27 19.22 19.85 19.91 20.09 20.23 20.26 20.25 20.34 20.01

3F 7.95 7.95 8.01 8.01 8.80 8.78 8.82 8.82

1F 6.14 6.14 6.17 6.17 6.67 6.66 6.67 6.67

3F 5.67 5.67

1F 4.80 4.80

3F 1.53 1.53 1.23 1.23 1.23 1.28 1.29 1.29 1.29 1.29

1F 1.08 1.08 0.85 0.85 0.85 0.88 0.88 0.88 0.88 0.88

3F 4.56 4.56 4.59 4.59 4.62 4.66 4.70 4.69 4.70 4.70

1F 3.01 3.01 3.03 3.03 3.05 3.07 3.08 3.08 3.09 3.09

3F 6.61 6.62 6.64 10.52 10.57 10.57 10.58 10.57 10.61 10.58

1F 4.33 4.33 4.34 6.89 6.90 6.90 6.91 6.88 6.92 6.91

3F 4.94 4.94 4.96 5.09 5.11 5.12 5.12 5.13 5.13 5.13

1F 3.14 3.14 3.14 3.22 3.23 3.23 3.23 3.24 3.24 3.24

3F 6.29 7.47 11.27 11.27 11.28 11.28 11.31 11.27 11.29 11.29

1F 4.88 5.50 8.25 8.25 8.25 8.24 8.26 8.24 8.25 8.25

3F 7.86 7.89 7.89

1F 5.51 5.52 5.52

3F 6.61 6.69 7.04 7.03 7.24 7.24 7.25 7.24 7.34 7.34

1F 6.00 6.03 6.24 6.23 6.42 6.42 6.42 6.42 6.47 6.47

3F 4.07 4.09 4.16 4.15 4.19 4.19 4.19 4.19 4.21 4.21

1F 4.43 4.44 4.49 4.49 4.53 4.53 4.54 4.53 4.55 4.55

3F 6.22 6.30 6.63 6.63 6.81 6.81 6.81 6.81 6.89 6.89

1F 5.42 5.44 5.64 5.64 5.78 5.78 5.78 5.78 5.82 5.82

3F 12.29 12.30 12.50 12.50 12.66 12.66 14.16 14.09 14.19 14.20

1F 11.12 11.12 11.26 11.26 11.35 11.35 12.68 12.65 12.70 12.70

Teziutlán II TZD 115

Tezoyuca TEZ 115

Tepoztlán II TPZ 115

Teziutlán TZT

115

69

Tepeji de Rodriguez TPI 115

Tepeyac TPY 115

Tepalcingo TPL 115

Tepeaca TPE 115

Temixco TIX

115

85

Tenosique TNQ 115

Temascal I TMU

230

115

Temascal II TMD

400

230

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Tehuantepec THT 115

Tejalpa TJA 115

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 109: Catalogo 2011-2020 r010212 Corto Circuito

109

Coordinación de Planificación

ÁREA ORIENTAL

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 3.67 3.60 4.35 4.34 4.34 4.35 4.39 4.39 4.40 4.40

1F 2.57 2.53 2.82 2.81 2.81 2.81 2.84 2.84 2.84 2.84

3F 3.53 3.54 3.55 3.58 3.57 3.58 3.90 3.90 3.92 3.92

1F 2.59 2.58 2.58 2.60 2.59 2.60 2.70 2.70 2.71 2.71

3F 6.87 7.13 8.47 8.47 8.48 8.51 8.53 8.50 8.51 8.51

1F 6.70 6.89 8.55 8.55 8.55 8.31 8.31 8.30 8.30 8.30

3F 1.71 1.72 1.93 1.93 1.93 1.99 1.99 1.99 1.99

1F 1.07 1.07 1.21 1.21 1.21 1.24 1.24 1.24 1.24

3F 0.69 0.77 0.78 0.80 0.80 0.80 0.80 0.80 0.80 0.80

1F 0.60 0.71 0.71 0.73 0.73 0.74 0.74 0.74 0.74 0.74

3F 2.87 2.85 2.87 2.91 2.93 3.16 3.16 3.18 3.18 3.18

1F 2.25 2.24 2.25 2.27 2.28 2.37 2.37 2.38 2.38 2.38

3F 3.00 3.00 3.00 3.00 3.01 3.01 3.02 3.02

1F 1.98 1.98 1.98 1.98 1.98 1.98 1.99 1.99

3F 3.10 3.10 3.10 3.11 3.21 3.20 3.45 3.45

1F 2.25 2.26 2.26 2.26 2.29 2.29 2.62 2.62

3F 4.58 4.58 4.60 4.81 4.82 4.82 4.93 4.92 4.94 4.93

1F 2.88 2.88 2.88 3.02 3.03 3.03 3.09 3.09 3.10 3.09

3F 6.41 6.41 6.45 6.45 13.96 13.90 13.99 14.00

1F 4.70 4.70 4.71 4.71 12.87 12.84 12.89 12.89

3F 4.04 4.04

1F 3.06 3.06

3F 1.20 1.20 1.20 1.20 1.20 1.20 1.22 1.22 1.22 1.22

1F 0.84 0.92 0.84 0.84 0.84 0.84 0.85 0.85 0.85 0.85

3F 4.56 4.61 4.95 4.94 4.96 4.96 4.97 4.96 5.03 5.03

1F 3.60 3.63 3.81 3.81 3.82 3.82 3.82 3.82 3.85 3.85

3F 1.38 1.38 1.38 1.39 1.38 1.39 1.41 1.41 1.41 1.41

1F 0.98 1.09 0.98 0.98 0.98 0.98 0.99 0.99 0.99 0.99

3F 1.07 1.07 1.07 1.14 1.29 1.32 1.32 1.32 1.32 1.32

1F 0.74 0.74 0.74 0.78 0.91 0.92 0.92 0.92 0.92 0.92

3F 1.57 1.57 1.57 1.57 1.57 1.58 1.58 1.58 1.58 1.58

1F 0.99 0.99 0.99 0.99 0.99 1.00 1.00 1.00 1.00 1.00

3F 14.71 14.74 14.82 14.95 12.56 12.56 13.01 14.11 14.16 14.13

1F 9.85 9.86 9.89 9.97 8.10 8.10 8.44 9.23 9.25 9.24

3F 27.90 28.10 28.28 28.31 28.36 28.37 28.78 28.24 28.50 28.52

1F 29.02 29.18 29.38 29.40 29.44 29.37 29.69 29.28 29.46 29.48

Tonantzintla TNZ 115

Tres Estrellas TTE 400

Tlaxiaco TXI 115

Tonalá TNA 115

Tlapacoyan TLY 115

Tlatlahuquitepec TUQ 115

Tlaltizapan TLZ

115

85

Tlapa TAN 115

Tlacotepec, Guerrero TLC 115

Tlacotepec, Puebla TTP 115

Tlacolula TLA 115

Tlacotalpan TLT 115

Tihuatlán II THD 115

Tilapa TIL

115

69

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Tierra Blanca TBL 115

Tierra Colorada TIE 115

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 110: Catalogo 2011-2020 r010212 Corto Circuito

110

Coordinación de Planificación

ÁREA ORIENTAL

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 4.68 5.49 5.89 5.89 5.90 5.90 5.89 5.89 5.89 5.99

1F 3.39 4.19 4.49 4.49 4.49 4.49 4.48 4.48 4.48 4.52

3F 3.63 3.70 4.04 4.04 4.04 4.05 4.05 4.05 4.05 4.05

1F 2.76 2.79 3.03 3.03 3.03 3.00 3.00 3.00 3.00 3.00

3F 22.78 22.85 22.88 22.88 22.93 22.94 22.99 22.81 23.02 23.03

1F 25.67 25.73 25.76 25.77 25.81 25.80 25.85 25.69 25.87 25.88

3F 10.75 10.82 10.89 11.00 11.04 11.04 11.06 11.04 11.32 11.21

1F 9.40 9.45 9.48 9.54 9.56 9.56 9.56 9.56 9.73 9.67

3F 5.16 5.08 7.87 7.87 7.89 7.92 7.94 7.94 7.98 7.96

1F 3.93 3.90 5.36 5.36 5.37 5.38 5.39 5.39 5.40 5.40

3F 4.59 4.53 6.99 6.99 7.00 7.02 7.04 7.04 7.07 7.06

1F 3.34 3.31 4.67 4.67 4.67 4.68 4.69 4.69 4.70 4.70

3F 11.70 11.66 11.70 11.70 11.71 11.79 11.84 11.84 11.85 11.84

1F 9.43 9.37 9.39 9.39 9.39 9.43 9.45 9.45 9.45 9.45

3F 9.81 9.47 9.49 9.49 9.49 9.63 9.67 9.67 9.67 9.66

1F 7.42 7.12 7.13 7.13 7.13 7.19 7.20 7.20 7.20 7.20

3F 11.86 11.75 11.79 11.79 11.79 11.90 11.96 11.96 11.96 11.95

1F 9.54 9.43 9.44 9.44 9.44 9.49 9.52 9.52 9.52 9.52

3F 14.86 14.77 14.83 14.84 14.84 14.89 14.98 14.98 14.98 14.97

1F 13.07 12.97 13.00 13.00 13.01 12.86 12.90 12.90 12.91 12.90

3F 11.29 11.30 11.36 11.37 11.39 11.39 11.41 11.40 11.41 11.38

1F 8.72 8.72 8.75 8.75 8.76 8.76 8.77 8.76 8.77 8.75

3F 8.48 8.48 8.48 8.49 8.49 8.49 8.48

1F 9.55 9.56 9.56 9.56 9.56 9.56 9.56

3F 6.08 6.08 6.10 6.10 6.11 6.11 6.11 6.11 6.12 6.11

1F 4.07 4.07 4.08 4.08 4.08 4.08 4.08 4.08 4.08 4.08

3F 3.00 2.98 3.35 3.36 3.37 3.44 3.44 3.44 3.45 3.45

1F 2.02 2.02 2.17 2.17 2.17 2.21 2.21 2.21 2.21 2.21

3F 7.51 7.51 7.54 7.60 7.44 7.44 7.48 7.56 7.58 7.57

1F 4.83 4.83 4.84 4.87 4.76 4.76 4.78 4.83 4.84 4.84

3F 1.28 1.29 1.36 1.36 1.36 1.36 1.36 1.36 1.36 1.36

1F 0.85 0.85 0.88 0.88 0.88 0.88 0.88 0.88 0.89 0.89

3F 6.12 6.12 6.13 6.13 6.14 6.13 7.18 7.18

1F 5.78 5.78 5.79 5.79 5.80 5.79 6.56 6.56

3F 12.31 9.27 9.55 9.53 9.55 9.55 13.43 13.42 13.48 13.48

1F 10.49 6.73 6.84 6.84 6.84 6.84 12.24 12.24 12.27 12.27

Veintiuno de Marzo VDM 115

Veracruz I VRU 115

Valsequillo VSE 115

Vega de Alatorre VDA 115

Uxpanapa I UXU 115

Valle Nacional VAN 115

Unión Carbide UCT 115

Unión Fenosa UFG 115

Tuxtla Gutiérrez Norte TXN 115

Tuxtla Gutiérrez Sur TXS 115

Tuxtla Gutiérrez I TGU 115

Tuxtla Gutiérrez II TGD 115

Tuxtepec II TXD 115

Tuxtepec III TXT 115

Tuxpan Vapor TUV 400

Tuxpango TPG 115

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Tulipán TLN 115

Tuxpan II TUD 115

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 111: Catalogo 2011-2020 r010212 Corto Circuito

111

Coordinación de Planificación

ÁREA ORIENTAL

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 14.64 13.16 13.35 13.34 13.41 13.42 13.79 13.76 13.88 13.88

1F 19.45 17.01 17.23 17.21 17.29 17.30 18.60 18.57 18.71 18.72

3F 23.45 19.70 20.09 20.05 20.12 20.13 21.27 21.24 21.41 21.41

1F 23.96 20.12 20.39 20.35 20.40 20.41 23.00 22.98 23.12 23.12

3F 12.44 12.46 12.53 12.52 12.98 12.98 13.07 13.03 13.13 13.12

1F 9.60 9.61 9.64 9.63 10.26 10.26 10.31 10.29 10.33 10.33

3F 1.47 1.47 1.47 1.47 1.47 1.50 1.50 1.50 1.50 1.50

1F 0.94 0.94 0.94 0.94 0.94 0.96 0.96 0.96 0.96 0.96

3F 8.29 8.31 10.38 10.38 10.38 10.39 10.49 10.49 10.49 10.91

1F 6.37 6.40 7.51 7.51 7.51 7.51 7.58 7.58 7.56 7.91

3F 9.00 9.03 10.27 10.27 10.27 10.28 10.32 10.32 10.32 10.42

1F 7.38 7.42 7.99 7.99 7.99 7.99 8.48 8.48 8.48 8.58

3F 11.48 11.48 13.45 13.45 13.46 13.46 13.56 13.56 13.57 13.62

1F 9.85 9.87 10.87 10.87 10.87 10.87 11.48 11.49 11.49 11.56

3F 8.98 9.14 10.65 10.65 10.66 10.67 10.36 10.37 10.37 10.60

1F 8.66 8.89 9.91 9.91 9.91 9.92 10.14 10.15 10.15 10.69

3F 13.30 13.41 16.47 16.47 16.48 16.49 16.40 16.40 16.40 16.94

1F 14.87 15.04 17.71 17.71 17.72 17.72 18.09 18.09 18.09 18.95

3F 9.94 9.99 12.51 12.51 12.51 12.51 12.66 12.66 12.66 18.23

1F 8.57 8.62 10.22 10.22 10.23 10.23 10.38 10.38 10.37 19.04

3F 9.22 9.23 9.27 9.28 9.29 9.30 9.30 9.30 9.31 9.28

1F 6.49 6.49 6.51 6.51 6.51 6.52 6.52 6.52 6.52 6.51

3F 42.67 42.94 43.57 43.63 44.17 44.21 44.21 44.02 44.54 44.10

1F 39.34 39.52 39.90 39.94 40.29 40.31 40.38 40.13 40.58 40.31

3F 19.93 19.95 20.15 20.26 20.42 20.43 20.43 20.38 20.50 20.37

1F 14.51 14.52 14.61 14.66 14.73 14.73 14.76 13.95 14.78 14.73

3F 5.01 5.01 5.01 4.56 4.57 4.57 4.57

1F 3.96 3.96 3.96 3.53 3.53 3.53 3.53

3F 6.82 6.80 6.83 6.83 8.32 8.33 8.36 8.35 8.39 8.38

1F 4.61 4.59 4.60 4.60 5.76 5.76 5.77 5.77 5.78 5.78

3F 16.31 16.33 16.45 16.45 17.33 17.34 17.50 17.43 17.60 17.58

1F 13.74 13.74 13.80 13.80 15.20 15.20 15.30 15.26 15.36 15.34

3F 4.29 4.29 4.31 4.31 5.15 5.14 5.16 5.16

1F 2.94 2.94 2.94 2.94 3.50 3.50 3.50 3.50

3F 3.36 3.36

1F 2.44 2.44

Vetrotex VET 115

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Veracruz II VRD

230

115

Villaflores VFD 115

Villahermosa Centro VHC 115

Villahermosa I VIU 115

Villahermosa II VID 115

Villahermosa Norte VHN

230

115

Villahermosa Poniente VIP 115

Vistamar VIS 115

Volkswagen VWG 115

Warner Lambert CSM 115

Xadani XDN 115

Xochicalco XOC

115

85

Xalostoc XAL 115

Xicotencatl XIT 115

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 112: Catalogo 2011-2020 r010212 Corto Circuito

112

Coordinación de Planificación

ÁREA ORIENTAL

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 21.28 21.54 21.70 21.72 21.91 21.92 21.69 21.63 21.77 21.67

1F 14.56 14.74 14.80 14.80 14.87 14.87 14.73 14.70 14.76 14.73

3F 7.63 7.60

1F 5.81 5.80

3F 4.73 4.73

1F 4.27 4.27

3F 4.83 4.83

1F 4.51 4.51

3F 4.77 4.77

1F 4.43 4.43

3F 4.85 4.85

1F 4.34 4.34

3F 21.81 21.91 25.69 25.65 29.80 29.83 29.82 28.83 30.22 30.31

1F 19.44 19.49 24.11 24.09 27.83 27.60 27.98 27.37 28.26 28.31

3F 19.09 19.13 20.25 20.24 21.16 21.17 21.39 21.09 21.52 21.54

1F 20.54 20.57 22.02 22.02 22.97 22.94 23.35 23.11 23.46 23.48

3F 18.61 18.63 19.27 19.27 19.80 19.81 20.45 20.31 20.50 20.52

1F 17.63 17.65 18.50 18.49 19.01 18.98 19.54 19.45 19.57 19.58

3F 1.75 1.74 1.75 1.94 2.43 2.52 2.52 2.53 2.53 2.53

1F 1.16 1.16 1.16 1.29 1.71 1.74 1.74 1.74 1.74 1.74

3F 2.32 2.33 2.35 2.35 2.41 2.41 2.41 2.41 2.41 2.41

1F 1.86 1.86 1.87 1.86 1.91 1.91 1.91 1.91 1.92 1.92

3F 1.93 1.90 1.91 1.91 2.08 2.08 2.08 2.08 2.08 2.08

1F 1.26 1.23 1.23 1.23 1.33 1.33 1.33 1.33 1.33 1.33

3F 2.55 2.56 2.56 2.56 2.56 2.57 2.56 2.56 2.56 2.56

1F 1.66 1.66 1.66 1.66 1.66 1.67 1.66 1.67 1.67 1.67

3F 15.68 15.70 16.33 16.34 16.81 16.82 17.21 17.01 17.31 17.32

1F 14.55 14.56 15.05 15.06 15.37 15.37 16.58 16.46 16.65 16.66

3F 15.73 15.74 16.08 16.08 16.34 16.34 18.41 18.30 18.47 18.48

1F 17.29 17.30 17.62 17.62 17.84 17.84 20.17 20.07 20.21 20.22

3F 7.67 7.67 7.72 7.72 7.76 7.76 7.79 7.78 7.80 7.80

1F 7.57 7.57 7.61 7.62 7.64 7.64 7.75 7.74 7.75 7.75

3F 5.55 5.53 5.63 5.63 5.63 7.08 7.13 7.16 7.16 7.17

1F 6.44 6.43 6.52 6.52 6.52 8.63 8.68 8.71 8.71 8.72

3F 3.85 3.84 3.88 3.88 3.88 4.53 4.54 4.56 4.56 4.56

1F 3.48 3.47 3.50 3.50 3.50 4.02 4.03 4.04 4.04 4.04

Zapata II ZPD 115

Zapata Poniente EZA 115

Zanatepec ZNT 115

Zapata ZAP

230

115

85

Zacapoaxtla ZXP 115

Zacatepec ZTP 115

Yucudaa YUC 115

Xúchiles CH 4 XCH-G4 115

Xúchiles CH 5 XCH-G5 115

Yautepec Potencia YTP

400

230

115

Xúchiles CH 2 XCH-G2 115

Xúchiles CH 3 XCH-G3 115

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Xoxtla XOX 115

Xúchiles CH 1 XCH-G1 115

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 113: Catalogo 2011-2020 r010212 Corto Circuito

113

Coordinación de Planificación

ÁREA ORIENTAL

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 4.06 4.38 4.44 4.68 4.63 5.72 5.86 5.87 5.87 5.87

1F 3.60 3.87 3.91 4.05 4.00 4.80 4.86 4.87 4.86 4.86

3F 4.16 4.23 4.28 4.69 4.63 5.66 5.81 5.82 5.82 5.82

1F 3.61 3.68 3.71 3.98 3.94 4.66 4.73 4.73 4.73 4.73

3F 2.66 2.66 2.67 3.23 3.23 3.23 3.39 3.39 3.40 3.39

1F 1.66 1.67 1.67 2.04 2.04 2.04 2.14 2.14 2.14 2.14

3F 0.85

1F 0.80

3F 13.35 13.38 13.57 13.55 13.72 13.72 13.94 13.84 14.09 14.07

1F 10.39 10.40 10.48 10.47 11.46 11.46 11.59 11.54 11.66 11.65

3F 17.19 17.21 17.35 17.35 18.23 18.24 18.42 18.34 18.53 18.51

1F 14.90 14.91 14.98 14.98 16.55 16.55 16.67 16.62 16.73 16.72

3F 4.31 4.30 4.40 4.42 4.42 4.42 4.42 4.42 5.11 5.11

1F 2.86 2.86 2.89 2.89 2.89 2.89 2.89 2.89 3.66 3.66Zongolica ZGL 115

Zinacatepec ZIP

115

69

Zocac ZOC

230

115

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Zihuatanejo I ZIH 115

Zihuatanejo II ZHD 115

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____

Page 114: Catalogo 2011-2020 r010212 Corto Circuito

114

Coordinación de Planificación

ÁREA OCCIDENTAL

ÁREAOCCIDENTAL

ESTUDIO DE CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

______________Catálogo de Corto Circuito 2011-2020 _______Catálogo de Corto Circuito 2011-2020_____

Page 115: Catalogo 2011-2020 r010212 Corto Circuito

115

Coordinación de PlanificaciónRED ELÉCTRICA PRINCIPAL 2011

ÁREA OCCIDENTAL

14.1

-1113

85.4-900

90.4-79588.2-900+5-1113

2X375 MW

74-1

113

50-1

113

25-900+4-111327.4-1113

11.3-900+1.8-1113

56-9

00+13-1

113

Tesistán

Aguamilpa

El Cajón

Tepic II

La Yesca

A Mazatlán II

Ixtlahuacán

Acatlán

Atequiza

Zapotlanejo

Colima II

Melaque

P.V. Manzanillo

Carapan

Héroes deCarranza

A Jilotepec

Dañu

General Motors

Peñasquito

Cañada

Primero de Mayo

El Salero

CruzAzul

AguascalientesPotencia

QuerétaroPotencia

Maniobras

206.5-1113

74.8

-1113

43-111395-1113

5-3x1113

44-1113

88-3x1113

54-1113

A Topilejo

22-1113

28-1113

20-1113

(Área Noroeste )

(Área Central )

83.4

-900

49.4

-1113

60 MVAR

91-9

00

207-1

113

85-900

Zona Guadalajara

Zona Aguascalientes

59-1113+4-477

5.2-

900

6-1113

La Manga

120-900

24-900

Juando

Troncal evolutivo 01-03-2011 MAGD

254-1

113

177-

1113

3X320 MW

2X375 MVA 400/230kV

2X100 MVA 230/115kV

106.5

-900

2X375 MVA 400/230kV

2X100 MVA 230/115kV

2X100 MVA 230/115kV

Op. Inic.115kV

3X300 MW

1X225 MVA 400/230kV

107-1

113

46-9

00+

3.1

-1113

49-1113 21.6-1113

148.6-1113

143-900+3.1-1113

146-1113

186-1

113

64.9-900

178-1

113

96-9

00

78-900

60-900

76-900

10-1113

3.8-900

107-1113

239-1

113

115.6-

1113

110-

900

74-900+1-1113

235-900

68-1

113

60-795

71.3-900

275-3

x1113

233-1113

66-9

00

119.4-1113

10.6-795+

20-1113

20-1

113

18-1113

25-795+

5-1113

55.8

-795+3-9

00

30-7

95

51-1113

20-79520-900

13.6

-900

33-795+7-900

40-795

50-1113

63-3x1113

17-795

10-795+7-900

39-795

27-1113

31-3x1113

140.22-1113

149.7-1113

148.4-795

143.9-900

121-7

95+

7-1

113

218.1

-1113

220.8

-1113

35-900

35-1113

39-1113

8-900+13.1-1113

17.8-900+0.3-1113

77.7

-900+

1-1

113

99-7

95

4.5-795+2-1113

88.7

-1113

78-7

95+

1-1

113

37-9

00+

4.6

-1113

34-9

00+

2.6

-1113

17.5-900

23.5-900

23.6-1113

24-3x1113

21.4

-900

196.8-3x1113

127.8-1113

125-3x1113+0.9-1113

25-900 38-900+2.3-1113

13.5-900

82-1

113

258-3x1113

62 MVAR

25 MVAR

2 x 50 MVAR

75 MVAR

2 x 75 MVAR

75 MVAR

50 MVAR

2x100 MVAR

100 MVAR

25 MVAR

50 MVAR

50 MVAR

223-1

113

50 MVAR

2 X50 MVAR

50 MVAR

2011

INFORMACIÓN RESERVADA DE ACUERDO

CON LA LEY FEDERAL DE TRANSPARENCIA Y

ACCESO A LA INFORMACIÓN PÚBLICA

GUBERNAMENTAL

150 MVAR

2 x 75 MVAR

150 MVAR

45-1113

3-1113

37.3

-1113

109.2-1113

2 x 50 MVAR

175.2

-1113

1X760 MW

30-1113

46-1

113

211.5-1113

20-900+

14.6-1113

30-900+

4-1113

2 x 75 MVAR

20.4-900+

24.5-1113

30-900+

13.1-1113

9-900+25-1113

20-795+3-900

Zona Lázaro Cárdenas

Zona Guadalajara

Zona Aguascalientes

Cañada2 X375 MVA 400/230 kV

121-7

95+

7-1

113

50-1

113

8.3

-795+

7-1

113

218.

1-11

13

220.8-1

113

140.22-1113

149.7

-1113

148.4-795

143.

9-90

0

174.8-

1113 5

4-1

113

185-1

113

119.4

-1113

88.2

-900+

5-1

113

90.4

-795

39-900

11-900

17.5

4-7

95

16.6

-900

27-9

00

A El Potosí

A El P

otosí

A San Luis I

A Villa de

Reyes

A Ixtlahuacá

n

A S

an J

uan

de los L

agos

A Z

apotl

anejo

A P

otr

erillo

s

A L

eón

III

A Prim

ero d

e

Mayo

A C

ru

z A

zu

l

A C

ale

ra II

-90 MVAR300 MVAR

50 MVAR

50 MVAR

1 X375 MVA 400/115kV150 MVAR

2 X60 MVA230/23 kV

2 X60 MVA230/23 kV

1 X100 MVA230/69 kV

1 X60 MVA 230/23 kV

2 X100 MVA230/69 kV

1 X375 MVA 400/230 kV

2 X60 MVA 230/23 kV

1 X100 MVA 230/69 kV

2 X60 MVA230/23 kV

2X125 MVA 230/69kV

2 X60 MVA 230/23 kV

1X60 MVA 230/23kV

2 X60 MVA 230/23 kV

1 X225 MVA 230/69 kV

49.9-900

36-1113

33-900

33-900

6.9-900

22-9

00+

6-1

113

24-9

00

6-1113

44-9

00

49-900

18.5

-900

3-90

0

27-900

3.5

-900+

9-1

113

16.6-1113

19-9

00+

16.7

-1113

19-9

00+

9-1

113

4.7-1113

5-1

113

29-397

43-900

ZapotlanejoGuadalajara Norte

Agua Prieta

Guadalajara Oriente

Niños Héroes

Zapopan

Ixtlahuacán

Álamos

San Martín

Colón

Guadalajara I

Side. Guad.

60.4-1

113

148.6-1113

143-900+3-1113

146-1113

A Cerro Blanco

A La Yesca

178-1

113

96-9

00

A M

azam

itla

A C

d.

Gu

zm

án

A M

an

zan

illo

38-1

113

211.5-1113

64.9-900

186-

1113

A Salamanca II

A Ocotlán

2 X120 MW

50-1113

109.2-1113175.2-1113

32.2-1113

A Aguascalientes

Potencia

Pote

ncia

A A

guasca

liente

s

197-

1113

85-9

00

A M

anzanillo

AzulAgua

16-1113

56.8-900

17.8

-795

11.6-900

50-900

21.5

-795

17-900

275-3

x1113

46-1

113239-1

113

Nks

Sicartsa II

Fertimex

Sicartsa I

A Pitirera

A C

arap

an

A D

onato

Guerr

a

A P

itir

era

A Ixta

pa Pote

ncia

74.8

-111

3

Zona Lázaro Cárdenas

Vallarta Potencia3X100 MVA 230/115kV

AguascalientesOriente

1 X225 MVA 230/115 kV1 X125 MVA230/115 kV

Aguas. I

AguascalientesPotencia

2X300 MVA 400/230kV1X375 MVA 400/115kV

2 X300 MVA 400/230 kV

1X 100 MVA 230/69 kV

1X 375 MVA 400/69 kV

Tesistán

3.5-900+0.2-1113

1 X60 MVA230/23 kV

Tuzania

2X300 MVA 400/230kV2X100 MVA 230/69kV

Acatlán

-200 MVAR

60 MVAR

60 MVAR

2 X60 MVA 230/161 kV

2 X100 MVA 230/69 kV

Guadalajara II

2X300MVA400/230kV

Atequiza

71.3-9

00A Ixta

pa

Potencia

1X100MVA230/115kV

4x80 MW La Villita

Carboeléctricadel Pacífico

1X678MW

Colomo2X100 MVA 230/115kV

P.V. Manzanillo II

2X350 MW

Cd.Guzmán2X100 MVA 230/115kV

60MVAR

Mazamitla(Switcheo)

UruapanPotencia

1X100 MVA 230/115kV

1X100 MVA 230/161kV

Pitirera4X200 MW2X180 MVA400/230kV

963.53 MVAR40%, 40% Y 50%

450 MVAR -450 MVAR

DonatoGuerra

(Área Central )

AgustínMillán

(Área Central )

A Volcán Gordo(Área Central )

Almoloya(Área Central )

Zimapán

1X100 MVA

230/115kV

2X146 MW

San Juan del Río II1X225 MVA230/115kV

Morelia Potencia2X100 MVA 230/115kV

AtlacomulcoPotencia(Área Central )

QuerétaroPotencia

2X375 MVA 400/230kV

1X225 MVA 230/115kV

Santa María

1X375 MVA

400/115kV

Celaya III2X100 MVA 230/115kV

Potrerillos1X375 MVA 400/230kV

Silao II2X100 MVA 230/115kV

León II2X100 MVA 230/115kV

León IV1X225 MVA 230/115kV

León III2X100 MVA 230/115kV

1X225 MVA

230/115kV

San Juan de los Lagos

Charcas Potencia1X100 MVA 230/115kV

A Ramos Arizpe Potencia

(Área Noreste )

Moctezuma Potencia

El Potosí2X375 MVA 400/230kV1X375 MVA 400/115kV

San Luis I2X100 MVA 230/115kV La Pila

1X225 MVA 230/115kV

-70 MVAR200 MVAR

San Luis II2X100 MVA 230/115kV

Calera II2X100 MVA 230/115kV

Fresnillo1X225 MVA 230/115kV

Zacatecas II2X100 MVA 230/115kV

22.4-900+1.8-1113

19.9-795+19.3-900

Abasolo II2X100 MVA230/115kV

P.V. Salamanca

Irapuato II2X100 MVA 230/115kV

Celaya II2X100 MVA 230/115kV

Qro. I1X100 MVA230/115 kV

Conin1X225 MVA 230/115kV

19-900+2.3-1113

Nopala(Área Central )

San Bernabe(Área Central )

A Las Mesas

(Área Noreste )

Santa Fe1X225 MVA

230/115kV

Las Delicias592 MW

San Luis de la Paz II

2X100 MVA 230/115kV

Tula(Área Central )

(Área Central )A Hil

A Pie de la Cuesta

(Área Oriental )

Ixtapa Potencia

1X100 MVA 161/115kV

Apatzingán

Zamora1X100 MVA 230/115kV

Ocotlán2X100 MVA 230/115kV

A Anáhuac Potencia(Área Noreste )

6X350MW

C.T. Petacalco

Lázaro CárdenasPotencia

3X375 MVA 400/230kV

2X100 MVA 230/115kV

40-1113 23.5-795

17.5-900

Cerro Blanco

Subdirección de Programación

Coordinación de Planificación

Subgerencia de Programación de Redes Eléctricas

Red Eléctrica Principal

Área Occidental

Jalisco

Zacatecas

Jalisco

Zacatecas

Jalisco

Jalisco

Colima

Jalisco

Colima

Micho

acánC

olim

a

Micho

acánJa

lisco

Gua

najuato

Jalis

co

Aguascalientes

Zacatecas

Micho

acán

Gue

rrero

Mic

hoacán

Est

ado d

e M

éxico

MichoacánGuanajuato

Michoacán

Querétaro

San

Luis Potosí

Querétaro

Querétaro

HidalgoQue

réta

roGuana

juat

o

Jalisco

Guanaju

ato

Jalisco

Zacatecas

San Luis Potosí

Guanajuato

Sonora

Sin

alo

a

Est

ado d

e M

éxico

More

los

San

Luis P

otos

í

Zaca

teca

s

AguascalientesJalisco

Zacate

cas

Sonora

Nayarit

Nayarit

Nayarit

Jalisco

Nayarit

San Luis Potosí

Tamaulipas

D.F.

50 MVAR

44-9

00

251-1

113

3X100 MVA230/69 kV

Op. Inic.115kV

2X100 MVA 230/115 kV

Op. Inic.230kV

Op. Inic.230kV

2X 21 MVAR

Op. In

ic.23

0kV

Op. Inic.

161k

V

30-1

113

3.5-900+2-1113

1X225 MVA230/115 kV

10.5-1113

14.2-1113

Manzanillo I (SF6)

0.9-1113

0.8-1113

207.2-900

A Jerónimo Ortíz(Área Norte)

2X100 MVA 230/115kV

2X300 MVA 400/230kV

1x300 MW1X250 MW

Villa de Reyes2x350 MW

1X100 MVA 230/115kV

El Sauz220 MW 1X122 MW

2X100 MVA 230/115kV

1X128 MW 1X129 MW

Los Azufres194.5 MW

37.2-1113+9.4-795

Tapeixtles2X225 MVA 400/230kV1X375 MVA 400/115kV

Tecomán

Op. In

ic.115kV

A Z

acate

cas I

I

91-9

00

75 MVAR

34-1

113

Océano Pacífico

19-795

21-900

26.1-1113

Salamanca II225 MVA 400/115 kV

Las Fresas1X375 MVA 400/115 kV

100 MVA 230/115 kV

S i m b o l o g í a

400 kV

Ciclo Combinado

Geotermoeléctrica

Hidroeléctrica

Térmica Convencional

Dual

Carboeléctrica

Nivel de Tensión

230 kV

115 kV

161 kV, 69 kV y media tensión

Subestación

Línea de Transmisión

Reactor

Compensador Estático de Vars

Estructura de Doble CircuitoTendido del Primero

Nuevos proyectos

Retiros o traslados

75 MVAR

75 MVAR

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 116: Catalogo 2011-2020 r010212 Corto Circuito

116

Coordinación de PlanificaciónRED ELÉCTRICA PRINCIPAL 2020

ÁREA OCCIDENTAL

60 MVAR

207-1

113

178-1

113

60MVAR

75 MVAR

177-1

113

177-1

113

85-900

53-900

54-1113

14.1

-1113

16.5-900+10.2-1113

1X225 MVA

230/115kV

14-1

113

125-9

00+

1-1

113

85.4-900

90.4-795

27.5

-900

+7.8

-1113

61.5-900+

2.8-1113

2X375 MW

74-1

113

50-1

113

25-900+4-111327.4-1113

11.3-900+1.8-1113

31-9

00+0.1

-1113

138.2-900

NuevoVallarta

Tesistán

Aguamilpa

El Cajón

Tepic II

La Yesca

A Mazatlán II

Ixtlahuacán

Acatlán

Atequiza

Zapotlanejo

Colima II

Melaque

Carapan

Héroes deCarranza

A Jilotepec

Dañu

General Motors

Peñasquito

Cañada

Primero de Mayo

El Salero

CruzAzul

AguascalientesPotencia

QuerétaroPotencia

Maniobras

206.5-1113

74.8-1113

43-111395-1113

5-3x1113

44-1113

88-3x1113

54-1113

A Topilejo

22-1113

28-1113

20-1113

(Área Noroeste )

(Área Central )

34-9

00 +

0.5

-1113

67.4

-1113

49.4

-900 +

0.5

-1113

83.4-900+16-1113

2-900+16-1

113

Zona Guadalajara

Zona Aguascalientes

59-1113+4-477

5.2-

900

6-1113

La Manga

120-900

24-900

Juando

Troncal evolutivo 01-03-2011 MAGD

254-1

113

177-

1113

60-1

113

52-3

x1113

3X320 MW

2X375 MVA 400/230kV

3X100 MVA 230/115kV

90.5

-900+10.2

-1113

2X375 MVA 400/230kV

2X100 MVA 230/115kV

2X100 MVA 230/115kV

Op. Inic.115kV

107-1

113

46-9

00+

3.1

-1113

49-1113 21.6-1113

148.6-1113

143-900+3.1-1113

146-1113

186-1

113

178-1

113

96-9

00

78-900

60-900

76-900

3.8-900

107-1113

244-1

113

115.6-

1113

110-

900

74-900+1-1113

110-900+1-1113

32.7-1113

68-1

113

60-795

71.3-900

275-3

x1113

233-1113

66-9

00

119.4-1113

10.6-795+

20-1113

20-1

113

18-1113

25-795+

5-1113

55.8

-795+3-9

00

30-7

95

51-1113

26.1-1113

18-79518-900

13.6

-900

33-795+7-900

40-795

50-1113

63-3x1113

17-795

10-795+7-900

39-795

27-1113

31-3x1113

140.22-1113

149.7-1113

148.4-795

143.9-900

121-7

95+

7-1

113

218.1

-1113

220.8

-1113

35-900

35-1113

39-1113

8-900+13.1-1113

17.8-900+0.3-1113

77.7

-900+

1-1

113

99-7

95

5-1113-2C/F

88.7

-1113

78-7

95+

1-1

113

37-9

00+

4.6

-1113

34-9

00+

2.6

-1113

17.5-900

23.5-900

23.6-1113

24-3x1113

21.4

-900

196.8-3x1113

127.8-1113

125-3x1113+0.9-1113

25-900 38-900+2.3-1113

13.5-900

82-1

113

230-3x1113

62 MVAR

25 MVAR

2 x 50 MVAR

75 MVAR

2 x 75 MVAR

75 MVAR

50 MVAR

2x100 MVAR

100 MVAR

25 MVAR

50 MVAR

50 MVAR

223-1

113

75 MVAR

50 MVAR

2 X50 MVAR

50 MVAR

2020

INFORMACIÓN RESERVADA DE ACUERDO

CON LA LEY FEDERAL DE TRANSPARENCIA Y

ACCESO A LA INFORMACIÓN PÚBLICA

GUBERNAMENTAL

150 MVAR

2 x 75 MVAR

150 MVAR

45-1113

3-1113

37.3

-1113

2X375 MW

109.2-1113

2 x 50 MVAR

175.2

-1113

30-1113

46-1

113

20-900+

14.6-1113

30-900+

4-1113

2 x 75 MVAR

20.4-900+

24.5-1113

30-900+

13.1-1113

9-900+25-1113

25-900+

13.1-1113

20-795+3-900

Zona Lázaro Cárdenas

Zona Guadalajara

Zona Aguascalientes

A S

oyata

l

Cañada2 X375 MVA 400/230 kV

121-7

95+

7-1

113

61-9

00 +

1-1

113

50-1

113

8.3

-795+

7-1

113

218.

1-11

13

220.8-1

113

140.22-1113

149.7

-1113

148.4-795

143.

9-90

0

174.8-

1113 5

4-1

113

185-1

113

119.4

-1113

88.2

-900+

5-1

113

90.4

-795

39-900

11-900

17.5

4-7

95

16.6

-900

27-9

00

A El Potosí

A El P

otosí

A San Luis I

A Villa de

Reyes

A Ixtlahuacá

n

A S

an J

uan

de los L

agos

A Z

apotl

anejo

A P

otr

erillo

s

A L

eón

III

A Prim

ero d

e

Mayo

A C

ru

z A

zu

l

A C

ale

ra II

-90 MVAR300 MVAR

50 MVAR

50 MVAR

1 X375 MVA 400/115kV150 MVAR

El Llano470 MW

2 X60 MVA230/23 kV

2 X60 MVA230/23 kV

1 X100 MVA230/69 kV

1 X60 MVA 230/23 kV

2 X60 MVA 230/23 kV

1 X100 MVA 230/69 kV

2 X60 MVA230/23 kV

2X125 MVA 230/69kV

2 X60 MVA 230/23 kV

1X60 MVA 230/23kV

2 X60 MVA 230/23 kV

1 X225 MVA 230/69 kV

49.9-900

36-1113

33-900

33-900

6.9-900

28.1

-795 A

CSS

23.6

-795 A

CSS

4.7-795ACSS

44-9

00

49-900

18.5

-900

3-90

0

27-900

3.5

-900+

9-1

113

16.6-1113

19-9

00+

16.7

-1113

19-9

00+

9-1

113

4.7-1113

5-1

113

12-1

113

Ope. Inic.161kV

36.5-900+4.7-1113

Guadalajara Norte

Agua Prieta

Niños Héroes

Zapopan

Ixtlahuacán

Álamos

San Martín

Colón

Guadalajara I

Side. Guad.

60.4-1

113

148.6-1113

143-900+3-1113

146-1113

A Cerro Blanco

A La Yesca

38-1

113

2 X120 MW

50-1113

109.2-1113175.2-1113

32.2-1113

A Aguascalientes

Potencia

AzulAgua

16-1113

56.8-900

17.8

-795

11.6-900

50-900

21.5

-795

17-900

275-3

x1113

46-1

113239-1

113

Nks

Sicartsa II

Fertimex

Sicartsa I

A Pitirera

A C

arap

an

A D

onato

Guerr

a

A P

itir

era

A Ixta

pa Pote

ncia

74.8

-111

3

Zona Lázaro Cárdenas

Vallarta Potencia3X100 MVA 230/115kV

150 MVAR -50 MVAR

AguascalientesOriente

1 X225 MVA 230/115 kV1 X125 MVA230/115 kV

Aguas. I

AguascalientesPotencia

2X300 MVA 400/230kV1X375 MVA 400/115kV

2 X300 MVA 400/230 kV

1X 100 MVA 230/69 kV

1X 375 MVA 400/69 kV

Tesistán

1 X60 MVA 230/23 kV

3.5-900+0.2-1113

1 X60 MVA230/23 kV

Tuzania

3X300 MVA 400/230kV

2X100 MVA 230/69kV1X100 MVA 230/115kV

Acatlán

-200 MVAR

2 X60 MVA 230/161 kV

2 X100 MVA 230/69 kV

Guadalajara II

Industrial4X75 MVA 230/69 kV2X60 MVA 230/23 kV

Guadalajara

71.3-900A Ix

tapa

Potencia

1X100MVA230/115kV

4x80 MW La Villita

Carboeléctricadel Pacífico

1X678MW

Colomo1X100 MVA 230/115kV

P.V. Manzanillo II2X760 MW

Cd.Guzmán2X100 MVA 230/115kV

Mazamitla(Switcheo)

UruapanPotencia

1X100 MVA 230/115kV

1X100 MVA 230/161kV

PatzcuaroPotencia1X100 MVA

230/115kV

Pitirera4X200 MW2X180 MVA400/230kV

963.53 MVAR40%, 40% Y 50%

450 MVAR -450 MVAR

DonatoGuerra

(Área Central )

AgustínMillán

(Área Central )

A Volcán Gordo(Área Central )

Almoloya(Área Central )

Zimapán

1X100 MVA

230/115kV

2X146 MW

San Juan del Río II1X225 MVA230/115kV

Los Azufres309.5 MW

Morelia Potencia2X100 MVA 230/115kV

Tarimbaro1X100 MVA 230/115kV

AtlacomulcoPotencia(Área Central )

QuerétaroPotencia

2X375 MVA 400/230kV

1X225 MVA 230/115kV

Santa María

1X375 MVA

400/115kV

Celaya III2X100 MVA 230/115kV

Potrerillos1X375 MVA 400/230kV1X375 MVA 400/115 kV

Silao II2X100 MVA 230/115kV

León II2X100 MVA 230/115kV

León IV1X225 MVA 230/115kV

León III2X100 MVA 230/115kV

1X225 MVA

230/115kV

San Juan de los Lagos

Soyatal

Charcas Potencia1X100 MVA 230/115kV

A Ramos Arizpe Potencia

(Área Noreste )

Moctezuma Potencia1X100 MVA 230/115kV

El Potosí2X375 MVA 400/230kV1X375 MVA 400/115kV

San Luis I2X100 MVA 230/115kV

Villa de Reyes

La Pila2X375 MVA 400/115kV

-70 MVAR200 MVAR

San Luis II2X100 MVA 230/115kV

Calera II2X100 MVA 230/115kV

Fresnillo1X225 MVA 230/115kV

A Vicente Guerrero II(Área Norte )

Zacatecas II2X100 MVA 230/115kV

200 MVAR -70 MVAR

1X100 MVA 230/115kVPedro Moreno

22.4-900+1.8-1113

19.9-795+19.3-900

Salamanca II1X375 MVA 400/115 kV

Abasolo II2X100 MVA230/115kV

2X100 MVA 230/115kV

1X300 MVA 400/230kV

P.V. Salamanca

Salamanca CC1x470 MW1X629 MW

Irapuato II2X100 MVA 230/115kV

Celaya II2X100 MVA 230/115kV

Qro. I2X225 MVA 230/115kV

Conin1X225 MVA 230/115kV

19-900+2.3-1113

Nopala(Área Central )

San Bernabe(Área Central )

A Las Mesas

(Área Noreste )

Jiliapán190 MW

Santa Fe1X225 MVA

230/115kV

Las Delicias592 MW

San Luis de la Paz II

2X100 MVA 230/115kV

Tula(Área Central )

(Área Central )A Hil

A Pie de la Cuesta

(Área Oriental )

Ixtapa Potencia1 x 375 MVA 400/230 kV2 x 100 MVA 230/115 kV

1X375 MVA 400/230kV

ApatzingánPotencia

1X100 MVA 230/115kV

Apatzingán

Zamora2X100 MVA 230/115kV

Ocotlán3X100 MVA 230/115kV

A Anáhuac Potencia(Área Noreste )

Las Fresas1X375 MVA 400/115 kV

6X350MW

C.T. Petacalco

Lázaro CárdenasPotencia

3X375 MVA 400/230kV

2X100 MVA 230/115kV

40-1113

40-1113

75 MVAR

36-1

113

23.5-795+4-1113

17.5-900+4-113

7-1113

1X375 MVA 400/230kVSan José el Alto

Cerro Blanco

400/230kV

Subdirección de Programación

Coordinación de Planificación

Subgerencia de Programación de Redes Eléctricas

Red Eléctrica Principal

Área Occidental

Jalisco

Zacatecas

Jalisco

Zacatecas

Jalisco

Jalisco

Colima

Jalisco

Colima

Micho

acánC

olim

a

Micho

acánJa

lisco

Gua

najuato

Jalis

co

Aguascalientes

Zacatecas

Micho

acán

Gue

rrero

Mic

hoacán

Est

ado d

e M

éxico

MichoacánGuanajuato

Michoacán

Querétaro

San

Luis Potosí

Querétaro

Querétaro

HidalgoQue

réta

roGuana

juat

o

Jalisco

Guanaju

ato

Jalisco

Zacatecas

San Luis Potosí

Guanajuato

Sonora

Sin

alo

a

Est

ado d

e M

éxico

More

los

San

Luis P

otos

í

Zaca

teca

s

AguascalientesJalisco

Zacate

cas

Sonora

Nayarit

Nayarit

Nayarit

Jalisco

Nayarit

San Luis Potosí

Tamaulipas

D.F.

1X225 MVA 230/115kV

13.4-900+

4.7-1113

50 MVAR

44-9

00

251-1

113

35-1

113

35-1

113

1X100 MVA230/69 kV

5-1113

2X300MVA400/230kV

Atequiza

3X100 MVA230/69 kV

1X225 MVA230/115kV

Corregidora

100-1

113

P.V. Manzanillo2X760 MW

1X225 MVA 400/230kV

Manzanillo I (SF6)

El Sauz220 MW 1X122 MW

2X100 MVA 230/115kV

1X128 MW 1X129 MW

37.2-1113

Tapeixtles2X225 MVA 400/230kV1X375 MVA 400/115kV

Valle de Tecomán1X100 MVA 230/115kV

10-3x1

113

53-900A Ocotlán

13-900

186-

1113

207-

1113

A M

anzanillo

50 MVAR

Pote

ncia

A A

guasca

liente

s

178-1

113

96-9

00

A M

azam

itla

A C

d.

Gu

zm

án

A M

an

zan

illo

85-9

00

60 MVAR 75

MVAR

A M

an

zan

illo

177-1

113

54-1113

14.1

-1113

Cajititlán100 MVA 230/69 kV

Cajititlán

100 MVA 230/69 kV

34-1

113

60 MVAR

1 X375 MVA 400/230 kV

Zapotlanejo

60 MVAR

60 MVAR

211.5-1113

211.5-1113 A Salamanca II12-1113

2 X100 MVA230/69 kV

Guadalajara Oriente

1 X60 MVA 230/23 kV

2x350 MW1X100 MVA 230/115kV

Océano Pacífico

Manzanillo II (SF6)

61-9

00+

1-1

113

30-9

00+

1-1

113

S i m b o l o g í a

400 kV

Ciclo Combinado

Geotermoeléctrica

Hidroeléctrica

Térmica Convencional

Dual

Carboeléctrica

Nivel de Tensión

230 kV

115 kV

161 kV, 69 kV y media tensión

Subestación

Línea de Transmisión

Reactor

Compensador Estático de Vars

Estructura de Doble CircuitoTendido del Primero

Nuevos proyectos

Retiros y traslados

1X300 MVA

66-1

113

Cadereyta1X225 MVA 230/115kV

70 MVAR

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 117: Catalogo 2011-2020 r010212 Corto Circuito

117

Coordinación de PlanificaciónADICIONES Y RETIROS DE GENERACIÓN

ÁREA OCCIDENTAL

ADICIONES:

Nombre de la Central Año Capacidad

Manzanillo I Repotenciación U1 2011 460 MW

La Yesca U1 2012 375 MW

La Yesca U2 2012 375 MW

Manzanillo I Repotenciación U2 2012 460 MW

Salamanca Fase I 2013 470 MW

Azufres III Fase I 2014 50 MW

Occidental I (Bajío) 2017 470 MW

Manzanillo II Repotenciación U1 2018 460 MW

Azufres III Fase II 2018 25 MW

Río Moctezuma 2019 190 MW

Manzanillo II Repotenciación U2 2020 460 MW

Salamanca 2020 629 MW

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 118: Catalogo 2011-2020 r010212 Corto Circuito

118

Coordinación de PlanificaciónADICIONES Y RETIROS DE GENERACIÓN

ÁREA OCCIDENTAL

RETIROS:

Nombre de la Central Año Capacidad

Salamanca U3 y U4 2013 550 MW

Azufres U2-U5 2014 20 MW

Manzanillo I U3 y U4 2016 600 MW

Azufres U6, U9 y U10 2018 15 MW

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 119: Catalogo 2011-2020 r010212 Corto Circuito

119

Coordinación de PlanificaciónPRINCIPALES PROYECTOS DE TRANSMISIÓN Y TRANSFORMACIÓN

Proyecto Año Nivel de tensión

Cañada Bco. 3 2011 400/115 kV

Tesistán Bco. 5 2011 400/69 kV

Red asociada a la CH La Yesca 2011 400 kV

Red asociada a la central Salamanca CC 2012 230 kV

Nueva Vallarta Bco. 1 2013 230/115 kV

Acatlán Bco. 5 (sustitución) 2014 230/115 kV

Tepic II Bco. 5 2014 230/115 kV

Querétaro I Bco. 1 (sustitución) 2015 230 kV

Guadalajara Industrial Bco. 2 2015 230/69 kV

Apatzingán Potencia Bco. 1 2016 400/230 kV

Purépecha Potencia Bco. 1 2016 400/115 kV

Red asociada a Occidental I (Bajío) 2016 400 kV

ÁREA OCCIDENTAL

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 120: Catalogo 2011-2020 r010212 Corto Circuito

120

Coordinación de PlanificaciónPRINCIPALES PROYECTOS DE TRANSMISIÓN Y TRANSFORMACIÓN

Proyecto Año Nivel de tensión

Niños Héroes Bco. 3 2017 230/69 kV

Pedro Moreno Bco. 1 2017 230/115 kV

San José el Alto Bco. 1 2018 400/230 kV

La Pila Bco. 1 (sustitución) 2018 400/115 kV

Potrerillos Bco. 4 2018 400/115 kV

Red asociada a Jiliapan 2018 230 kV

Red asociada a la repotenciación de Manzanillo II, U2 2019 400 kV

Red asociada a Salamanca 2019 230 kV

Red asociada a Guadalajara I 2020 230 kV

ÁREA OCCIDENTAL

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 121: Catalogo 2011-2020 r010212 Corto Circuito

121

Coordinación de PlanificaciónPRINCIPALES PROYECTOS DE TRANSMISIÓN Y TRANSFORMACIÓN

Los proyectos de transmisión importantes en el Área Occidental son, en su mayoría, redes asociadas a centrales y

tienen un impacto importante para las subestaciones adyacentes, aunque la mayor contribución a los niveles de corto

circuito, se presenta con la entrada de la central correspondiente.

Al igual que las redes asociadas, la construcción de nuevas subestaciones de potencia o el incremento en la capacidad

de transformación instalada en las subestaciones existentes trae consigo un incremento del nivel de cortocircuito en las

subestaciones que están dentro del área de influencia del proyecto.

Por ejemplo, en el 2012 con la entrada en operación de la repotenciación de la unidad 2 de Manzanillo II se incrementa

el nivel de cortocircuito de 17 a 19.2 kA y de 21 a 24 kA trifásico y monofásico respectivamente.

En 2013, con el entronque de la LT en 230 kV Irapuato II – León IV en la subestación Silao II, se incrementa el nivel de

corto en el bus de 230 kV de 9 a 12 kA.

ÁREA OCCIDENTAL

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 122: Catalogo 2011-2020 r010212 Corto Circuito

122

Coordinación de PlanificaciónPRINCIPALES PROYECTOS DE TRANSMISIÓN Y TRANSFORMACIÓN

En 2016, con la entrada en operación de la subestación Purépecha potencia se incrementa el nivel de cortocircuito

ENTRE 1 Y 6 kA en las subestaciones Cotija, Jiquilpan, Sahuayo, Vistahermosa, Guascuaro, Periban, Ocotlán, Jamay,

Zamora, etc, aunque la corriente de cortocircuito trifásica no supera los 15 kA.

En 2017, la entrada en operación del banco 3 de subestación Niños Héroes incrementa el nivel de corto en los buses

de 69 kV principalmente en los buses de 69 kV de las subestaciones Alameda (de 9 a 18 kA), Fresno (de 13 a 22 kA),

México (de 15 a 20 kA), Zapopan (de 22 a 26 kA) y Praxair (12 a 18 kA).

Con la construcción de la subestación Pedro Moreno, en 2017, se incrementa el cortocircuito en las subestaciones

Lagos, Lagos Galera y La Virgen.

Con los proyecto San José el Alto y Corregidora, se incrementarían los niveles de cortocircuito en la zona Querétaro,

siendo las subestaciones Conín (de 18 a 22 kA), El Sáuz (de 18 a 20 kA) , Querétaro I (de 35 a 40 kA 1f), Querétaro

Poniente (de 15 a 21 kA 3f) y Satélite (18 a 20 kA).

ÁREA OCCIDENTAL

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 123: Catalogo 2011-2020 r010212 Corto Circuito

123

Coordinación de PlanificaciónPRINCIPALES PROYECTOS DE TRANSMISIÓN Y TRANSFORMACIÓN

La sustitución de la transformación en la subestación La Pila por bancos 400/115 kV incrementaría los niveles de

cortocircuito en las subestaciones de 115 kV aledañas a esta subestación. Sobresale entre estas el bus en 115 kV de

La Pila ( de 19 a 27 kA 1f) y San Luis I (de 21 a 26 kA 3f). Las subestaciones de las industrias, a las cuales se les

proporciona el servicio de energía eléctrica en 115 kV, cercanas a La Pila quedan con niveles de cortocircuito del orden

de los 20 kA.

Con la subestación Cajititlan (2018), se incrementa el nivel cortocircuito en las subestaciones Tableros Emman, Siapa

Soledad, San Jorge, Quaker, Poncitlán II, Edosa y CIBA.

En 2020, con la entrada en operación de la repotenciación de la unidad 2 de Manzanillo II y de la CCC Salamanca se

incrementa el nivel de cortocircuito en las subestaciones Manzanillo (de 24 a 27 KA 1f) y Salamanca CC (de 25 a 33 kA

1f) respectivamente.

ÁREA OCCIDENTAL

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 124: Catalogo 2011-2020 r010212 Corto Circuito

124

Coordinación de PlanificaciónPRINCIPALES PROYECTOS DE TRANSMISIÓN Y TRANSFORMACIÓN

En resumen, en el Área Occidental y en el nivel de 400 kV, las subestaciones Lázaro Cárdenas Potencia, Manzanillo,

Pitirera y Tapeixtles son las que presentan al 2020 los niveles máximos de cortocircuito monofásico con valores de 31,

27, 23 y 22 kA respectivamente.

En el nivel de 230 kV las subestaciones Lázaro Cárdenas Potencia, Salamanca CC, Salamanca y Querétaro Potencia

alcanzan valores máximos de corto circuito trifásico de 36, 33, 32 y 29 kA respectivamente.

En el nivel de 115 kV las subestaciones Querétaro I, Corregidora, La Pila y Santa María son las que presentan los

niveles máximos de corto circuito trifásico con valores de 33, 30, 27 y 27 kA respectivamente.

Finalmente, en el nivel de 69 kV las subestaciones Guadalajara I, Tesistán, Zapopán y Niños Héroes llegan a valores de

32, 32, 27 y 27 kA respectivamente.

ÁREA OCCIDENTAL

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 125: Catalogo 2011-2020 r010212 Corto Circuito

125

Coordinación de Planificación

ÁREA OCCIDENTAL

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 15.48 15.51 15.73 15.71 15.83 15.77 15.98 19.20 19.24 19.271F 13.89 13.98 14.13 14.11 14.18 14.15 14.27 16.60 16.62 16.643F 8.84 8.85 8.84 8.84 8.88 8.83 8.92 8.92 8.94 9.111F 8.51 8.52 8.51 8.51 8.53 8.51 8.56 8.56 8.57 8.683F 6.13 6.14 6.14 6.14 6.16 6.13 6.19 6.20 6.22 6.401F 5.51 5.51 5.51 5.52 5.52 5.51 5.54 5.55 5.56 5.663F 9.54 9.55 9.54 9.54 9.58 9.53 9.62 9.63 9.66 9.851F 10.20 10.21 10.19 10.20 10.23 10.19 10.26 10.27 10.29 10.443F 6.95 6.95 6.95 7.07 6.89 6.82 7.28 7.41 7.62 7.851F 6.32 6.33 6.32 6.39 6.18 6.12 6.80 6.88 7.01 7.163F 4.41 4.42 4.42 4.56 4.54 4.46 4.51 4.57 4.58 4.741F 3.20 3.20 3.20 3.27 3.26 3.19 3.21 3.24 3.24 3.343F 1.24 1.24 1.27 1.27 1.27 1.27 1.27 1.27 1.27 1.271F 0.81 0.81 0.82 0.82 0.82 0.82 0.82 0.82 0.82 0.823F 15.66 16.42 16.72 16.81 16.77 16.35 16.62 16.91 18.28 18.881F 15.64 16.48 16.65 16.95 16.90 16.69 16.92 16.99 18.86 19.253F 18.58 19.19 19.31 19.47 19.47 19.15 19.62 19.53 22.24 22.771F 20.97 21.98 21.78 22.31 22.29 22.04 22.78 22.33 25.65 26.093F 8.86 8.86 8.82 8.82 8.82 8.99 9.041F 10.12 10.12 10.08 10.09 10.08 10.26 10.293F 25.89 24.24 26.08 24.37 24.46 24.31 24.40 24.48 25.51 25.721F 28.40 26.94 28.41 27.08 27.14 27.03 27.15 27.15 28.17 28.333F 16.16 16.18 16.21 16.20 16.21 16.20 16.19 16.67 17.45 17.481F 17.43 17.44 17.46 17.46 17.46 17.45 17.45 17.84 18.42 18.433F 12.00 12.04 12.23 12.20 12.35 12.28 12.53 13.22 13.27 13.301F 10.97 11.13 11.25 11.23 11.32 11.27 11.42 11.91 11.96 11.973F 14.76 14.79 15.00 14.98 15.09 15.04 15.22 18.88 18.92 18.961F 13.03 13.12 13.26 13.25 13.31 13.28 13.39 16.19 16.23 16.253F 10.99 10.98 11.01 11.02 11.54 11.51 11.55 11.54 11.61 11.701F 8.16 8.16 8.17 8.18 8.37 8.36 8.38 8.37 8.40 8.433F 5.16 5.16 5.16 5.26 5.15 5.07 5.33 5.41 5.48 5.661F 4.06 4.07 4.07 4.11 4.02 3.96 4.20 4.24 4.27 4.373F 13.65 13.70 13.79 13.66 13.85 13.86 14.24 14.36 14.38 14.431F 10.81 10.84 10.88 10.82 10.90 10.90 11.08 11.16 11.16 11.183F 13.19 13.20 13.40 13.39 13.40 13.40 13.43 17.15 17.27 17.401F 9.96 9.96 10.10 10.10 10.10 10.10 10.11 13.93 13.98 14.04

ACL

Aceros de México ADM

Agostaderito AGO

Agrogen ART

Aeropuerto Morelia AER 115

115

115

Aceros San Luis ASL 115

Acueducto ACU 69

69

115

230

Acatlán ATN

Acerlan

230

115

Acaponeta ACP 115

400

Abastos ABS 115

Acámbaro AQM 115

230

115Abasolo II ABA

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

3M de México 3MM 115

Abasolo ABS 115

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 126: Catalogo 2011-2020 r010212 Corto Circuito

126

Coordinación de Planificación

ÁREA OCCIDENTAL

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 9.72 9.85 9.89 10.21 10.06 10.00 11.46 11.47 11.62 11.821F 9.54 9.66 9.68 9.57 9.80 9.76 11.30 11.31 11.40 11.523F 2.85 2.85 2.98 2.98 2.99 2.99 3.00 3.00 3.00 3.011F 1.96 1.96 2.02 2.02 2.02 2.02 2.02 2.02 2.02 2.023F 12.31 12.55 12.63 12.74 12.81 12.73 12.79 12.84 13.05 13.191F 13.32 13.58 13.65 13.75 13.80 13.75 13.79 13.83 13.98 14.083F 11.43 11.53 11.57 11.56 11.59 11.56 11.72 11.74 11.80 11.841F 13.90 14.02 14.04 14.05 14.09 14.07 14.21 14.23 14.27 14.303F 2.69 2.69 2.80 2.80 2.81 2.81 2.82 2.82 2.82 2.821F 1.83 1.83 1.88 1.88 1.89 1.89 1.89 1.89 1.89 1.893F 12.29 12.33 12.40 12.31 12.45 12.45 12.81 12.85 12.87 12.911F 9.59 9.61 9.64 9.61 9.66 9.66 9.85 9.87 9.88 9.893F 11.89 11.96 12.09 11.84 12.19 12.20 12.12 13.04 13.07 13.141F 10.77 10.82 10.90 10.76 10.95 10.96 10.54 11.47 11.48 11.513F 17.64 17.72 17.87 17.62 17.98 17.99 18.51 18.88 18.91 18.981F 16.88 16.95 17.05 16.90 17.11 17.12 17.25 17.72 17.74 17.783F 17.39 17.47 17.62 17.36 17.72 17.73 18.34 18.61 18.64 18.701F 15.68 15.74 15.83 15.69 15.88 15.89 16.16 16.40 16.42 16.453F 15.72 15.84 16.09 15.62 16.25 16.26 17.53 17.83 17.88 18.001F 16.04 16.16 16.34 16.02 16.46 16.47 17.40 17.69 17.72 17.793F 21.60 21.72 21.96 21.55 22.12 22.13 23.23 23.53 23.58 23.681F 23.44 23.57 23.77 23.46 23.90 23.91 24.80 25.10 25.13 25.213F 14.32 14.37 14.47 14.32 14.54 14.55 14.94 15.12 15.14 15.191F 11.76 11.79 11.84 11.77 11.87 11.87 12.01 12.17 12.17 12.193F 15.06 15.29 15.66 15.35 16.30 15.79 18.41 18.51 18.64 19.041F 15.53 15.80 16.11 15.89 16.82 16.08 18.94 19.03 19.12 19.393F 17.81 17.97 18.26 17.68 18.47 18.50 19.92 20.25 20.32 20.501F 19.87 20.06 20.33 19.84 20.50 20.53 21.77 22.11 22.16 22.303F 19.85 19.95 20.14 19.90 20.26 20.27 21.23 21.35 21.40 21.501F 19.43 19.54 19.67 19.52 19.76 19.74 20.57 20.66 20.68 20.753F 11.41 11.45 11.51 11.43 11.55 11.56 11.86 11.90 11.92 11.951F 8.67 8.69 8.71 8.68 8.73 8.73 8.88 8.90 8.90 8.913F 1.65 1.64 1.85 1.61 1.61 1.61 1.61 1.61 1.61 1.611F 1.08 1.07 1.32 1.04 1.04 1.04 1.04 1.04 1.04 1.043F 12.05 12.06 12.08 12.08 12.08 12.08 12.09 12.52 12.63 12.671F 9.18 9.18 9.20 9.19 9.19 9.19 9.20 9.40 9.45 9.46

AGP

Aguascalientes Potencia APT

Ahuacatlán AHN

Alambres y Circuitos AYC

Aguascalientes Sur ASS 115

115

115

230

115

115

115

400

Aguascalientes Oriente AGS

Aguascalientes Poniente

Aguascalientes Norte AGN 115

230

230

115Aguascalientes I AGT

Aguamilpa Servicios SEA 115

Aguascalientes Centro ACE 115

Agua Prieta APR 230

Aguamilpa AGM 400

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Agua Azul AGZ 230

Agua Milpa AGM 115

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 127: Catalogo 2011-2020 r010212 Corto Circuito

127

Coordinación de Planificación

ÁREA OCCIDENTAL

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 9.37 9.39 9.49 9.50 9.50 9.56 18.60 18.60 18.77 19.281F 6.74 6.75 6.79 6.80 6.80 6.83 14.45 14.46 14.52 14.723F 10.14 10.29 10.33 10.64 10.47 10.40 11.46 11.47 11.63 11.821F 10.24 10.37 10.40 10.42 10.49 10.45 11.50 11.51 11.61 11.733F 16.35 16.46 16.51 14.30 14.23 14.20 14.23 14.21 14.29 14.411F 17.40 17.51 17.55 15.59 15.54 15.51 15.55 15.54 15.60 15.693F 7.42 7.43 7.45 8.29 8.26 8.24 8.30 8.24 8.29 8.321F 5.03 5.04 5.04 5.61 5.60 5.60 5.62 5.60 5.61 5.623F 15.78 15.79 16.08 16.06 16.08 16.07 16.12 16.92 17.04 17.171F 12.40 12.40 12.61 12.60 12.61 12.61 12.62 13.01 13.06 13.113F 15.86 15.90 16.11 16.09 16.21 16.15 16.37 18.62 18.79 18.821F 14.57 14.65 14.78 14.77 14.84 14.80 14.93 16.37 16.51 16.523F 6.53 6.54 6.57 6.10 6.72 6.65 6.83 6.98 6.99 6.921F 5.68 5.68 5.69 5.45 5.77 5.74 5.83 5.96 5.96 5.923F 3.70 3.73 3.73 3.73 3.77 3.74 3.72 3.74 3.74 3.761F 2.73 2.74 2.74 2.74 2.76 2.75 2.73 2.74 2.75 2.753F 2.51 2.51 2.51 2.51 2.53 2.52 2.51 2.52 2.52 2.521F 2.20 2.21 2.21 2.21 2.22 2.21 2.21 2.21 2.21 2.213F 4.38 4.11 4.05 4.11 4.11 4.11 4.11 4.11 4.11 4.111F 4.12 3.96 3.92 3.96 3.96 3.96 3.96 3.96 3.96 3.963F 3.23 3.23 3.22 3.21 3.22 3.23 3.231F 2.28 2.28 2.28 2.28 2.28 2.28 2.283F 4.55 3.23 4.041F 3.08 2.29 1.543F 8.52 8.53 8.73 8.73 8.95 8.78 9.03 9.03 9.06 9.231F 6.66 6.66 6.74 6.79 6.88 6.81 6.91 6.91 6.92 6.993F 1.50 1.50 1.50 1.50 1.50 1.54 1.54 1.54 1.54 1.541F 1.48 1.48 1.48 1.48 1.48 1.50 1.51 1.51 1.51 1.513F 2.91 2.91 2.91 2.92 2.91 2.53 2.53 2.53 2.53 2.541F 2.12 2.12 2.12 2.12 2.12 1.86 1.86 1.86 1.86 1.863F 3.59 3.65 3.60 4.88 4.89 4.89 4.90 4.911F 2.77 2.95 2.76 4.81 4.82 3.78 3.79 3.783F 1.86 1.86 3.47 3.49 3.47 3.86 3.86 3.86 3.86 3.871F 1.34 1.34 1.65 1.65 1.65 1.70 1.70 1.70 1.71 1.713F 5.71 5.77 5.74 5.69 6.28 6.18 6.18 6.25 6.28 6.331F 3.93 3.95 3.93 3.91 4.58 4.55 4.55 4.58 4.59 4.61

AAE

Antúnez ANN

Apasco Manzanillo APP

115

69

115

Angamacutiro ARO 69

Angamaracutiro II ANM 115

115

69

115

Ameca AMK

American Axle

69

Amatitán AMT 69

Alzada AZA

Alza ALZ 115

115

Alto Carbón ALC 115

Aluprint ALU 115

69

Almex ALX 69

Álamos ALS

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Alameda ALA 69

230

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 128: Catalogo 2011-2020 r010212 Corto Circuito

128

Coordinación de Planificación

ÁREA OCCIDENTAL

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 17.82 17.83 17.80 17.84 17.88 17.98 18.11 18.10 18.28 18.621F 13.81 13.82 13.79 13.83 13.83 13.93 13.98 14.01 14.09 14.233F 8.30 8.30 8.30 8.30 8.31 8.31 8.33 8.37 8.41 8.461F 5.58 5.58 5.59 5.59 5.59 5.59 5.60 5.61 5.62 5.643F 13.20 13.21 13.21 13.21 13.22 13.23 13.28 13.40 13.48 13.611F 9.56 9.57 9.57 9.57 9.57 9.58 9.60 9.65 9.68 9.723F 7.19 7.19 7.21 7.28 7.321F 7.18 7.18 7.19 7.25 7.283F 3.24 3.24 3.29 3.30 3.68 4.31 4.29 4.31 4.34 4.351F 2.99 2.99 3.01 3.50 3.54 4.35 4.34 4.35 4.37 4.383F 4.77 4.77 5.02 5.13 3.93 8.07 8.05 8.08 8.12 8.161F 4.73 4.73 4.89 6.20 4.18 9.36 9.35 9.37 9.41 9.443F 8.03 8.05 8.06 8.11 8.161F 6.89 6.90 6.90 6.93 6.953F 8.22 8.22 8.24 8.30 8.341F 9.26 9.27 9.28 9.33 9.373F 16.83 16.85 16.87 16.87 16.87 16.86 16.85 17.38 18.23 18.261F 18.83 18.84 18.87 18.86 18.87 18.86 18.85 19.31 19.99 20.013F 2.88 2.88 2.88 2.90 2.90 3.25 3.25 3.25 3.25 3.301F 1.90 1.90 1.90 1.91 1.91 2.11 2.11 2.11 2.11 2.133F 5.64 5.65 5.65 6.10 6.08 7.86 7.87 7.88 7.89 8.151F 5.61 5.61 5.62 5.99 5.97 7.13 7.14 7.14 7.15 7.303F 1.78 1.78 1.84 1.78 1.78 1.80 1.69 1.80 1.80 1.801F 1.31 1.31 1.32 1.31 1.31 1.31 1.27 1.31 1.31 1.313F 3.71 3.74 3.71 3.69 4.23 4.19 4.19 4.22 4.23 4.261F 2.43 2.44 2.42 2.41 3.20 3.19 3.19 3.20 3.20 3.213F 2.22 2.22 1.43 2.22 2.22 2.22 1.43 2.22 2.22 2.221F 1.75 1.75 1.23 1.76 1.76 1.76 1.23 1.76 1.76 1.763F 2.75 2.75 2.39 2.75 2.75 2.75 2.39 2.75 2.75 2.751F 1.83 1.83 1.57 1.84 1.83 1.83 1.57 1.83 1.83 1.833F 25.12 25.14 26.77 26.75 26.78 26.78 26.89 30.49 30.88 31.281F 27.38 27.40 30.01 30.01 30.03 30.03 30.12 33.93 34.25 34.563F 22.89 22.90 24.20 24.18 24.21 24.21 24.29 27.53 27.86 28.181F 23.00 23.01 24.74 24.74 24.76 24.76 24.81 27.78 27.99 28.20

ARM

Arteva II (Celanese Conin) AS2

Apatzingán I APZ

Arteva I (Celanese Kosa) ASQ 115

115

Arteaga ATG 69

Arteaga II ATD 115

Arboleda ARB 115

69

115

Ario de Rosales ARA

Armería

Arancia AIA 115

Arandas ARS 115

400

230Apatzingán Potencia APP

161

115

Apaseo Oriente APO 115

230

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Apaseo APS 115

Apaseo Industrial API 115

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 129: Catalogo 2011-2020 r010212 Corto Circuito

129

Coordinación de Planificación

ÁREA OCCIDENTAL

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 15.71 15.75 15.97 15.95 16.07 16.01 16.22 19.37 19.43 19.461F 14.20 14.30 14.45 14.43 14.50 14.47 14.59 16.86 16.89 16.913F 15.57 15.60 15.84 15.81 15.93 15.87 16.08 19.94 20.10 20.141F 14.06 14.16 14.33 14.31 14.38 14.35 14.47 17.50 17.70 17.723F 5.89 5.95 5.92 5.90 6.28 6.19 6.17 6.23 6.26 6.311F 4.29 4.31 4.29 4.28 4.72 4.69 4.68 4.70 4.72 4.733F 14.89 15.01 15.03 15.071F 12.42 12.49 12.50 12.523F 3.84 3.96 3.86 3.96 3.96 3.95 3.95 3.96 3.97 3.981F 3.23 3.29 3.23 3.29 3.29 3.29 3.29 3.29 3.30 3.303F 14.85 15.43 15.60 16.34 15.77 15.45 15.63 15.87 16.30 16.791F 14.47 15.00 15.09 16.41 15.82 15.63 15.21 15.39 15.72 15.983F 16.43 16.71 16.82 19.08 18.72 18.54 17.56 17.49 17.85 18.341F 18.99 19.39 19.48 22.48 22.03 21.89 20.40 20.48 20.81 21.073F 18.12 18.21 18.27 12.08 12.04 12.05 11.94 15.01 15.08 15.351F 23.31 23.46 23.53 16.22 16.16 16.18 16.03 19.71 19.79 20.093F 4.13 4.14 4.14 4.18 4.18 5.76 5.76 5.77 5.78 5.931F 2.88 2.88 2.88 2.90 2.89 3.98 3.98 3.99 3.99 4.053F 4.18 4.19 4.19 3.97 3.97 4.00 4.00 14.15 14.21 7.601F 3.03 3.03 3.03 2.95 2.95 2.97 2.96 13.29 13.32 5.643F 2.03 2.34 2.04 2.32 2.32 2.31 2.04 2.04 2.05 2.051F 1.34 1.49 1.34 1.47 1.48 1.47 1.30 1.30 1.30 1.303F 9.01 9.02 9.25 9.24 9.49 9.30 9.58 9.59 9.62 9.811F 7.17 7.18 7.27 7.33 7.43 7.35 7.46 7.47 7.48 7.563F 6.80 6.81 10.14 10.12 10.13 11.30 11.76 11.78 11.81 12.001F 5.20 5.20 8.30 8.29 8.29 8.75 8.97 8.98 8.99 9.063F 3.45 3.43 3.46 3.51 3.49 3.85 3.85 3.85 3.86 3.921F 2.35 2.34 2.38 2.39 2.39 2.53 2.53 2.53 2.53 2.553F 7.33 7.34 7.34 7.75 7.65 7.27 7.53 7.81 7.82 8.681F 8.06 8.07 8.07 8.46 8.39 7.63 7.84 8.06 8.13 9.293F 7.93 7.94 7.94 8.42 8.31 7.87 8.17 8.50 8.51 9.531F 9.37 9.38 9.38 9.91 9.80 8.78 9.06 9.36 9.45 11.063F 5.54 5.54 5.94 6.14 6.08 7.83 7.83 7.86 7.87 8.171F 4.24 4.23 4.71 4.78 4.76 5.78 5.78 5.79 5.79 5.943F 3.48 3.48 3.62 3.53 4.19 4.19 4.33 4.33 4.33 4.191F 3.13 3.13 0.27 3.22 3.57 3.57 3.64 3.64 3.64 3.52

AYA

Ballesteros BAS

Banderas BND

Atequiza ATQ

Azúfres Switcheo AZS 115

115

115

Ayotlán AYN 115

Azúfres AZD 115

Autlán AUT 115

115

115

Aventec AVC

Ayala

Atotonilco ATO 115

Atotonilquillo ATL 69

230

69

Atentique AQQ 115

400

Asmoles ASM 115

Asunción ASN 115

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Arvin Meritor ARM 115

Ashulman México ASC 115

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 130: Catalogo 2011-2020 r010212 Corto Circuito

130

Coordinación de Planificación

ÁREA OCCIDENTAL

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 2.47 2.47 2.47 2.39 2.49 2.48 2.51 2.52 2.52 2.511F 1.68 1.68 1.68 1.66 1.69 1.69 1.69 1.70 1.70 1.703F 21.36 21.38 22.56 22.54 22.56 22.56 22.64 25.10 25.36 25.631F 20.76 20.77 22.24 22.23 22.25 22.25 22.30 24.26 24.42 24.583F 4.64 4.64 4.66 4.65 4.67 4.66 5.36 5.36 5.36 5.371F 3.14 3.14 3.14 3.14 3.14 3.14 3.74 3.75 3.75 3.753F 15.89 15.92 16.15 16.12 16.25 16.19 16.40 19.27 19.37 19.411F 14.48 14.57 14.72 14.70 14.77 14.74 14.87 16.86 16.94 16.963F 5.58 5.58 6.00 5.99 6.00 5.78 5.45 5.99 6.76 6.771F 4.57 4.58 5.21 5.27 5.27 4.89 4.38 5.32 5.72 5.723F 3.48 3.49 3.48 3.49 3.49 3.91 3.91 3.91 3.91 3.931F 2.94 2.94 2.94 2.94 2.94 3.25 3.25 3.25 3.25 3.263F 1.97 1.97 1.97 1.97 1.97 2.02 2.02 2.02 2.03 2.031F 2.47 2.47 2.47 2.47 2.47 2.53 2.53 2.53 2.53 2.533F 5.11 6.57 6.57 6.37 6.37 6.39 6.39 6.45 6.46 6.481F 3.43 5.18 4.44 4.57 4.57 4.58 4.58 4.60 4.61 4.613F 13.25 13.23 13.32 13.29 13.63 13.59 13.73 13.62 13.80 13.891F 9.74 9.74 9.77 9.76 9.89 9.88 9.95 9.89 9.95 9.983F 2.74 4.44 4.441F 3.17 5.00 5.003F 7.31 10.23 10.241F 9.78 13.50 13.513F 11.25 11.37 14.801F 10.23 10.29 14.713F 15.59 15.66 15.961F 15.62 15.67 16.983F 6.03 6.04 6.08 5.08 6.30 6.17 6.47 6.69 6.69 6.571F 6.47 6.48 6.51 5.69 6.68 6.59 6.82 7.07 7.07 6.963F 9.05 9.07 9.11 7.84 9.37 9.23 9.56 9.76 9.77 9.631F 10.94 10.96 11.00 9.72 11.25 11.12 11.43 11.68 11.68 11.553F 6.34 6.35 6.37 5.76 6.50 6.43 6.59 6.69 6.69 6.631F 5.66 5.66 5.67 5.34 5.74 5.71 5.79 5.86 5.86 5.823F 3.82 3.83 3.83 3.82 3.84 3.84 3.86 3.88 3.88 3.881F 2.50 2.50 2.50 2.50 2.50 2.50 2.51 2.52 2.52 2.523F 6.93 6.94 6.93 7.04 6.94 6.89 7.17 7.29 7.53 7.731F 6.45 6.46 6.45 6.51 6.42 6.39 6.81 6.88 7.04 7.16

CPE

Botello BOT

Calera Industrial CAI 115

115

115

Calvillo CVO

Campestre

230

115Calera CAL

115

Cajitittlán CJT

230

69

Cadereyta CDY

Bugambilias BUG 69

230

69

Buenavista Norte BNN 115

Boquilla BQL 115

115

Bocas BOC 115

Bom Lam BLM 115

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Bañón BON 115

Black & Decker (APPLICA) APM 115

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 131: Catalogo 2011-2020 r010212 Corto Circuito

131

Coordinación de Planificación

ÁREA OCCIDENTAL

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 13.65 13.81 14.27 13.93 15.09 14.22 16.70 16.82 16.90 17.141F 14.15 14.33 14.78 14.53 15.56 14.60 17.18 17.31 17.36 17.523F 16.98 17.12 17.44 16.76 17.67 17.61 18.64 18.95 19.01 19.091F 19.72 19.90 20.23 19.61 20.45 20.36 21.40 21.73 21.77 21.833F 19.84 19.94 20.18 19.79 20.40 20.31 21.37 22.01 22.05 22.091F 20.54 20.64 20.85 20.57 21.04 20.92 21.89 22.51 22.53 22.563F 2.16 2.16 2.16 2.18 2.18 2.28 2.28 2.28 2.28 2.311F 1.43 1.43 1.43 1.44 1.44 1.47 1.47 1.47 1.47 1.483F 11.04 11.12 11.11 11.22 11.15 11.24 11.37 11.42 11.48 11.821F 10.47 10.53 10.52 10.63 10.56 10.87 10.95 10.98 11.03 11.243F 14.00 14.08 14.03 14.39 14.31 14.71 14.86 14.94 15.00 15.531F 16.53 16.61 16.56 16.98 16.88 17.30 17.46 17.53 17.60 18.083F 13.23 13.26 13.22 13.28 13.24 13.99 14.03 14.08 14.11 14.361F 15.87 15.91 15.87 15.94 15.90 16.65 16.68 16.73 16.76 16.993F 10.97 10.97 10.97 11.01 11.00 11.34 11.36 11.39 11.41 11.571F 11.01 11.02 11.01 11.05 11.03 11.27 11.29 11.31 11.33 11.433F 7.71 7.71 7.67 7.73 7.72 7.72 7.70 7.75 7.75 7.751F 5.81 5.81 5.80 5.82 5.82 5.82 5.81 5.83 5.83 5.833F 19.65 19.66 20.49 20.47 20.49 20.49 20.56 22.76 22.98 23.201F 17.60 17.60 18.47 18.46 18.47 18.47 18.50 20.01 20.12 20.233F 15.28 15.30 15.32 15.32 15.32 15.31 15.30 15.73 16.43 16.451F 15.83 15.84 15.86 15.85 15.86 15.85 15.84 16.17 16.64 16.653F 16.70 16.77 16.82 10.21 10.18 10.19 10.11 12.20 12.25 12.421F 17.37 17.45 17.48 11.48 11.45 11.46 11.38 13.08 13.12 13.253F 10.10 10.11 10.11 10.10 10.24 10.10 10.31 10.31 10.34 10.581F 7.34 7.35 7.33 7.34 7.39 7.34 7.41 7.41 7.42 7.513F 2.17 5.25 4.46 5.26 5.26 5.24 5.25 5.25 5.30 5.321F 1.78 4.11 4.10 4.11 4.11 4.11 4.11 4.11 4.13 4.143F 8.70 8.70 8.63 8.74 8.71 8.72 8.68 8.75 8.75 8.751F 6.80 6.80 6.77 6.82 6.81 6.81 6.79 6.82 6.82 6.823F 4.86 4.86 4.86 4.87 4.86 4.95 4.96 4.96 4.97 4.991F 3.73 3.74 3.73 3.74 3.74 3.78 3.78 3.79 3.79 3.803F 10.03 10.04 10.02 10.13 10.15 11.12 11.18 11.17 11.29 11.451F 7.20 7.20 7.19 7.28 7.28 8.00 8.01 8.02 8.07 8.133F 5.87 5.89 5.89 6.07 6.07 7.09 7.09 7.22 7.24 7.491F 4.79 4.80 4.80 4.89 4.89 5.37 5.37 5.53 5.54 5.63

CLE

Cañada KDA

Carapan CRP

Castillo CST

Celanece Carapan CME 115

115

115

Celanese Celaya CEE

Celanese Ocotlán

Catarina CTA 115

Cayacal CAY 115

Cartones Ponderosa CAP 115

69

115Castro del Río CIO

Carbonser CSR 115

Cardanes CES 115

115

Carapan Distribución CRD 115

400

230

115

Capilla de Guadalupe CPG 115

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

400

230

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 132: Catalogo 2011-2020 r010212 Corto Circuito

132

Coordinación de Planificación

ÁREA OCCIDENTAL

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 14.43 14.44 14.40 14.47 14.51 15.22 15.34 15.33 15.67 16.081F 12.97 12.98 12.94 13.02 13.03 13.59 13.65 13.66 13.94 14.173F 15.42 15.43 15.39 15.64 15.69 18.14 18.29 18.28 18.58 19.041F 12.41 12.42 12.39 12.65 12.65 14.98 15.05 15.06 15.25 15.473F 15.72 15.75 15.67 15.65 15.71 15.63 15.87 15.89 16.79 17.751F 14.24 14.25 14.17 14.21 14.22 14.19 14.32 14.36 15.09 15.643F 21.80 21.82 21.76 21.74 21.81 21.75 21.96 21.95 22.49 23.171F 23.08 23.10 23.02 23.04 23.08 23.04 23.20 23.21 23.72 24.243F 15.32 15.34 15.25 15.23 15.24 15.15 15.46 15.46 17.11 18.661F 13.55 13.56 13.41 13.52 13.47 13.47 13.63 13.65 15.32 16.293F 17.09 17.10 17.06 17.13 17.17 17.92 18.09 18.08 18.60 19.191F 17.78 17.80 17.72 17.83 17.85 18.55 18.67 18.67 19.27 19.733F 17.08 17.10 17.06 17.05 17.10 17.06 17.19 17.18 17.48 17.871F 14.70 14.71 14.68 14.69 14.70 14.69 14.75 14.76 14.94 15.143F 12.45 12.46 12.44 12.44 12.46 12.54 12.61 12.61 12.82 13.071F 9.63 9.63 9.61 9.62 9.63 9.67 9.70 9.70 9.82 9.923F 11.42 11.43 11.41 12.05 12.08 12.80 12.88 12.87 13.01 13.221F 8.28 8.28 8.27 8.82 8.82 9.38 9.41 9.41 9.48 9.563F 6.59 6.64 6.65 6.65 6.65 6.65 6.65 6.62 6.74 6.741F 4.48 4.50 4.46 4.50 4.50 4.48 4.50 4.49 4.53 4.443F 1.15 1.15 1.15 1.15 1.15 1.15 1.43 1.43 1.43 1.431F 0.75 0.75 0.75 0.75 0.75 0.75 0.94 0.94 0.94 0.943F 4.14 4.27 4.16 4.28 4.28 4.26 4.26 4.28 4.29 4.301F 3.59 3.67 3.59 3.67 3.67 3.66 3.66 3.67 3.67 3.683F 6.03 6.04 6.04 6.93 6.92 6.91 6.91 6.91 6.93 6.961F 4.11 4.11 4.12 5.32 5.32 5.32 5.32 5.32 5.33 5.343F 5.58 5.59 5.58 5.64 5.55 5.53 5.61 5.69 5.86 5.961F 4.80 4.81 4.80 4.83 4.78 4.77 4.88 4.92 5.01 5.063F 12.43 12.69 12.75 12.75 12.79 12.72 12.96 13.01 13.16 13.261F 13.84 14.12 14.15 14.17 14.70 14.65 14.82 14.86 14.97 15.043F 8.09 8.25 8.39 8.40 8.44 8.461F 9.55 9.71 9.82 9.83 9.86 9.873F 7.94 7.95 7.98 6.99 8.18 8.07 8.32 8.48 8.48 8.381F 8.53 8.54 8.56 7.77 8.71 8.64 8.83 8.97 8.97 8.893F 11.92 11.94 11.98 12.00 18.11 18.05 18.18 18.12 18.32 18.921F 9.24 9.26 9.27 9.28 14.54 14.52 14.58 14.55 14.63 14.88

CER

Cervecería Modelo CMM

Celaya II CYA

Celaya III CEY

Cementos Tolteca, Ciudad Guzmán CTK

230

115

69

Cerro Blanco CRB

Cervecera Coronna

Cepamisa CMS 115

400

Cementos Moctezuma, Matehuala CEM 115

115

69Cemex México, Guadalajara CEG

Celaya Sur CYS 115

Cementos Mexicanos. San Juan del Río CMX 230

Celaya Industrial CYI 115

Celaya Poniente CLP 115

230

115

230

115

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Celaya Aeropuerto CAE 115

Celaya I CLY 115

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 133: Catalogo 2011-2020 r010212 Corto Circuito

133

Coordinación de Planificación

ÁREA OCCIDENTAL

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 1.51 1.53 1.51 1.51 1.51 1.51 1.51 1.51 1.51 1.521F 0.96 0.97 0.96 0.96 0.97 0.96 0.96 0.96 0.96 0.973F 5.43 5.44 5.45 4.75 4.75 4.75 4.73 6.46 6.47 11.041F 3.88 3.88 3.89 3.63 3.63 3.63 3.62 4.60 4.61 9.163F 4.65 4.65 4.66 4.65 4.66 4.65 5.10 5.10 5.10 5.111F 4.95 4.95 4.96 4.93 4.94 4.94 5.41 5.41 5.41 5.413F 3.86 3.86 3.87 3.87 3.88 3.87 4.18 4.18 4.18 4.181F 3.64 3.64 3.65 3.64 3.65 3.65 3.90 3.90 3.90 3.903F 3.25 3.25 3.26 3.26 3.27 3.27 4.00 4.01 4.01 4.011F 3.10 3.10 3.11 3.11 3.11 3.11 3.86 3.86 3.86 3.863F 5.00 5.00 5.02 5.01 5.03 5.02 5.54 5.55 5.55 5.551F 5.65 5.65 5.66 5.66 5.67 5.67 6.29 6.30 6.30 6.303F 2.39 2.39 2.44 2.46 2.22 2.83 2.83 2.84 2.84 2.841F 2.71 2.71 2.75 2.79 2.57 3.11 3.10 3.11 3.11 3.113F 6.21 6.23 6.21 6.06 6.06 6.08 6.08 6.12 6.13 6.151F 4.28 4.30 4.28 4.48 4.48 4.49 4.49 4.50 4.51 4.513F 13.23 13.26 13.22 13.28 13.24 13.99 14.03 14.08 14.11 14.361F 15.87 15.91 15.87 15.94 15.90 16.65 16.68 16.73 16.76 16.993F 4.13 4.13 4.14 3.93 3.93 3.96 3.95 12.98 13.03 7.311F 2.99 3.00 3.00 2.92 2.92 2.94 2.93 11.61 11.63 5.403F 5.14 5.15 5.16 4.80 5.25 5.21 5.31 5.38 5.38 5.341F 4.08 4.08 4.09 3.93 4.12 4.11 4.15 4.19 4.19 4.183F 18.13 18.17 18.06 18.03 18.42 17.98 18.62 18.63 18.76 19.691F 18.36 18.40 18.02 18.31 18.54 18.25 18.68 18.69 18.78 19.493F 18.07 18.11 18.39 18.36 18.52 18.44 18.73 21.68 21.98 22.031F 18.00 18.13 18.33 18.31 18.42 18.37 18.57 20.82 21.12 21.143F 6.48 6.63 6.52 6.21 6.28 6.18 6.23 6.30 6.33 6.381F 4.64 4.70 4.53 4.44 4.47 4.44 4.46 4.49 4.50 4.523F 17.37 17.38 17.49 17.47 17.49 17.49 17.53 18.28 18.44 18.581F 14.22 14.22 14.30 14.29 14.30 14.30 14.32 14.71 14.77 14.833F 4.90 4.90 5.30 5.29 5.34 5.34 5.37 5.37 5.38 5.381F 3.72 3.73 3.95 3.95 3.97 3.97 3.98 3.98 3.98 3.983F 4.87 5.04 4.93 5.05 5.06 5.00 5.01 5.04 5.08 5.121F 4.67 4.79 4.68 4.79 4.80 4.76 4.77 4.79 4.81 4.833F 6.40 6.75 6.45 6.76 6.76 6.71 6.72 6.75 6.79 6.821F 7.37 7.69 7.36 7.70 7.70 7.66 7.67 7.69 7.72 7.75

Charcas Potencia CHK

Cifunsa CIF

Cinco de Mayo MAY 115

Ciudad Guzmán CGM

230

115

Cihuatlán CIH 115

Cimatario CMT 115

Cieneguillas CGS 115

115

115Cigarrera CIG

Churintzio CRZ 115

Ciba CBA 69

Chilatán CHN 115

Chipilo CHI 115

230

115

Charcas CAK 115

Charcas IMMSA MCH 115

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Chamela CML 115

Chapala CHA 69

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 134: Catalogo 2011-2020 r010212 Corto Circuito

134

Coordinación de Planificación

ÁREA OCCIDENTAL

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 2.09 2.10 2.09 2.09 2.17 2.16 2.16 2.17 2.17 2.181F 1.34 1.34 1.34 1.34 1.42 1.42 1.42 1.42 1.42 1.423F 1.25 1.25 1.25 1.25 1.26 1.26 1.25 1.25 1.26 1.261F 0.82 0.82 0.82 0.82 0.83 0.82 0.82 0.82 0.82 0.823F 4.46 4.46 4.40 4.42 4.33 5.33 5.28 5.34 5.40 5.421F 4.64 4.65 4.60 4.67 4.55 5.34 5.31 5.34 5.40 5.413F 4.51 4.51 4.77 4.51 4.51 4.63 4.04 4.63 4.63 4.631F 4.86 4.86 4.99 4.86 4.86 4.95 4.43 4.95 4.95 4.953F 11.88 11.89 11.86 11.85 11.98 11.86 12.07 12.08 12.11 12.381F 8.93 8.94 8.91 8.92 8.95 8.93 9.01 9.01 9.02 9.133F 9.21 9.21 9.20 9.23 9.25 9.60 9.64 9.64 9.77 9.921F 6.91 6.91 6.90 6.93 6.93 7.14 7.16 7.16 7.23 7.293F 5.57 5.57 5.55 5.51 5.52 5.57 5.581F 4.42 4.42 4.42 4.39 4.39 4.41 4.423F 6.52 5.57 6.171F 4.42 4.42 1.383F 7.35 7.56 7.54 7.58 7.62 7.38 7.34 7.51 7.57 7.701F 7.12 7.26 7.24 7.27 7.31 7.16 7.13 7.23 7.27 7.363F 9.72 9.89 9.89 9.92 10.22 10.00 9.80 9.95 10.01 10.131F 11.29 11.46 11.45 11.48 11.79 11.60 11.40 11.53 11.59 11.703F 13.97 14.04 15.10 15.15 15.27 15.24 15.27 15.29 15.36 15.481F 14.51 14.58 15.42 15.46 15.54 15.52 15.54 15.55 15.60 15.683F 14.57 15.40 15.38 15.10 15.12 14.03 14.07 14.84 15.27 15.921F 16.67 17.46 17.12 16.89 16.95 15.97 16.01 16.71 17.10 17.683F 18.30 19.03 18.64 15.76 16.15 15.53 15.87 16.34 16.61 16.981F 20.99 21.65 18.80 16.75 17.15 16.65 17.10 17.48 17.70 18.003F 18.22 18.93 18.57 15.79 16.16 15.53 15.82 16.29 16.55 16.921F 20.54 21.18 18.57 16.63 16.99 16.50 16.87 17.24 17.45 17.743F 10.24 10.32 10.37 10.48 10.55 10.46 11.72 10.48 10.84 10.981F 9.68 9.76 9.78 9.88 9.92 9.88 10.92 9.88 10.10 10.173F 3.54 3.54 3.55 3.38 3.59 3.57 3.62 3.65 3.65 3.631F 2.56 2.56 2.56 2.50 2.57 2.57 2.58 2.60 2.60 2.593F 2.59 2.59 2.69 2.72 2.73 2.73 2.74 2.74 2.74 2.741F 1.75 1.75 1.80 1.81 1.82 1.82 1.82 1.82 1.82 1.823F 3.03 3.03 3.09 3.13 2.84 4.00 4.00 4.01 4.01 4.031F 2.24 2.24 2.26 2.37 2.18 2.79 2.79 2.79 2.79 2.80

CBR

Compañía Fresnillo CIA 115

115

115

Compostela CMP

Condémbaro

Colomo Distribución CDI 115

Colón SJZ 230

Colimilla CLL 69

Colomo COL

230

115

230

115Colima II CMD

115

69Cocula CLA

Cobarrubias CBB 115

Cobrecel COB 115

Cóbano CBN 161

Cóbano CBN 69

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Coahuayana CHY 115

Coalcomán CAN 115

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 135: Catalogo 2011-2020 r010212 Corto Circuito

135

Coordinación de Planificación

ÁREA OCCIDENTAL

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 15.71 15.72 15.75 15.74 15.75 15.74 15.73 16.19 16.92 16.941F 16.49 16.50 16.52 16.52 16.52 16.51 16.50 16.86 17.37 17.383F 18.03 18.04 18.04 18.00 18.02 18.02 18.08 21.72 22.14 22.431F 17.49 17.50 17.63 17.60 17.62 17.62 17.66 22.00 22.27 22.463F 22.05 22.07 22.16 22.13 22.15 22.14 22.20 23.85 24.15 24.351F 24.94 24.96 25.09 25.06 25.08 25.08 25.12 26.96 27.21 27.373F 9.19 9.20 9.18 9.22 9.23 9.54 9.58 9.58 9.71 9.861F 6.96 6.96 6.95 6.98 6.98 7.15 7.17 7.17 7.25 7.313F 2.71 2.71 2.71 2.71 2.71 2.71 2.71 2.73 2.73 2.731F 1.70 1.70 1.70 1.70 1.70 1.70 1.70 1.71 1.71 1.713F 14.13 14.17 14.21 9.88 9.86 9.86 9.78 11.72 11.76 11.921F 13.98 14.03 14.05 10.79 10.76 10.77 10.70 12.17 12.20 12.313F 23.00 23.43 23.991F 23.84 24.15 24.543F 29.27 29.63 30.031F 33.40 33.71 34.043F 8.89 8.90 8.89 8.94 8.96 9.47 9.51 9.51 9.61 9.741F 6.41 6.41 6.41 6.45 6.45 6.79 6.80 6.80 6.85 6.903F 2.19 2.19 2.19 2.22 2.22 5.43 5.43 5.44 5.44 5.531F 1.48 1.48 1.48 1.49 1.49 3.65 3.65 3.66 3.66 3.693F 6.66 6.66 6.66 6.74 6.61 6.59 6.70 6.81 7.05 7.201F 6.26 6.26 6.26 6.31 6.21 6.20 6.39 6.46 6.62 6.703F 2.85 2.85 2.92 2.95 2.59 3.58 3.58 3.58 3.59 3.591F 2.82 2.82 2.86 2.97 2.65 3.38 3.38 3.38 3.39 3.393F 5.77 5.79 5.82 5.58 5.85 5.85 6.02 6.12 6.13 6.101F 4.23 4.24 4.25 4.16 4.26 4.26 4.32 4.39 4.39 4.373F 12.24 12.25 12.20 12.18 12.19 12.13 12.33 12.33 13.36 14.291F 9.88 9.89 9.81 9.87 9.85 9.84 9.93 9.94 10.80 11.273F 11.79 11.80 11.69 11.68 13.79 13.67 13.87 13.87 13.95 14.531F 10.71 10.72 10.57 10.63 11.66 11.72 11.70 11.70 11.74 12.083F 4.03 4.06 4.06 4.07 4.12 4.08 4.05 4.07 4.08 4.101F 3.03 3.04 3.04 3.05 3.07 3.05 3.04 3.05 3.05 3.063F 5.93 5.93 5.92 5.92 5.94 5.92 5.96 5.96 5.97 6.041F 4.30 4.31 4.30 4.30 4.31 4.30 4.32 4.32 4.32 4.35

Conin CNI

Corregidora CRG

Crucero II CCR

Cuauhtémoc SCC 115

115Cuerámaro CUE

Cryoinfra Celaya CRY 230

Cryoinfra Salamanca ARG 115

Crisoba CSD 115

115

230Cruz Azul CZA

Cortazar CRT 115

Cotija CTJ 115

230

115

Coroneo COO 115

Corporación Occidente COC 69

115

Contincon CON 115

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Conductel CDT 115

230

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 136: Catalogo 2011-2020 r010212 Corto Circuito

136

Coordinación de Planificación

ÁREA OCCIDENTAL

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 6.14 6.16 6.16 6.36 6.36 7.48 7.48 7.64 7.65 7.931F 5.10 5.10 5.11 5.21 5.21 5.75 5.75 5.94 5.94 6.053F 3.53 3.53 3.53 3.47 3.47 3.53 3.53 5.08 5.08 4.421F 2.99 3.00 3.00 2.97 2.97 3.01 3.00 4.09 4.09 3.613F 3.01 3.01 3.01 3.03 2.97 2.96 3.47 3.50 3.55 3.591F 2.14 2.14 2.14 2.14 2.10 2.09 2.57 2.58 2.60 2.613F 17.57 17.65 17.80 17.55 17.91 17.92 18.64 18.82 18.85 18.921F 16.12 16.19 16.28 16.14 16.34 16.35 16.77 16.90 16.91 16.953F 5.13 5.13 5.07 5.09 5.14 6.17 6.13 6.18 6.29 6.321F 5.73 5.74 5.69 5.76 5.78 6.66 6.62 6.67 6.80 6.823F 16.24 16.27 16.49 16.47 16.60 16.54 16.76 19.07 19.25 19.291F 15.10 15.19 15.33 15.31 15.39 15.35 15.49 16.99 17.14 17.153F 14.35 14.40 14.45 10.08 10.05 10.05 9.97 11.99 12.04 12.201F 14.47 14.53 14.56 11.18 11.15 11.15 11.08 12.67 12.70 12.823F 5.13 5.18 5.13 5.09 6.07 5.98 5.98 6.04 6.07 6.121F 3.48 3.50 3.46 3.45 5.03 4.99 4.98 5.01 5.03 5.053F 11.75 11.76 11.72 11.71 11.86 11.69 11.95 11.95 12.00 12.361F 9.26 9.27 9.19 9.25 9.31 9.24 9.34 9.35 9.37 9.533F 12.05 12.21 12.25 12.24 12.26 12.25 12.25 12.14 12.55 12.571F 9.19 9.26 9.10 9.26 9.27 9.18 9.27 9.24 9.39 9.003F 18.17 18.22 18.50 18.47 18.63 18.55 18.84 22.07 22.34 22.391F 18.07 18.20 18.41 18.39 18.50 18.44 18.65 21.17 21.43 21.463F 12.83 12.84 12.78 12.77 12.77 12.71 12.93 12.93 14.06 15.091F 10.53 10.54 10.45 10.52 10.49 10.49 10.59 10.59 11.58 12.123F 2.11 2.11 1.18 2.11 2.11 2.11 1.18 2.11 2.11 2.111F 1.57 1.57 0.95 1.57 1.57 1.57 0.96 1.57 1.57 1.573F 3.11 3.11 3.66 3.60 4.28 4.28 4.42 4.42 4.42 3.941F 2.66 2.66 3.12 3.30 3.65 3.66 3.72 3.72 3.73 3.243F 3.30 3.28 3.32 3.28 3.28 3.28 3.28 3.28 3.30 3.301F 2.10 2.10 0.27 2.10 2.10 2.10 2.10 2.10 2.10 2.103F 16.69 16.73 16.97 16.94 17.08 17.01 17.25 19.73 19.98 20.021F 15.83 15.93 16.09 16.07 16.15 16.11 16.27 17.97 18.19 18.213F 23.58 23.59 25.00 24.97 25.00 25.00 25.10 28.44 28.79 29.131F 24.30 24.31 26.30 26.29 26.31 26.31 26.38 29.58 29.82 30.053F 6.47 6.48 6.47 6.47 6.59 7.92 7.93 7.95 8.21 8.231F 4.41 4.43 4.41 4.42 4.52 5.67 5.67 5.68 5.87 5.87

DHD

Cuitzeo CZO

De Acero Celaya DEA

Descansadero DSC

Dicumsa DIC 115

115

115

Distex DIX

Dolores Hidalgo

Destiladeras DST 115

Diatomita DTM 69

Dasa DAS 115

230

69

Danone DNN 115

Dañu DAN 230

Cydsa CLD 69

Danisco DAN 115

Cupatitzio CPT 161

Cupro CSL 115

Cuitzeo CTZ 115

Cumbres CUM 115

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

115

69

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 137: Catalogo 2011-2020 r010212 Corto Circuito

137

Coordinación de Planificación

ÁREA OCCIDENTAL

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 15.05 15.08 15.28 15.26 15.37 15.31 15.51 17.82 17.90 17.941F 13.39 13.47 13.59 13.58 13.63 13.61 13.72 15.19 15.25 15.273F 15.58 15.61 15.84 15.82 15.94 15.88 16.09 19.85 19.86 19.901F 14.06 14.16 14.32 14.31 14.37 14.34 14.47 17.37 17.38 17.403F 11.68 11.70 11.81 11.79 11.79 13.20 13.56 13.58 13.62 13.911F 10.14 10.15 10.23 10.23 10.23 10.87 11.04 11.05 11.06 11.193F 6.61 6.62 6.62 5.82 5.81 5.83 5.81 8.93 8.96 7.321F 4.87 4.88 4.88 4.57 4.56 4.57 4.56 6.95 6.96 5.503F 8.99 8.99 9.02 9.01 9.02 9.01 9.01 9.18 9.32 9.331F 6.17 6.17 6.18 6.18 6.18 6.18 6.18 6.26 6.30 6.303F 3.99 3.99 3.99 3.81 3.80 3.84 3.83 11.25 11.29 6.781F 2.89 2.89 2.89 2.82 2.82 2.84 2.83 9.43 9.45 4.943F 4.12 4.12 4.14 4.14 4.14 4.14 4.15 4.35 4.35 4.351F 2.73 2.74 2.74 2.74 2.75 2.74 2.75 2.83 2.83 2.833F 10.58 10.76 10.80 10.81 10.83 10.78 10.94 10.98 11.08 11.151F 12.83 13.04 13.07 13.08 13.27 13.24 13.37 13.39 13.47 13.523F 2.34 2.34 2.50 2.22 2.23 2.23 2.23 2.23 2.23 2.231F 1.54 1.54 1.67 1.44 1.44 1.44 1.44 1.44 1.44 1.443F 2.91 2.91 2.911F 2.71 2.78 2.803F 14.26 14.29 14.61 14.58 14.56 15.99 16.55 16.58 16.65 17.131F 13.29 13.32 13.52 13.55 13.54 14.32 14.62 14.64 14.67 14.923F 2.20 2.20 2.19 2.00 2.00 2.01 2.011F 1.40 1.40 1.40 1.27 1.28 1.28 1.283F 1.83 2.21 1.841F 1.22 1.41 1.223F 11.73 14.83 14.90 14.96 15.151F 10.24 15.10 15.15 15.19 15.323F 13.93 13.93 13.97 13.96 13.96 13.96 13.98 14.55 14.70 14.761F 11.07 11.07 11.10 11.09 11.09 11.09 11.10 11.40 11.46 11.493F 11.61 11.61 11.63 11.63 11.63 11.63 11.64 11.98 12.13 12.161F 8.46 8.46 8.47 8.47 8.47 8.47 8.47 8.63 8.68 8.693F 3.43 3.43 3.43 3.24 3.47 3.45 3.50 3.52 3.52 3.511F 2.55 2.55 2.55 2.48 2.56 2.56 2.57 2.58 2.59 2.583F 17.46 17.29 17.34 17.36 17.56 17.51 17.57 17.59 17.72 17.831F 13.20 13.14 13.15 13.17 13.25 13.23 13.25 13.26 13.31 13.35

El Pardillo PRL

El Pinar PNR

El Marquéz Sur MSU 115

115

69

El Llano LLO 400

El Marquéz MRQ 115

El Granjeno EGJ 115

El Grullo GRU

115

69

El Cajón Distribución SCJ 115

El Cuarenta ELC 115

El Arbolito ABO 115

El Cajón CJN 400

EFFEM (Qro) EFM 115

EFFEM (Jal) MTF 69

Ecos III ECS 115

Edosa (PEPSI) EDS 69

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Draexlmaier Comp. A. DCA 115

Eaton Truck ETR 115

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 138: Catalogo 2011-2020 r010212 Corto Circuito

138

Coordinación de Planificación

ÁREA OCCIDENTAL

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 11.35 11.41 11.61 11.53 11.79 11.69 12.23 12.07 12.09 12.151F 11.39 11.47 11.61 11.55 11.73 11.66 12.08 12.58 12.60 12.653F 15.27 15.33 15.64 15.58 15.83 15.72 16.22 16.20 16.23 16.281F 17.49 17.59 17.88 17.82 18.04 17.94 18.50 18.72 18.74 18.793F 20.00 20.05 20.29 20.23 20.45 20.35 20.85 20.81 20.84 20.891F 20.71 20.77 20.95 20.91 21.06 20.99 21.38 21.58 21.60 21.633F 1.79 1.79 1.78 1.80 1.80 1.80 1.80 1.83 1.831F 1.12 1.12 1.15 1.16 1.16 1.16 1.16 1.18 1.183F 16.00 16.06 16.10 9.33 9.31 9.31 9.24 10.95 10.99 11.131F 15.46 15.53 15.55 9.74 9.72 9.73 9.67 10.86 10.88 10.973F 18.18 18.20 18.21 18.18 18.20 18.20 18.22 20.46 20.99 21.131F 20.68 20.69 20.71 20.69 20.71 20.70 20.72 22.86 23.28 23.393F 22.17 22.19 22.22 22.21 22.22 22.21 22.20 23.03 23.77 23.831F 27.75 27.77 27.81 27.79 27.80 27.79 27.78 28.63 29.35 29.413F 3.97 3.97 3.97 3.97 3.97 4.68 4.69 4.69 4.70 4.741F 2.71 2.72 2.71 2.72 2.71 3.20 3.21 3.21 3.21 3.223F 21.09 21.15 21.26 21.33 23.85 23.74 24.13 23.85 24.25 24.651F 20.84 20.93 21.00 21.06 22.69 22.63 22.91 22.69 22.92 23.153F 4.49 4.49 4.50 4.49 4.51 4.51 4.54 4.57 4.57 4.571F 2.98 2.98 2.99 2.98 2.99 2.99 2.99 3.01 3.01 3.013F 5.27 5.28 6.52 6.51 6.51 7.24 7.33 7.33 7.34 7.411F 3.91 3.91 4.91 4.91 4.91 5.08 5.11 5.11 5.11 5.143F 9.07 9.08 9.15 9.14 9.18 9.16 9.23 9.88 9.96 9.971F 6.77 6.79 6.82 6.82 6.83 6.82 6.85 7.13 7.17 7.183F 8.20 8.20 8.20 8.20 8.21 8.23 8.25 8.26 8.31 8.381F 5.64 5.65 5.64 5.65 5.65 5.66 5.67 5.67 5.69 5.713F 8.89 8.91 8.92 6.58 6.57 6.57 6.54 7.32 7.34 7.401F 6.81 6.83 6.83 5.61 5.60 5.61 5.59 5.95 5.96 5.983F 4.58 4.58 4.59 4.58 4.60 4.60 4.65 4.65 4.65 4.661F 3.00 3.00 3.01 3.00 3.01 3.01 3.02 3.03 3.03 3.033F 19.65 19.66 20.49 20.47 20.49 20.49 20.56 22.76 22.98 23.201F 17.60 17.60 18.47 18.46 18.47 18.47 18.50 20.01 20.12 20.233F 13.33 13.37 13.40 13.39 13.34 13.31 13.28 13.21 13.29 13.351F 10.89 10.93 10.94 10.72 10.70 10.69 10.67 10.64 10.68 10.693F 14.04 14.09 14.13 9.82 9.80 9.80 9.73 11.63 11.68 11.841F 13.81 13.86 13.89 10.67 10.64 10.65 10.58 12.02 12.05 12.16

EME

Envases Inovativos EIN

Envases Universales EUM

El Potosí EPS

Engranes Cónicos ENC 115

69

69

Empaques Modernos EMP 69

Encarnación de Díaz ENC 115

El Toro TOO 115

115

115

Electroquímica ELQ

Empalme Escobedo

El Sol SOL 69

El Taray TAY 115

115

El Sol ESO 115

El Sáuz SAU

El Salto ESJ 69

230

115

El Realito REA 115

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

400

230

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 139: Catalogo 2011-2020 r010212 Corto Circuito

139

Coordinación de Planificación

ÁREA OCCIDENTAL

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 13.94 13.95 14.01 14.00 14.01 14.01 14.04 14.45 14.55 14.641F 10.68 10.69 10.72 10.72 10.72 10.72 10.73 10.92 10.95 10.993F 3.59 3.59 3.60 3.55 4.15 4.13 4.23 4.99 5.00 4.981F 2.36 2.37 2.37 2.36 2.75 2.75 2.80 3.54 3.54 3.533F 2.69 2.69 2.69 2.68 2.68 2.69 2.691F 1.92 1.92 1.92 1.92 1.92 1.92 1.923F 4.06 2.69 3.391F 2.84 1.93 1.723F 9.37 9.37 9.45 9.47 9.70 9.68 9.69 9.70 9.74 9.771F 6.59 6.60 6.63 6.64 6.72 6.71 6.72 6.72 6.73 6.743F 7.85 7.85 7.91 7.91 7.91 7.88 7.83 7.92 8.80 8.801F 5.45 5.46 5.50 5.51 5.51 5.48 5.44 6.15 6.50 6.503F 6.23 6.24 6.24 12.67 12.15 12.12 12.16 12.07 12.14 12.191F 4.26 4.27 4.27 9.66 9.44 9.44 9.45 9.41 9.44 9.463F 7.20 7.20 7.19 7.88 7.21 7.21 7.22 7.22 7.24 7.241F 5.34 5.35 5.34 5.67 5.35 5.35 5.35 5.35 5.36 5.363F 15.86 15.90 16.11 16.09 16.21 16.15 16.37 18.85 18.97 19.001F 14.52 14.61 14.75 14.74 14.80 14.77 14.90 16.55 16.64 16.663F 15.41 15.41 15.69 15.67 15.69 15.68 15.72 16.49 16.61 16.731F 12.01 12.02 12.21 12.21 12.21 12.21 12.23 12.59 12.64 12.683F 3.16 3.17 4.60 4.54 5.63 5.64 5.87 5.87 5.88 4.491F 2.72 2.72 2.92 4.89 5.69 5.70 5.86 5.86 5.86 3.883F 10.93 10.90 10.92 10.93 11.18 11.16 11.19 11.19 11.25 11.311F 7.69 7.69 7.70 7.70 7.79 7.78 7.79 7.79 7.81 7.833F 13.12 13.17 13.39 13.35 13.54 13.45 13.75 14.59 14.64 14.681F 12.60 12.81 12.97 12.94 13.06 13.00 13.20 13.86 13.92 13.943F 19.69 19.70 20.54 20.52 20.54 20.54 20.60 22.82 23.04 23.261F 17.66 17.67 18.53 18.53 18.54 18.54 18.57 20.09 20.20 20.313F 6.87 6.87 6.90 5.62 7.05 6.98 7.14 7.24 7.24 7.181F 7.59 7.60 7.62 6.48 7.74 7.69 7.81 7.90 7.90 7.853F 4.45 4.46 4.48 3.30 4.61 4.56 4.68 4.77 4.77 4.721F 4.67 4.67 4.69 3.68 4.79 4.75 4.84 4.91 4.91 4.883F 7.24 7.25 7.28 5.84 7.44 7.37 7.54 7.66 7.66 7.591F 8.58 8.59 8.62 7.16 8.78 8.71 8.87 8.98 8.98 8.923F 6.79 6.79 6.82 5.74 6.96 6.89 7.06 7.16 7.16 7.101F 6.64 6.64 6.66 5.91 6.75 6.71 6.81 6.88 6.88 6.84

FND

Fresnillo Potencia FSO

Fresnillo Sur FNO

Estancita ETA

230

115

115

Forjas Spicer FSP 115

Fresnillo Norte FRN 115

Flamingos FLA 115

69

230

Flextronics FLM

Fonderia

Fevisa Industrial FID 115

Field Cointeiner FCQ 115

Fertimex Guadalajara FTM 69

Fertimex Lázaro Cárdenas FTM 230

Experiencia EXP 69

Ezequiel Montes EZM 115

115

69

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Estadio Corregidora EST 115

Estancia de Ánimas EDA 115

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 140: Catalogo 2011-2020 r010212 Corto Circuito

140

Coordinación de Planificación

ÁREA OCCIDENTAL

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 13.76 13.79 13.83 13.86 13.84 13.89 22.81 22.71 23.03 23.991F 11.17 11.20 11.21 11.23 11.21 11.24 20.02 19.97 20.12 20.603F 22.11 22.13 23.39 23.37 23.40 23.40 23.48 26.14 26.43 26.711F 21.97 21.98 23.64 23.63 23.65 23.65 23.70 25.94 26.12 26.303F 6.52 6.53 6.72 6.72 6.88 6.77 6.93 6.94 6.95 7.051F 5.08 5.08 5.15 5.20 5.27 5.22 5.29 5.29 5.29 5.333F 11.39 11.43 11.59 11.56 11.69 11.63 11.83 12.39 12.41 12.441F 9.71 9.94 10.03 10.02 10.08 10.05 10.15 10.49 10.51 10.523F 15.66 15.70 15.91 15.88 16.00 15.94 16.16 18.45 18.60 18.631F 14.28 14.36 14.49 14.48 14.55 14.51 14.64 16.13 16.23 16.253F 8.75 8.77 8.81 8.75 8.85 8.84 9.03 9.09 9.10 9.111F 6.22 6.23 6.25 6.22 6.26 6.26 6.33 6.35 6.36 6.363F 12.05 12.09 12.12 9.08 9.06 9.06 9.00 10.61 10.64 10.781F 11.19 11.22 11.24 9.30 9.28 9.28 9.23 10.31 10.33 10.413F 10.49 11.22 12.42 12.46 12.49 12.701F 9.09 9.44 10.36 10.37 10.39 10.493F 16.73 16.76 16.53 16.52 21.14 20.85 21.33 21.34 21.52 22.921F 19.46 19.49 19.00 19.20 22.94 23.22 23.09 23.10 23.26 24.633F 14.18 14.20 14.03 14.02 17.19 17.00 17.32 17.33 17.44 18.361F 14.40 14.42 14.15 14.26 16.20 16.33 16.27 16.28 16.36 17.033F 10.99 10.99 10.83 11.09 11.01 11.02 10.89 11.06 11.07 11.071F 9.74 9.74 9.65 9.80 9.75 9.76 9.68 9.78 9.78 9.783F 12.88 12.89 12.98 13.06 13.21 13.08 13.12 13.15 13.80 14.041F 13.47 13.48 13.52 13.64 13.76 13.67 13.85 13.71 14.22 14.373F 28.44 28.52 28.76 28.90 31.17 30.96 32.15 31.11 31.95 32.491F 31.26 31.40 31.57 31.72 33.66 33.52 34.92 33.61 34.27 34.673F 13.61 13.68 13.76 15.07 14.91 14.78 14.61 14.32 14.62 14.791F 14.94 15.15 15.20 16.76 16.61 16.59 16.36 16.12 16.37 16.383F 5.50 5.51 5.52 5.66 5.64 5.63 5.61 5.58 5.61 5.631F 7.50 7.52 7.53 7.71 7.69 7.68 7.65 7.61 7.65 7.673F 23.38 23.50 23.57 24.42 24.25 24.14 24.04 23.82 24.07 24.281F 26.25 26.44 26.50 27.08 26.94 26.89 26.77 26.58 26.78 26.913F 11.01 11.06 12.16 12.05 11.96 12.05 11.73 11.96 12.091F 10.48 10.51 12.37 12.29 12.48 12.54 12.29 12.45 12.513F 23.90 21.32 21.23 21.39 21.08 21.33 21.491F 27.11 24.65 24.65 24.79 24.50 24.71 24.83

Guadalajara II GUD

69

Guadalajara Industrial GIN

230

69

230

161

Guacamayas GMY 115

Guadalajara I GDU

230

69

Grupo Real del Monte RM1 115

Grupo Real del Monte II RM2 115

Gosa ING 69

Gran Jardín GRJ 115

General Popo GPO 115

Gómez Portugal GPG 115

General Motors, Irapuato GMM 115

General Motors. San Luis Potosí GMC 230

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Fresno FRE 69

Gases Ind. Messer CRY 115

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 141: Catalogo 2011-2020 r010212 Corto Circuito

141

Coordinación de Planificación

ÁREA OCCIDENTAL

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 12.91 13.18 13.27 13.40 13.48 13.38 13.45 13.51 13.75 13.911F 13.97 14.26 14.34 14.46 14.52 14.46 14.50 14.55 14.72 14.843F 21.73 21.86 22.60 22.69 25.21 25.11 25.19 25.25 25.50 25.731F 25.28 25.48 26.33 26.42 28.93 28.84 28.91 28.95 29.16 29.353F 14.52 14.87 14.96 15.40 15.12 14.99 15.10 15.17 15.45 15.721F 15.21 15.56 15.62 16.07 15.75 15.66 15.73 15.78 15.97 16.313F 24.28 24.54 24.94 25.04 24.91 24.81 24.89 24.94 25.16 25.721F 27.24 27.54 27.87 28.01 27.85 27.77 27.83 27.87 28.04 28.553F 14.49 14.37 14.41 14.42 14.55 14.52 14.56 14.58 14.66 14.741F 10.47 10.43 10.45 10.45 10.51 10.49 10.51 10.51 10.54 10.573F 1.31 1.31 1.32 1.31 1.32 1.32 1.69 1.69 1.69 1.691F 0.85 0.85 0.85 0.85 0.85 0.85 1.12 1.12 1.12 1.123F 7.07 7.08 7.11 6.57 7.29 7.21 7.42 7.61 7.62 7.531F 6.41 6.42 6.43 6.13 6.54 6.49 6.61 6.78 6.78 6.733F 7.24 7.24 7.29 7.28 7.39 7.30 7.43 7.43 7.45 7.561F 5.03 5.03 5.05 5.05 5.09 5.06 5.10 5.10 5.11 5.143F 8.00 8.00 8.07 8.06 8.20 8.09 8.25 8.25 8.27 8.411F 5.69 5.69 5.71 5.72 5.77 5.73 5.79 5.79 5.79 5.843F 4.81 4.81 4.80 4.80 5.64 5.63 5.66 5.66 5.67 5.741F 3.36 3.36 3.35 3.35 3.60 3.78 3.60 3.60 3.60 3.633F 8.01 8.01 8.05 8.05 8.05 8.05 8.05 8.19 8.28 8.301F 5.37 5.37 5.39 5.39 5.39 5.39 5.39 5.45 5.47 5.473F 3.13 3.14 3.15 3.23 3.15 5.81 5.81 5.82 5.82 5.911F 2.26 2.26 2.27 2.32 2.27 3.96 3.96 3.96 3.97 4.003F 1.51 1.51 1.77 1.76 1.90 1.90 1.93 1.93 1.93 1.721F 1.07 1.07 0.27 1.29 1.34 1.34 1.34 1.34 1.34 1.193F 2.53 2.53 2.53 2.52 2.52 2.53 2.531F 1.89 1.89 1.89 1.88 1.88 1.89 1.893F 2.39 2.53 2.041F 1.77 1.89 1.703F 15.11 15.12 15.09 15.08 15.11 15.11 15.22 15.21 15.48 15.821F 12.49 12.50 12.47 12.48 12.49 12.50 12.54 12.55 12.71 12.873F 16.82 16.86 17.09 17.07 17.21 17.14 17.38 19.89 20.13 20.171F 16.02 16.13 16.28 16.27 16.35 16.31 16.47 18.20 18.42 18.443F 12.55 12.81 12.86 12.86 12.88 12.88 12.88 12.59 13.04 13.071F 8.95 9.05 8.99 9.06 9.07 9.03 9.08 8.98 9.13 8.97

GYS

Guevara GVA

Herdez HER

Héroes de Carranza HCR

Hacienda HCD 115

115

230

115

69

Guardian Industries VP GUI 115

115

115

Guáscaro GCR

Guayabitos

Guanajuato Sur GSU 115

Guarapo GRP 115

Guadalupe GPE 115

Guanajuato GTO 115

Guadalajara Tech GTP 69

Guadalcázar GDL 115

230

69Guadalajara Oriente GDO

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

230

69Guadalajara Norte GDN

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 142: Catalogo 2011-2020 r010212 Corto Circuito

142

Coordinación de Planificación

ÁREA OCCIDENTAL

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 9.18 9.20 9.22 10.55 10.49 10.47 10.56 10.47 10.54 10.591F 6.42 6.44 6.44 7.40 7.38 7.38 7.41 7.37 7.40 7.413F 14.37 14.42 14.45 9.20 9.18 9.18 9.12 10.77 10.81 10.941F 13.45 13.50 13.52 9.51 9.49 9.49 9.44 10.56 10.59 10.673F 10.07 10.09 10.18 10.17 10.22 10.20 10.28 11.70 11.70 11.721F 7.71 7.74 7.79 7.79 7.81 7.80 7.83 8.61 8.61 8.623F 9.55 9.58 9.59 6.93 6.92 6.92 6.88 7.77 7.79 7.861F 7.49 7.50 7.51 6.05 6.04 6.05 6.03 6.45 6.46 6.493F 1.35 1.35 1.40 1.35 1.35 1.36 1.27 1.36 1.36 1.361F 0.94 0.94 0.94 0.94 0.94 0.94 0.90 0.94 0.94 0.943F 3.71 3.72 3.71 3.71 3.72 3.71 3.73 3.73 3.73 3.761F 2.65 2.65 2.65 2.65 2.66 2.65 2.66 2.66 2.66 2.673F 11.78 11.83 14.64 14.69 15.17 15.13 15.16 15.18 15.26 15.341F 11.25 11.28 13.90 13.93 14.23 14.21 14.22 14.23 14.27 14.323F 4.63 4.63 4.65 4.65 4.65 4.64 4.62 4.72 4.99 4.991F 3.12 3.12 3.13 3.13 3.13 3.12 3.11 3.32 3.41 3.413F 1.99 1.99 1.92 1.92 1.92 1.50 1.91 1.95 2.00 2.001F 1.36 1.36 1.31 1.32 1.32 0.99 1.31 1.34 1.35 1.353F 11.69 11.72 11.74 15.51 15.44 15.40 15.35 15.27 15.37 15.481F 9.12 9.15 9.15 12.81 12.78 12.77 12.74 12.70 12.75 12.783F 1.17 1.17 0.85 1.17 1.17 1.17 0.86 1.17 1.18 1.181F 0.82 0.82 0.66 0.82 0.82 0.82 0.66 0.82 0.82 0.823F 9.88 9.91 10.03 10.01 10.11 10.06 10.24 10.44 10.46 10.481F 8.16 8.21 8.27 8.26 8.31 8.29 8.38 8.50 8.51 8.523F 14.88 14.91 15.11 15.09 15.19 15.14 15.33 17.87 20.23 20.271F 13.12 13.19 13.31 13.30 13.36 13.33 13.44 15.10 17.90 17.923F 18.66 18.67 19.48 19.46 19.48 19.48 19.54 21.68 21.88 22.081F 16.49 16.50 17.32 17.32 17.33 17.33 17.35 18.84 18.94 19.033F 18.51 18.56 18.85 18.81 18.98 18.90 19.20 22.33 22.66 22.711F 18.75 18.89 19.10 19.08 19.20 19.14 19.36 21.82 22.16 22.193F 14.89 14.92 15.13 15.11 15.22 15.17 15.35 18.74 18.76 18.791F 13.14 13.23 13.37 13.36 13.41 13.39 13.50 15.99 16.00 16.023F 1.19 1.19 0.87 1.19 1.19 1.20 0.87 1.20 1.20 1.201F 0.84 0.84 0.66 0.84 0.84 0.84 0.66 0.84 0.84 0.843F 5.11 5.11 5.07 4.96 4.94 5.21 5.18 5.21 5.32 5.341F 4.12 4.12 4.10 4.05 4.04 4.16 4.15 4.16 4.31 4.32

IVP

Infiernillo IFR

Inpamex INP

Industrias Selva ISV 115

69

115

Industrias Michelin MIC 115

Industrias Monterrey IMS 115

Iguana IGA 69

230

115

Industria Minera MNR

Industria Vidriera

Humedades HUM 115

IBM México IBM 69

Huentitán HNT 69

Huichápan HCH 115

Huacana HUC 69

Huanímaro HNM 115

Hitchiner Man Company HIM 115

Honda HON 69

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Higuerillas HIG 69

HILASAL HLS 69

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 143: Catalogo 2011-2020 r010212 Corto Circuito

143

Coordinación de Planificación

ÁREA OCCIDENTAL

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 18.01 18.05 17.98 17.95 18.36 17.96 18.57 18.59 18.69 19.491F 15.80 15.82 15.69 15.77 15.96 15.77 16.08 16.09 16.14 16.573F 17.55 17.61 17.44 17.39 17.93 17.03 18.34 18.37 18.70 21.401F 17.52 17.58 16.12 17.55 17.73 17.12 17.99 18.01 18.25 20.373F 19.70 19.75 19.62 19.58 20.04 19.53 20.28 20.30 20.45 21.561F 21.22 21.26 20.76 21.15 21.46 21.06 21.64 21.66 21.78 22.743F 15.01 15.03 14.96 14.94 15.20 14.92 15.34 15.35 15.43 16.021F 12.98 13.00 12.83 12.95 13.07 12.93 13.14 13.14 13.18 13.513F 8.46 8.47 8.47 8.47 8.56 8.48 8.61 8.61 8.63 8.771F 5.91 5.91 5.91 5.91 5.94 5.92 5.96 5.96 5.97 6.013F 13.85 13.87 13.83 13.82 14.03 13.83 14.15 14.16 14.21 14.621F 10.81 10.82 10.77 10.79 10.86 10.80 10.93 10.93 10.96 11.133F 13.91 13.93 13.89 13.87 14.09 13.88 14.22 14.23 14.28 14.711F 10.87 10.89 10.83 10.86 10.94 10.87 11.00 11.01 11.03 11.213F 9.98 11.09 11.17 14.12 11.21 11.10 11.30 11.38 11.58 11.721F 7.79 10.11 10.15 13.72 10.18 10.13 10.24 10.27 10.38 10.443F 5.16 5.16 5.41 5.40 5.38 6.79 6.79 6.80 6.81 7.011F 4.13 4.12 4.36 4.15 4.14 5.06 5.06 5.07 5.07 5.163F 4.89 4.90 4.90 5.20 5.16 9.54 9.56 9.57 9.59 9.871F 4.31 4.31 4.32 4.51 4.48 7.83 7.83 7.84 7.85 7.993F 5.36 5.37 5.38 5.36 5.46 5.40 5.52 5.53 5.53 5.551F 4.27 4.27 4.28 4.27 4.32 4.29 4.34 4.34 4.34 4.353F 2.12 2.12 2.12 2.12 2.12 2.12 2.13 2.14 2.14 2.141F 1.35 1.35 1.35 1.35 1.35 1.35 1.35 1.35 1.35 1.353F 1.38 1.38 1.39 1.39 1.39 1.38 1.37 1.44 1.52 1.521F 0.88 0.88 0.89 0.89 0.89 0.89 0.88 0.99 1.02 1.023F 9.30 9.33 9.33 9.89 9.88 13.47 13.48 13.56 13.60 14.871F 10.20 10.23 10.23 10.73 10.72 13.86 13.86 13.96 13.99 15.273F 4.18 4.18 4.17 4.17 4.80 4.79 4.81 4.81 4.82 4.861F 2.86 2.86 2.85 2.85 3.03 3.16 3.04 3.04 3.04 3.053F 3.54 3.54 4.35 4.27 5.24 5.24 5.45 5.45 5.46 4.741F 3.20 3.20 3.52 4.30 4.93 4.93 5.06 5.06 5.06 4.193F 8.38 8.40 8.43 8.39 8.45 8.46 8.62 8.64 8.65 8.661F 6.01 6.02 6.03 6.02 6.04 6.04 6.12 6.12 6.13 6.133F 2.83 2.83 2.84 2.72 2.86 2.85 2.88 2.90 2.90 2.891F 1.97 1.97 1.97 1.94 1.98 1.98 1.99 2.00 2.00 1.99

JPN

Jatco JAT

Jerez JRZ

Irapuato II IRA

Jarretaderas JDA 115

115

115

Jamay JMY 115

Jaral del Progreso JDP 115

Jalostotitlán JLT 115

115

115

Jalpa JAP

Jalpan

Ixtlán IXT 115

Jacona JCN 115

Irapuato Villas IRC 115

Ixtlahuacán IXT 400

Irapuato Norte IRN 115

Irapuato Poniente IPP 115

115

Irapuato Industrial IRI 115

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Irapuato I IRP 115

230

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 144: Catalogo 2011-2020 r010212 Corto Circuito

144

Coordinación de Planificación

ÁREA OCCIDENTAL

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 9.58 9.59 9.82 9.81 9.81 11.17 11.40 11.41 11.43 11.621F 7.90 7.90 8.02 8.01 8.01 8.48 8.57 8.58 8.59 8.663F 3.01 2.98 2.99 3.03 3.02 3.31 3.31 3.31 3.32 3.361F 2.02 2.00 2.02 2.03 2.03 2.15 2.15 2.15 2.15 2.173F 9.71 9.82 9.82 9.98 10.08 10.09 10.111F 7.34 7.39 7.39 7.41 7.50 7.50 7.513F 2.10 4.19 4.191F 2.00 5.16 5.163F 3.82 3.82 3.82 3.92 3.91 9.77 9.78 9.81 9.82 10.171F 2.82 2.82 2.82 2.86 2.86 7.39 7.39 7.40 7.41 7.573F 3.80 3.76 3.80 3.77 3.77 3.76 3.77 3.77 3.79 3.801F 2.45 2.44 2.45 2.44 2.44 2.44 2.44 2.44 2.45 2.453F 4.21 4.21 4.20 4.20 4.83 4.82 4.85 4.85 4.85 4.901F 2.88 2.88 2.87 2.88 3.06 3.19 3.06 3.06 3.06 3.083F 1.84 1.98 1.85 1.98 1.98 1.98 1.98 1.98 1.99 1.991F 1.27 1.33 1.19 1.33 1.33 1.33 1.33 1.33 1.33 1.333F 4.25 4.25 4.26 4.26 4.27 4.27 4.38 4.38 4.38 4.381F 2.80 2.80 2.81 2.81 2.81 2.81 2.87 2.87 2.87 2.873F 11.72 11.72 11.92 12.34 12.35 12.36 12.38 12.82 12.89 12.951F 8.52 8.52 8.66 9.22 9.23 9.23 9.24 9.43 9.45 9.473F 15.41 15.41 15.69 15.67 15.69 15.68 15.72 16.49 16.61 16.731F 12.01 12.02 12.21 12.21 12.21 12.21 12.23 12.59 12.64 12.683F 13.72 13.73 13.75 13.74 13.75 13.74 13.73 14.07 14.58 14.601F 12.47 12.48 12.49 12.49 12.49 12.48 12.48 12.67 12.93 12.943F 13.46 13.48 13.52 13.55 14.53 14.48 14.63 14.52 14.67 14.821F 10.76 10.78 10.80 10.82 11.23 11.21 11.28 11.23 11.28 11.343F 5.97 5.98 5.98 6.24 6.23 8.16 8.17 8.19 8.20 8.581F 4.91 4.92 4.92 5.05 5.05 6.22 6.22 6.24 6.24 6.433F 9.82 9.89 9.83 9.64 10.14 7.85 7.86 7.88 8.23 8.251F 7.53 7.62 7.54 7.50 8.08 5.78 5.78 5.79 6.07 6.073F 4.28 4.28 4.29 4.28 4.34 4.30 4.37 4.38 4.38 4.391F 3.00 3.01 3.01 3.01 3.03 3.01 3.04 3.04 3.04 3.043F 5.82 5.82 5.77 5.62 5.60 5.95 5.92 5.96 6.09 6.121F 4.93 4.94 4.91 4.83 4.82 4.99 4.98 5.00 5.21 5.223F 3.78 3.80 3.80 3.81 3.85 3.82 3.79 3.81 3.82 3.841F 2.80 2.81 2.81 2.81 2.83 2.81 2.80 2.81 2.81 2.82

ELA

Kimberly Clark KIM

La Cueva LCV 115

115

115

La Esperanza LAE

La Estrella

La Barca LBC 115

La California CLF 115

Kellogs de México KGL 115

115

69Kodak KDK

Julián Carrillo JCR 115

Jurica JUR 115

Joyuela JYU 115

Juan Rulfo JRO 115

Jiquilpan JQL 115

Jocotepec JCT 69

Jesús María (AGS) JMA 115

Jiliapan JIL 230

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Jesús del Monte JEM 115

Jesús María JMA 115

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 145: Catalogo 2011-2020 r010212 Corto Circuito

145

Coordinación de Planificación

ÁREA OCCIDENTAL

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 6.47 6.48 6.48 6.17 6.18 6.19 6.19 6.24 6.26 6.271F 4.32 4.33 4.33 4.44 4.44 4.44 4.44 4.46 4.47 4.473F 7.69 7.69 7.75 7.74 7.74 7.74 7.75 7.91 7.97 7.981F 5.12 5.12 5.15 5.15 5.15 5.15 5.15 5.21 5.23 5.233F 3.07 3.23 3.08 3.15 3.16 3.14 3.12 3.13 3.13 3.151F 2.01 2.08 1.99 2.04 2.05 2.04 2.02 2.02 2.02 2.023F 13.20 13.22 13.87 13.83 13.84 15.19 16.37 16.41 16.47 16.861F 12.85 12.87 13.40 13.39 13.39 14.19 15.06 15.09 15.12 15.343F 8.22 8.21 8.22 8.22 8.22 8.22 8.22 8.79 8.89 8.921F 5.87 5.87 5.87 5.87 5.87 5.87 5.87 6.18 6.21 6.223F 13.25 13.26 13.27 13.27 13.27 13.27 13.26 13.57 13.93 13.951F 11.12 11.12 11.13 11.13 11.13 11.13 11.13 11.27 11.43 11.443F 6.72 6.72 6.72 6.73 7.01 7.07 7.091F 4.89 4.89 4.89 4.89 5.00 5.02 5.033F 1.55 1.55 1.55 1.55 1.56 1.55 1.55 1.55 1.55 1.561F 1.02 1.02 1.02 1.02 1.03 1.02 1.02 1.02 1.02 1.033F 7.75 7.75 7.43 7.81 7.76 7.76 7.46 7.78 7.78 7.791F 6.18 6.18 5.95 6.22 6.19 6.19 5.96 6.20 6.20 6.203F 10.06 10.07 10.15 10.14 10.14 11.43 11.68 11.69 11.72 11.921F 8.26 8.27 8.30 8.30 8.30 8.78 8.88 8.89 8.90 8.983F 4.65 4.66 4.65 4.66 4.65 5.97 5.98 5.99 5.99 6.071F 3.22 3.23 3.23 3.23 3.23 4.16 4.17 4.17 4.17 4.203F 4.11 4.11 4.11 4.11 4.11 4.86 4.86 4.87 4.87 4.911F 2.82 2.82 2.82 2.82 2.82 3.35 3.35 3.35 3.35 3.363F 11.17 11.20 11.251F 11.25 11.29 11.323F 12.70 12.75 13.26 13.23 13.38 13.31 13.63 12.96 12.98 13.011F 12.06 12.32 12.83 12.81 12.90 12.86 13.13 11.29 11.30 11.313F 18.76 18.81 19.17 19.13 19.30 19.22 19.53 27.09 27.35 27.431F 19.27 19.49 19.84 19.81 19.93 19.88 20.13 29.07 29.43 29.493F 8.10 8.15 8.10 6.79 7.10 7.13 7.13 7.15 10.95 10.971F 5.96 6.02 5.97 4.99 5.32 5.33 5.33 5.34 9.29 9.303F 2.36 1.87 1.87 1.87 1.87 1.87 1.87 1.87 1.88 1.881F 1.50 1.24 1.24 1.24 1.24 1.24 1.24 1.24 1.24 1.243F 5.74 5.31 5.29 5.31 5.31 5.31 5.31 5.32 5.33 5.331F 3.91 3.87 3.87 3.87 3.87 3.87 3.87 3.88 3.88 3.88

La Piedad Poniente LPP

La Pila SPI

La Vega LVG

La Soledad SDD 115

69

69La Venta LVA

230

115

La Piedad LPI 115

115

400

La Mira LMR 115

La Mora MRA 115

La Mansion II MAN 230

La Minita MNT 115

La Manga MAG 230

La Mansión MNS 115

La Huerta HRT 115

La Joya LJY 115

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

La Fragua FRA 115

La Griega GRI 115

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 146: Catalogo 2011-2020 r010212 Corto Circuito

146

Coordinación de Planificación

ÁREA OCCIDENTAL

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 4.06 4.07 4.15 4.14 4.02 4.12 8.21 8.27 8.28 8.351F 2.80 2.80 2.84 2.84 2.74 2.77 7.37 7.41 7.42 7.453F 4.84 6.04 6.06 6.65 6.07 6.04 6.09 6.11 6.15 6.191F 3.25 8.28 8.30 8.90 8.31 8.29 8.33 8.34 8.39 8.413F 4.22 4.22 4.31 4.31 4.23 4.34 8.31 8.36 8.37 8.451F 2.93 2.93 2.96 2.96 2.90 2.93 7.38 7.42 7.43 7.463F 4.37 4.37 4.47 4.46 4.22 4.33 6.23 6.25 6.26 6.301F 3.05 3.05 3.09 3.09 2.89 2.93 4.61 4.62 4.62 4.643F 2.04 2.04 2.04 2.04 2.04 2.04 2.04 2.04 2.04 2.051F 1.37 1.37 1.37 1.37 1.37 1.37 1.37 1.37 1.37 1.373F 4.43 4.43 4.44 4.17 4.50 4.47 4.55 4.60 4.60 4.571F 3.35 3.35 3.36 3.25 3.38 3.37 3.40 3.43 3.43 3.423F 4.23 4.24 4.23 4.25 4.21 4.24 4.26 4.29 5.32 5.371F 3.09 3.10 3.09 3.10 3.08 3.09 3.12 3.13 4.20 4.223F 15.39 15.43 15.65 15.63 15.75 15.69 15.89 19.55 19.57 19.601F 13.81 13.91 14.06 14.05 14.11 14.08 14.20 17.00 17.00 17.023F 4.83 4.84 4.85 4.57 4.93 4.89 4.99 5.06 5.06 5.021F 3.74 3.74 3.74 3.63 3.78 3.76 3.80 3.85 3.85 3.833F 12.62 12.64 12.59 12.58 12.76 12.56 12.86 12.86 12.92 13.331F 10.19 10.20 10.10 10.18 10.25 10.16 10.29 10.29 10.32 10.513F 7.23 7.25 8.15 8.21 8.35 8.34 8.41 8.41 8.43 8.431F 6.30 6.31 6.98 7.04 7.11 7.11 7.14 7.14 7.15 7.153F 2.14 2.14 1.27 2.14 2.14 2.15 1.27 2.15 2.15 2.151F 1.63 1.63 1.04 1.63 1.63 1.63 1.04 1.63 1.63 1.633F 17.95 18.06 17.99 17.93 17.96 17.98 18.04 18.27 18.35 18.451F 21.39 21.53 21.44 21.39 21.69 21.72 21.77 21.98 22.55 22.643F 1.29 1.29 1.29 1.24 1.29 1.29 1.30 1.30 1.30 1.301F 0.87 0.87 0.87 0.85 0.87 0.87 0.87 0.87 0.87 0.873F 14.98 15.08 14.99 14.92 15.01 15.01 15.95 16.00 16.15 17.141F 14.49 14.58 14.34 14.44 14.15 14.60 15.13 15.17 15.26 15.923F 21.98 22.04 21.94 21.90 22.36 21.94 22.69 22.71 22.84 23.791F 21.36 21.41 21.23 21.31 21.49 21.36 21.82 21.84 21.92 22.553F 7.31 7.32 7.33 18.04 17.00 16.95 17.02 16.84 16.99 17.091F 5.13 5.13 5.14 15.57 15.02 15.02 15.05 14.95 15.03 15.073F 9.41 9.42 9.72 9.71 9.70 10.24 10.66 10.67 10.70 10.881F 7.65 7.66 7.83 7.83 7.83 8.05 8.25 8.26 8.27 8.34

LDE

Las Fresas LFS

Las Pintas LPS

Las Torres TOR

115

69

115

Las Fajas FAJ 115

400

Las Brisas BRI 115

69

230

Las Cañas CAN

Las Delicias

Lampotal LPL 115

Lapem LPM 115

Lagunillas LAG 115

Lamosa Revestimientos LMR 115

Laguna Larga LGL 115

Laguna Seca LAS 115

Lagos de Moreno LGS 115

Lagos Galera LGN 115

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

La Virgen LVR 115

La Yesca YCA 400

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 147: Catalogo 2011-2020 r010212 Corto Circuito

147

Coordinación de Planificación

ÁREA OCCIDENTAL

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 1.20 1.20 1.36 1.36 1.44 1.44 1.45 1.45 1.45 1.331F 0.84 0.84 0.27 0.96 0.98 0.98 0.99 0.99 0.99 0.903F 18.11 18.16 18.43 18.40 18.56 18.48 18.77 21.72 21.99 22.041F 18.08 18.21 18.41 18.39 18.50 18.44 18.65 20.90 21.16 21.183F 10.93 10.93 10.81 10.99 10.95 10.96 10.88 11.01 11.01 11.011F 9.30 9.30 9.24 9.34 9.31 9.32 9.28 9.34 9.34 9.343F 25.11 25.14 25.22 25.31 25.29 25.38 25.60 25.18 25.72 25.781F 30.59 30.62 30.73 30.84 30.80 30.90 31.02 30.61 31.14 31.193F 29.09 29.10 29.09 29.28 29.25 29.32 29.70 30.05 29.86 29.891F 36.09 36.11 36.10 36.46 36.26 36.37 36.74 37.20 36.90 36.933F 17.54 17.54 17.37 17.63 17.60 17.65 17.59 17.78 17.77 17.781F 20.35 20.36 20.20 20.43 20.41 20.46 20.40 20.58 20.57 20.573F 5.54 5.54 5.55 4.81 4.80 4.80 4.80 4.80 4.81 4.821F 3.74 3.74 3.74 3.41 3.40 3.40 3.41 3.40 3.41 3.413F 12.52 12.56 12.79 12.73 12.70 13.70 14.35 14.39 14.50 15.341F 13.29 13.34 13.57 13.65 13.62 14.28 14.77 14.80 14.88 15.473F 17.39 17.43 17.99 17.93 17.92 20.73 21.67 21.72 21.83 22.621F 20.01 20.06 20.74 20.75 20.73 23.10 23.90 23.94 24.03 24.673F 11.30 11.32 11.73 11.70 11.70 12.41 12.86 12.88 12.92 13.211F 9.98 9.99 10.30 10.32 10.32 10.67 10.91 10.92 10.94 11.083F 9.93 9.95 10.29 10.27 10.27 10.88 11.36 11.38 11.41 11.611F 8.25 8.26 8.46 8.46 8.46 8.72 8.97 8.97 8.99 9.073F 10.16 10.19 10.27 10.21 10.26 10.78 11.84 11.91 11.96 12.311F 9.67 9.70 9.79 9.77 9.79 10.04 11.08 11.12 11.15 11.353F 14.37 14.40 15.48 15.43 15.45 17.08 18.84 18.91 18.98 19.501F 15.78 15.81 16.95 16.93 16.94 18.17 19.95 20.01 20.06 20.443F 8.23 8.24 9.91 9.88 9.84 10.46 10.84 10.86 10.93 11.441F 7.91 7.93 9.62 9.77 9.74 10.12 10.36 10.38 10.42 10.733F 14.91 14.94 15.74 15.70 15.67 16.89 17.59 17.62 17.71 18.291F 16.20 16.23 17.23 17.31 17.29 18.24 18.80 18.82 18.88 19.323F 10.93 10.95 11.46 11.44 11.44 12.27 13.03 13.06 13.10 13.351F 9.69 9.70 10.04 10.04 10.04 10.44 10.91 10.92 10.94 11.053F 14.25 14.28 14.66 14.62 14.60 15.81 16.36 16.39 16.46 16.961F 13.34 13.36 13.62 13.67 13.65 14.32 14.63 14.65 14.68 14.943F 8.38 8.39 10.89 10.87 10.87 12.03 12.65 12.68 12.71 12.931F 6.84 6.85 9.22 9.21 9.21 9.71 10.06 10.07 10.08 10.17

LNP

León Norte LNN 115

115

115

León Oriente LNO

León Poniente

230

115León IV LNC

León Centro LCO 115

León III LNT

230

115

LNU 115

León Alfaro LNA 115

León

Lechera Guadalajara LEG 69

LNU 230

230

115

Lázaro Cárdenas Potencia LCP

Lázaro Cárdenas Dist. LCD 115

400

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Las Varas LVR 115

Latincasa LAT 115

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 148: Catalogo 2011-2020 r010212 Corto Circuito

148

Coordinación de Planificación

ÁREA OCCIDENTAL

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 8.90 8.93 8.98 8.96 8.94 8.93 8.94 8.95 8.97 9.041F 6.34 6.36 6.37 6.37 6.36 6.36 6.36 6.36 6.37 6.393F 13.66 13.69 13.88 13.86 13.95 13.91 14.07 17.61 17.72 17.751F 11.76 11.84 11.97 11.96 12.00 11.98 12.08 14.81 14.90 14.913F 3.72 3.72 3.92 3.72 3.72 3.80 3.36 3.80 3.80 3.801F 3.50 3.50 3.57 3.50 3.50 3.54 3.25 3.54 3.54 3.553F 3.78 3.79 3.80 3.81 4.38 4.38 4.28 4.55 4.55 4.551F 2.46 2.46 2.46 2.49 2.88 2.88 2.79 3.00 3.00 3.003F 1.34 1.34 1.34 1.31 1.35 1.34 1.35 1.35 1.35 1.351F 0.88 0.88 0.88 0.87 0.88 0.88 0.88 0.88 0.88 0.883F 2.84 2.84 2.86 2.91 2.79 4.15 4.15 4.15 4.16 4.191F 2.00 2.00 2.01 2.06 1.99 2.75 2.75 2.75 2.75 2.763F 8.63 8.64 8.75 8.74 8.73 8.99 9.13 9.13 9.16 9.331F 6.45 6.46 6.48 6.51 6.50 6.60 6.65 6.65 6.66 6.723F 1.11 0.86 1.11 0.85 0.85 0.85 0.85 0.85 0.85 0.851F 0.72 0.62 0.72 0.62 0.62 0.62 0.62 0.62 0.62 0.623F 5.16 5.16 5.18 5.08 5.62 5.58 5.68 7.07 7.07 7.051F 3.51 3.51 3.51 3.48 3.84 3.83 3.86 5.28 5.29 5.283F 15.02 15.05 15.26 15.24 15.34 15.29 15.49 18.18 18.24 18.271F 13.29 13.37 13.50 13.49 13.54 13.52 13.63 15.43 15.48 15.493F 9.94 9.94 9.93 12.55 12.57 12.59 12.66 12.66 12.76 12.961F 6.86 6.86 6.85 9.00 9.00 9.03 9.05 9.06 9.10 9.183F 17.55 17.56 18.12 18.11 18.12 18.12 18.17 19.64 19.80 19.971F 14.65 14.66 15.15 15.14 15.15 15.15 15.17 16.02 16.09 16.163F 17.65 17.69 17.95 17.92 18.08 18.00 18.27 21.06 21.32 21.371F 17.32 17.44 17.63 17.61 17.71 17.66 17.84 19.90 20.14 20.163F 14.99 15.02 15.24 15.22 15.33 15.28 15.47 19.27 19.32 19.351F 13.33 13.43 13.58 13.57 13.62 13.60 13.71 16.68 16.72 16.743F 4.00 4.00 4.01 3.79 4.06 4.04 4.10 4.14 4.14 4.121F 2.96 2.96 2.97 2.88 2.99 2.98 3.00 3.02 3.02 3.013F 14.68 14.71 14.92 14.90 15.01 14.96 15.14 18.77 18.82 18.851F 12.93 13.02 13.16 13.15 13.21 13.18 13.29 16.06 16.10 16.123F 17.04 19.23 19.22 19.29 19.25 16.26 16.31 18.38 19.47 21.601F 21.33 24.25 24.21 24.30 24.26 20.46 20.51 23.25 24.49 27.293F 13.40 14.11 14.10 13.93 13.94 13.01 13.04 13.70 14.06 14.621F 15.50 16.19 16.09 15.95 15.97 15.09 15.11 15.75 16.09 16.61

Mabe Querétaro MMQ

Mabe Sanyo MSY

Manufacturas Vitromex MFU 115

Manzanillo MNZ

400

230

Mallasan SA de CV MAL 115

Malpaso MPO 115

Mabe Celaya MLS 115

115

115

Luis Moya LMY 115

Mabe Aguascalientes MLS 115

Los Sauces LSA 115

Los Volcanes VCS 69

Los Hernández HDZ 115

Los Reyes RYS 115

Lombardia LOB 69

Loreto LOR 115

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Línea Dos del Tren TRN 69

Logistik Park LGP 115

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 149: Catalogo 2011-2020 r010212 Corto Circuito

149

Coordinación de Planificación

ÁREA OCCIDENTAL

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 2.19 2.19 2.19 2.22 2.22 2.20 2.21 2.23 2.23 2.271F 1.45 1.45 1.45 1.46 1.46 1.45 1.45 1.46 1.46 1.483F 15.11 15.17 15.29 15.09 15.39 15.38 15.94 16.13 16.15 16.181F 12.41 12.44 12.51 12.41 12.55 12.54 12.83 12.93 12.94 12.963F 1.96 1.96 1.96 1.96 1.96 1.96 2.03 2.03 2.03 2.031F 1.45 1.45 1.46 1.45 1.45 1.45 1.49 1.49 1.49 1.493F 1.96 1.96 1.96 1.96 1.96 1.96 2.03 2.04 2.04 2.041F 1.46 1.46 1.46 1.45 1.46 1.45 1.49 1.49 1.49 1.493F 11.48 11.71 11.75 11.77 11.75 11.82 11.91 12.06 12.14 12.371F 8.23 8.33 8.35 8.37 8.36 9.25 9.28 9.34 9.40 9.493F 4.14 4.34 4.15 4.18 4.21 4.17 4.16 4.18 4.20 4.221F 2.77 2.87 2.74 2.78 2.79 2.78 2.77 2.78 2.78 2.793F 4.09 4.28 4.10 4.12 4.15 4.11 4.11 4.13 4.14 4.161F 2.74 2.82 2.70 2.74 2.75 2.74 2.73 2.74 2.74 2.753F 15.46 15.50 15.55 15.56 15.57 15.61 20.27 20.22 20.46 21.171F 15.35 15.40 15.43 15.45 15.48 15.52 17.81 17.79 17.90 18.263F 12.57 12.61 12.82 12.78 12.95 12.87 13.15 13.91 13.96 14.001F 11.77 11.97 12.09 12.07 12.17 12.12 12.30 12.87 12.92 12.943F 1.90 1.90 1.90 1.91 1.91 1.93 1.94 1.94 1.94 1.951F 1.23 1.23 1.23 1.23 1.23 1.24 1.24 1.24 1.24 1.243F 2.00 2.00 2.00 1.86 1.87 1.87 1.871F 1.28 1.28 1.27 1.19 1.19 1.19 1.193F 1.69 2.01 2.331F 1.03 1.28 1.533F 8.20 8.22 8.24 9.29 9.24 9.22 9.29 9.22 9.28 9.311F 5.64 5.65 5.65 6.38 6.36 6.36 6.39 6.36 6.38 6.393F 1.05 1.05 1.05 1.01 1.05 1.05 1.05 1.06 1.06 1.051F 0.71 0.71 0.71 0.70 0.71 0.71 0.71 0.71 0.71 0.713F 1.73 1.73 1.73 1.72 1.73 1.73 1.78 1.78 1.78 1.781F 1.25 1.25 1.25 1.25 1.25 1.25 1.28 1.28 1.28 1.283F 13.88 13.90 14.05 14.03 14.13 14.08 14.28 14.56 14.58 14.601F 12.81 12.84 12.94 12.92 12.98 12.95 13.12 13.27 13.29 13.303F 5.74 5.74 5.77 5.77 5.83 5.78 5.86 5.86 5.87 5.941F 3.86 3.86 3.87 3.87 3.89 3.87 3.90 3.90 3.90 3.923F 4.68 4.72 4.86 4.83 6.78 6.68 4.94 4.98 5.00 5.031F 3.20 3.22 3.29 3.28 4.77 4.74 3.37 3.38 3.39 3.40

MTC

Mezquitán MZI

Mina San Javier XAV 115

115

115

Minas las Torres MTR

Minatitlán

Miguel Auza MGU 115

Mina la Paz MLP 115

115

69

69Miconsa MIC

Mexinox MXO 230

Mexticacán MCA 115

Melaque Potencia MQP 115

México MXJ 69

Mazamitla MTA 400

Melaque Distribución MLQ 115

Matehuala MHS 115

Matehuala Sur MTS 115

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Maravatio MRT 115

Margaritas MRS 115

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 150: Catalogo 2011-2020 r010212 Corto Circuito

150

Coordinación de Planificación

ÁREA OCCIDENTAL

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.981F 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.633F 6.27 6.28 6.30 5.33 6.42 6.36 6.50 6.58 6.59 6.531F 5.95 5.95 5.97 5.33 6.04 6.00 6.08 6.14 6.14 6.113F 2.94 2.94 2.95 5.80 3.49 3.48 3.50 3.91 3.91 3.901F 1.90 1.90 1.90 4.25 2.27 2.27 2.27 2.62 2.62 2.623F 4.61 4.61 4.58 4.42 4.40 4.68 4.66 4.69 4.69 4.711F 3.81 3.81 3.80 3.72 3.70 3.84 3.84 3.85 3.86 3.873F 8.29 8.49 8.36 7.80 7.89 7.75 7.83 7.94 7.99 8.081F 6.29 6.38 6.09 5.90 5.94 5.89 5.94 5.98 6.01 6.043F 12.29 12.34 12.37 12.34 12.10 12.07 12.18 12.06 12.15 12.211F 9.67 9.71 9.72 9.00 8.91 8.90 8.95 8.89 8.93 8.953F 6.03 6.04 6.04 5.78 5.78 5.79 5.79 5.84 5.85 5.861F 4.00 4.00 4.00 4.10 4.10 4.10 4.11 4.12 4.13 4.133F 7.08 7.09 7.10 7.111F 7.19 7.20 7.20 7.213F 5.41 5.42 5.43 5.43 5.45 5.44 8.15 8.16 8.16 8.171F 3.93 3.93 3.94 3.94 3.94 3.94 7.93 7.94 7.94 7.953F 16.03 15.96 16.01 16.03 16.58 16.52 16.59 16.60 16.72 16.861F 12.29 12.28 12.30 12.31 12.53 12.51 12.54 12.54 12.59 12.633F 12.17 12.19 12.31 12.29 12.36 12.33 12.47 12.88 12.92 12.931F 9.95 9.97 10.03 10.02 10.05 10.03 10.12 10.32 10.34 10.343F 5.92 5.98 5.98 5.99 6.10 6.02 5.95 6.00 6.03 6.071F 5.04 5.07 5.07 5.07 5.13 5.10 5.06 5.08 5.09 5.123F 7.28 7.29 7.28 7.39 7.26 7.23 7.42 7.56 7.84 8.041F 7.13 7.13 7.13 7.20 7.10 7.08 7.41 7.50 7.70 7.833F 7.49 7.50 7.50 7.65 7.36 7.27 7.92 8.07 8.30 8.601F 7.04 7.05 7.04 7.13 6.75 6.67 7.71 7.81 7.97 8.173F 7.57 7.58 7.57 7.70 7.42 7.36 8.07 8.23 8.53 8.771F 7.41 7.42 7.42 7.50 7.09 7.05 8.41 8.52 8.76 8.933F 5.58 5.59 5.59 5.66 5.44 5.46 5.13 5.29 5.44 5.581F 5.58 5.59 5.59 5.64 5.44 5.45 5.48 5.62 5.75 5.853F 9.02 9.04 9.03 9.18 8.94 8.90 9.12 9.32 9.78 10.071F 10.64 10.65 10.64 10.78 10.51 10.48 11.04 11.24 11.75 12.023F 8.29 8.30 8.29 8.77 8.84 8.84 9.02 9.05 9.05 9.071F 8.98 8.99 8.98 6.22 6.25 6.25 6.32 6.33 6.33 6.34

MEL

Moctezuma MZM

Moralete MTE

Morelia II MRD

230

115

115

Morelia potencia MRP

Morelos

Morelia Industrial MOI 115

Morelia Norte MOR 115

Montesillos MTS 115

115

115

115

Mojonera MOJ 69

Mission Hills MHL 115

230

Miramar MRM 115

Miravalle MVE 69

Minera Real de Ángeles RAG 115

Mirador MRR 115

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Minera Bolaños BLA 115

Minera Fresnillo CMF 115

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 151: Catalogo 2011-2020 r010212 Corto Circuito

151

Coordinación de Planificación

ÁREA OCCIDENTAL

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 8.76 8.78 8.82 8.77 8.94 8.84 9.09 9.12 9.12 9.151F 6.21 6.22 6.24 6.22 6.29 6.25 6.35 6.36 6.36 6.373F 3.97 3.97 3.96 3.96 4.52 4.51 4.53 4.53 4.54 4.581F 2.70 2.70 2.69 2.69 2.85 2.97 2.85 2.85 2.85 2.873F 14.62 14.68 14.79 14.60 14.88 14.87 15.40 15.57 15.59 15.631F 11.86 11.90 11.95 11.87 12.00 11.99 12.25 12.34 12.35 12.373F 13.46 13.48 13.52 13.55 14.53 14.48 14.63 14.52 14.67 14.821F 10.76 10.78 10.80 10.82 11.23 11.21 11.28 11.23 11.28 11.343F 4.14 4.14 4.17 4.02 4.92 4.92 5.11 5.11 5.11 5.131F 4.11 4.11 4.05 4.01 4.58 4.58 4.70 4.70 4.70 4.743F 9.68 9.90 9.94 9.98 10.94 10.86 10.92 10.97 11.19 11.511F 9.35 9.54 9.56 9.59 10.98 10.93 10.97 11.00 11.15 11.353F 25.46 25.34 25.52 25.48 25.86 27.721F 24.73 24.66 24.77 24.75 24.97 26.093F 15.11 15.12 15.11 15.16 15.15 15.17 15.28 15.37 15.32 15.331F 12.38 12.39 12.39 12.43 12.40 12.42 12.46 12.51 12.48 12.483F 7.32 7.33 7.36 7.33 7.37 7.38 7.50 7.51 7.52 7.531F 5.12 5.13 5.14 5.13 5.15 5.14 5.20 5.21 5.21 5.213F 15.42 15.46 15.66 15.64 15.76 15.70 15.90 18.29 18.39 18.431F 13.91 13.99 14.11 14.10 14.16 14.13 14.25 15.81 15.88 15.903F 6.45 6.46 6.45 6.99 6.99 7.01 7.02 7.07 7.09 7.111F 4.34 4.36 4.35 5.27 5.27 5.28 5.28 5.30 5.31 5.323F 18.41 18.48 18.52 4.55 4.54 4.54 4.54 4.54 4.55 4.561F 17.40 17.48 17.50 3.19 3.19 3.19 3.19 3.19 3.19 3.203F 3.34 3.34 3.82 3.82 3.82 4.12 4.13 4.13 4.13 4.131F 2.83 2.83 2.86 2.85 2.95 2.95 2.96 2.96 2.96 2.963F 3.27 3.27 4.42 4.42 4.71 4.71 4.72 4.651F 2.32 3.90 4.98 4.98 5.23 5.24 5.24 4.443F 5.50 5.43 7.05 7.05 7.42 7.42 7.43 5.101F 6.42 7.01 8.78 8.78 9.17 9.17 9.18 4.703F 16.63 16.74 17.40 17.46 17.49 17.44 17.48 17.51 17.61 17.821F 15.38 15.47 15.87 15.91 15.92 15.90 15.91 15.93 15.98 16.103F 6.36 6.39 6.39 7.12 7.10 7.61 7.60 7.59 7.62 9.741F 5.92 5.94 5.94 6.44 6.43 6.81 6.79 6.82 6.83 8.603F 9.36 9.39 9.40 9.97 9.96 13.60 13.62 13.70 13.74 15.041F 10.33 10.36 10.36 10.88 10.87 14.09 14.10 14.21 14.23 15.56

Niños Héroes NHE

Novacel NVC

Nueva Italia NVI

Oblatos OBL 69

Ocotlán OCN

230

115

230

115Nuevo Vallarta Potencia NVP

Nogales NGA 115

69

69

Nissan NIS 115

Nitropiso NTR 115

69

Nippon Kokan Steel NKS 230

Muelle MUE 115

230

Motodiesel MDI 115

Motorola MTR 69

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Morelos MRE 115

Moroleón MLO 115

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 152: Catalogo 2011-2020 r010212 Corto Circuito

152

Coordinación de Planificación

ÁREA OCCIDENTAL

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 6.94 6.95 6.97 6.70 7.40 7.35 7.53 10.96 10.97 10.871F 5.21 5.22 5.23 5.13 5.51 5.50 5.57 10.92 10.93 10.853F 10.09 10.09 10.08 12.78 12.81 12.83 12.90 12.90 13.01 13.211F 6.97 6.98 6.97 9.21 9.21 9.24 9.26 9.27 9.31 9.393F 1.43 1.43 1.43 1.43 1.43 1.30 1.44 1.44 1.44 1.441F 0.91 0.91 0.91 0.91 0.91 0.82 0.91 0.91 0.91 0.913F 21.36 21.40 21.53 21.61 22.84 22.73 23.38 22.81 23.26 23.541F 19.40 19.45 19.52 19.57 20.28 20.23 20.74 20.26 20.50 20.643F 6.94 6.96 7.00 7.00 7.00 6.99 6.96 7.02 7.23 7.241F 7.89 7.91 7.00 7.95 7.95 7.93 7.91 7.98 8.16 8.153F 6.82 6.83 6.96 6.96 6.96 6.89 6.79 7.09 7.52 7.531F 8.04 8.05 7.98 8.17 8.17 8.11 8.01 8.35 8.75 8.753F 6.05 9.68 9.72 10.89 10.89 10.92 10.94 11.12 11.17 11.211F 4.26 6.91 6.93 8.69 8.69 8.71 8.71 8.80 8.82 8.843F 15.01 15.02 15.04 15.04 15.04 15.03 15.02 15.44 16.08 16.111F 14.89 14.90 14.91 14.91 14.92 14.91 14.90 15.19 15.59 15.603F 7.71 7.71 7.66 7.73 7.72 7.72 7.69 7.75 7.75 7.751F 5.81 5.81 5.79 5.82 5.82 5.82 5.81 5.83 5.83 5.833F 7.31 7.32 7.35 7.26 7.40 7.39 7.53 7.93 7.93 7.931F 5.13 5.14 5.15 5.12 5.18 5.18 5.24 5.55 5.55 5.553F 3.72 3.72 3.73 3.72 3.73 3.73 3.76 3.77 3.77 3.781F 2.43 2.43 2.43 2.43 2.43 2.43 2.44 2.44 2.44 2.453F 2.82 2.82 2.83 2.79 3.52 3.51 3.54 4.09 4.09 4.081F 1.84 1.84 1.84 1.83 2.31 2.31 2.31 2.81 2.81 2.803F 17.24 17.28 17.53 17.50 17.65 17.58 17.83 20.50 20.78 20.821F 16.66 16.77 16.94 16.93 17.02 16.97 17.14 19.04 19.30 19.333F 5.08 5.09 5.06 5.01 5.00 5.19 5.18 5.20 5.21 5.241F 5.60 5.60 5.59 5.54 5.53 5.69 5.68 5.70 5.70 5.723F 15.80 15.85 15.89 15.89 15.82 15.77 15.73 15.63 15.74 15.831F 13.86 13.92 13.93 13.59 13.55 13.54 13.51 13.46 13.51 13.543F 3.43 3.43 3.42 3.41 3.40 3.45 3.45 3.47 5.11 5.141F 2.36 2.36 2.36 2.36 2.35 2.37 2.37 2.38 4.61 4.633F 3.71 3.731F 3.50 3.513F 6.16 6.201F 6.84 6.88

P.I. Buena Vista BNA 115

P.P.G. Industrial PPG 115

230

115P.H. Zimapán ZMN

Ojuelos OJU 115

P. Farmacéuticos Collins PFC 69

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Ojo Caliente OCL 115

Ojo Seco OJO 115

Paracho II POD 115

Parque Industrial PQI 69

Palo Alto PAO 115

115

115

Pánfilo Natera PFN

Papel Potosí

P.T.M. PMT 115

Pabellón PAB 115

Pátzcuaro Norte PTN 115

Pátzcuaro Potencia PTP230

115

PPT

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 153: Catalogo 2011-2020 r010212 Corto Circuito

153

Coordinación de Planificación

ÁREA OCCIDENTAL

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 3.51 3.51 3.51 3.50 3.49 3.53 3.54 3.55 5.63 5.671F 2.43 2.43 2.43 2.43 2.42 2.44 2.45 2.45 5.33 5.353F 7.52 7.69 7.71 7.801F 6.45 6.57 6.58 6.623F 9.31 9.39 9.40 9.491F 9.78 9.86 9.87 9.933F 3.86 3.88 3.86 3.78 3.81 3.79 3.84 3.85 3.86 3.871F 3.86 3.87 3.70 3.74 3.77 3.76 3.83 3.84 3.85 3.853F 8.03 8.03 7.99 8.05 8.04 8.05 8.03 8.07 8.07 8.071F 6.13 6.13 6.11 6.13 6.13 6.13 6.13 6.14 6.14 6.143F 11.98 11.99 11.88 11.87 14.03 13.90 14.11 14.12 14.19 14.791F 10.99 11.00 10.84 10.90 11.98 12.04 12.02 12.02 12.06 12.433F 10.33 10.33 10.32 10.38 10.40 11.00 11.06 11.06 11.20 11.391F 7.77 7.77 7.76 7.81 7.82 8.22 8.24 8.25 8.33 8.403F 9.22 9.25 9.30 9.29 9.27 9.25 9.26 9.27 9.30 9.371F 6.62 6.63 6.65 6.65 6.64 6.63 6.64 6.64 6.65 6.673F 3.68 3.68 3.68 3.68 3.69 3.68 3.69 3.69 3.70 3.731F 2.66 2.66 2.66 2.66 2.66 2.66 2.67 2.67 2.67 2.683F 15.35 15.41 15.46 10.42 10.39 10.39 10.31 12.50 12.55 12.731F 16.10 16.17 16.20 11.93 11.89 11.90 11.82 13.67 13.71 13.863F 4.52 4.56 4.69 4.66 6.46 6.36 4.76 4.80 4.82 4.851F 3.08 3.09 3.16 3.15 4.51 4.47 3.23 3.25 3.25 3.263F 11.37 11.38 11.46 11.44 11.51 11.48 11.63 11.63 11.64 11.651F 8.90 8.91 8.94 8.93 8.96 8.95 9.01 9.05 9.05 9.063F 3.17 3.18 3.34 3.33 3.36 3.35 3.37 3.37 3.37 3.371F 2.21 2.22 2.29 2.29 2.30 2.30 2.30 2.30 2.30 2.303F 10.60 10.63 10.68 10.61 10.71 10.72 10.98 11.01 11.02 11.051F 7.91 7.92 7.94 7.92 7.96 7.95 8.08 8.09 8.10 8.113F 2.27 2.27 2.29 2.71 2.24 3.04 3.04 3.04 3.04 3.061F 1.57 1.58 1.58 1.87 1.57 1.97 1.97 1.97 1.97 1.973F 14.29 14.34 14.38 9.27 9.25 9.25 9.18 10.87 10.91 11.051F 13.45 13.50 13.52 9.64 9.61 9.62 9.56 10.73 10.75 10.843F 13.62 13.65 13.85 13.82 13.81 15.65 16.16 16.19 16.25 16.671F 12.85 12.88 13.04 13.04 13.04 14.04 14.33 14.34 14.37 14.593F 2.91 2.91 2.99 3.03 2.61 3.76 3.76 3.77 3.78 3.781F 2.50 2.50 2.54 2.71 2.36 3.09 3.09 3.09 3.10 3.10

PIZ

Pedro Moreno PRO

Peñasco PEN

Peñitas PTS

Petroquímica INP 69

115

115

Piel PEL

Pinzándaro

Peñuelas PEU 115

Periban PRB 115

Peña Colorada PEC 115

115

115

Pénjamo PNJ 115

Penwalt MXM 69

Pemsa PEM 115

Penal PNL 69

Pemex, Lázaro Cárdenas PMX 115

Pemex, Salamanca PMX 115

115

Peletizadora Tapeixtles PTP 69

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Pátzcuaro Sur PCS 115

230

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 154: Catalogo 2011-2020 r010212 Corto Circuito

154

Coordinación de Planificación

ÁREA OCCIDENTAL

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 4.82 4.83 4.86 4.67 5.91 5.92 6.19 6.20 6.20 6.231F 5.37 5.38 5.26 5.20 6.21 6.22 6.43 6.43 6.43 6.503F 21.40 21.43 21.53 21.57 21.59 21.79 21.95 21.65 22.07 22.131F 23.29 23.32 23.40 23.44 23.45 23.70 23.85 23.65 23.94 23.583F 15.24 15.25 15.26 15.19 15.29 15.33 15.38 17.15 15.41 15.431F 17.22 17.23 17.24 17.19 17.26 17.30 17.35 19.09 17.37 17.353F 11.30 11.31 11.32 11.32 11.32 11.32 11.31 11.53 11.88 11.891F 10.25 10.25 10.26 10.26 10.26 10.26 10.25 10.38 10.56 10.573F 6.83 6.83 6.82 6.82 6.83 6.82 6.84 6.84 6.89 6.951F 4.72 4.72 4.72 4.72 4.72 4.72 4.73 4.73 4.75 4.773F 4.03 4.04 4.04 3.85 3.85 3.88 3.88 11.18 11.21 6.811F 2.94 2.94 2.94 2.87 2.87 2.89 2.89 9.35 9.36 5.003F 5.77 5.78 5.78 5.54 5.54 5.55 5.55 5.59 5.60 5.621F 3.81 3.82 3.81 3.90 3.90 3.91 3.91 3.92 3.93 3.933F 16.66 16.67 17.02 17.01 17.02 17.02 17.07 18.04 18.18 18.321F 13.35 13.36 13.63 13.62 13.63 13.63 13.65 14.14 14.20 14.263F 13.08 13.18 13.20 13.10 13.45 13.42 14.61 14.66 14.77 15.421F 12.19 12.28 12.26 12.23 12.42 13.22 14.09 14.12 14.19 14.603F 13.33 13.38 13.51 13.44 13.47 13.90 14.71 14.76 14.85 15.521F 15.39 15.45 15.57 15.54 15.55 15.38 16.11 16.15 16.23 16.763F 13.73 13.75 15.81 15.77 15.78 20.88 21.60 21.64 21.73 22.331F 16.43 16.46 18.73 18.70 18.70 21.54 22.08 22.10 22.16 22.583F 7.95 8.14 8.14 8.151F 5.60 5.72 5.73 5.733F 7.62 7.62 7.63 7.63 7.63 7.63 7.62 7.72 7.82 7.831F 5.44 5.44 5.45 5.45 5.45 5.44 5.44 5.48 5.51 5.513F 4.08 4.08 4.24 4.31 3.53 6.04 6.03 6.04 6.06 6.091F 3.64 3.64 3.73 4.23 3.36 5.37 5.37 5.37 5.39 5.403F 11.92 11.94 11.98 12.00 11.98 12.02 18.18 18.12 18.32 18.921F 9.24 9.26 9.27 9.28 9.27 9.29 14.58 14.55 14.63 14.883F 7.65 7.66 7.71 7.68 8.91 8.91 9.15 9.25 9.25 9.271F 5.14 5.16 5.18 5.16 6.27 6.26 6.37 6.40 6.40 6.413F 7.81 7.81 7.82 7.82 7.82 7.82 7.84 7.88 7.91 7.951F 5.22 5.22 5.22 5.22 5.22 5.23 5.23 5.25 5.26 5.273F 6.05 6.06 6.07 5.21 5.21 5.21 5.19 8.71 8.73 11.821F 4.41 4.42 4.42 4.09 4.09 4.09 4.08 6.67 6.68 10.03

GTR

Pitirera PIT

Potrerillos POS

Pozo Bravo POB

Primero de Mayo PMY 400

115

69

Procter & Gamble PTG

Productos Quaker

Pradera PAD 115

Praxair PRX 69

115

115

115PPG PPG

400

230

Porcelanite Guanajuato POR 115

Porcelanite Querétaro PRC 115

Polivin POL 115

Poncintlán II PNC 69

230

Pitsa CPC 115

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Pitillal PLL 115

400

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 155: Catalogo 2011-2020 r010212 Corto Circuito

155

Coordinación de Planificación

ÁREA OCCIDENTAL

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 11.44 11.46 11.56 11.54 11.61 11.58 11.70 11.99 12.02 12.031F 9.30 9.32 9.37 9.36 9.39 9.38 9.45 9.59 9.60 9.613F 5.16 5.17 5.19 5.18 5.19 5.19 5.21 5.35 5.35 5.351F 4.19 4.22 4.23 4.22 4.23 4.23 4.23 4.30 4.30 4.303F 13.85 13.86 13.83 13.82 13.85 13.83 13.91 13.91 14.12 14.391F 11.43 11.43 11.41 11.42 11.43 11.42 11.46 11.46 11.58 11.703F 8.34 8.35 8.33 8.33 8.38 8.33 8.42 8.42 8.44 8.571F 6.02 6.02 6.01 6.01 6.03 6.01 6.04 6.05 6.05 6.103F 9.60 9.63 9.65 9.27 9.25 9.23 9.22 9.20 9.23 9.271F 6.82 6.84 6.84 6.69 6.68 6.68 6.67 6.66 6.67 6.693F 11.26 11.55 11.39 10.27 10.43 10.17 10.32 10.51 10.62 10.771F 9.52 9.66 9.05 8.56 8.66 8.54 8.65 8.75 8.80 8.873F 9.83 9.90 9.97 10.02 10.251F 8.65 8.69 8.72 8.75 8.873F 17.61 17.67 17.73 17.78 18.321F 17.61 17.65 17.70 17.73 18.103F 7.85 7.86 7.85 7.87 7.86 8.19 8.20 8.22 8.23 8.311F 6.59 6.59 6.59 6.60 6.59 6.79 6.79 6.80 6.81 6.843F 2.76 2.76 2.76 2.76 2.76 2.62 2.62 2.63 2.63 2.631F 2.06 2.06 2.06 2.06 2.06 1.95 1.95 1.95 1.95 1.953F 1.32 1.32 1.36 1.32 1.32 1.33 1.26 1.33 1.33 1.331F 0.92 0.92 0.93 0.92 0.92 0.93 0.90 0.93 0.93 0.933F 21.09 21.11 21.18 21.10 21.14 21.13 21.27 23.19 23.62 24.061F 21.21 21.23 22.08 22.01 22.04 22.04 22.14 24.38 24.68 24.993F 26.98 27.00 28.92 28.89 28.94 28.93 29.06 33.04 33.51 33.971F 31.48 31.50 35.07 35.06 35.10 35.10 35.21 40.04 40.49 40.923F 11.47 11.48 11.56 11.55 11.56 11.56 11.58 11.89 11.95 12.011F 8.29 8.29 8.34 8.34 8.34 8.34 8.35 8.47 8.49 8.513F 18.59 18.60 18.84 18.81 18.83 18.83 18.89 19.73 19.90 20.081F 15.47 15.47 15.65 15.64 15.65 15.65 15.67 16.12 16.19 16.273F 18.88 18.89 19.56 19.54 19.56 19.56 19.61 21.20 21.40 21.581F 16.44 16.45 17.11 17.10 17.11 17.11 17.14 18.11 18.20 18.283F 15.80 15.81 16.00 15.98 15.99 15.99 16.02 16.91 17.05 17.151F 12.94 12.94 13.09 13.08 13.08 13.08 13.10 13.58 13.64 13.683F 15.65 15.66 15.95 15.93 15.95 15.94 15.99 21.52 21.71 21.921F 12.43 12.43 12.64 12.64 12.64 12.64 12.66 19.24 19.34 19.45

Purépecha PUP

Querétaro Oriente QRE

Querétaro Poniente QPE

Querétaro Norte QRN 115

115

115

Querétaro Industrial QRI 115

Querétaro Maniobras QMR 115

Puruarán PUU 69

Querétaro I QRO

230

115

Purépero PRP 115

Puruándiro PUR 115

400

115

Puente Grande PNG 69

Puerto Interior PRT 115

Proteínas y Oléicos PRO 115

Pueblo Nuevo PNV 115

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Progreso SPD 115

Pronapade PPN 115

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 156: Catalogo 2011-2020 r010212 Corto Circuito

156

Coordinación de Planificación

ÁREA OCCIDENTAL

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 19.98 20.00 19.99 19.96 19.95 20.00 20.33 21.37 21.85 22.431F 15.96 15.97 15.95 15.97 15.91 15.96 16.10 18.43 18.66 18.953F 19.45 19.49 19.42 19.39 19.35 19.41 19.82 20.05 20.42 21.191F 17.80 17.83 17.75 17.79 17.65 17.76 17.97 18.88 19.10 19.563F 24.56 24.60 24.54 24.48 24.57 24.54 24.84 25.22 25.77 26.581F 27.10 27.15 27.15 27.13 27.16 27.16 27.40 28.30 28.77 29.443F 24.74 24.76 24.89 24.85 24.89 24.88 25.01 26.15 26.45 26.831F 28.77 28.79 28.94 28.91 28.94 28.94 29.05 30.25 30.51 30.843F 17.95 17.96 18.11 18.09 18.11 18.11 18.17 20.07 20.25 20.461F 15.59 15.60 15.72 15.71 15.72 15.71 15.75 17.51 17.59 17.693F 2.27 2.27 2.27 2.26 2.26 2.28 2.28 2.29 2.90 2.911F 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.51 2.16 2.163F 2.93 2.93 2.93 2.67 2.96 2.95 2.98 2.99 2.99 2.981F 2.19 2.19 2.20 2.09 2.21 2.20 2.21 2.22 2.22 2.213F 15.57 15.60 15.83 15.81 15.93 15.87 16.08 19.78 19.80 19.831F 14.04 14.14 14.30 14.29 14.35 14.32 14.45 17.29 17.30 17.323F 15.35 15.37 15.18 15.17 15.09 18.74 19.12 19.13 19.27 20.391F 16.57 16.59 16.23 16.37 16.21 19.19 19.10 19.11 19.22 20.153F 2.42 2.42 2.42 2.24 2.44 2.43 2.45 2.46 2.46 2.451F 1.74 1.75 1.75 1.68 1.75 1.75 1.76 1.76 1.76 1.763F 7.70 7.71 7.98 7.97 8.20 8.04 8.28 8.28 8.30 8.451F 6.34 6.34 6.44 6.53 6.63 6.56 6.66 6.67 6.67 6.743F 14.50 14.55 14.59 10.13 10.10 10.10 10.02 12.06 12.11 12.281F 14.70 14.75 14.78 11.28 11.25 11.26 11.19 12.81 12.84 12.973F 3.88 3.88 3.89 3.98 3.98 9.86 9.87 9.90 9.92 10.331F 2.88 2.88 2.88 2.92 2.92 7.62 7.62 7.64 7.64 7.853F 3.85 3.86 3.87 3.87 3.88 3.87 3.88 4.07 4.07 4.071F 2.53 2.53 2.53 2.53 2.53 2.53 2.54 2.61 2.61 2.613F 8.20 8.37 8.27 7.70 7.79 7.64 7.72 7.83 7.89 7.971F 6.21 6.29 6.01 5.81 5.86 5.80 5.86 5.90 5.92 5.953F 17.53 17.64 17.42 17.36 16.75 17.09 17.91 17.96 18.15 19.521F 17.95 18.05 17.16 17.66 15.82 16.74 17.16 17.24 17.36 18.453F 23.33 23.43 22.40 22.35 21.46 20.72 21.86 21.87 22.51 28.041F 28.02 28.14 24.41 26.29 24.22 23.67 24.61 24.64 25.28 32.313F 17.05 17.08 16.84 16.83 17.10 21.29 21.79 21.80 21.99 23.451F 20.22 20.25 19.72 19.93 20.26 24.22 24.11 24.12 24.29 25.80

SHY

Salamanca SLM

400

230

115

Saint Gobain Calmar SCA 115

Salahua SLH 115

Romita RTA 115

69

115

Sach SCH

Sahuayo

Resistol RTL 115

Río Grande RGR 115

Rancho Grande RAG 115

REMY Componentes DEL 115

Querétaro Sur QRS 115

Quiroga QRG 115

230

115

Querétaro Potencia QRP

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Querétaro Pot. Maniobras QRM 400

400

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 157: Catalogo 2011-2020 r010212 Corto Circuito

157

Coordinación de Planificación

ÁREA OCCIDENTAL

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 22.67 22.46 22.40 21.62 20.86 22.02 22.04 22.70 28.481F 26.27 24.07 26.25 24.44 23.86 24.84 24.86 25.54 33.233F 17.32 17.45 17.28 17.22 16.93 17.18 18.07 18.13 18.32 19.661F 17.43 17.55 16.96 17.28 16.06 17.01 17.38 17.45 17.57 18.563F 11.75 11.78 11.94 11.93 11.77 11.56 11.89 11.89 12.06 13.371F 9.38 9.40 9.38 9.63 9.44 9.35 9.49 9.49 9.58 10.353F 13.28 13.29 13.17 13.16 13.11 22.31 22.80 22.82 22.96 24.071F 12.97 12.98 12.81 12.87 12.79 23.30 17.73 17.74 17.80 18.343F 15.13 15.15 14.97 14.96 14.88 19.51 19.91 19.92 20.07 21.211F 15.92 15.94 15.62 15.75 15.60 19.56 18.97 18.98 19.07 19.933F 12.08 12.10 11.99 11.98 11.94 18.09 18.41 18.42 18.52 19.281F 11.08 11.09 10.96 11.00 13.89 16.43 13.96 13.97 14.01 14.363F 12.95 12.97 12.84 12.83 12.77 17.07 17.37 17.38 17.48 18.281F 12.22 12.23 12.05 12.12 12.04 15.31 14.45 14.46 14.51 14.963F 1.26 1.26 1.26 1.25 2.92 2.91 2.91 3.17 3.17 3.171F 0.80 0.80 0.80 0.80 1.87 1.87 1.86 2.07 2.07 2.073F 3.44 3.45 3.45 3.44 3.46 3.46 3.48 3.49 3.49 3.491F 2.24 2.24 2.24 2.24 2.24 2.24 2.24 2.25 2.25 2.253F 3.97 3.97 3.97 4.13 4.13 4.10 4.12 4.14 4.15 4.221F 2.62 2.62 2.62 2.71 2.71 2.69 2.69 2.70 2.71 2.743F 5.80 10.44 10.46 10.10 10.11 10.13 10.15 10.31 10.34 10.381F 4.05 7.89 7.91 7.88 7.88 7.89 7.90 7.97 7.98 8.003F 3.88 3.84 3.89 3.85 3.85 3.85 3.85 3.85 3.87 3.881F 2.50 2.49 2.50 2.49 2.49 2.49 2.49 2.49 2.50 2.503F 6.28 6.29 6.30 6.51 6.51 7.70 7.71 7.82 7.84 8.151F 5.25 5.25 5.26 5.37 5.37 5.95 5.95 6.09 6.09 6.243F 7.79 7.80 7.84 7.69 7.95 7.96 8.12 9.15 9.16 9.141F 5.54 5.55 5.56 5.51 5.64 5.66 5.72 6.70 6.71 6.703F 2.33 2.34 2.33 2.23 2.23 2.23 2.241F 1.51 1.51 1.51 1.44 1.44 1.44 1.443F 3.26 1.69 3.27 1.69 1.69 1.68 1.65 1.65 1.65 1.651F 2.14 1.38 2.14 1.38 1.38 1.38 1.34 1.34 1.34 1.353F 4.25 4.27 4.25 4.20 4.32 4.33 4.33 4.33 4.47 4.471F 2.86 2.88 2.86 2.85 2.95 2.96 2.96 2.96 3.05 3.053F 6.17 6.18 8.58 8.56 8.57 9.88 10.04 10.04 10.06 10.191F 4.77 4.78 7.03 7.02 7.02 7.39 7.45 7.45 7.46 7.50

SDP

San Fco. del Rincón SFQ

Salamanca II SMD

San Agustín SAG

69

115

115

San Clemente SCM

San Diego Peñuelas

San Antonio SAN 115

115

Samsung SSG 115

69

115San Andrés SDS

Salitre STE 115

Salvatierra SVT 115

Salamanca Sur SSU 115

Salinas SNS 115

Salamanca Norte SLN 115

Salamanca Poniente SMP 115

230

115

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Salamanca CC SLMCC 230

400

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 158: Catalogo 2011-2020 r010212 Corto Circuito

158

Coordinación de Planificación

ÁREA OCCIDENTAL

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 1.83 1.83 1.83 1.83 1.84 1.93 1.93 1.93 1.94 1.941F 1.16 1.16 1.16 1.16 1.16 1.22 1.22 1.22 1.23 1.233F 10.26 10.29 10.35 10.25 10.40 10.39 10.65 10.77 10.78 10.791F 7.63 7.64 7.67 7.63 7.69 7.68 7.80 7.86 7.86 7.863F 10.78 10.80 10.87 10.76 10.93 10.91 11.21 11.34 11.35 11.371F 8.13 8.15 8.18 8.14 8.20 8.19 8.33 8.39 8.40 8.403F 15.36 15.36 15.41 15.40 15.41 15.39 15.39 15.83 16.36 16.401F 12.18 12.19 12.21 12.21 12.21 12.21 12.20 12.50 12.71 12.733F 7.59 7.60 7.34 7.65 7.60 7.61 7.36 7.62 7.63 7.631F 6.03 6.03 5.85 6.06 6.03 6.03 5.86 6.04 6.04 6.043F 2.02 2.02 2.02 1.89 2.03 2.03 2.04 2.05 2.05 2.041F 1.42 1.42 1.42 1.37 1.42 1.42 1.42 1.43 1.43 1.423F 6.86 6.87 6.88 6.01 6.00 6.03 6.00 9.40 9.43 7.641F 5.10 5.11 5.11 4.77 4.77 4.78 4.77 7.43 7.44 5.803F 2.24 2.24 2.24 2.27 2.27 3.48 3.48 3.48 3.48 3.531F 1.50 1.50 1.50 1.53 1.53 2.25 2.25 2.26 2.26 2.273F 15.99 16.26 16.581F 13.53 13.66 13.813F 22.52 22.96 23.271F 23.48 23.78 24.003F 7.03 7.05 7.03 6.20 6.20 6.22 6.22 6.26 6.28 6.291F 4.84 4.86 4.84 4.56 4.56 4.57 4.57 4.58 4.59 4.593F 6.03 6.04 6.05 6.03 6.16 6.08 6.23 6.24 6.24 6.261F 4.86 4.86 4.87 4.86 4.92 4.88 4.95 4.95 4.96 4.963F 7.13 7.15 7.20 7.12 7.59 7.25 7.77 7.80 7.82 7.871F 6.63 6.65 6.67 6.63 6.93 6.71 7.03 7.05 7.06 7.093F 9.53 9.55 9.58 9.53 9.88 9.67 10.06 10.09 10.10 10.151F 10.74 10.77 10.80 10.75 11.07 10.88 11.22 11.24 11.25 11.293F 16.00 16.01 16.04 16.03 16.04 16.03 16.02 16.49 17.20 17.231F 16.18 16.19 16.21 16.21 16.21 16.20 16.20 16.53 16.99 17.003F 12.67 12.70 12.71 12.70 12.71 12.71 12.71 13.25 13.71 13.761F 11.75 11.77 11.77 11.78 11.78 11.77 11.78 12.13 12.38 12.383F 18.65 18.67 18.71 18.70 18.71 18.69 18.67 19.34 20.43 20.471F 23.61 23.64 23.67 23.67 23.68 23.66 23.64 24.40 25.53 25.563F 15.63 15.65 15.67 15.66 15.67 15.66 15.65 16.10 16.80 16.821F 15.74 15.75 15.77 15.77 15.77 15.76 15.76 16.08 16.52 16.53

SJM

San Jose El Alto SJA

San Juan de los Lagos JDL

230

115

115

San Juan del Río II SRD

San Juan del Río Man.

115

San Juan del Río SJR 115

San Juan de los Lagos II SJD

San José Iturbide SJI 115

115

230

400

230

San Jorge SAJ 69

San José de Gracia SJG 115

San Isidro SIO 115

San Jerónimo SJE 115

San Francisco Industrial SFI 115

San Idelfonso SFS 115

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

San Felipe SFL 115

San Francisco SFR 115

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 159: Catalogo 2011-2020 r010212 Corto Circuito

159

Coordinación de Planificación

ÁREA OCCIDENTAL

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 9.60 9.60 9.61 9.61 9.61 9.61 9.61 9.77 9.98 9.991F 7.33 7.34 7.34 7.34 7.34 7.34 7.34 7.40 7.48 7.483F 13.33 13.48 13.34 12.45 13.56 13.65 13.66 13.73 15.20 15.241F 11.86 12.12 11.87 11.31 13.16 13.22 13.23 13.27 15.38 15.413F 16.48 17.14 16.52 16.97 16.99 17.03 17.08 17.29 17.36 17.451F 17.37 18.88 17.43 18.69 19.21 19.25 19.29 19.45 20.42 20.503F 16.28 16.51 16.30 15.48 17.24 17.38 17.42 17.53 20.00 20.071F 16.46 16.98 16.49 16.08 20.13 20.27 20.29 20.39 25.87 25.943F 13.06 13.11 13.43 13.40 13.57 13.49 14.02 14.08 14.11 14.141F 13.16 13.26 13.52 13.49 13.61 13.55 14.30 14.19 14.21 14.233F 17.44 17.48 17.72 17.68 17.84 17.77 18.07 18.53 18.57 18.601F 18.69 18.76 18.95 18.92 19.04 18.99 19.34 19.69 19.72 19.753F 15.04 15.07 15.28 15.25 15.36 15.31 15.50 18.11 20.54 20.581F 13.33 13.41 13.53 13.52 13.58 13.55 13.66 15.39 18.31 18.333F 10.47 10.48 10.56 10.54 10.60 10.57 10.68 10.87 10.89 10.901F 7.76 7.77 7.80 7.79 7.81 7.80 7.85 7.93 7.94 7.943F 13.59 13.61 13.76 13.74 13.83 13.79 13.96 14.77 14.83 14.851F 11.24 11.27 11.35 11.34 11.38 11.36 11.45 11.86 11.90 11.913F 13.09 13.11 13.24 13.22 13.30 13.26 13.42 13.97 14.03 14.051F 10.33 10.36 10.42 10.41 10.44 10.43 10.50 10.75 10.79 10.793F 13.42 13.47 13.71 13.67 13.86 13.77 14.08 14.97 15.02 15.061F 13.07 13.31 13.47 13.44 13.57 13.51 13.72 14.44 14.50 14.523F 20.66 20.72 21.08 21.03 21.25 21.14 21.52 25.29 25.68 25.741F 22.88 23.08 23.40 23.36 23.54 23.46 23.78 27.31 27.77 27.823F 11.21 11.23 11.33 11.31 11.38 11.35 11.46 11.92 11.95 11.971F 8.75 8.77 8.81 8.81 8.83 8.82 8.88 9.08 9.10 9.113F 10.62 10.79 10.84 11.18 10.98 10.90 11.65 11.67 11.82 12.021F 10.43 10.57 10.60 10.73 10.69 10.65 11.30 11.32 11.41 11.523F 2.98 2.98 2.99 2.98 3.01 3.00 3.03 3.03 3.03 3.041F 2.08 2.09 2.09 2.08 2.10 2.09 2.10 2.10 2.10 2.103F 10.34 10.35 10.34 10.52 10.54 10.77 10.78 10.86 10.93 10.981F 8.10 8.10 8.10 8.18 8.20 8.37 8.38 8.41 8.45 8.473F 8.35 8.35 8.35 8.43 8.45 8.55 8.57 8.60 8.65 8.691F 5.98 5.98 5.98 6.01 6.02 6.09 6.09 6.10 6.12 6.143F 5.47 5.48 9.93 9.92 9.92 11.72 11.95 11.96 11.98 12.171F 4.10 4.10 8.64 8.63 8.63 9.19 9.29 9.29 9.30 9.37

ROQ

San Luis de la Paz II SPA

San Luis II SLD

San Luis Potosí SLP

San Miguel Allende MAL 115

115

115

San Miguel Allende sur SMS

San Roque

San Martín SMT 230

San Miguel SMG 115

230

115

115San Luis Progreso SPR

San Luis Oriente SLO 115

San Luis Poniente SLW 115

San Luis Industrial SLI 115

San Luis Norte SLN 115

230

115

230

115

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

San Juan del Río Ote. SJO 115

San Luis de la Paz SAP 115

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 160: Catalogo 2011-2020 r010212 Corto Circuito

160

Coordinación de Planificación

ÁREA OCCIDENTAL

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 11.59 11.52 11.64 11.56 11.74 11.71 11.77 11.74 11.89 11.951F 8.18 8.16 8.20 8.17 8.23 8.22 8.25 8.23 8.29 8.313F 5.97 5.97 5.97 5.97 5.97 5.97 5.98 5.98 6.02 6.071F 4.06 4.06 4.06 4.06 4.06 4.06 4.06 4.06 4.08 4.093F 10.52 10.53 10.52 10.64 10.64 10.66 10.69 10.91 10.98 11.051F 9.88 9.89 9.90 9.98 9.99 10.00 10.02 10.16 10.20 10.253F 14.48 14.48 14.48 14.95 14.97 15.06 15.09 15.32 15.40 15.491F 16.94 16.95 16.96 17.41 17.43 17.53 17.55 17.76 17.84 17.913F 17.64 17.70 17.59 17.56 17.41 17.53 18.01 18.10 18.33 19.221F 16.37 16.41 16.20 16.31 15.95 16.19 16.44 16.75 16.89 17.443F 25.98 26.01 25.93 26.05 26.14 26.42 26.72 26.68 27.10 27.901F 24.54 24.56 24.45 24.63 24.59 25.04 25.21 25.29 25.56 26.063F 6.44 5.84 5.73 5.84 5.84 5.84 5.84 5.84 5.85 5.851F 8.31 7.63 7.48 7.63 7.63 7.63 7.63 7.63 7.64 7.643F 4.04 4.04 4.31 4.30 4.34 4.34 4.36 4.36 4.36 4.361F 2.94 2.94 3.08 3.08 3.09 3.09 3.09 3.10 3.10 3.103F 10.48 10.49 10.56 10.55 10.61 10.58 10.69 10.88 10.90 10.911F 7.76 7.78 7.80 7.80 7.82 7.81 7.85 7.94 7.95 7.953F 8.15 8.16 8.15 8.31 7.81 7.73 8.94 9.13 9.47 9.781F 8.30 8.30 8.30 8.40 7.59 7.53 10.08 10.24 10.56 10.823F 17.49 17.50 18.03 18.02 18.04 18.03 18.09 20.50 20.68 20.861F 14.59 14.60 15.06 15.05 15.06 15.06 15.08 17.66 17.74 17.833F 3.53 4.10 3.55 4.10 4.10 4.09 4.09 4.10 4.12 4.131F 2.76 3.06 2.37 3.06 3.06 3.06 3.06 3.06 3.07 3.073F 1.15 1.15 1.17 1.17 1.17 1.17 1.18 1.18 1.18 1.181F 0.75 0.75 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.763F 6.02 6.03 6.04 7.03 7.02 7.02 6.98 7.90 7.92 7.991F 4.10 4.11 4.11 6.19 6.18 6.18 6.16 6.61 6.62 6.663F 1.80 1.82 3.08 1.81 1.81 1.81 1.81 1.81 1.81 1.811F 1.23 1.24 1.94 1.23 1.23 1.23 1.23 1.23 1.23 1.233F 7.77 7.79 7.79 11.36 11.31 11.29 11.27 11.25 11.30 11.371F 5.51 5.52 5.52 8.78 8.76 8.75 8.75 8.74 8.76 8.783F 4.58 4.58 4.59 4.09 4.08 4.08 4.07 5.46 5.47 8.501F 3.17 3.18 3.18 3.01 3.01 3.01 3.00 3.77 3.78 6.513F 5.77 5.77 5.78 5.00 5.00 5.00 4.98 7.23 7.25 13.701F 4.16 4.17 4.17 3.88 3.88 3.88 3.87 5.26 5.27 12.66

SDM

Santa Fé STF

Santa María SMR

Sayula SYL

Siapa SPA 69

69

69

Siapa Chapala STC

Siapa Soledad

SCI SCI 69

Servicios La Yesca SYL 115

Satélite STL 115

115

115Sayulita SAY

Santiago SNG 115

Santiaguito STG 115

Santa Rosa SRO 69

Santiago SIN 115

400

115

230

115

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Santa Cruz SCU 69

Santa Cruz SCZ 115

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 161: Catalogo 2011-2020 r010212 Corto Circuito

161

Coordinación de Planificación

ÁREA OCCIDENTAL

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 11.60 11.63 11.67 11.67 11.76 11.74 11.87 11.74 11.84 11.911F 8.44 8.46 8.47 8.31 8.34 8.34 8.40 8.34 8.37 8.393F 13.26 13.28 13.21 13.20 13.20 13.13 13.37 13.37 14.58 15.701F 11.03 11.04 10.94 11.01 10.98 10.98 11.09 11.10 12.18 12.783F 10.98 10.98 10.97 12.66 11.00 11.01 11.04 11.04 11.07 11.081F 9.31 9.31 9.30 10.34 9.32 9.32 9.33 9.33 9.35 9.353F 15.82 15.83 15.82 15.88 15.87 15.89 16.00 16.10 16.04 16.061F 13.20 13.20 13.20 13.24 13.22 13.23 13.28 13.34 13.30 13.313F 4.11 4.11 4.12 4.19 4.19 4.18 4.16 4.15 4.16 4.171F 4.24 4.25 4.24 4.31 4.30 4.29 4.28 4.26 4.28 4.283F 11.18 11.20 11.68 11.67 12.21 11.85 12.41 12.42 12.46 12.781F 10.51 10.53 10.74 10.96 11.28 11.06 11.39 11.39 11.42 11.603F 9.78 9.80 12.43 12.40 13.61 12.70 14.08 14.10 14.24 15.221F 9.15 9.17 10.22 12.05 12.79 12.20 13.05 13.06 13.14 13.743F 13.30 13.32 14.13 14.11 14.83 14.32 15.10 15.12 15.18 15.681F 14.95 14.98 15.53 16.06 16.68 16.23 16.90 16.91 16.97 17.393F 9.02 9.03 9.27 9.26 9.51 9.32 9.60 9.60 9.63 9.831F 7.19 7.19 7.28 7.34 7.44 7.36 7.48 7.48 7.49 7.573F 11.18 11.20 11.68 11.67 12.21 11.85 12.41 12.42 12.46 12.781F 10.51 10.53 10.74 10.96 11.28 11.06 11.39 11.39 11.42 11.603F 13.73 13.76 13.92 13.90 14.00 13.95 14.11 15.87 15.96 15.991F 11.75 11.81 11.89 11.88 11.93 11.91 11.99 13.00 13.06 13.073F 11.60 11.63 11.67 11.67 11.76 11.74 11.87 11.74 11.84 11.911F 8.44 8.46 8.47 8.31 8.34 8.34 8.40 8.34 8.37 8.393F 11.89 11.91 12.00 11.99 12.06 12.03 12.17 12.28 12.29 12.311F 9.54 9.56 9.60 9.60 9.63 9.61 9.69 9.75 9.75 9.763F 7.29 7.30 7.211F 7.02 7.02 6.953F 12.00 12.01 11.901F 13.30 13.30 13.213F 6.71 6.73 7.50 7.62 7.73 7.73 7.79 7.79 7.80 7.811F 5.67 5.68 6.21 6.31 6.37 6.36 6.39 6.39 6.39 6.393F 3.64 3.64 3.64 3.54 3.53 3.58 3.57 6.43 6.44 5.061F 2.80 2.80 2.80 2.76 2.76 2.78 2.78 4.85 4.85 3.783F 2.15 2.15 2.15 2.15 2.15 2.15 2.16 2.16 2.16 2.171F 1.45 1.45 1.45 1.45 1.45 1.45 1.45 1.45 1.45 1.45

TBY

Silao II SID

Sistemas Electrónicos J. SEJ

Soledad de G. Sánchez SDG

Tabacalera TAB 115

69

115

Tableros Emman EMM

Tacubaya

230

115Soyatal SOY

Siposa SIP 115

69

115

Silao Industrial SII 115

Silao Norte SIN 115

230

115

Siderúrgica Guadalajara SID 161

Silao SIL 115

Sicartsa I SIC 230

Sicartsa II SCD 230

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Siapa Toluquilla SIT 69

Sibasa SIB 230

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 162: Catalogo 2011-2020 r010212 Corto Circuito

162

Coordinación de Planificación

ÁREA OCCIDENTAL

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 6.06 3.64 3.62 3.64 3.64 3.64 3.64 3.64 3.64 3.641F 4.12 2.59 2.58 2.59 2.59 2.59 2.59 2.59 2.59 2.593F 0.70 0.59 0.70 0.59 0.59 0.59 0.58 0.59 0.59 0.591F 0.47 0.44 0.47 0.44 0.44 0.44 0.43 0.43 0.43 0.433F 5.59 5.60 5.66 5.40 7.15 7.15 7.56 7.56 7.57 7.581F 7.20 7.22 7.15 6.95 8.88 8.89 9.32 9.32 9.33 9.423F 2.78 2.84 2.79 2.84 2.84 2.83 2.84 2.84 2.85 2.851F 2.11 2.14 2.11 2.14 2.14 2.13 2.14 2.14 2.14 2.143F 11.22 11.24 11.33 11.32 11.38 11.35 11.46 11.98 12.03 12.051F 8.54 8.56 8.60 8.59 8.61 8.60 8.65 8.87 8.90 8.903F 5.05 5.05 5.06 5.43 5.41 6.69 6.70 6.70 6.71 6.901F 4.83 4.83 4.84 5.12 5.11 5.84 5.84 5.85 5.85 5.953F 2.75 2.75 2.75 2.76 2.771F 1.91 1.91 1.91 1.92 1.923F 14.99 15.49 14.92 13.04 13.64 13.20 14.33 14.71 14.93 15.231F 14.57 14.91 13.21 12.18 12.77 12.49 13.94 14.19 14.34 14.533F 15.66 17.43 17.43 17.49 17.46 15.03 15.08 16.76 18.05 19.761F 18.40 20.35 20.30 20.36 20.35 17.80 17.84 19.69 21.05 22.853F 15.41 16.34 16.33 16.19 16.23 15.00 15.04 15.91 16.41 17.161F 18.93 19.94 19.84 19.70 19.85 18.55 18.58 19.52 20.06 20.843F 19.80 20.59 20.74 19.22 19.31 18.41 18.52 19.16 19.55 20.071F 21.05 21.72 21.44 20.33 20.42 19.68 19.95 20.51 20.83 21.273F 2.77 2.77 2.77 2.83 2.82 2.79 2.81 2.83 2.83 2.901F 1.87 1.88 1.88 1.90 1.90 1.87 1.88 1.89 1.89 1.923F 2.64 2.64 2.63 2.63 2.62 2.67 2.63 2.67 2.67 2.671F 2.14 2.14 2.14 2.14 2.14 2.15 2.14 2.15 2.15 2.163F 5.07 5.16 5.29 5.421F 5.23 5.29 5.39 5.483F 8.94 9.13 9.45 9.751F 10.36 10.53 10.84 11.113F 5.15 5.15 5.15 5.58 5.58 5.57 5.59 5.60 5.61 5.671F 3.33 3.33 3.33 3.62 3.62 3.61 3.61 3.62 3.62 3.653F 12.31 12.36 12.38 12.13 12.09 12.06 12.04 11.99 12.05 12.111F 9.36 9.39 9.40 9.27 9.25 9.25 9.23 9.21 9.24 9.263F 9.97 9.97 9.99 9.99 9.99 9.98 9.97 10.31 10.80 10.811F 8.11 8.11 8.12 8.12 8.12 8.12 8.11 8.43 8.64 8.64

TOM

Tapeixtles Potencia TPX

Tarandacuao TDC

Taretan TAR

Tarimoro TRM 115

69

115

Tateposco TAT

Técnica Omya

230

115Tarímbaro TAO

115

115

69

400

230

Tapalpa TPP 115

Tapeixtles Distribución TAP 115

Tangamanga TGM 115

Tangancícuaro TGR 115

Tamarindos TMI 115

Tamazula TAZ 115

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Tala TLA 69

Talpa TPA 69

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 163: Catalogo 2011-2020 r010212 Corto Circuito

163

Coordinación de Planificación

ÁREA OCCIDENTAL

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 8.35 8.37 8.40 8.35 8.42 8.43 8.58 8.61 8.62 8.631F 5.86 5.87 5.88 5.87 5.89 5.89 5.96 5.97 5.97 5.973F 19.65 19.66 20.49 20.47 20.49 20.49 20.56 22.76 22.98 23.201F 17.60 17.60 18.47 18.46 18.47 18.47 18.50 20.01 20.12 20.233F 6.14 6.21 6.17 6.12 6.91 6.80 6.79 6.87 6.91 6.971F 4.31 4.34 4.30 4.29 5.35 5.30 5.30 5.33 5.35 5.373F 2.88 2.89 2.88 2.81 2.81 2.82 2.821F 1.92 1.92 1.92 1.88 1.88 1.88 1.883F 4.12 2.89 4.131F 2.69 1.93 2.693F 5.27 5.33 5.27 5.22 6.38 6.28 6.28 6.35 6.38 6.431F 3.59 3.60 3.56 3.54 5.56 5.51 5.51 5.54 5.56 5.593F 2.79 3.01 2.80 2.95 2.97 2.95 2.35 2.36 2.36 2.371F 1.83 1.93 1.82 1.90 1.91 1.90 1.50 1.50 1.50 1.503F 4.11 4.11 4.16 4.16 4.16 4.14 4.10 4.39 4.89 4.891F 2.73 2.73 2.77 2.77 2.77 2.75 2.72 3.33 3.52 3.523F 1.09 1.09 1.11 1.11 1.11 1.11 1.11 1.11 1.11 1.111F 0.71 0.71 0.72 0.72 0.72 0.72 0.72 0.72 0.72 0.723F 5.33 5.33 5.35 5.33 5.36 5.36 5.42 5.43 5.43 5.441F 3.57 3.57 3.58 3.57 3.58 3.58 3.61 3.61 3.61 3.613F 16.01 16.02 16.16 16.14 16.16 16.16 16.20 16.75 16.87 17.001F 12.81 12.81 12.90 12.90 12.90 12.90 12.92 13.18 13.23 13.283F 3.45 3.45 3.45 3.45 3.49 3.46 3.51 3.52 3.52 3.521F 2.50 2.50 2.50 2.50 2.51 2.50 2.52 2.52 2.52 2.523F 2.02 2.02 2.05 2.06 1.89 2.32 2.32 2.32 2.33 2.331F 2.01 2.01 2.04 2.06 1.93 2.22 2.22 2.22 2.22 2.223F 5.32 5.32 5.33 5.44 5.45 6.02 6.04 6.06 6.07 6.221F 3.94 3.95 3.95 4.00 4.00 4.22 4.23 4.24 4.25 4.313F 5.91 5.92 5.93 6.08 6.09 6.92 6.94 6.97 6.98 7.211F 4.60 4.60 4.61 4.68 4.68 5.04 5.04 5.07 5.07 5.183F 9.63 9.64 9.67 9.66 9.67 9.66 9.66 9.85 10.01 10.031F 6.68 6.68 6.70 6.70 6.70 6.70 6.70 6.78 6.83 6.843F 8.17 8.19 9.36 9.47 9.65 9.64 9.74 9.74 9.76 9.771F 7.57 7.58 8.57 8.69 8.80 8.80 8.84 8.84 8.85 8.85

Tecolotlán TEN

Teocaltiche TEO

Tepalcatepec TLC

Tepeyac TPY 115

115Tepic TES

Tepatitlán II TPD 115

Tepetitlán TPT 115

Tejeda TJD 115

115

115

Tecuala TEL 115

Tecuán TCN 115

Tecomates TCS 115

Tecozautla TCZ 115

69

Tecomán TCM 115

Tecolapa TOA 115

115

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Tecnológico Aguascalientes TAG 115

Tecnomac TNO 115

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 164: Catalogo 2011-2020 r010212 Corto Circuito

164

Coordinación de Planificación

ÁREA OCCIDENTAL

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 12.42 12.58 12.63 12.62 12.66 12.62 12.87 12.90 12.99 13.051F 14.00 14.16 14.16 14.23 14.34 14.33 14.50 14.52 14.58 14.623F 10.86 10.93 10.97 10.94 11.46 11.44 11.72 11.73 11.78 11.811F 13.44 13.52 13.49 13.61 14.17 14.15 14.41 14.42 14.46 14.473F 10.87 10.91 13.10 13.04 13.39 13.37 13.56 13.57 13.60 13.621F 12.32 12.36 15.23 15.23 15.57 15.56 15.71 15.72 15.74 15.753F 6.74 6.75 7.53 7.77 7.89 7.88 7.94 7.95 7.96 7.971F 5.70 5.70 6.24 6.45 6.51 6.50 6.53 6.53 6.53 6.543F 2.64 2.55 2.53 2.55 2.55 2.55 2.55 2.55 2.55 2.551F 2.03 1.99 1.98 1.99 1.99 1.99 1.99 1.99 1.99 1.993F 2.22 2.32 1.94 2.32 2.32 2.32 2.31 2.31 2.32 2.321F 1.72 1.81 1.83 1.80 1.80 1.80 1.80 1.80 1.80 1.803F 4.19 4.04 3.89 4.04 4.04 4.04 4.04 4.04 4.04 4.051F 3.53 3.49 3.00 3.49 3.49 3.48 3.48 3.48 3.49 3.493F 7.91 7.91 7.94 7.94 7.94 7.93 7.91 8.92 9.93 9.941F 5.74 5.74 5.75 5.75 5.75 5.75 5.73 7.24 7.68 7.683F 21.77 21.83 21.93 22.00 21.96 22.06 26.68 26.54 26.97 27.591F 29.51 29.71 29.83 29.94 29.86 30.05 35.95 35.78 36.28 37.013F 12.22 12.52 12.49 11.64 11.71 11.38 11.34 11.57 11.71 11.901F 10.12 10.27 10.00 9.62 9.66 9.50 9.48 9.60 9.66 9.753F 13.28 13.31 13.50 13.47 13.46 15.20 15.68 15.70 15.76 16.161F 12.35 12.37 12.52 12.52 12.51 13.43 13.69 13.70 13.73 13.933F 15.46 16.40 16.60 16.63 16.65 16.38 16.69 16.89 17.51 17.911F 16.24 17.64 17.76 17.88 17.91 17.73 17.96 18.09 18.63 18.913F 17.37 18.14 18.28 18.38 18.63 18.41 18.57 18.73 19.37 19.771F 20.41 21.41 21.52 21.67 21.97 21.79 22.04 22.17 22.77 23.123F 32.29 31.47 31.66 31.70 32.10 31.92 32.11 32.22 32.62 32.951F 32.00 31.41 31.53 31.60 31.90 31.80 31.92 31.98 32.26 32.463F 12.22 13.81 13.82 13.84 13.88 13.84 13.87 13.89 13.98 14.031F 13.14 14.61 14.62 14.64 14.67 14.65 14.67 14.69 14.76 14.793F 13.86 13.91 14.01 13.85 14.07 14.08 14.52 14.62 14.64 14.681F 11.13 11.16 11.20 11.14 11.23 11.23 11.44 11.50 11.50 11.523F 16.57 16.61 16.85 16.82 16.96 16.89 17.13 20.10 20.24 20.281F 15.48 15.58 15.74 15.73 15.80 15.77 15.92 18.04 18.16 18.18

Tepic II TED

Tequila II TQD

Tesistán TSN

Texas Instruments TXI 115

115Thyssenkrupp Sasa KRH

69

Tesistán B TSN 69

Termofil y Espumados TER 115

400

230

Térmica Zapopan TZP 69

Terminal de Gas Manzanillo TGN 115

69

Tequisquiápan TEQ 115

Tequila TQA 69

115

115

Tepic Industrial TID 115

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

400

230

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 165: Catalogo 2011-2020 r010212 Corto Circuito

165

Coordinación de Planificación

ÁREA OCCIDENTAL

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 17.05 17.09 17.34 17.31 17.45 17.38 17.63 20.36 20.55 20.591F 16.32 16.43 16.59 16.57 16.66 16.62 16.78 18.73 18.88 18.913F 11.60 11.63 11.67 11.67 11.76 11.74 11.87 11.74 11.84 11.911F 8.44 8.46 8.47 8.31 8.34 8.34 8.40 8.34 8.37 8.393F 16.17 16.19 15.98 15.97 20.54 20.28 20.73 20.74 20.90 22.201F 18.14 18.17 17.74 17.91 21.34 21.72 21.47 21.48 21.61 22.783F 1.74 1.74 1.75 1.74 1.75 1.75 1.75 1.75 1.75 1.761F 1.10 1.11 1.11 1.10 1.11 1.11 1.11 1.11 1.11 1.113F 6.07 6.08 6.09 6.27 6.27 7.27 7.28 7.32 7.33 7.611F 4.86 4.87 4.87 4.96 4.96 5.41 5.42 5.46 5.46 5.603F 22.38 22.40 23.62 23.60 23.63 23.62 23.71 26.85 27.15 27.461F 22.09 22.10 23.67 23.66 23.68 23.68 23.73 26.51 26.70 26.893F 8.25 8.26 8.32 8.32 8.46 8.34 8.52 8.52 8.54 8.701F 5.91 5.91 5.94 5.95 5.99 5.95 6.01 6.01 6.02 6.083F 18.94 18.95 19.79 19.77 19.79 19.79 19.85 22.07 22.27 22.481F 16.87 16.87 17.73 17.73 17.74 17.74 17.77 19.33 19.43 19.533F 5.64 5.65 5.65 5.80 5.71 5.58 5.85 5.96 6.02 6.331F 4.67 4.67 4.67 4.75 4.68 4.55 4.77 4.83 4.87 5.073F 15.69 15.73 15.96 15.94 16.06 16.00 16.21 20.15 20.31 20.351F 14.23 14.34 14.50 14.49 14.56 14.52 14.66 17.77 17.98 18.003F 24.28 24.29 25.81 25.79 25.82 25.82 25.92 29.28 29.64 30.011F 25.73 25.75 28.04 28.03 28.05 28.05 28.13 31.47 31.74 32.013F 3.86 3.98 3.88 3.98 3.98 3.97 3.97 3.98 3.99 4.001F 3.26 3.32 3.26 3.32 3.32 3.31 3.31 3.32 3.32 3.333F 14.90 15.42 15.52 15.62 15.73 15.58 15.69 15.79 16.22 16.481F 15.31 15.81 15.88 15.97 16.06 15.97 16.08 16.14 16.43 16.603F 13.52 13.54 13.57 13.60 14.75 14.71 14.78 14.76 14.88 15.041F 11.35 11.37 11.39 11.40 11.95 11.93 11.97 11.95 12.00 12.073F 11.40 11.41 11.30 11.30 13.25 13.14 13.32 13.33 13.40 13.931F 10.17 10.18 10.04 10.10 11.02 11.08 11.06 11.06 11.09 11.403F 3.99 3.99 3.98 3.97 4.54 4.53 4.55 4.55 4.56 4.601F 2.71 2.71 2.70 2.70 2.86 2.98 2.87 2.87 2.87 2.883F 7.91 7.92 7.81 7.51 7.46 8.17 8.10 8.18 8.21 8.261F 8.40 8.41 8.33 8.08 8.03 8.59 8.54 8.60 8.68 8.723F 5.27 5.27 5.22 5.22 5.22 5.38 5.24 5.39 5.39 5.401F 6.93 6.93 6.87 6.87 6.86 7.06 6.89 7.06 7.06 7.08

Túxpan TUX

Tuzania TUZ

Uriangato URG 115

Uruapan III UPT

115

69

Universidad Auntónoma Gud. UAG 69

Univex UVX 115

Turboreactores TBR 115

115

230

Tres Marías TMA 115

Tres Naciones TNC 115

Trejo TJO 115

Tremec TRE 115

Tototlán TTO 115

Tractores Agropecuarios TRA 115

Tkchem TKS 115

Tlaltenango TLO 115

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Tisamatic TIS 115

Titán TIT 69

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 166: Catalogo 2011-2020 r010212 Corto Circuito

166

Coordinación de Planificación

ÁREA OCCIDENTAL

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 4.95 4.95 4.91 5.11 5.00 6.77 6.75 6.80 7.11 7.181F 5.15 5.16 5.12 5.45 5.21 6.69 6.68 6.71 7.19 7.243F 5.24 5.25 5.19 5.22 5.35 6.35 6.31 6.36 6.48 6.521F 5.87 5.88 5.83 5.92 6.05 6.89 6.86 6.90 7.08 7.103F 7.98 7.99 7.89 7.40 7.34 8.20 8.14 8.22 8.21 8.261F 9.30 9.31 9.23 8.74 8.64 9.48 9.43 9.50 9.55 9.603F 8.57 8.59 9.99 10.01 10.22 10.21 10.22 10.23 10.27 10.301F 7.04 7.06 7.99 8.00 8.10 8.09 8.10 8.10 8.11 8.133F 8.52 8.53 8.73 8.73 8.95 8.78 9.03 9.03 9.06 9.231F 6.66 6.66 6.74 6.79 6.88 6.81 6.91 6.91 6.92 6.993F 4.97 4.76 6.07 6.08 6.36 6.37 6.37 6.401F 5.20 5.41 6.51 6.51 6.74 6.74 6.75 6.833F 3.92 3.79 4.58 4.58 4.74 4.75 4.75 4.771F 3.53 3.65 4.11 4.11 4.20 4.21 4.21 4.243F 4.65 4.66 4.68 4.50 5.64 5.65 5.90 5.90 5.90 5.931F 5.03 5.04 4.87 4.86 5.73 5.74 5.91 5.91 5.92 5.983F 3.70 3.71 3.72 3.61 4.31 4.31 4.45 4.46 4.46 4.481F 3.44 3.44 3.52 3.37 3.76 3.76 3.84 3.84 3.84 3.863F 3.47 3.48 3.28 3.28 4.76 4.76 5.15 5.15 5.16 5.151F 4.18 4.19 2.33 3.98 5.47 5.47 5.86 5.87 5.87 5.863F 5.70 5.71 5.76 5.49 7.30 7.31 7.73 7.73 7.74 7.791F 7.52 7.54 7.48 7.21 9.31 9.32 9.80 9.80 9.81 9.973F 5.90 5.73 5.74 5.86 5.92 6.021F 5.18 5.10 5.10 5.16 5.20 5.243F 14.98 15.04 15.16 14.96 15.27 15.24 15.81 16.02 16.04 16.071F 12.28 12.31 12.38 12.29 12.43 12.41 12.71 12.83 12.84 12.853F 4.37 4.38 4.38 4.41 4.44 4.55 4.59 4.60 4.60 4.641F 3.03 3.04 3.04 3.04 3.05 3.10 3.11 3.11 3.11 3.133F 5.88 5.88 5.90 5.80 5.92 5.97 6.07 6.90 6.90 6.891F 4.02 4.02 4.03 4.00 4.03 4.07 4.12 4.89 4.89 4.883F 8.69 8.70 8.65 8.64 11.88 11.82 11.96 11.97 12.00 12.301F 6.97 6.97 6.92 6.94 8.11 9.14 8.14 8.14 8.15 8.263F 5.23 5.17 6.89 6.78 6.78 6.86 6.90 6.961F 3.51 3.50 7.61 7.52 7.51 7.58 7.62 7.673F 4.06 4.07 4.24 4.32 3.45 6.19 6.18 6.19 6.22 6.241F 3.73 3.73 3.83 4.50 3.39 5.91 5.90 5.91 5.93 5.94

VTN

Valle de Aguascalientes VAA

Valle de Tecomán VTN

Valle Verde VAV

Uruapan Potencia UPP

Valle de Santiago VAS 115

115

115

Valle de Guadalupe VGP 115

Valle de las Delicias VDD 115

115

230

115

Vallarta Potencia VTP

Valle de Tecomán

Vallarta III VTT 115

230

Vallarta Centro CEN 115

Vallarta I VRT 115

USM USM 115

Vallarta Aeropuerto AER 115

115

USI USI 69

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

230

161

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 167: Catalogo 2011-2020 r010212 Corto Circuito

167

Coordinación de Planificación

ÁREA OCCIDENTAL

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 1.02 1.02 1.02 0.99 1.03 1.03 1.03 1.03 1.03 1.031F 0.69 0.69 0.69 0.68 0.69 0.69 0.69 0.69 0.69 0.693F 1.30 1.30 1.30 1.30 1.33 1.33 1.33 1.331F 0.91 0.91 0.91 0.91 0.93 0.93 0.93 0.933F 12.79 12.80 12.77 12.83 12.86 13.41 13.50 13.50 13.76 14.071F 10.89 10.89 10.86 10.92 10.93 11.32 11.36 11.36 11.56 11.723F 4.95 4.95 4.97 4.97 4.98 4.97 4.99 5.12 5.12 5.131F 3.97 3.99 4.00 4.00 4.00 4.00 4.01 4.07 4.07 4.073F 3.92 3.93 3.93 4.03 4.03 6.80 6.80 6.82 6.83 7.031F 2.91 2.91 2.92 2.96 2.96 4.85 4.85 4.86 4.86 4.953F 5.59 5.60 5.59 5.16 5.17 5.18 5.18 5.21 5.22 5.231F 3.76 3.77 3.76 3.67 3.67 3.68 3.68 3.69 3.69 3.693F 2.33 2.33 2.33 2.34 2.34 2.341F 1.52 1.52 1.52 1.52 1.52 1.523F 17.55 17.56 18.12 18.11 18.12 18.12 18.17 19.64 19.80 19.971F 14.65 14.66 15.15 15.14 15.15 15.15 15.17 16.02 16.09 16.163F 8.70 8.70 8.63 8.74 8.71 8.72 8.68 8.75 8.75 8.751F 6.80 6.80 6.77 6.82 6.81 6.81 6.79 6.82 6.82 6.823F 7.64 7.75 7.75 7.77 7.95 7.82 7.69 7.79 7.82 7.901F 7.40 7.47 7.47 7.48 7.61 7.53 7.45 7.50 7.53 7.573F 2.59 2.59 2.60 2.60 2.60 2.60 4.60 4.61 4.61 4.611F 1.71 1.71 1.71 1.71 1.71 1.71 3.53 3.53 3.54 3.543F 16.76 16.86 17.16 17.15 17.36 17.26 17.61 18.31 18.34 18.371F 19.10 19.20 19.47 19.47 19.65 19.56 19.86 20.42 20.46 20.483F 8.72 8.73 8.78 8.78 8.81 8.79 8.84 9.28 9.28 9.291F 9.35 9.49 9.53 9.53 9.55 9.54 9.58 9.94 9.95 9.953F 8.50 8.51 8.56 8.56 8.58 8.57 8.62 9.03 9.04 9.041F 8.95 9.07 9.11 9.11 9.13 9.12 9.16 9.48 9.49 9.493F 3.10 3.10 3.11 3.10 4.14 4.14 4.11 4.54 4.54 4.531F 2.00 2.00 2.00 2.01 2.72 2.72 2.69 3.05 3.05 3.053F 5.16 5.16 5.16 5.17 5.16 5.26 5.27 5.28 5.28 5.311F 4.22 4.22 4.22 4.23 4.22 4.29 4.30 4.30 4.30 4.313F 8.71 8.72 8.77 8.69 9.00 8.98 7.95 8.19 8.19 8.191F 6.37 6.38 6.40 6.37 6.57 6.56 5.60 5.76 5.76 5.763F 8.86 8.87 8.85 8.89 8.90 9.27 9.31 9.31 9.42 9.551F 6.54 6.54 6.53 6.56 6.56 6.78 6.79 6.80 6.86 6.91

VIG

Villa Jiménez VIJ 115

115

115

Villa Juárez VLJ

Villagrán

Villa de Reyes Distribuación VIR 115

Villa Hidalgo VHO 115

Villa de Arista VAR 115

Villa de Reyes VDR

230

115

Viga Trefilados VGT 115

Villa de Álvarez VVA 115

Victoria VCT 115

Vidriera Querétaro VID 115

Venustiano Carranza VCN 115

Veratec de México VTC 115

Velcon VEL 115

Ventilla VLT 115

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Valparaiso VPS 115

Vanegas VNS 115

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 168: Catalogo 2011-2020 r010212 Corto Circuito

168

Coordinación de Planificación

ÁREA OCCIDENTAL

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 17.45 17.45 17.41 17.42 17.50 17.52 17.59 17.58 17.67 17.681F 19.53 19.53 19.49 19.50 19.57 19.59 19.64 19.65 19.72 19.733F 13.11 13.12 12.82 13.29 13.14 13.15 12.90 13.20 13.21 13.221F 13.85 13.85 13.59 14.02 13.86 13.88 13.65 13.91 13.92 13.923F 5.90 5.91 5.92 6.19 6.19 10.06 10.08 10.11 10.13 10.591F 4.77 4.78 4.78 4.92 4.92 7.83 7.84 7.86 7.86 8.103F 18.48 18.49 19.13 19.12 19.13 19.13 19.19 20.87 21.06 21.251F 15.80 15.81 16.40 16.40 16.40 16.40 16.43 17.46 17.54 17.623F 5.11 5.13 5.12 4.77 4.78 4.79 4.79 4.81 4.82 4.831F 3.41 3.42 3.41 3.35 3.35 3.36 3.36 3.36 3.37 3.373F 5.25 5.27 5.26 4.90 4.90 4.91 4.91 4.94 4.95 4.951F 3.51 3.52 3.51 3.45 3.45 3.46 3.46 3.47 3.47 3.473F 3.58 3.58 3.65 3.65 3.65 3.61 3.56 4.02 4.78 4.781F 2.38 2.38 2.44 2.45 2.45 2.41 2.36 3.47 3.85 3.853F 5.83 5.84 6.01 6.01 6.01 5.92 5.921F 4.15 4.15 4.33 4.34 4.34 4.24 4.243F 11.60 11.63 11.67 11.67 11.76 11.74 11.87 11.74 11.84 11.911F 8.44 8.46 8.47 8.31 8.34 8.34 8.40 8.34 8.37 8.393F 6.41 6.42 7.12 7.25 7.35 7.35 7.40 7.40 7.41 7.421F 5.31 5.32 5.78 5.89 5.94 5.94 5.96 5.96 5.96 5.963F 3.79 3.79 3.79 3.81 3.81 6.74 6.75 6.76 6.77 6.951F 2.56 2.56 2.56 2.56 2.56 4.71 4.71 4.72 4.72 4.803F 4.94 4.94 4.94 4.95 4.94 5.03 5.04 5.05 5.05 5.081F 3.77 3.77 3.77 3.77 3.77 3.82 3.82 3.82 3.82 3.833F 6.18 6.19 6.21 5.72 6.34 6.27 6.43 6.54 6.54 6.481F 5.20 5.21 5.21 4.97 5.28 5.25 5.32 5.40 5.40 5.373F 6.52 6.54 6.58 5.76 6.84 6.68 7.11 7.48 7.49 7.271F 6.65 6.67 6.70 6.10 6.88 6.77 7.09 7.72 7.72 7.503F 9.57 9.59 9.63 8.72 9.98 9.83 10.23 10.62 10.63 10.471F 10.91 10.93 10.98 10.16 11.29 11.16 11.51 12.12 12.12 11.943F 5.47 5.48 5.49 5.05 5.59 5.54 5.66 5.73 5.73 5.691F 4.50 4.50 4.51 4.31 4.55 4.53 4.58 4.63 4.63 4.613F 6.18 6.18 6.20 5.62 6.32 6.26 6.41 6.50 6.51 6.451F 5.44 5.44 5.46 5.14 5.52 5.49 5.56 5.62 5.62 5.593F 16.12 16.23 16.37 16.18 16.12 16.07 16.11 16.13 16.22 16.431F 13.30 13.37 13.43 13.35 13.31 13.29 13.30 13.31 13.35 13.45

ZLT

Villita VIL

Zacapu ZCP

Zacatecas ZCT

Zacatecas III ZTR 115

115

69

Zacatecas Sur ZCS

Zalatitán

230

115Zacatecas II ZCD

Yurécuaro YUR 115

115

115

Vtech Innovations VTI 69

Xalisco XLC 115

Vizarrón VIZ 115

Vizarrón Maniobras VZM 115

Vitromex VT1 115

Vitromex II VT2 115

Vista Hermosa VIH 115

Vitro ANC. ANC 115

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

230

115

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 169: Catalogo 2011-2020 r010212 Corto Circuito

169

Coordinación de Planificación

ÁREA OCCIDENTAL

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 5.95 5.95 5.96 6.44 6.42 8.59 8.60 8.62 8.63 8.931F 5.92 5.93 5.94 6.34 6.32 7.81 7.82 7.83 7.83 8.023F 6.05 6.07 6.07 7.96 7.94 6.98 6.99 7.00 7.01 7.641F 5.45 5.46 5.46 7.13 7.12 6.04 6.04 6.05 6.06 6.443F 6.49 6.50 6.51 7.13 7.10 9.49 9.50 9.52 9.53 9.911F 7.47 7.48 7.49 8.19 8.16 10.22 10.22 10.24 10.25 10.573F 5.39 5.63 5.43 5.64 5.64 5.61 5.61 5.63 5.66 5.681F 5.42 5.59 5.41 5.59 5.59 5.57 5.57 5.59 5.60 5.623F 10.07 10.31 10.36 10.40 10.50 10.95 11.00 11.06 11.28 11.531F 9.92 10.13 10.15 10.19 10.75 10.92 10.96 10.99 11.14 11.293F 21.77 21.83 21.93 22.00 21.96 22.06 26.68 26.59 26.98 27.591F 29.51 29.71 29.83 29.94 29.86 30.05 35.95 35.78 36.27 37.003F 11.79 12.22 12.32 12.33 12.35 12.18 12.36 12.49 12.73 13.001F 11.18 11.56 11.62 11.69 11.72 11.62 11.66 11.74 11.87 12.023F 15.56 15.95 16.05 16.79 16.29 16.13 16.28 16.35 16.66 17.001F 17.25 17.68 17.76 18.74 17.99 17.88 17.97 18.03 18.27 18.573F 4.62 4.63 4.63 4.54 4.54 4.53 4.53 4.52 4.53 4.541F 3.00 3.00 3.00 2.98 2.97 2.97 2.97 2.97 2.97 2.973F 5.21 5.21 5.24 5.24 5.25 5.24 5.27 5.70 5.71 5.711F 3.54 3.55 3.56 3.56 3.56 3.56 3.57 3.77 3.78 3.783F 4.81 4.81 4.38 4.38 4.38 2.67 4.36 4.57 4.84 4.851F 3.96 3.96 3.58 3.61 3.61 1.86 3.55 3.76 3.88 3.883F 6.01 6.02 6.01 6.02 6.01 7.56 7.57 7.58 7.59 7.691F 4.45 4.45 4.45 4.45 4.45 5.76 5.76 5.77 5.77 5.813F 6.75 6.76 6.76 7.02 6.90 6.67 7.02 7.21 7.27 7.791F 6.19 6.20 6.20 6.36 6.26 5.98 6.29 6.40 6.46 6.903F 14.76 14.76 14.94 14.96 14.96 15.06 17.15 17.18 17.30 17.441F 11.27 11.28 11.36 11.37 11.37 11.42 12.84 12.84 12.89 12.943F 5.05 5.05 5.01 5.01 5.01 5.16 5.00 5.16 5.16 5.171F 6.11 6.11 6.08 6.07 6.07 6.22 6.06 6.22 6.22 6.23

Zamora Potencia ZRP

Zapopan ZPA

Zináparo ZID

Zoquipan ZQP 69

Zumpimito ZMP 69

Zimapán ZIM 115

115

115Zinapécuaro ZIN

Zapotlanejo Distribución ZPD 69

Zaragoza ZAG 115

Zapotlanejo ZPO 400

Zapotlanejo ZPO 230

230

69

115

Zapoltitic ZTT 115

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Zamora ZMA 115

230

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____

Page 170: Catalogo 2011-2020 r010212 Corto Circuito

170

Coordinación de PlanificaciónESTUDIO DE CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

ÁREA NOROESTE

ÁREANOROESTE

______________Catálogo de Corto Circuito 2011-2020 _______Catálogo de Corto Circuito 2011-2020_____

Page 171: Catalogo 2011-2020 r010212 Corto Circuito

171

Coordinación de PlanificaciónRED ELÉCTRICA PRINCIPAL 2011

ÁREA NOROESTE

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 172: Catalogo 2011-2020 r010212 Corto Circuito

172

Coordinación de PlanificaciónRED ELÉCTRICA PRINCIPAL 2020

ÁREA NOROESTE

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 173: Catalogo 2011-2020 r010212 Corto Circuito

173

Coordinación de PlanificaciónADICIONES Y RETIROS DE GENERACIÓN

ÁREA NOROESTE

ADICIONES:

Nombre de la Central Año Capacidad

Agua Prieta II (CC) 2013 477 MW

Noroeste (El Fresnal) (CC) 2016 772 MW

Hermosillo (CC) 2020 836 MW

RETIROS:

Nombre de la Central Año Capacidad

Carlos Rodríguez Rivero (Guaymas II) U1 y U2 2017 168 MW

Carlos Rodríguez Rivero (Guaymas II) U3 y U4 2019 316 MW

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 174: Catalogo 2011-2020 r010212 Corto Circuito

174

Coordinación de PlanificaciónADICIONES Y RETIROS DE GENERACIÓN

ÁREA NOROESTE

En 2013 está programada la entrada en operación de la central generadora Agua Prieta II, la cual se ubicará en el

predio denominado Ejido Agua Prieta, a 8 kilómetros al norte de Naco Nogales.

Con la inclusión de este proyecto de generación, en la subestación Ejido Agua Prieta se espera un nivel de corto

circuito trifásico de 10.20 kA y monofásico de 12.20 kA. Asimismo, se tendrá un incremento de 7.01 kA a 10.47 kA en

la corriente de falla trifásica de la subestación El Fresnal, y de 8.85 kA a 12.97 en la monofásica de la misma

subestación, además de incrementos del orden de 1.00 kA en las subestaciones Nacozari y Subestación Cananea.

Para 2016 se considera la entrada en operación de la central Noroeste en el sitio El Fresnal, con una capacidad de

772 MW. Esta central inyectará su potencia generada en el nivel de tensión de 400 kV y permitirá cubrir el suministro

eléctrico de las regiones de Cananea, Nacozari, Nogales y Hermosillo, principalmente.

Con la adición de este proyecto se esperan niveles de corto circuito de 8.89 kA trifásicos y 10.31 kA monofásicos en la

barra de 400 kV de El Fresnal, así como 14.51 kA y 17.88 kA trifásicos y monofásicos respectivamente, en el bus de

230 kV de la misma subestación.

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 175: Catalogo 2011-2020 r010212 Corto Circuito

175

Coordinación de Planificación ADICIONES Y RETIROS DE GENERACIÓN

ÁREA NOROESTE

Adicionalmente, el proyecto Noroeste (El Fresnal) considera la construcción de las subestaciones Las Mesetas, en

Nacozari y Seri, en Hermosillo. En el momento de su entrada en operación, en el bus de 400 kV de Las Mesetas se

alcanzará una corriente de falla trifásica de 7.90 kA y una monofásica de 6.79 kA, mientras que en el nivel de 230 kV se

esperan corrientes de falla trifásica y monofásica de 11.13 kA y 9.57 kA, respectivamente. En Seri se tendrá un nivel de

corto circuito trifásico de 6.42 kA y un monofásico de 5.81 kA en 400 kV, así como 13.25 kA trifásicos y 12.34 kA

monofásicos en 230 kV.

Finalmente, en 2020 se considera la adición de 836 MW de generación en la central eléctrica Hermosillo.

Tentativamente, se ha supuesto que el proyecto quedará instalado en el predio de la subestación Seri, en el nivel de

tensión de 230 kV.

Con la entrada en operación de Hermosillo se espera un incremento en el nivel de falla de la subestación Seri de

12.63 kA a 19.69 kA trifásicos y de 11.99 kA a 21.84 kA monofásicos, en el nivel de 230 kV. De igual forma, se prevén

incrementos de entre 3.00 kA y 4.00 kA en las corrientes de falla trifásica y monofásica en las subestaciones que

conforman el anillo de 230 kV de la ciudad de Hermosillo, así como en Planta Guaymas Dos y Guaymas Cereso.

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 176: Catalogo 2011-2020 r010212 Corto Circuito

176

Coordinación de PlanificaciónPRINCIPALES PROYECTOS DE TRANSMISIÓN Y TRANSFORMACIÓN

ÁREA NOROESTE

Proyecto Año Nivel de tensión

Conversión a 400 kV Culiacán-Los Mochis 2011 400/230 kV

SE Guaymas Cereso 2011 230/115 kV

SE Hermosillo Cuatro (Ampliación) 2011 230/115 kV

SE El Mayo 2012 230/115 kV

Red asociada a Agua Prieta II 2012 230 kV

Interconexión BC-SIN 2014 400/230 kV

LT Nacozari-Hermosillo Cinco 2014 400 kV

Red asociada a Noroeste (El Fresnal) 2015 400/230 kV

SE Peñasco Potencia 2016 230/115 kV

LT Santa Ana-Hermosillo Loma 2016 230 kV

LT Santa Ana-Nogales Aeropuerto 2016 230 kV

Conversión a 400 kV Los Mochis-Obregón 2017 400/230 kV

SE Esperanza 2019 230/115 kV

Red asociada a Hermosillo 2020 400/230 kV

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 177: Catalogo 2011-2020 r010212 Corto Circuito

177

Coordinación de PlanificaciónPRINCIPALES PROYECTOS DE TRANSMISIÓN Y TRANSFORMACIÓN

ÁREA NOROESTE

La inclusión de nuevos proyectos de transmisión en el área Noroeste y los cambios en la topología de la red troncal y la

de subtransmisión, son factores que influyen directamente en los niveles de corto circuito de las subestaciones.

Uno de los proyectos relevantes en el área es la conversión de tensión de 230 kV a 400 kV del enlace Culiacán-Los

Mochis, programada para entrar en operación en 2011. Para ello se requiere la construcción de la subestación

Choacahui, la cual se ubicará al norte de la ciudad de Los Mochis. Durante el año de entrada del proyecto, Choacahui

presenta un nivel de corto circuito trifásico de 4.50 kA en 400 kV y 8.55 kA en 230 kV, mientras que las corrientes de

corto circuito monofásico alcanzarán valores de 3.90 kA en el nivel de tensión de 400 kV y 7.63 kA en 230 kV.

En 2014 se interconectará el área Baja California con el Sistema Interconectado Nacional (SIN) a través de un enlace

asíncrono entre las subestaciones Cucapáh, en Baja California y Seis de Abril, en el área Noroeste. Cuando el proyecto

inicie su operación, Seis de Abril alcanzará niveles de corto circuito de 2.80 kA trifásicos y 2.87 kA monofásicos en

400 kV, así como 6.20 kA trifásicos y 6.53 kA monofásicos en el nivel de tensión de 230 kV. La corriente de corto

circuito más alta en esta subestación se presenta en el nivel de tensión de 115 kV, con una magnitud de 8.60 kA

trifásicos y 10.38 kA monofásicos.

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 178: Catalogo 2011-2020 r010212 Corto Circuito

178

Coordinación de PlanificaciónPRINCIPALES PROYECTOS DE TRANSMISIÓN Y TRANSFORMACIÓN

ÁREA NOROESTE

Otro proyecto a destacar es la conversión a 400 kV del enlace Los Mochis-Obregón, programado para entrar en

operación en 2017. Con la entrada de este proyecto, en la subestación Bácum se alcanzarán niveles de corto circuito

trifásico de 4.99 kV en 400 kV, 9.59 kA en 230 kV y 12.77 kA en 115 kV, mientras que las corrientes de corto circuito

monofásico tendrán magnitudes de 4.85 kA en 400 kV, 9.73 kA en 230 kV y 14.69 kA en 115 kV. En general, con el

proyecto se observa un incremento cercano a 1.00 kA en las subestaciones de 230 kV de la zona Obregón. Por su

parte, en la subestación Choacahui se esperan niveles de corto circuito trifásico de 5.70 kA y 8.58 kA en 400 kV y

230 kV respectivamente, además de corrientes de fallas monofásicas de 4.97 kA en 400 kV y 7.91 kA en 230 kV.

Al final del periodo, los niveles de corto circuito más altos en la red de 400 kV se observan en las subestaciones

Mazatlán Dos, con 9.91 kA trifásicos y 9.93 kA monofásicos, originados por la interconexión del Noroeste con el área

Occidental del país, y El Fresnal, con 9.25 kA trifásicos y 10.66 kA monofásicos, en virtud de la concentración de

generación en esta región.

En la red de 230 kV, las corrientes de corto circuito más elevadas se presentan en Seri, con 19.69 kA trifásicos y

21.84 kA monofásicos, en las subestaciones que conforman el anillo de 230 kV de la zona Hermosillo, con un promedio

de 16.00 kA, Ejido Agua Prieta y El Fresnal, con valores promedio de 14.00 kA trifásicos y 17.00 kA monofásicos, y

Mazatlán Dos, con 14.93 kA trifásicos y 17.44 kA monofásicos. En el resto de las subestaciones de 230 kV del área, los

niveles de corto circuito varían alrededor de los 10.00 kA o valores menores.

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 179: Catalogo 2011-2020 r010212 Corto Circuito

179

Coordinación de PlanificaciónPRINCIPALES PROYECTOS DE TRANSMISIÓN Y TRANSFORMACIÓN

ÁREA NOROESTE

En el nivel de subtransmisión (115 kV), los valores de corto circuito más elevados al final del periodo se observan en las

zonas con mayor concentración de generación y mayor crecimiento de carga.

En Culiacán, por ejemplo, el valor promedio de corto circuito al año 2020 será de 12.00 kA, destacando La Higuera y

Subestación Culiacán Potencia con valores trifásicos de 15.70 kA y 16.10 kA respectivamente, y monofásicos de

20.09 kA y 18.53 kA.

En la zona Hermosillo, el nivel de corto circuito promedio en la red de 115 kV es de 14.00 kA. Los valores más elevados

se presentan en Hermosillo Cinco (24.90 kA trifásicos, 28.95 kA monofásicos), Hermosillo Cuatro (24.82 kA trifásicos,

29.00 kA monofásicos), Hermosillo Loma (18.58 kA trifásicos, 21.42 kA monofásicos), Hermosillo Tres (17.09 kA

trifásicos, 16.53 kA monofásicos) y Hermosillo Uno (19.80 kA trifásicos, 17.10 kA monofásicos).

En Mazatlán, los valores más elevados se observan en Mazatlán Dos con 21.33 kA trifásicos y 24.68 kA monofásicos, y

Mazatlán Uno, con 16.79 kA trifásicos y 15.65 kA monofásicos. El valor promedio en esta zona es de 13.00 kA.

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 180: Catalogo 2011-2020 r010212 Corto Circuito

180

Coordinación de PlanificaciónPRINCIPALES PROYECTOS DE TRANSMISIÓN Y TRANSFORMACIÓN

ÁREA NOROESTE

En la zona Los Mochis el nivel de corto circuito promedio es de 10.00 kA. Los valores más altos se presentan en Los

Mochis Industrial y Louisiana, con un promedio de 13.00 kA trifásicos y 15.00 kA monofásicos, mientras que en

Obregón destacan las subestaciones Bácum (13.38 kA trifásicos, 15.28 kA monofásicos), Ciudad Obregón Cuatro

(13.40 kA trifásicos, 15.31 kA monofásicos), Ciudad Obregón Dos (13.63 kA trifásicos, 14.34 kA monofásicos) y Ciudad

Obregón Tres (13.74 kA trifásicos, 16.17 kA monofásicos).

Finalmente, en Guaymas el nivel de corto circuito trifásico más alto al 2020 se tendrá en Planta Guaymas Dos, con

13.19 kA trifásicos y 14.25 kA monofásicos, y en Guaymas Cereso, con 14.69 kA trifásicos y 16.67 kA monofásicos.

En general, se observa un incremento en los niveles de corto circuito en el área, originado por los nuevos proyectos de

generación y por los refuerzos en la red de transmisión.

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 181: Catalogo 2011-2020 r010212 Corto Circuito

181

Coordinación de Planificación

ÁREA NOROESTE

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 3.53 3.64 3.68 3.72 3.71 4.40 4.40 4.39 4.38 4.42

1F 3.96 4.05 4.09 4.11 4.11 4.69 4.69 4.67 4.67 4.70

3F 1.86 1.86 1.87 1.87 1.88 1.89 1.88 1.88 2.06 2.09

1F 1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.45 1.46

3F 1.84 1.84 1.84 1.85 1.85 1.86 1.86 1.86 2.00 2.03

1F 1.30 1.30 1.30 1.30 1.30 1.31 1.30 1.30 1.48 1.49

3F 1.59 1.59 1.59 1.60 1.61 1.61 1.61 1.61 1.71 1.73

1F 1.11 1.11 1.11 1.12 1.12 1.12 1.12 1.12 1.25 1.25

3F 1.90 1.90 1.90 1.91 1.91 1.92 1.92 1.92 2.07 2.10

1F 1.34 1.34 1.34 1.34 1.34 1.35 1.35 1.35 1.53 1.54

3F 1.88 1.88 1.88 1.89 1.90 1.90 1.90 1.90 2.08 2.11

1F 1.26 1.26 1.26 1.26 1.26 1.26 1.26 1.26 1.46 1.47

3F 0.64 0.63 0.63 0.64 0.64 0.71 0.71 0.71 0.71 0.71

1F 0.44 0.43 0.43 0.43 0.43 0.52 0.52 0.52 0.52 0.52

3F 1.23 3.36 3.60 3.63 3.68 3.77 3.77 3.77 3.77 3.78

1F 0.96 3.49 3.68 3.70 3.74 3.81 3.81 3.81 3.81 3.82

3F 6.34 6.34 6.43 6.43 6.88 6.91

1F 5.38 5.38 5.43 5.43 5.78 5.80

3F 4.36 4.36 4.36 4.37 4.37 4.37 4.36 4.38

1F 3.35 3.35 3.35 3.35 3.36 3.36 3.35 3.36

3F 1.32 1.33 1.33 1.33 1.33 1.33 1.33 1.33 1.33 1.33

1F 1.06 1.06 1.06 1.06 1.06 1.06 1.06 1.06 1.06 1.06

3F 3.68 3.75 3.77 3.92 3.88 3.94 3.94 3.94 3.94 3.96

1F 2.86 2.89 2.90 2.96 2.95 2.98 2.98 2.98 2.97 2.98

3F 11.05 11.08 11.12 9.85 10.06 10.29 10.25 9.94 9.81 10.47

1F 8.78 8.79 8.81 7.46 7.54 7.63 7.61 7.27 7.22 7.48

3F 4.84 4.84 4.86 4.86 4.84 4.87

1F 3.80 3.80 3.81 3.81 3.80 3.81

3F 3.29 3.32 3.33 3.58 3.50 3.54 3.54 3.54 3.54 3.55

1F 2.80 2.81 2.82 2.95 2.91 2.94 2.94 2.94 2.94 2.94

3F 2.05 2.06 2.07 2.13 2.11 2.13 2.13 2.13 2.13 2.13

1F 1.53 1.53 1.53 1.56 1.55 1.56 1.56 1.56 1.56 1.56

115

115

Aguaruto ATO 115

Ahome AHM 115

Altar

Altares

ATA

ATR

Arroyo Seco ASE 115

Angostura ANG 115

Antimonio ANT 115

Álamos AAM 115

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Acco de Velopment MCC 115

Acuícola Cardonal ACA 115

Agrícola Sonoyta AGS 115

Agua Prieta AGI 115

Acuícola Tastiota ATS 115

Acuícolas ACU 115

Acuícola San Nicolás ASN 115

Acuícola Selecta ASL 115

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 182: Catalogo 2011-2020 r010212 Corto Circuito

182

Coordinación de Planificación

ÁREA NOROESTE

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 4.99 4.99 4.70 5.28

1F 4.85 4.85 4.63 5.07

3F 6.20 6.20 6.20 6.24 6.27 6.30 9.59 9.59 8.78 10.40

1F 6.38 6.39 6.39 6.41 6.43 6.46 9.73 9.73 9.09 10.40

3F 10.28 10.28 10.25 10.30 10.34 10.38 12.77 12.77 12.04 13.38

1F 11.97 11.98 11.94 11.98 12.02 12.05 14.69 14.69 14.01 15.28

3F 5.28 5.28 5.48 5.48 5.48 5.48 5.50 5.50 5.49 5.50

1F 6.19 6.19 6.37 6.37 6.37 6.37 6.38 6.38 6.38 6.39

3F 8.83 8.85 8.88 9.03 9.31 9.55 9.50 9.49 8.65 9.28

1F 6.62 6.62 6.64 6.69 6.80 6.89 6.87 6.87 6.19 6.42

3F 2.10 2.77 2.77 2.77 2.77 2.77 2.77 2.77 2.78

1F 1.48 1.89 1.89 1.89 1.89 1.89 1.89 1.89 1.89

3F 9.59 9.62 9.66 9.69 10.76 10.76 10.24 11.12

1F 9.51 9.54 9.56 9.58 10.29 10.29 9.95 10.50

3F 5.10 5.18 5.21 6.39 6.20 6.31 6.31 6.31 6.30 6.33

1F 4.53 4.57 4.58 5.59 5.48 5.56 5.56 5.56 5.56 5.57

3F 5.91 6.03 6.08 6.68 6.52 6.64 6.64 6.64 6.64 6.67

1F 5.58 5.65 5.68 6.08 5.98 6.07 6.07 6.07 6.06 6.08

3F 9.71 9.72 9.68 9.71 9.75 9.78 11.10 11.10 10.55 11.51

1F 9.69 9.70 9.64 9.67 9.69 9.71 10.62 10.62 10.26 10.87

3F 7.25 7.25 7.27 7.36 7.45 7.55 7.53 7.53 7.46 7.76

1F 4.98 4.98 4.99 5.02 5.05 5.08 5.07 5.07 5.05 5.15

3F 7.29 7.31 7.36 7.79 8.17 8.58 8.52 8.52 8.26 9.71

1F 6.23 6.24 6.27 6.51 6.74 6.94 6.91 6.91 6.79 7.62

3F 7.03 7.04 7.05 7.15 7.24 7.35 7.33 7.32 7.25 7.57

1F 5.59 5.60 5.60 5.64 5.68 5.73 5.72 5.72 5.69 5.83

3F 8.44 8.44 8.64 8.65 8.65 8.66 8.68 8.68 8.62 8.73

1F 7.23 7.23 7.33 7.34 7.34 7.34 7.36 7.36 7.33 7.39

3F 6.17 6.17 6.17 5.92 5.95 5.98 5.77 5.77 5.48 5.95

1F 4.51 4.52 4.52 4.30 4.31 4.32 4.23 4.23 4.07 4.26

3F 5.01 5.10 5.14 5.53 5.42 5.52 5.52 5.52 5.51 5.54

1F 4.31 4.36 4.38 4.58 4.53 4.59 4.59 4.59 4.58 4.60

3F 8.42 8.42 8.32 8.35 8.37 8.40 9.23 9.23 8.84 9.50

1F 7.98 7.99 7.83 7.84 7.86 7.87 8.37 8.37 8.15 8.51

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

400

Bacurato BRT 115

Bagotes BAG 115

230

115

Bizaní BZI 115

Bácum BCM

Caborca CBA 115

Bamoa BAM 115

Banderas BAN 115

Cementos del Yaqui CDY 230

Cementos Portland CPN 115

Cajeme CAJ 115

Cementos Apasco CAP 115

Cerro Cañedo CCA 115

115

Centenario CNT 115

Centinela CTN 115

Cervecería Modelo COR

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 183: Catalogo 2011-2020 r010212 Corto Circuito

183

Coordinación de Planificación

ÁREA NOROESTE

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 4.50 4.51 4.52 4.52 4.53 4.53 5.70 5.70 5.55 5.84

1F 3.90 3.91 3.92 3.92 3.92 3.92 4.97 4.97 4.91 5.07

3F 8.55 8.55 8.63 8.65 8.66 8.66 8.58 8.58 8.43 8.70

1F 7.63 7.65 7.69 7.71 7.71 7.71 7.91 7.91 7.85 8.01

3F 4.67 4.72 4.71 5.90 5.90 5.90 5.89 5.95

1F 5.56 5.60 5.59 6.79 6.79 6.79 6.78 6.84

3F 7.31 7.31 7.32 7.36 7.40 7.43 8.97 8.97 8.31 9.50

1F 7.80 7.85 7.85 7.88 7.91 7.94 9.38 9.38 8.85 9.76

3F 11.08 11.08 11.05 11.09 11.14 11.18 12.86 12.86 12.13 13.40

1F 13.08 13.11 13.05 13.09 13.13 13.17 14.83 14.83 14.15 15.31

3F 11.16 11.16 11.08 11.13 11.17 11.22 13.06 13.06 12.31 13.63

1F 12.37 12.39 12.22 12.26 12.30 12.33 13.90 13.90 13.30 14.34

3F 7.28 7.28 7.29 7.33 7.37 7.41 8.25 8.25 7.62 8.65

1F 7.83 7.86 7.86 7.89 7.92 7.95 8.65 8.65 8.14 8.91

3F 11.60 11.60 11.55 11.60 11.64 11.69 13.20 13.20 12.42 13.74

1F 14.09 14.11 14.03 14.08 14.12 14.17 15.68 15.68 14.91 16.17

3F 8.93 8.94 8.94 8.97 9.00 9.03 10.01 10.01 9.56 10.33

1F 8.32 8.33 8.33 8.35 8.36 8.38 8.95 8.95 8.70 9.12

3F 4.98 4.98 4.99 4.99 4.99 4.99 5.02 5.02 5.02 5.03

1F 5.92 5.92 5.93 5.93 5.93 5.93 5.95 5.95 5.96 5.97

3F 3.11 3.11 6.48 6.47 6.47 6.47 6.56 6.56 6.93 6.96

1F 2.26 2.26 5.03 5.03 5.03 5.03 5.07 5.07 5.31 5.32

3F 4.63 4.63 4.63 4.65 4.66 4.68 4.53 4.53 4.35 4.64

1F 3.65 3.65 3.65 3.66 3.67 3.67 3.60 3.60 3.49 3.62

3F 11.20 11.19 11.22 11.21 11.22 11.22 11.45 11.46 11.50 11.58

1F 10.32 10.32 10.34 10.33 10.33 10.34 10.47 10.47 10.55 10.59

3F 12.37 12.37 12.43 12.43 12.44 12.44 12.72 12.72 12.98 13.08

1F 11.57 11.57 11.64 11.64 11.65 11.65 11.77 11.78 12.07 12.13

3F 12.21 12.21 12.33 12.32 12.33 12.33 12.65 12.65 13.47 13.59

1F 11.83 11.83 12.09 12.08 12.08 12.08 12.28 12.28 13.19 13.27

3F 12.56 12.56 12.60 12.60 12.61 12.61 12.91 12.91 12.99 13.09

1F 11.93 11.93 11.96 11.95 11.96 11.96 12.14 12.14 12.28 12.34

3F 11.18 11.17 11.26 11.26 11.26 11.26 11.53 11.53 12.07 12.16

1F 10.03 10.03 10.17 10.17 10.17 10.17 10.32 10.32 10.83 10.88

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

115

230

230

115

400

230

115

Comedero CMR 115

Costa Rica CSA 115

115

Cócorit CCI 115

Culiacán Cinco CUI 115

Culiacán Cuatro CUC 115

Cruz de Piedra CDP 115

Culiacán Centro CCC 115

Culiacán Dos CUD 115

115Culiacán Sur CUS

Choacahui CHO

Cibuta CBT

Ciudad Obregón Cuatro COC

Ciudad Obregón Dos COD

Ciudad Obregón Tres COT

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 184: Catalogo 2011-2020 r010212 Corto Circuito

184

Coordinación de Planificación

ÁREA NOROESTE

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 9.23 9.23 9.28 9.28 9.29 9.30 9.65 9.65 9.58 9.71

1F 10.00 10.00 10.04 10.04 10.05 10.05 10.33 10.33 10.48 10.58

3F 13.40 13.38 13.42 13.40 13.41 13.41 13.73 13.73 13.78 13.89

1F 15.85 15.83 15.87 15.84 15.85 15.85 16.16 16.16 16.30 16.40

3F 9.84 9.19 9.20 8.77 8.78 8.78 8.92 8.92 9.03 9.08

1F 8.61 7.70 7.71 7.16 7.17 7.17 7.23 7.23 7.32 7.34

3F 12.85 12.85 12.83 12.81 12.84 12.83 12.82 12.82 12.81 12.84

1F 10.62 10.63 10.59 10.58 10.59 10.60 10.49 10.49 10.49 10.50

3F 12.79 12.77 12.79 12.79 12.76 12.76 12.75 12.78

1F 11.31 11.31 11.32 11.32 11.17 11.17 11.17 11.18

3F 10.86 10.88 10.93 10.50 10.73 10.98 10.93 10.27 10.13 10.81

1F 9.06 9.07 9.09 8.58 8.69 8.80 8.78 7.94 7.89 8.18

3F 6.27 10.20 10.62 11.47 13.45 13.44 13.44 13.41 13.68

1F 6.77 12.20 12.61 13.80 15.87 15.86 15.87 15.84 16.08

3F 11.07 11.07 11.10 11.09 11.09 11.09 11.32 11.32 11.37 11.45

1F 10.06 10.05 10.07 10.06 10.07 10.07 10.19 10.20 10.27 10.31

3F 1.25 1.25 1.25 1.44 1.44 1.44 1.45 1.45 1.44 1.45

1F 1.07 1.07 1.07 1.17 1.17 1.17 1.17 1.17 1.17 1.17

3F 11.72 11.72 11.71 11.73

1F 9.64 9.64 9.64 9.65

3F 2.81 2.84 2.85 3.17 3.12 3.15 3.15 3.15 3.15 3.15

1F 2.22 2.23 2.23 2.45 2.43 2.44 2.44 2.44 2.44 2.44

3F 5.57 8.89 8.88 8.88 8.83 9.25

1F 5.70 10.31 10.30 10.30 10.27 10.66

3F 5.81 7.01 10.47 10.94 12.05 14.51 14.50 14.50 14.45 14.79

1F 6.68 8.85 12.97 13.45 14.88 17.88 17.87 17.88 17.83 18.18

3F 3.83 4.17 4.20 4.27 4.39 4.39 4.39 4.39 4.41

1F 5.44 5.97 6.02 6.13 6.35 6.35 6.35 6.34 6.37

3F 2.69 2.69 2.69 3.75 3.76 3.76 3.76 3.76 3.75 3.77

1F 3.13 3.13 3.13 4.13 4.13 4.13 4.13 4.13 4.12 4.14

3F 11.81 11.82 11.84 11.81 11.85 11.84 11.98 11.98 11.97 12.01

1F 12.10 12.10 12.12 12.10 12.13 12.13 12.21 12.21 12.21 12.24

3F 13.83 13.84 13.82 13.81 13.83 13.83 13.64 13.64 13.63 13.66

1F 16.02 16.03 16.01 15.99 16.01 16.02 15.80 15.80 15.80 15.82

230

115

115

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Culiacán Tres CUT

Culiacán Uno CUU

El Barrio CUO 115

Del Mar DMA 115

115

115

Delfín DFN

Dynatech DYN

400

El Carrizo CRZ 115

115El Cid CID

El Deseo DSE

115

230

230

115

El Habal HBL

115

El Fresnal EFR

El Fuerte EFU

115

Ejido Agua Prieta EAP 230

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 185: Catalogo 2011-2020 r010212 Corto Circuito

185

Coordinación de Planificación

ÁREA NOROESTE

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 6.21 6.22 6.24 6.25 6.26 6.13 6.13 5.96 6.24

1F 6.53 6.54 6.55 6.56 6.57 6.45 6.45 6.33 6.54

3F 9.11 9.13 9.13 9.15 9.16 9.01 9.01 8.83 9.14

1F 11.25 11.27 11.28 11.30 11.31 11.15 11.15 10.96 11.27

3F 10.71 10.71 10.74 10.74 10.75 10.75 10.97 10.97 11.08 11.16

1F 9.10 9.10 9.13 9.13 9.13 9.13 9.23 9.23 9.35 9.39

3F 8.73 8.73 8.74 8.79 8.85 8.91 8.38 8.38 7.78 8.76

1F 7.87 7.87 7.87 7.90 7.93 7.96 7.64 7.64 7.15 7.73

3F 1.46 1.66 1.66 1.66 1.66 1.85 1.85 1.85 1.85 1.85

1F 0.91 0.96 0.96 0.96 0.96 1.08 1.08 1.08 1.08 1.08

3F 1.74 1.74

1F 1.01 1.01

3F 6.33 6.95

1F 5.59 5.92

3F 6.15 6.15 6.17 6.23 6.32 6.41 6.35 6.35 8.85 9.42

1F 4.62 4.62 4.63 4.65 4.69 4.72 4.70 4.70 9.43 9.87

3F 7.05 7.06 7.07 7.16 7.24 7.34 7.28 7.28 7.18 7.48

1F 5.64 5.64 5.65 5.68 5.72 5.76 5.73 5.73 5.69 5.82

3F 4.91 4.91 5.43 5.44 5.44 5.44 5.44

1F 3.11 3.11 3.49 3.49 3.49 3.49 3.49

3F 13.59 13.60 13.62 13.74 13.87 14.01 11.87 11.87 10.71 12.55

1F 14.46 14.47 14.49 14.57 14.67 14.77 12.47 12.47 11.19 12.58

3F 9.62 9.62 9.63 9.66 9.66 9.59 9.72

1F 8.56 8.56 8.56 8.59 8.59 8.55 8.62

3F 9.49 9.50 9.54 9.21 9.38 9.57 9.54 9.03 8.93 9.45

1F 7.68 7.68 7.70 7.33 7.41 7.49 7.47 6.86 6.82 7.03

3F 4.25 4.25 4.28

1F 3.96 3.95 3.97

3F 2.30 2.37 3.25 3.09 3.25 3.26 3.23 3.23 3.21 3.25

1F 1.64 1.70 2.40 2.24 2.40 2.40 2.39 2.39 2.38 2.39

3F 4.65 4.64 5.33 5.87 5.70 6.37 6.36 6.37 6.34 6.55

1F 3.43 3.40 3.68 4.00 4.18 4.56 4.55 4.55 4.57 4.66

3F 8.61 8.61 8.51 8.54 8.56 8.59 9.46 9.46 9.05 9.74

1F 8.05 8.06 7.89 7.91 7.92 7.94 8.45 8.45 8.22 8.59

3F 7.03 7.03 8.04 8.05 8.05 8.05 8.11 8.11 8.07 8.13

1F 7.05 7.05 7.85 7.86 7.86 7.86 7.89 7.89 7.87 7.91

115El Tule CLI

Empalme EPM

230

115

El Mayo MYO

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Escuinapa Sur EPS 115

230

115

Escuinapa EPA 115

115

115

Estrella del Mar ETM

Fátima FMA

Flores Magón RFL

115

115

Esperanza ESP

Estación Torres ETO 115

115

230

115

Fundición FUC

Fundidora Mexicana de Cobre LCF

115

115

Frontera FRT

Guamúchil GML 115

Galletera Mexicana SA. (Gamesa) GMA

Ford Motor Company FRH

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 186: Catalogo 2011-2020 r010212 Corto Circuito

186

Coordinación de Planificación

ÁREA NOROESTE

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 6.38 6.38 6.63 6.64 6.64 6.65 6.73 6.73 6.68 6.78

1F 6.33 6.34 6.54 6.55 6.55 6.55 6.61 6.61 6.58 6.64

3F 8.48 8.49 9.64 9.65 9.65 9.65 9.73 9.73 9.68 9.77

1F 10.15 10.16 11.32 11.33 11.34 11.34 11.41 11.41 11.37 11.45

3F 6.34 6.35 6.35 6.35 6.38 6.38 6.36 6.40

1F 5.59 5.60 5.60 5.60 5.61 5.61 5.60 5.62

3F 3.14 3.15 5.94 5.94 5.94 5.94 5.97 5.97 5.95 5.99

1F 2.38 2.38 4.47 4.47 4.47 4.47 4.48 4.48 4.47 4.49

3F 9.00 9.01 9.03 9.17 9.33 9.49 9.67 9.67 8.10 11.36

1F 9.20 9.21 9.23 9.32 9.43 9.54 10.28 10.28 8.37 11.07

3F 12.64 12.65 12.68 12.69 12.82 12.95 13.50 13.50 12.00 14.69

1F 14.03 14.04 14.05 14.01 14.11 14.22 15.89 15.89 14.01 16.67

3F 11.00 11.06 11.17 11.67 12.54 13.62 13.51 13.50 13.14 16.20

1F 12.09 12.13 12.22 12.62 13.34 14.21 14.13 14.12 14.13 16.64

3F 11.73 11.75 11.80 12.07 12.39 12.74 12.67 12.67 12.45 13.52

1F 9.30 9.31 9.33 9.44 9.57 9.71 9.69 9.68 9.60 10.04

3F 10.58 10.63 10.74 11.68 12.54 13.54 13.40 13.40 12.77 16.60

1F 11.15 11.18 11.27 12.05 12.90 13.63 13.53 13.53 13.08 16.57

3F 19.83 19.90 20.04 20.81 21.63 22.62 22.41 22.38 21.75 24.90

1F 23.88 23.95 24.08 24.84 25.68 26.61 26.42 26.39 25.79 28.95

3F 10.38 10.43 10.52 11.01 12.39 13.41 13.28 13.27 12.72 16.55

1F 11.50 11.53 11.61 12.00 13.35 14.16 14.07 14.06 13.71 17.33

3F 18.18 18.25 18.40 19.06 20.42 21.65 21.44 21.42 20.76 24.82

1F 22.03 22.10 22.24 22.88 24.33 25.51 25.31 25.29 24.78 29.00

3F 13.26 13.30 13.38 13.72 14.26 14.88 14.80 14.77 14.44 16.16

1F 12.01 12.03 12.07 12.22 12.51 12.83 12.79 12.77 12.62 13.51

3F 11.18 11.01 11.81

1F 9.04 8.97 9.34

3F 10.66 10.72 10.84 11.35 12.02 13.28 13.17 13.16 12.74 15.61

1F 11.60 11.65 11.75 12.15 12.69 13.74 13.66 13.65 13.44 15.70

3F 14.86 14.91 15.02 15.45 16.11 17.00 16.89 16.76 16.35 18.58

1F 17.83 17.88 17.99 18.40 19.03 19.89 19.79 19.66 19.31 21.42

3F 11.45 11.48 11.54 11.80 12.25 12.71 12.64 12.62 12.38 13.67

1F 9.60 9.61 9.64 9.76 9.97 10.18 10.15 10.14 10.05 10.63

3F 14.65 14.69 14.78 15.14 15.79 16.43 16.31 16.28 15.91 17.93

1F 13.11 13.13 13.18 13.30 13.65 13.97 13.91 13.88 13.72 14.77

Guamúchil Tres GMT

230GMD

115

Guasave GSV

Guamúchil Dos

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

230

115

115

115

230

115

Hermosillo Dos HLD 115

230

Hermosillo Industrial HIN 115

Hermosillo Nueve HLN 115

115

230

115

230

115

Guaymas Cereso GCE

Hermosillo Cuatro HLC

Hermosillo Misión HMI 115

Hermosillo Aeropuerto HAE

Hermosillo Cereso HCE

Hermosillo Cinco HLI

Hermosillo Loma HLM

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 187: Catalogo 2011-2020 r010212 Corto Circuito

187

Coordinación de Planificación

ÁREA NOROESTE

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 15.10 15.14 15.22 15.68 16.21 16.80 16.68 16.68 16.31 18.16

1F 13.69 13.71 13.76 14.00 14.30 14.60 14.54 14.54 14.35 15.36

3F 12.62 12.65 12.72 13.04 13.62 14.18 14.09 14.07 13.78 15.42

1F 11.03 11.05 11.08 11.24 11.55 11.82 11.78 11.77 11.65 12.47

3F 12.34 12.38 12.46 12.74 13.11 13.57 13.50 13.14 12.89 14.12

1F 10.61 10.63 10.66 10.78 10.96 11.18 11.15 10.75 10.65 11.23

3F 10.76 10.82 10.98 11.57 12.15 13.17 13.05 13.05 12.57 15.54

1F 11.18 11.22 11.33 11.77 12.23 12.96 12.88 12.88 12.59 14.83

3F 14.38 14.44 14.54 14.95 15.40 15.98 15.89 15.72 15.39 17.09

1F 14.66 14.70 14.77 15.05 15.37 15.77 15.71 15.55 15.33 16.53

3F 15.98 16.03 16.13 16.54 17.28 18.03 17.89 17.86 17.41 19.80

1F 15.02 15.05 15.10 15.23 15.67 16.08 16.00 15.95 15.73 17.10

3F 3.16 3.16 5.25 5.26 5.26 5.26 5.28 5.28 5.26 5.29

1F 2.35 2.35 3.77 3.78 3.78 3.78 3.78 3.78 3.78 3.79

3F 2.34 2.34 2.34 3.59 3.59 3.59 3.60 3.60 3.59 3.60

1F 2.50 2.50 2.50 3.57 3.57 3.57 3.57 3.57 3.57 3.57

3F 10.61 10.45 11.25

1F 7.91 7.85 8.17

3F 2.32 5.92 5.93 5.93 5.94 5.94 5.88 5.88 5.80 5.93

1F 1.69 4.94 4.95 4.94 4.95 4.95 4.92 4.92 4.88 4.94

3F 7.03 7.03 7.04 7.04 7.05 7.05 6.97 6.97 6.89 7.02

1F 8.05 8.06 8.06 8.07 8.07 8.08 8.00 8.00 7.93 8.05

3F 7.23 7.22 7.23 7.23 7.23 7.23 7.29 7.29 7.30 7.32

1F 8.04 8.03 8.04 8.04 8.04 8.04 8.09 8.09 8.10 8.12

3F 3.42 3.52 3.56 3.59 3.58 3.83 3.83 3.83 3.82 3.85

1F 2.88 2.93 2.94 2.95 2.95 3.06 3.06 3.06 3.06 3.07

3F 4.12 4.26 4.31 4.81 4.62 4.76 4.76 4.76 4.75 4.79

1F 4.08 4.16 4.20 4.55 4.43 4.54 4.54 4.54 4.53 4.56

3F 6.62 6.76 6.83 7.62 7.40 7.56 7.56 7.56 7.55 7.59

1F 6.98 7.09 7.13 7.79 7.63 7.77 7.77 7.77 7.76 7.79

3F 3.50 3.61 3.65 3.69 3.68 4.37 4.37 4.35 4.34 4.38

1F 3.52 3.60 3.62 3.65 3.64 4.11 4.11 4.09 4.08 4.10

3F 8.29 7.97 7.99 7.69 7.70 7.70 7.81 7.81 7.97 8.01

1F 6.53 6.17 6.18 5.87 5.87 5.87 5.91 5.91 6.02 6.03

3F 4.66 4.66 5.86 5.87 5.87 5.87 5.89 5.89 5.87 5.91

1F 3.84 3.84 4.77 4.77 4.77 4.77 4.78 4.78 4.77 4.79

Hermosillo Siete HLE 115

230

115

115Hermosillo Seis HLS

115

Hernando de Villafañe HVF

Hornillos HRS

115Hermosillo Uno HLU

Hermosillo Tres HLT

Industrial San Carlos ISC 115

Huatabampo HPO

HYA

Hotelera HOT 115

230

230

115

115

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Industrial Caborca ICA

115

Ímuris IMR 115

Huites HTS

Humaya

115

115

Hermosillo Ocho HLO

Juan José Rios JJR 115

Jaime Sevilla Poyastro JSP 115

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 188: Catalogo 2011-2020 r010212 Corto Circuito

188

Coordinación de Planificación

ÁREA NOROESTE

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 2.31 2.04 2.04 2.13 2.10 3.73 3.72 3.72 3.72 3.73

1F 1.57 1.34 1.34 1.37 1.36 3.28 3.28 3.28 3.28 3.29

3F 1.03 1.03 1.03 1.03 1.03 1.03 1.03 1.03 1.03

1F 0.72 0.72 0.72 0.72 0.72 0.71 0.71 0.71 0.71

3F 6.37 6.38 6.39 6.39 6.40 6.40 6.90 6.90 6.83 6.96

1F 6.31 6.32 6.32 6.32 6.33 6.33 6.70 6.70 7.01 7.10

3F 9.92 9.92 9.95 9.95 9.96 9.96 10.46 10.46 10.40 10.55

1F 10.74 10.75 10.78 10.77 10.78 10.79 11.21 11.21 11.96 12.09

3F 13.00 12.98 13.06 13.03 13.04 13.04 13.41 13.41 15.54 15.70

1F 15.80 15.78 15.87 15.83 15.84 15.84 16.22 16.22 19.92 20.09

3F 12.62 12.61 12.64 12.62 12.63 12.63 12.92 12.92 12.97 13.06

1F 13.72 13.71 13.74 13.72 13.72 13.72 13.95 13.95 14.06 14.14

3F 2.11 2.12 2.22 2.19 3.44 3.44 3.44 3.44 3.45

1F 1.42 1.42 1.45 1.44 3.02 3.02 3.02 3.02 3.02

3F 2.65 2.65 2.66 2.66 2.66 2.67 2.62 2.62 2.56 2.66

1F 1.98 1.98 1.98 1.98 1.98 1.98 1.96 1.96 1.93 1.97

3F 11.59 11.59 11.76 11.84

1F 10.22 10.22 10.40 10.45

3F 13.05 13.09 13.18 13.30 13.78 14.38 14.30 14.01 13.72 15.25

1F 12.53 12.55 12.60 12.35 12.63 12.98 12.94 12.64 12.49 13.35

3F 2.18 2.10 2.10 2.20 2.17 3.42 3.42 3.42 3.42 3.43

1F 1.52 1.44 1.45 1.48 1.47 3.29 3.29 3.29 3.29 3.29

3F 5.89 7.90 7.88 7.88 7.81 8.45

1F 5.19 6.79 6.78 6.78 6.82 7.24

3F 9.15 11.13 11.11 11.12 11.04 11.68

1F 7.93 9.57 9.55 9.55 9.66 10.08

3F 2.53 2.53 5.02 5.03 5.03 5.03 5.05 5.05 5.03 5.06

1F 1.91 1.91 3.46 3.46 3.46 3.46 3.46 3.46 3.46 3.47

3F 3.42 3.49 3.51 3.61 3.58 3.65 3.65 3.65 3.64 3.66

1F 2.62 2.64 2.65 2.69 2.68 2.71 2.71 2.71 2.71 2.71

3F 9.65 9.54 9.56 9.46 9.46 9.46 9.63 9.63 9.69 9.75

1F 8.51 8.32 8.33 8.18 8.19 8.19 8.27 8.27 8.33 8.36

3F 3.97 3.98 3.99 3.90 3.90 3.76 3.98

1F 2.96 2.97 2.97 2.93 2.93 2.85 2.94

3F 10.69 10.69 11.13 11.15 11.15 11.15 11.21 11.21 11.11 11.29

1F 10.56 10.57 10.88 10.87 10.87 10.87 10.92 10.92 10.85 10.97Los Mochis Colinas LMC 115

Loma de Rodriguera CUN 115

Los Algodones LAL 115

400

230

Leyva Solano LVS 115

Llano Blanco LLB 115

Las Mesetas MST

La Primavera PRI 115

115

115

Ladrilleras LAD

Las Conchas

La Isla ISL 115

La Laguna LGN 115

La Misa LMA 115

115

La Cholla LCH

La Cruz STC

400

230La Higuera HGA

115

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

115

LSC

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 189: Catalogo 2011-2020 r010212 Corto Circuito

189

Coordinación de Planificación

ÁREA NOROESTE

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 8.35 8.36 8.39 8.42 8.43 8.44 8.52 8.52 8.39 8.63

1F 8.03 8.11 8.12 8.16 8.17 8.17 8.24 8.24 8.16 8.31

3F 9.00 9.00 9.08 9.17 9.17 9.17 9.22 9.22 9.15 9.27

1F 10.03 10.05 10.12 10.26 10.26 10.26 10.31 10.31 10.25 10.35

3F 8.25 8.25 8.44 8.47 8.48 8.48 8.54 8.54 8.43 8.63

1F 8.67 8.69 8.86 8.88 8.89 8.89 8.96 8.96 8.87 9.02

3F 11.78 11.78 12.61 12.64 12.65 12.65 12.72 12.72 12.60 12.82

1F 13.75 13.76 14.61 14.64 14.64 14.65 14.72 14.72 14.61 14.81

3F 9.92 9.92 10.26 10.29 10.29 10.30 10.34 10.34 10.25 10.41

1F 9.20 9.20 9.40 9.42 9.43 9.43 9.46 9.46 9.41 9.50

3F 10.80 10.80 11.20 11.15 11.15 11.16 11.21 11.21 11.11 11.29

1F 10.86 10.87 11.16 11.05 11.05 11.05 11.10 11.10 11.04 11.15

3F 8.99 9.00 9.15 9.18 9.19 9.19 9.23 9.23 9.09 9.34

1F 9.48 9.50 9.63 9.65 9.66 9.66 9.76 9.76 9.66 9.85

3F 11.93 11.94 12.27 12.26 12.27 12.27 12.32 12.32 12.20 12.42

1F 13.96 13.98 14.29 14.27 14.28 14.28 14.36 14.36 14.25 14.45

3F 4.41 4.59 4.66 4.71 4.70 4.97 4.96 4.96 4.96 5.01

1F 3.83 3.90 3.94 3.96 3.95 4.09 4.09 4.09 4.08 4.11

3F 1.68 1.69 1.69 1.69 1.69 1.69 1.69 1.69 1.68 1.69

1F 1.43 1.44 1.44 1.44 1.44 1.44 1.44 1.44 1.43 1.44

3F 12.45 12.45 12.41 12.40 12.42 12.42 10.80 10.80 10.80 10.82

1F 10.77 10.77 10.72 10.72 10.73 10.73 8.91 8.91 8.91 8.92

3F 1.99 1.99 2.08 2.05 2.84 2.84 2.84 2.84 2.84

1F 1.43 1.43 1.47 1.46 2.35 2.35 2.35 2.35 2.35

3F 8.70 8.70 8.71 8.70 8.71 10.49 10.54 10.54 10.53 10.55

1F 6.17 6.17 6.18 6.17 6.18 7.88 7.89 7.89 7.89 7.90

3F 12.95 12.95 12.96 12.94 12.96 12.96 12.99 12.99 12.98 13.01

1F 10.56 10.57 10.56 10.55 10.56 10.57 10.52 10.52 10.52 10.53

3F 9.55 9.57 9.61 9.57 9.62 9.62 9.86 9.87 9.85 9.91

1F 9.65 9.67 9.71 9.68 9.72 9.76 9.88 9.88 9.89 9.93

3F 14.63 14.64 14.68 14.64 14.69 14.68 14.89 14.90 14.88 14.93

1F 17.15 17.16 17.20 17.16 17.21 17.23 17.40 17.40 17.39 17.44

3F 21.01 21.03 21.07 21.03 21.08 21.08 21.28 21.29 21.27 21.33

1F 24.40 24.43 24.46 24.42 24.47 24.49 24.62 24.63 24.62 24.68

3F 14.84 14.85 14.77 14.75 14.77 14.77 14.69 14.69 14.68 14.71

1F 13.82 13.82 13.70 13.68 13.70 13.70 13.40 13.40 13.40 13.42

Los Mochis Uno LMU 115

230Louisiana LOU

Maniobra Mina Cobre del Mayo MMC 115

Los Mochis Tres LMT

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

230

115

Luis Donaldo Colosio LDO 115

115

230

115

115

Los Mochis Dos LMD

Los Mochis Industrial LMI

Mazatlán Centro MAC 115

Marina MRN 115

400

115

115

Mazatlán Norte MZN 115

230

115

Mayan MYN

Mazatlán Aeropuerto MAE

Mazatlán Dos MZD

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 190: Catalogo 2011-2020 r010212 Corto Circuito

190

Coordinación de Planificación

ÁREA NOROESTE

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 12.61 12.62 12.07 12.06 12.08 12.07 12.07 12.07 12.07 12.09

1F 11.15 11.15 10.53 10.52 10.53 10.53 10.45 10.45 10.45 10.46

3F 11.23 11.24 11.21 11.20 11.21 11.21 11.28 11.29 11.28 11.30

1F 9.49 9.50 9.47 9.47 9.47 9.47 9.49 9.49 9.49 9.50

3F 16.60 16.61 16.64 16.61 16.65 16.65 16.76 16.76 16.74 16.79

1F 15.56 15.57 15.59 15.57 15.60 15.60 15.62 15.63 15.62 15.65

3F 7.99 7.76 7.77 7.50 7.50 7.50 7.61 7.61 7.80 7.84

1F 6.19 5.94 5.94 5.66 5.66 5.66 5.70 5.70 5.82 5.83

3F 1.41 1.42 1.42 1.42 1.42 1.42 1.41 1.41 1.41 1.42

1F 1.13 1.13 1.13 1.13 1.13 1.13 1.13 1.13 1.13 1.13

3F 3.24 3.43 3.61 3.64 3.67 3.76 3.75 3.75 3.75 3.77

1F 3.21 2.99 3.08 3.09 3.11 3.15 3.15 3.15 3.15 3.16

3F 4.69 4.68 5.39 5.94 5.77 6.45 6.45 6.45 6.42 6.63

1F 3.47 3.43 3.72 4.06 4.24 4.62 4.62 4.62 4.64 4.73

3F 2.96 2.97 2.97 2.99 3.00 3.02 3.02 3.01 3.00 3.06

1F 2.14 2.14 2.14 2.15 2.15 2.16 2.16 2.16 2.15 2.17

3F 3.33 3.33 3.33 3.35

1F 2.79 2.79 2.79 2.80

3F 8.44 8.44 8.64 8.66 8.66 8.67 8.69 8.69 8.63 8.74

1F 7.19 7.20 7.30 7.30 7.31 7.31 7.33 7.33 7.30 7.35

3F 9.58 9.58 9.84 9.49 9.50 9.50 9.53 9.53 9.46 9.59

1F 8.79 8.80 8.95 8.46 8.46 8.46 8.49 8.49 8.45 8.52

3F 3.64 3.64 3.89 3.89 3.89 3.89 3.90 3.90 3.89 3.91

1F 2.78 2.78 2.89 2.89 2.89 2.89 2.90 2.90 2.89 2.90

3F 1.45 1.46 1.46 1.46 1.46 1.46 1.46 1.46 1.45 1.46

1F 1.28 1.29 1.29 1.29 1.29 1.29 1.28 1.28 1.28 1.29

3F 3.37 3.38 3.38 3.38 3.39 3.40 3.32 3.32 3.22 3.38

1F 2.57 2.57 2.57 2.57 2.57 2.57 2.54 2.54 2.48 2.55

3F 6.26 6.25 7.57 8.70 8.34 9.85 9.83 9.84 9.78 10.28

1F 5.01 4.94 5.56 6.35 6.79 7.85 7.83 7.84 7.89 8.17

3F 10.18 10.22 10.26 10.29 11.63 11.63 11.02 12.06

1F 10.41 10.44 10.46 10.49 11.43 11.43 11.02 11.71

3F 7.91 9.39 9.46 9.41 9.49 9.50 9.30 9.30 9.10 9.44

1F 7.19 9.03 9.12 9.03 9.14 9.15 8.99 8.99 8.86 9.07

3F 6.36 3.75 3.75 3.75 3.75 3.76 3.73 3.73 3.70 3.75

1F 5.42 2.70 2.70 2.70 2.70 2.70 2.69 2.69 2.68 2.70

230

115

115

Navojoa Industrial NVI 115

Nacozari NRI

Nainari NAI

Navojoa NVJ

Mocorito MOC 115

Mocúzari MRI 115

Morelos LA MLA 115

Minera Suaqui Verde MSV 115

Mochis Centro MCE 115

Mochis Las Villas MLV 115

Minera María S.A. MMA 115

230

115

Minera Mexicana de Cobre LCD

Minera Nyco S.A. PIA

115

115

Mina Cobre del Mayo MCM 115

Mazatlán Uno MZU

Milenium MIL

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

115

115

Mazatlán Oriente MZO

Mazatlán Tecnológico MTE

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 191: Catalogo 2011-2020 r010212 Corto Circuito

191

Coordinación de Planificación

ÁREA NOROESTE

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 6.30 6.99 7.74 6.90 7.76 7.77 7.64 7.64 7.50 7.73

1F 5.07 5.68 6.62 5.56 6.63 6.63 6.55 6.55 6.48 6.59

3F 8.54 8.52 8.56 8.57 8.41 8.41 8.24 8.52

1F 7.78 7.74 7.80 7.80 7.68 7.68 7.58 7.74

3F 3.34 3.34 3.34 3.34 3.19 3.19 3.21 3.21 3.32 3.33

1F 2.53 2.53 2.53 2.53 2.38 2.38 2.38 2.38 2.45 2.45

3F 3.49 3.61 3.65 3.68 3.67 4.36 4.36 4.34 4.33 4.37

1F 3.53 3.61 3.64 3.66 3.65 4.12 4.12 4.09 4.09 4.11

3F 2.45 2.56 2.61 2.64 2.63 3.86 3.86 3.86 3.85 3.91

1F 2.63 2.71 2.75 2.77 2.77 3.79 3.79 3.79 3.79 3.83

3F 4.43 4.61 4.69 4.74 4.72 5.93 5.93 5.93 5.92 5.99

1F 5.37 5.55 5.62 5.67 5.65 6.89 6.89 6.89 6.88 6.94

3F 3.58 3.70 3.75 3.78 3.77 4.50 4.50 4.46 4.45 4.49

1F 3.75 3.83 3.87 3.89 3.88 4.41 4.41 4.36 4.35 4.38

3F 4.08 4.08 4.08 4.09 4.09 4.10 4.10 4.10 4.09 4.12

1F 5.12 5.12 5.12 5.13 5.14 5.15 5.14 5.14 5.14 5.16

3F 3.58 3.70 3.75 3.78 3.77 4.49 4.49 4.48 4.47 4.51

1F 4.08 4.18 4.22 4.25 4.24 4.86 4.86 4.84 4.84 4.87

3F 3.25 3.27 3.31 3.39 3.39 3.39 3.38 3.40

1F 3.07 3.09 3.11 3.16 3.16 3.16 3.16 3.17

3F 3.27 3.31 3.33 3.35 3.35 3.38 3.38 3.38 3.37 3.41

1F 2.44 2.45 2.46 2.46 2.46 2.48 2.48 2.48 2.47 2.49

3F 10.01 10.01 9.87 9.91 9.95 9.98 11.17 11.18 10.62 11.57

1F 10.27 10.28 10.02 10.05 10.07 10.10 10.94 10.94 10.56 11.18

3F 4.03 4.15 4.20 4.28 4.26 4.38 4.38 4.38 4.37 4.41

1F 3.22 3.27 3.29 3.32 3.31 3.37 3.37 3.37 3.37 3.38

3F 11.21 11.52 11.84 11.78 11.64 11.46 12.41

1F 8.62 8.75 8.87 8.85 8.69 8.63 9.01

3F 2.20 2.11 2.12 2.21 2.18 3.37 3.37 3.37 3.37 3.38

1F 1.55 1.47 1.47 1.51 1.50 3.44 3.44 3.44 3.44 3.44

3F 2.65 2.65 2.65 2.65 2.65 2.66 2.71 2.71 2.68 2.72

1F 2.45 2.45 2.45 2.45 2.45 2.45 2.48 2.48 2.47 2.49

3F 2.90 2.90 2.90 2.90 2.91

1F 3.00 3.00 3.00 3.00 3.01

3F 4.29 4.29 4.29 4.28 4.29

1F 5.08 5.08 5.08 5.08 5.09

Oviachic OVI 115

230

115

Peñasco Potencia PPE

Ocuca OCU 115

Olivos OLS 115

Oriente OTE 115

Nuevo Progreso NVP 115

Oasis OAS 115

Obregón Uno OBU 115

Nogales Norte NGN 115

Novillo NVL 115

Nuevo Nogales NNG 115

Nogales NGS 115

230

115

Nogales Aeropuerto NGA

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Navojoa Norte NVN 115

Navojoa Oriente NVO 115

Navolato NTO 115

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 192: Catalogo 2011-2020 r010212 Corto Circuito

192

Coordinación de Planificación

ÁREA NOROESTE

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 1.69 1.69 1.68 1.68 1.68 1.68 1.68 1.68 1.68 1.68

1F 1.19 1.19 1.19 1.19 1.19 1.19 1.19 1.19 1.19 1.19

3F 10.32 10.33 10.36 10.55 10.73 10.93 10.66 10.66 8.53 11.14

1F 11.83 11.84 11.87 12.03 12.19 12.36 12.14 12.14 8.65 10.60

3F 14.80 14.81 14.83 14.95 15.10 15.26 12.46 12.46 11.17 13.19

1F 17.56 17.58 17.60 17.69 17.83 17.98 14.16 14.16 12.49 14.25

3F 2.14 2.06 2.06 2.16 2.13 3.44 3.44 3.44 3.44 3.45

1F 1.54 1.45 1.46 1.49 1.48 3.28 3.28 3.28 3.28 3.28

3F 3.02 3.01 3.02 3.02 3.02 3.20 3.20 3.15 3.23

1F 2.22 2.22 2.22 2.22 2.22 2.29 2.30 2.28 2.31

3F 9.20 9.20 9.17 9.20 9.23 9.26 10.79 10.79 10.26 11.20

1F 8.91 8.92 8.87 8.89 8.91 8.93 9.98 9.98 9.66 10.22

3F 8.81 8.81 8.83 8.86 8.89 8.91 8.53 8.53 8.17 8.77

1F 8.65 9.24 9.26 9.28 9.30 9.31 8.89 8.89 8.62 9.06

3F 9.68 10.66 10.68 10.69 10.71 10.73 10.47 10.47 10.21 10.65

1F 10.25 11.60 11.61 11.62 11.64 11.66 11.38 11.38 11.17 11.52

3F 10.37 10.63 10.75 11.47 11.21 11.44 11.44 11.44 11.41 11.55

1F 12.04 12.27 12.38 13.02 12.79 13.00 13.00 13.00 12.98 13.10

3F 2.33 2.23 2.24 2.35 2.31 3.79 3.79 3.79 3.79 3.80

1F 1.65 1.56 1.56 1.60 1.59 3.95 3.95 3.95 3.95 3.95

3F 1.68 1.68 2.33 2.33 2.33 2.33 2.34 2.34 2.39 2.39

1F 1.17 1.17 1.64 1.64 1.64 1.64 1.65 1.65 1.67 1.67

3F 6.51 6.59 6.74 6.87 6.84 6.83 6.38 6.72

1F 4.46 4.48 4.53 4.57 4.56 4.56 4.25 4.36

3F 10.09 10.17 10.25 10.10 10.10 9.23 10.71

1F 9.06 9.11 9.15 9.24 9.24 8.55 9.44

3F 1.89 2.11 2.11 2.11 2.11 2.43 2.43 2.43 2.43 2.43

1F 1.18 1.24 1.24 1.24 1.24 1.44 1.44 1.44 1.44 1.44

3F 4.86 4.87 4.87 4.87 4.88 4.88 4.86 4.89

1F 3.67 3.67 3.67 3.67 3.67 3.67 3.67 3.68

3F 2.68 2.67 2.68 2.84 2.79 3.10 3.10 3.10 3.10 3.10

1F 2.14 2.12 2.12 2.20 2.17 2.48 2.48 2.48 2.48 2.48

3F 5.45 5.45 6.39 6.39 6.39 6.39 6.43 6.43 6.41 6.44

1F 4.95 4.95 5.65 5.65 5.65 5.65 5.67 5.67 5.66 5.68

3F 5.38 5.38 5.39 5.20 5.22 5.24 5.08 5.08 4.85 5.22

1F 4.22 4.22 4.22 4.03 4.03 4.04 3.96 3.96 3.83 3.99

Sahuaro SHO 115

115

115

Salvador Alvarado SAA

San Carlos SCR

Rocafuerte RCF 115

Rosario ROS 115

Ruíz Cortínez RCO 115

Puerto Peñasco PPA 115

Quila QLA 115

Quiroga QRG 115

230

115

Puerto Libertad PLD 230

Pueblo Nuevo PNO

Playa Encanto PLY 115

115

115

Progreso PRG

Providencia PVD

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Piaxtla PXT 115

230

115

Planta Guaymas Dos PGD

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 193: Catalogo 2011-2020 r010212 Corto Circuito

193

Coordinación de Planificación

ÁREA NOROESTE

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 2.33 2.34 2.35 2.36 2.35 2.35 2.59 2.64

1F 1.65 1.65 1.66 1.66 1.66 1.66 1.96 1.97

3F 4.97 5.02 4.97 4.97 6.18 6.45

1F 3.60 3.62 3.60 3.60 5.46 5.60

3F 4.49 4.49 6.43 6.44 6.44 6.44 6.47 6.47 6.45 6.49

1F 3.71 3.71 5.20 5.20 5.21 5.21 5.22 5.22 5.21 5.23

3F 3.15 3.15 3.15 3.15 3.15 3.15 3.16 3.16 3.17 3.17

1F 2.93 2.93 2.93 2.93 2.93 2.93 2.94 2.94 2.94 2.95

3F 6.18 7.02 7.41 7.69 7.61 8.88 8.86 8.86 8.81 9.13

1F 6.43 6.87 7.12 7.29 7.24 8.35 8.34 8.34 8.31 8.51

3F 8.80 9.51 9.84 10.09 10.01 10.95 10.94 10.94 10.90 11.15

1F 10.40 10.97 11.26 11.48 11.41 12.41 12.40 12.40 12.37 12.58

3F 8.26 8.26 8.26 8.39 8.39 8.44 8.48

1F 6.67 6.67 6.67 6.73 6.73 6.77 6.79

3F 3.12 3.13 3.13 3.14 3.17 3.19 3.17 3.17 3.62 3.71

1F 2.26 2.26 2.26 2.27 2.28 2.28 2.28 2.28 2.88 2.92

3F 2.80 2.46 2.49 2.49 2.49 2.49 2.50

1F 2.87 2.56 2.65 2.65 2.65 2.64 2.65

3F 4.80 4.91 4.96 6.20 5.70 5.82 5.82 5.82 5.81 5.86

1F 5.20 5.29 5.33 6.53 6.07 6.38 6.37 6.37 6.37 6.40

3F 7.09 7.22 7.28 8.60 8.15 8.36 8.36 8.36 8.35 8.40

1F 8.74 8.87 8.93 10.38 9.90 10.24 10.24 10.24 10.23 10.28

3F 5.76 6.42 6.38 6.38 6.23 8.01

1F 5.39 5.81 5.79 5.79 5.71 8.10

3F 12.11 13.25 13.14 13.14 12.63 19.69

1F 11.59 12.34 12.27 12.27 11.99 21.84

3F 8.48 8.48 8.49 8.52 8.54 8.57 9.45 9.45 9.04 9.73

1F 7.68 7.69 7.69 7.71 7.72 7.74 8.22 8.22 8.01 8.36

3F 0.85 0.84 0.84 0.86 0.85 0.99 0.99 0.99 0.99 0.99

1F 0.58 0.57 0.57 0.58 0.58 0.74 0.74 0.74 0.74 0.74

3F 1.95 1.95 1.96 1.96 1.97 1.98 1.97 1.97 2.14 2.17

1F 1.39 1.39 1.39 1.39 1.40 1.40 1.40 1.40 1.60 1.61

3F 4.14 6.14 7.41 7.66 7.89 8.78 8.77 8.77 8.74 8.96

1F 5.76 5.81 6.56 6.71 6.84 7.34 7.33 7.33 7.32 7.43

3F 4.81 5.22 5.66 5.73 5.80 6.02 6.02 6.02 6.02 6.06

1F 6.89 5.91 6.29 6.35 6.42 6.61 6.60 6.60 6.60 6.64

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

San Enrique SEN 115

115

115

San Isidro SIS

San Rafael SRF

Sanalona SLA 115

230

115

Santa Ana STA

230

115

400

Seis de Abril SSA

115

115

400

Santa Fé SFE

Santa Inés STI

230

Sinatex S.A. SIN 115

Sonoyta SNY 115

Seri SER

Subestación Bahía Kino SBK 115

230

115

Subestación Cananea SCN

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 194: Catalogo 2011-2020 r010212 Corto Circuito

194

Coordinación de Planificación

ÁREA NOROESTE

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 2.88 2.88 2.88 2.89 2.92 2.93 2.92 2.92 3.36 3.44

1F 1.90 1.90 1.91 1.91 1.92 1.92 1.92 1.92 2.41 2.44

3F 11.56 11.59 11.65 11.91 12.30 12.75 12.68 12.68 12.44 13.68

1F 9.58 9.60 9.63 9.72 9.89 10.09 10.07 10.06 9.97 10.51

3F 2.50 2.50 2.50 2.51 2.53 2.54 2.53 2.53 2.81 2.86

1F 1.79 1.80 1.80 1.80 1.80 1.81 1.81 1.81 2.16 2.18

3F 9.49 9.49 9.53 9.53 9.54 9.54 9.93 9.93 9.87 9.99

1F 10.40 10.40 10.44 10.44 10.45 10.45 10.76 10.76 10.98 11.08

3F 15.31 15.31 15.38 15.38 15.39 15.39 15.86 15.86 15.95 16.10

1F 17.56 17.57 17.64 17.63 17.65 17.65 18.07 18.07 18.39 18.53

3F 2.57 2.57 2.57 2.58 2.60 2.61 2.60 2.60 2.89 2.95

1F 1.83 1.83 1.83 1.83 1.84 1.84 1.84 1.84 2.21 2.23

3F 4.26 4.26 4.27 4.29 4.34 4.38 4.35 4.35 5.22 5.42

1F 3.13 3.14 3.14 3.15 3.16 3.18 3.17 3.17 4.45 4.55

3F 1.68 1.68 1.68 1.68 1.68 1.68 1.71 1.71

1F 1.17 1.17 1.17 1.17 1.17 1.17 1.18 1.18

3F 10.19 10.19 10.21 9.55 9.62 9.68 9.16 9.16 8.44 9.62

1F 9.40 9.40 9.41 8.51 8.55 8.58 8.24 8.24 7.66 8.34

3F 1.56 1.56 1.56 1.57 1.57 1.58 1.57 1.57 1.68 1.70

1F 1.11 1.11 1.11 1.11 1.11 1.11 1.11 1.11 1.24 1.24

3F 1.59 1.59 1.59 1.59 1.60 1.61 1.60 1.60 1.71 1.73

1F 1.13 1.13 1.13 1.13 1.13 1.13 1.13 1.13 1.26 1.27

3F 2.30 2.26 2.26 2.23 2.23 2.23 2.24 2.24 2.25 2.25

1F 1.67 1.64 1.64 1.61 1.61 1.61 1.61 1.61 1.62 1.62

3F 6.33 6.34 6.35 6.41 6.52 6.61 6.55 6.55 8.70 9.26

1F 4.81 4.82 4.82 4.84 4.89 4.92 4.90 4.89 8.74 9.11

3F 15.05 15.09 15.19 15.61 16.39 17.13 17.00 16.98 16.57 18.91

1F 14.19 14.22 14.28 14.50 14.98 15.39 15.32 15.31 15.11 16.48

3F 2.30 2.30 2.30 2.31 2.32 2.33 2.32 2.32 2.59 2.64

1F 1.53 1.53 1.53 1.54 1.54 1.54 1.54 1.54 1.85 1.87

3F 3.61 3.62 3.62 3.64 3.67 3.70 3.68 3.68 4.29 4.42

1F 2.64 2.64 2.64 2.64 2.66 2.67 2.66 2.66 3.51 3.57

3F 3.70 3.70 3.71 3.73 3.76 3.79 3.77 3.77 4.41 4.55

1F 2.70 2.70 2.70 2.71 2.72 2.73 2.73 2.73 3.63 3.69

3F 2.11 2.11 2.11 2.11 2.13 2.14 2.13 2.13 2.32 2.36

1F 1.50 1.50 1.50 1.51 1.51 1.51 1.51 1.51 1.75 1.77

115

230

115

115

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Subestación Cinco Costa SBI 115

Subestación Colinas SCL 115

Subestación Cuatro Costa SBC

Subestación El Dorado SED 115

115

115

115

Subestación Siete Costa SBE 115

115

115

115

115

Subestación Río Sonora SRS 115

Subestación Culiacán Potencia SCP

Subestación Diez Costa SBZ

Subestación Guaymas Uno SGU

Subestación Nueve Costa SBN

Subestación Ocho Costa SBO

Subestación Pericos SPE

Subestación Punto P SPP

Subestación Tres Costa SBT

Subestación Uno Costa SBU

Subestación Seis Costa SBS 115

Subestación Dos Costa SBD 115

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 195: Catalogo 2011-2020 r010212 Corto Circuito

195

Coordinación de Planificación

ÁREA NOROESTE

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 8.87 8.88 8.16 8.16 8.16 8.29 8.29 8.36 8.40

1F 7.36 7.37 6.48 6.48 6.48 6.54 6.54 6.59 6.61

3F 5.94 5.94 5.95 5.94 5.95 9.45 9.49 9.49 9.48 9.50

1F 3.88 3.88 3.88 3.88 3.88 6.86 6.87 6.87 6.87 6.87

3F 2.87 2.87 3.55 3.55 3.55 3.55 3.56 3.56 3.55 3.57

1F 2.18 2.18 2.63 2.63 2.63 2.63 2.63 2.63 2.63 2.63

3F 12.16 12.57 13.08 13.02 12.87 12.62 13.91

1F 11.11 11.34 11.63 11.60 11.48 11.36 12.06

3F 9.04 9.04 9.00 9.03 9.06 9.08 10.04 10.04 9.58 10.35

1F 8.56 8.57 8.50 8.51 8.53 8.55 9.12 9.12 8.86 9.29

3F 8.46 8.46 8.44 8.47 8.49 8.52 9.46 9.46 9.06 9.75

1F 8.28 8.29 8.26 8.28 8.30 8.31 8.94 8.94 8.69 9.11

3F 5.86 5.86 5.97 5.96 5.96 5.96 5.97 5.97 5.95 6.00

1F 4.79 4.79 4.85 4.83 4.83 4.83 4.84 4.84 4.82 4.85

3F 8.29 8.30 8.41 8.43 8.43 8.44 8.47 8.47 8.39 8.53

1F 9.08 9.08 9.18 9.19 9.20 9.20 9.23 9.23 9.17 9.28

3F 9.86 9.27 9.29 8.92 8.93 8.93 9.07 9.07 9.12 9.17

1F 8.70 7.95 7.96 7.53 7.54 7.54 7.61 7.61 7.65 7.68

3F 1.94 1.94 1.94 1.95 1.96 1.97 1.97 1.96 1.96 1.98

1F 1.36 1.36 1.37 1.37 1.37 1.37 1.37 1.37 1.37 1.38

3F 2.42 4.07 4.08 4.07 4.08 4.08 4.05 4.05 4.01 4.08

1F 1.71 2.99 3.00 3.00 3.00 3.00 2.99 2.99 2.97 3.00

3F 3.89 3.89 3.89 3.89 3.90 3.90 4.20 4.20 4.12 4.26

1F 2.94 2.94 2.94 2.94 2.95 2.95 3.08 3.08 3.05 3.11

3F 3.19 3.19 3.19 3.19 3.19 3.20 3.32 3.32 3.27 3.35

1F 2.27 2.27 2.27 2.27 2.27 2.27 2.32 2.32 2.30 2.33

3F 12.01 12.02 11.99 11.98 12.00 12.00 11.20 11.20 11.20 11.22

1F 10.79 10.79 10.77 10.76 10.77 10.77 9.91 9.91 9.90 9.91

3F 2.75 2.75 2.75 2.75 2.76 2.76 2.90 2.90 2.86 2.93

1F 2.05 2.05 2.04 2.05 2.05 2.05 2.11 2.11 2.10 2.12

3F 1.55 1.59 1.93 1.87 1.93 1.93 1.92 1.92 1.91 1.92

1F 1.08 1.10 1.36 1.31 1.36 1.36 1.36 1.36 1.36 1.36

3F 8.16 8.17 8.17 8.31 8.31 8.76 8.81

1F 6.48 6.49 6.49 6.54 6.55 6.86 6.88

3F 12.16 12.19 12.25 12.52 12.90 13.29 13.22 13.21 12.97 14.19

1F 9.76 9.77 9.79 9.89 10.05 10.21 10.18 10.17 10.08 10.60

Villa Juárez VIJ 115

Villas del Cedro VCD 115

Villas del Pitic VIP 115

Valle del Yaqui Dos VYD 115

Venadillo VND 115

Vicam VCM 115

Ures URE 115

Valle del Mayo VMY 115

Valle del Yaqui VDY 115

Topolobampo TPO 115

Topolobampo Dos TPD 230

Tres Ríos TSR 115

115

115

Tobarito TOB 115

Tecnológico Hermosillo TEH

Tetabiate TTB

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Subestación Valle VAL 115

Subestación Villa Unión SVU 115

Tamazula TZU 115

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 196: Catalogo 2011-2020 r010212 Corto Circuito

196

Coordinación de Planificación

ÁREA NOROESTE

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 5.28 5.30 5.32 5.37 5.40 5.46 5.45 5.43 5.40 5.57

1F 3.89 3.90 3.91 3.92 3.93 3.95 3.95 3.94 3.93 3.99

3F 1.58 1.59 1.59 1.59 1.59

1F 1.12 1.12 1.12 1.12 1.12

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Viñedos VÑD 115

Zapotillo ZAP 115

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____

Page 197: Catalogo 2011-2020 r010212 Corto Circuito

197

Coordinación de PlanificaciónESTUDIO DE CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

ÁREA NORTE

ÁREANORTE

______________Catálogo de Corto Circuito 2011-2020 _______Catálogo de Corto Circuito 2011-2020_____

Page 198: Catalogo 2011-2020 r010212 Corto Circuito

198

Coordinación de PlanificaciónRED ELÉCTRICA PRINCIPAL 2011

ÁREA NORTE

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 199: Catalogo 2011-2020 r010212 Corto Circuito

199

Coordinación de PlanificaciónRED ELÉCTRICA PRINCIPAL 2020

ÁREA NORTE

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 200: Catalogo 2011-2020 r010212 Corto Circuito

200

Coordinación de PlanificaciónADICIONES Y RETIROS DE GENERACIÓN

ÁREA NORTE

ADICIONES:

Nombre de la Central Año Capacidad

Norte II (Chihuahua) 2013 459 MW

Norte III (Juárez) 2015 954 MW

Norte IV (Torreón) 2019 918 MW

RETIROS:

Nombre de la Central Año Capacidad

Francisco Villa U4 y U5 2014 300 MW

Samalayuca U1 y U2 2015 316 MW

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 201: Catalogo 2011-2020 r010212 Corto Circuito

201

Coordinación de PlanificaciónADICIONES Y RETIROS DE GENERACIÓN

ÁREA NORTE

Derivado de la entrada de nuevos proyectos de generación dentro del área y mediante inyecciones de potencia de

áreas vecinas como el Noroeste y en mayor medida el Noreste, se produce un incremento en los niveles de corto

circuito trifásico y monofásico para las subestaciones adyacentes a los sitios con nueva generación en los niveles de

230 y 115 kV, durante todo el horizonte de planeación de mediano plazo, es decir hasta el 2020 y que en forma

cronológica tendrá el siguiente comportamiento:

En abril de 2013, se tiene programada la entrada en operación de la CCC Norte II y su red asociada en el nivel de 230

kV en el sitio El Encino II, en las inmediaciones de la actual subestación El Encino. Este proyecto incrementará el nivel

de corto circuito trifásico de la zona Chihuahua con respecto al 2012, como lo muestran los valores en los buses de 230

kV de las subestaciones El Encino de 14.56 kA a 23.32 kA, en la SE División del Norte pasan de 9.82 kA a 12.63 kA,

en la SE Ávalos de 11.53 kA a 15.26 kA y en Chihuahua Norte de 9.10 kA a 12.26 kA.

Para las corrientes monofásicas se pasa en El Encino de 15.75 kA a 26.93 kA, en la SE División del Norte pasan de

8.12 kA a 10.22 kA, en la SE Ávalos de 9.88 kA a 13.09 kA y en Chihuahua Norte de7.01 kA a 9.49 kA.

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 202: Catalogo 2011-2020 r010212 Corto Circuito

202

Coordinación de PlanificaciónADICIONES Y RETIROS DE GENERACIÓN

ÁREA NORTE

En abril del 2015 con la CCC Norte III y su red asociada en el nivel de 230 kV en el sitio Cereso, entre las

subestaciones Reformar y la actual CT Samalayuca, el efecto será un incremento en los valores de corriente de corto

circuito en la zona Juárez. Por ejemplo en el nivel de 230 kV las corrientes trifásicas de Samalayuca varían de 21.35

kA a 26.10 kA y en Terranova de 12.81 kA a 18.26 kA con respecto al 2014. En sus valores de corrientes monofásicas

varían en Samalayuca de 27.28 kA a 31.41 y en Terranova de 11.50 kA a 13.05 kA.

Para abril de 2019 entrará en operación la CCC Norte IV y su red asociada ubicada en el sitio El Encino II 230 kV.

Con ella se incrementará el nivel de corto circuito trifásico de la zona, por ejemplo los valores en 230 kV trifásicos de las

subestaciones El Encino II pasan de 21.33 kA a 32.47 kA, División del Norte de 12.09 kA a 14.55 kA , Ávalos de 14.19

kA a 17.81 kA y Chihuahua Norte de 11.85 kA a 13.93 kA, respecto a los valores encontrados en el 2018. En valores

monofásicos en El Encino II pasan de 25.43 kA a 39.34 kA, División del Norte de 9.96 kA a 11.29 kA , Ávalos de 12.40

kA a 14.59 kA y Chihuahua Norte de 9.30 kA a 10.37 kA

En el cálculo de corrientes de corto circuito del área fue considerado el retiro de las centrales que se indicaron, ya que

éstos están programados en forma coordinada con los nuevos proyectos de generación, es decir solo hasta que las

nuevas centrales operen a su máxima disponibilidad se consideran viables los retiros.

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 203: Catalogo 2011-2020 r010212 Corto Circuito

203

Coordinación de PlanificaciónPRINCIPALES PROYECTOS DE TRANSMISIÓN Y TRANSFORMACIÓN

ÁREA NORTE

Proyecto Año Nivel de tensión

S. E. San Pedro Potencia 2012 230/115 kV

Red asociada a CCC Norte II (El Encino II ) 2012 230 kV

L.T. Jerónimo Ortiz – La Trinidad 2012 230 kV

S. E. Moctezuma Ampliación 2013 400 kV

L. T. El Encino Moctezuma (cambio de tensión de operación) 2013 400 kV

L.T. El Encino II – Cuauhtémoc II 2014 230 kV

Red asociada a CCC Norte III (Cereso ) 2014 230 kV

S. E. Santiago II Ampliación 2015 230/115 kV

S. E. Vicente Guerrero II 2015 230/115 kV

S. E. Mesteñas Ampliación 2015 230/115 kV

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 204: Catalogo 2011-2020 r010212 Corto Circuito

204

Coordinación de PlanificaciónPRINCIPALES PROYECTOS DE TRANSMISIÓN Y TRANSFORMACIÓN

ÁREA NORTE

Proyecto Año Nivel de tensión

L. T. Cereso – Paso del Norte 2016 230 kV

S. E. Terranova Ampliación 2016 230/115 kV

S. E. Chihuahua Norte (sustitución ) 2016 230/115 kV

S. E. Torreón Sur Ampliación 2016 400/115 Kv

Red asociada a CCC Norte IV (El Encino II) 2018 230 kV

Cuauhtémoc II – Quevedo 2019 230 kV

S. E. Quevedo Ampliación 2019 230/115 kV

S. E. Francisco Villa Ampliación 2019 230/115 kV

S. E. Paso del Norte Ampliación 2019 230/115 kV

S. E. Ascensión Ampliación 2020 230/115 kV

Camargo II – Santiago II 2020 230 kV

Nuevo Casas Grandes II – Ascensión II 2020 230 kV

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 205: Catalogo 2011-2020 r010212 Corto Circuito

205

Coordinación de PlanificaciónPRINCIPALES PROYECTOS DE TRANSMISIÓN Y TRANSFORMACIÓN

ÁREA NORTE

En diciembre de 2012 en la zona Cuauhtémoc, se instalará una nueva subestación denominada San Pedro Potencia

230/115 kV, cuyo efecto en los niveles de corriente de corto circuito de las subestaciones cercanas al área de influencia

de este proyecto es un ligero incremento, que en promedio no llega a 1 kA en todas las subestaciones de la zona.

Para marzo de 2013 en la zona Moctezuma, se incrementará la capacidad de transformación 400/230 kV con la

ampliación de un transformador de 300 MVA en la subestación del mismo nombre, este proyecto incluye el cambio de

tensión de operación de la línea Moctezuma – El encino de 230 kV a 400 kV, sin embargo el incremento en los niveles

de corto circuito es mínimo y casi imperceptible en los buses de 115 kV de las subestaciones de distribución de la zona.

En mayo del 2015, en el subsistema Vicente Guerrero, al sur de la zona Durango se reforzará la transformación con la

entrada en operación de la subestación de potencia Vicente Guerrero II 230/115 kV, esto incrementará el nivel de corto

circuito en el área de influencia que tendrá dicho proyecto, como lo refleja el cambio en 115 kV de las subestaciones de

distribución del subsistema Vicente Guerrero con relación al 2014.

Con la ampliación de la transformación 230/115 kV en las subestaciones Mesteñas (zona Camargo – Delicias) y

Santiago II (zona Parral - Santiago) en el 2015 se mantienen sin cambios relevantes los niveles de corto circuito en

dichas zonas.

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 206: Catalogo 2011-2020 r010212 Corto Circuito

206

Coordinación de PlanificaciónPRINCIPALES PROYECTOS DE TRANSMISIÓN Y TRANSFORMACIÓN

ÁREA NORTE

Este mismo comportamiento se tiene en el 2019 en las zonas Cuauhtémoc, Camargo – Delicias y Juárez con las

ampliaciones en la capacidad de transformación 230/115 kV que están programadas en las subestaciones de potencia

Quevedo, Francisco Villa y Paso del Norte respectivamente.

Para el 2020, con la ampliación de la transformación 230/115 kV en la SE Ascensión II y la segunda línea en 230 kV

entre dicha subestación y la SE Nuevo Casas Grandes II, se presenta un ligero incremento en los niveles de corto

circuito de la zona Casas Grandes.

El valor más alto para el nivel de falla al final del horizonte de planeación se encuentra en la zona Torreón - Gómez

Palacio, en el nivel de 115 kV de la SE Gómez Palacio con un valor de 40.64 kA para la corriente trifásica y de

33.88 kA para la monofásica. El bus de 400 kV con el valor más alto fue Torreón Sur con 9.71 kA y en 230 kV el

registro más alto fue de 37.46 kA en la SE Samalayuca.

Finalmente se detectó que la zona con valores más altos (en promedio) en el nivel de falla trifásica y monofásica es

Torreón – Gómez Palacio, seguida de la zona Juárez.

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 207: Catalogo 2011-2020 r010212 Corto Circuito

207

Coordinación de Planificación

ÁREA NORTE

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 16.96 16.95 16.97 16.68 17.08 17.25 17.25 17.26 17.54 16.751F 13.38 13.42 13.43 13.30 13.48 13.55 13.55 13.55 13.75 13.053F 5.92 5.54 5.88 6.28 5.85 6.31 6.31 6.31 6.79 6.791F 5.12 4.82 5.00 5.43 5.12 5.14 5.26 5.26 5.53 5.663F 9.97 9.97 10.00 10.02 11.02 11.03 11.03 11.28 11.08 11.181F 7.86 7.86 7.96 7.88 7.09 7.09 7.09 7.66 7.09 7.383F 1.37 1.41 1.41 1.41 1.41 1.41 1.43 1.431F 0.47 0.71 0.71 0.71 0.71 0.71 0.71 0.713F 15.44 13.73 13.71 13.72 14.00 14.10 14.11 14.11 14.32 14.081F 12.08 10.30 10.28 10.50 10.63 10.67 10.67 10.67 10.81 10.653F 3.61 3.50 3.64 3.64 3.60 3.61 3.61 3.61 3.70 3.671F 2.35 2.27 2.34 2.34 2.33 2.33 2.33 2.33 2.36 2.343F 12.81 11.08 11.09 11.06 11.29 11.34 11.35 11.35 11.43 11.361F 9.40 7.89 7.90 7.85 7.96 7.98 7.98 7.99 8.02 7.993F 15.50 15.50 15.52 15.15 15.49 15.67 15.68 15.68 15.90 13.251F 11.88 12.21 12.21 12.06 12.20 12.28 12.28 12.28 12.42 9.783F 2.12 2.10 2.15 2.16 2.34 3.19 3.19 3.19 3.30 3.301F 1.47 1.46 1.48 1.49 1.56 2.18 2.18 2.18 2.24 2.923F 8.77 8.59 9.52 9.54 9.35 9.62 9.62 9.63 10.28 10.391F 6.28 6.14 6.71 6.72 6.65 6.78 6.73 6.74 7.06 7.073F 3.42 3.41 3.50 3.79 3.76 3.77 3.77 3.77 4.04 4.041F 2.25 2.24 2.27 2.48 2.47 2.47 2.47 2.47 2.60 2.593F 9.65 9.46 10.57 10.59 10.37 10.55 10.55 10.56 11.37 11.481F 7.08 6.92 7.62 7.63 7.54 7.63 7.60 7.61 7.98 7.993F 13.46 13.46 13.50 12.89 13.28 13.51 13.51 13.53 13.71 13.701F 11.59 12.87 12.90 12.59 12.77 12.91 12.91 12.92 13.05 13.233F 15.73 15.85 15.87 15.10 15.44 15.93 15.93 15.95 16.09 13.711F 14.31 14.48 14.52 13.29 13.83 14.61 14.62 14.64 14.87 11.103F 6.48 6.50 6.50 6.37 6.43 6.51 6.51 6.51 6.54 6.121F 4.51 5.18 5.18 5.13 5.15 5.19 5.19 5.19 5.20 5.023F 5.92 5.89 6.35 7.31 7.20 7.21 7.21 7.21 7.66 7.661F 4.25 4.24 4.47 5.36 5.32 5.32 5.32 5.32 5.52 5.493F 2.55 2.52 2.62 2.64 2.53 2.91 2.91 2.91 3.08 3.081F 1.70 1.69 1.72 1.73 1.64 1.74 1.95 1.95 2.01 2.013F 4.14 4.13 4.24 4.28 4.96 5.01 4.52 4.53 5.76 5.781F 2.77 2.76 2.77 2.79 3.37 3.43 2.98 2.99 7.47 7.50

AON

Arenales ARE 115

115

115

Armendáriz ARM

Ascensión

115

Arcadio ADI 115

Andalucía AND

Álvaro Obregón AVO 115

115

230

Américas AMR

Altavista ATV 115

Altec Electrónica ATC 115

Alianza AZA 115

Allende ALL 115

Álamos AMS 115

Aldama AMA 115

Aeropuerto AEP 115

Agnico Eagle AEA 115

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Abastos ABA 115

Abraham González ABR 115

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 208: Catalogo 2011-2020 r010212 Corto Circuito

208

Coordinación de Planificación

ÁREA NORTE

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 2.74 2.74 2.84 2.87 3.84 3.90 2.96 2.97 3.94 3.961F 1.74 1.74 1.75 1.76 2.35 2.41 1.83 1.83 5.00 5.023F 4.31 4.30 4.43 4.47 5.16 5.22 4.62 4.63 6.17 6.201F 2.95 2.94 2.95 2.97 3.58 3.65 3.09 3.09 9.68 9.723F 10.99 10.90 12.29 12.30 11.94 11.98 11.98 11.98 13.09 10.451F 8.36 8.30 9.20 9.21 9.04 9.05 9.05 9.05 9.57 7.403F 11.72 11.71 11.81 11.78 13.07 13.07 13.07 13.78 13.45 13.081F 9.57 9.56 9.77 9.59 9.02 9.02 9.02 10.07 9.12 8.853F 11.62 11.53 15.26 15.29 14.14 14.17 14.17 14.19 17.81 17.861F 10.00 9.88 13.09 13.11 12.37 12.38 12.39 12.40 14.59 14.163F 15.65 15.50 18.47 18.49 17.68 17.73 17.73 17.74 20.30 19.341F 13.82 13.67 16.37 16.39 15.83 15.86 15.86 15.87 17.55 16.503F 10.45 10.45 10.54 10.50 11.59 11.60 11.60 12.02 11.79 11.911F 8.10 8.10 8.27 8.12 7.27 7.27 7.27 7.91 7.31 7.613F 0.59 0.59 1.51 1.57 1.56 1.56 1.56 1.56 1.58 1.581F 0.42 0.42 0.49 0.79 0.79 0.79 0.79 0.79 0.79 0.793F 6.01 6.20 6.20 5.76 5.81 6.21 6.21 6.21 6.24 6.111F 5.57 5.69 5.69 4.05 5.47 5.70 5.70 5.70 5.71 5.643F 5.06 5.05 5.21 5.24 5.28 5.30 5.30 5.32 5.33 5.341F 3.36 3.25 3.24 3.25 3.28 3.30 3.39 3.40 3.59 3.593F 3.23 4.07 4.05 4.03 4.05 4.06 4.06 4.06 4.08 4.061F 2.06 2.62 2.60 2.60 2.60 2.61 2.61 2.61 2.62 2.613F 1.38 1.37 1.40 1.40 1.47 1.76 1.76 1.76 1.80 1.801F 0.93 0.93 0.93 0.94 0.96 1.15 1.16 1.16 1.17 1.333F 3.68 3.59 3.70 6.21 5.81 6.19 6.19 6.19 6.66 6.661F 5.28 5.16 5.31 8.65 8.13 8.62 8.63 8.63 9.23 9.243F 2.74 2.71 2.78 3.18 3.07 3.16 3.16 3.16 3.27 3.271F 2.23 2.21 2.24 2.40 2.35 2.39 2.39 2.39 2.43 2.443F 16.67 16.66 16.68 16.48 16.87 17.04 17.05 17.06 17.31 16.331F 12.92 13.04 13.05 12.96 13.13 13.20 13.20 13.20 13.37 12.463F 6.83 6.67 7.19 7.65 7.02 7.10 7.10 7.10 7.71 7.711F 5.90 5.78 6.07 6.93 6.37 5.94 5.98 5.98 6.34 6.553F 7.02 6.67 7.92 7.99 6.67 6.70 6.70 6.70 7.87 7.871F 5.83 5.63 6.29 6.73 5.42 5.27 5.32 5.33 6.03 6.733F 9.07 8.79 9.75 10.14 9.04 9.25 9.25 9.26 10.31 10.311F 8.26 8.05 8.67 9.63 8.37 8.21 8.26 8.26 9.03 9.62

115

Ascensión II AOD

Ávalos AVL

Boquilla BOQ

Búfalo

Camargo I CGU 115

230Camargo II CGD

115

115

California CFN 115

BUF

Bermejillo BER 115

Bolívar BOL 115

Batopilas BAT 115

Benito Juárez BJZ 115

Aztecas AZT 115

Basaseachi BSS 115

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

230

115

230

115

Auma AUM 115

Automotive Lighting ALI 115

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 209: Catalogo 2011-2020 r010212 Corto Circuito

209

Coordinación de Planificación

ÁREA NORTE

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 3.47 3.47 3.50 3.47 3.52 2.03 2.03 2.03 2.03 2.031F 2.29 2.29 2.31 2.30 2.32 1.30 1.30 1.30 1.30 1.303F 4.60 5.12 5.46 5.46 5.40 5.61 5.61 5.61 5.82 5.871F 3.03 3.44 3.64 3.64 3.62 3.73 3.68 3.69 3.81 3.823F 10.09 10.09 10.28 10.13 11.12 11.12 11.12 11.90 11.67 11.111F 7.62 7.62 7.91 7.64 6.95 6.95 6.95 7.64 7.08 6.703F 6.32 6.31 6.57 6.65 6.79 6.88 6.85 6.87 6.94 6.971F 4.35 4.33 4.35 4.40 4.53 4.62 4.56 4.58 5.80 5.823F 11.02 10.90 10.91 11.42 11.62 11.68 11.69 11.69 11.76 11.701F 7.84 7.83 7.83 8.01 8.10 8.12 8.12 8.12 8.15 8.133F 0.96 1.02 1.02 1.02 1.02 1.02 1.02 1.02 1.03 1.021F 0.62 0.66 0.65 0.65 0.66 0.66 0.66 0.66 0.66 0.663F 11.18 10.90 12.43 12.45 12.13 12.68 12.68 12.69 13.87 14.681F 8.43 8.17 9.23 9.24 9.10 9.43 9.30 9.31 9.96 10.553F 3.37 3.37 3.37 3.38 3.49 3.49 3.49 3.50 3.49 3.281F 2.23 2.23 2.23 2.23 2.16 2.16 2.16 2.21 2.16 2.093F 11.80 11.90 11.91 12.08 12.33 12.40 12.40 12.41 12.49 12.421F 8.43 8.57 8.57 8.60 8.72 8.74 8.74 8.74 8.78 8.753F 6.05 6.04 6.05 6.06 6.42 6.42 6.42 6.48 6.42 5.741F 4.30 4.30 4.32 4.31 4.06 4.06 4.06 4.23 4.06 3.803F 8.21 8.21 8.33 8.13 8.44 8.44 8.45 8.45 8.46 8.451F 6.11 6.11 6.25 6.15 6.30 6.31 6.31 6.31 6.31 6.313F 12.50 12.50 12.75 12.57 14.10 14.10 14.10 15.28 14.90 14.101F 10.11 10.11 10.55 10.14 9.08 9.08 9.08 10.26 9.27 8.723F 0.93 0.93 0.80 0.80 1.18 1.18 1.18 1.18 1.18 1.181F 0.61 0.61 0.54 0.53 0.77 0.77 0.77 0.77 0.77 0.773F 11.67 11.66 11.97 11.72 13.08 13.09 13.09 14.30 13.97 13.071F 9.16 9.16 9.64 9.18 8.10 8.10 8.10 9.08 8.30 7.703F 8.81 9.21 9.22 8.79 8.37 9.23 9.24 9.24 9.29 9.001F 10.89 11.36 11.37 10.93 10.50 11.39 11.39 11.39 11.45 11.153F 9.99 9.10 12.26 12.29 11.75 11.82 11.82 11.85 13.93 14.031F 7.83 7.01 9.49 9.51 9.25 9.31 9.29 9.30 10.37 10.283F 12.42 12.80 15.14 15.16 14.72 16.37 16.37 16.39 18.35 18.831F 9.57 10.48 12.60 12.62 12.38 13.68 13.12 13.13 14.82 15.003F 13.33 12.11 13.98 14.01 13.60 14.13 14.13 14.14 15.63 17.011F 11.12 9.27 10.60 10.62 10.43 10.75 10.63 10.64 11.46 12.61

230

115

115

Chaveña CVA 115

Chávez Uno CZU 115

Chihuahua Norte CUN

Chihuahua Planta CUP

Cerro del Mercado Maniobras CDM 115

115

115

Chamizal CZL

Charcos CHA

Cementos Mexicanos Torreón CMT 115

Cereso Juárez CER 115

Cementos Chihuahua CCU 115

Cementos Chihuahua Juárez CCJ 115

Caterpillar Torreón CAR 115

Ceballos CEB 115

Cartagena CTG 115

Casas Grandes CGR 115

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Canatlán II CND 115

Carolinas CAR 115

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 210: Catalogo 2011-2020 r010212 Corto Circuito

210

Coordinación de Planificación

ÁREA NORTE

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 11.08 10.93 12.35 12.38 12.05 12.11 12.11 12.12 13.23 13.201F 8.38 8.25 9.15 9.17 9.02 9.05 9.05 9.05 9.56 9.453F 10.48 10.39 13.19 13.21 12.38 12.40 12.40 12.42 15.15 15.241F 8.76 8.66 10.83 10.84 10.36 10.37 10.38 10.39 11.90 11.673F 14.53 14.37 16.87 16.89 16.22 16.31 16.31 16.32 18.46 18.081F 12.42 12.27 14.34 14.35 13.95 13.99 13.99 14.00 15.29 14.733F 10.35 10.35 10.52 10.40 11.43 11.43 11.43 12.18 11.94 11.421F 7.91 7.90 8.17 7.92 7.27 7.27 7.27 8.01 7.39 7.043F 3.78 3.68 3.79 6.09 5.70 5.75 5.75 5.75 6.15 6.151F 4.79 4.68 4.80 7.08 6.71 6.69 6.69 6.69 7.05 7.063F 0.49 0.49 0.49 0.49 0.49 0.45 0.45 0.45 0.45 0.451F 0.36 0.36 0.36 0.36 0.36 0.34 0.34 0.34 0.34 0.343F 1.40 1.40 1.13 1.13 2.10 2.10 2.11 2.11 2.11 2.111F 0.89 0.89 0.73 0.73 1.38 1.38 1.38 1.38 1.38 1.383F 9.07 9.01 9.93 9.94 9.70 9.73 9.73 9.73 10.45 8.141F 6.58 6.54 7.08 7.09 6.98 6.99 6.99 7.00 7.30 5.543F 10.30 10.01 11.34 11.36 11.10 11.79 11.79 11.80 12.79 13.201F 7.73 7.46 8.41 8.42 8.31 8.73 8.56 8.56 9.18 9.403F 11.47 11.09 12.79 12.81 12.48 13.56 13.56 13.57 14.89 15.271F 9.00 8.60 9.95 9.96 9.81 10.53 10.23 10.24 11.20 11.363F 2.41 2.41 2.41 2.41 2.46 2.46 2.46 2.47 2.46 2.361F 1.55 1.55 1.56 1.55 1.52 1.52 1.52 1.55 1.52 1.493F 8.78 10.41 10.41 9.94 10.08 10.44 10.44 10.45 10.55 10.441F 6.90 8.15 8.16 7.23 8.02 8.17 8.17 8.17 8.23 8.163F 0.96 0.96 3.15 3.41 3.39 3.39 3.39 3.39 3.47 3.471F 0.63 0.63 0.76 2.36 2.35 2.35 2.35 2.35 2.39 2.383F 1.52 1.51 1.54 1.54 1.63 2.00 2.00 2.00 2.05 2.051F 1.03 1.02 1.03 1.04 1.07 1.32 1.32 1.32 1.34 1.553F 1.51 1.57 1.56 1.56 1.56 1.56 1.58 1.581F 0.49 0.76 0.76 0.76 0.76 0.76 0.77 0.773F 3.38 3.37 3.39 3.66 3.63 3.63 3.63 3.63 3.90 3.901F 2.22 2.21 2.19 2.38 2.38 2.38 2.38 2.38 2.50 2.503F 10.96 10.84 10.85 11.36 11.56 11.62 11.62 11.63 11.69 11.641F 7.79 7.78 7.78 7.96 8.05 8.06 8.07 8.07 8.10 8.083F 22.78 22.77 22.81 22.02 22.69 22.99 23.00 23.01 23.60 22.441F 21.46 21.28 21.31 20.81 21.24 21.41 21.41 21.42 22.06 20.78

115

115

115

Cuadro de Maniobras Bolívar BOL 115

Cuadro de Maniobras Cahuisori CMC 115

Cuadro de Maniobras Montiac CMM

Cuadro de Maniobras Renault CDR

Cuadro de Maniobras Campo 108 AVO

Conejos CJM 115

115

115

Coronel COR

Creel CEE

Complejo Industrial CIN 115

Componentes de Chihuahua COM 115

Compañía Minera Sabinas MSA 115

Complejo de Seguridad Pública CSP 115

Colina CLN 115

Compañía Minera Basis MBA 115

115

Colegio CLG 115

Chuvíscar CHU

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Chihuahua Poniente CPN 115

230

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 211: Catalogo 2011-2020 r010212 Corto Circuito

211

Coordinación de Planificación

ÁREA NORTE

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 5.81 5.78 6.29 7.04 6.94 6.94 6.94 6.95 7.34 7.341F 4.10 4.08 4.30 4.98 4.94 4.94 4.94 4.94 5.11 5.083F 4.11 4.08 4.54 5.94 5.80 5.81 5.81 5.81 6.36 6.361F 2.83 2.82 3.03 4.09 4.04 4.04 4.04 4.04 4.26 4.213F 6.45 6.41 6.96 8.13 8.00 8.00 8.00 8.01 8.55 8.551F 4.73 4.71 5.00 6.13 6.08 6.08 6.08 6.08 6.34 6.293F 8.07 7.77 8.83 8.97 7.85 7.99 7.99 7.99 9.97 9.971F 6.85 6.67 7.28 7.40 6.04 6.07 6.18 6.18 7.19 7.253F 6.54 6.33 7.02 7.11 6.39 6.47 6.47 6.47 7.71 7.711F 5.13 5.03 5.37 5.43 4.66 4.67 4.74 4.74 5.31 5.343F 11.69 11.68 11.81 11.75 13.04 13.04 13.04 13.81 13.49 13.051F 9.44 9.44 9.68 9.47 8.83 8.83 8.83 9.86 8.94 8.633F 13.86 13.84 13.86 14.59 14.90 15.00 15.01 15.02 15.14 15.011F 10.33 10.47 10.48 10.73 10.87 10.90 10.91 10.91 10.97 10.883F 10.70 10.35 10.36 10.58 10.77 10.82 10.82 10.83 10.89 10.841F 7.51 7.28 7.29 7.35 7.43 7.44 7.44 7.45 7.47 7.453F 3.59 4.71 4.68 4.65 4.68 4.69 4.70 4.70 4.72 4.691F 2.30 3.05 3.03 3.03 3.04 3.04 3.04 3.04 3.05 3.043F 0.73 0.73 1.52 1.58 1.57 1.57 1.57 1.57 1.59 1.591F 0.50 0.50 0.56 1.03 1.03 1.03 1.03 1.03 1.04 1.033F 10.20 9.82 12.63 12.66 12.06 12.08 12.08 12.09 14.55 14.601F 8.47 8.12 10.22 10.24 9.94 9.95 9.95 9.96 11.29 11.093F 14.46 14.11 16.68 16.76 16.19 16.36 16.36 16.38 18.46 18.691F 12.34 11.98 14.08 14.14 13.83 13.93 13.91 13.92 15.18 15.133F 3.50 3.50 3.50 3.50 3.62 3.62 3.62 3.64 3.62 3.391F 2.32 2.32 2.32 2.32 2.24 2.24 2.24 2.30 2.24 2.173F 10.30 10.30 10.47 10.16 10.67 10.67 10.68 10.69 10.69 10.691F 8.08 8.08 8.35 8.17 8.46 8.47 8.46 8.46 8.47 8.473F 9.79 9.79 9.88 9.42 9.94 9.95 9.97 9.97 9.98 9.971F 7.94 7.94 8.20 7.92 8.24 8.26 8.25 8.26 8.26 8.263F 12.15 12.15 12.47 12.05 12.73 12.73 12.75 12.76 12.76 12.761F 10.48 10.49 10.94 10.66 11.12 11.13 11.13 11.13 11.14 11.133F 5.57 5.52 7.88 7.90 7.62 7.63 7.63 7.64 8.95 8.961F 5.67 5.63 7.89 7.90 7.69 7.69 7.69 7.71 8.92 8.623F 14.81 14.56 23.32 23.37 21.40 21.43 21.43 21.47 31.97 31.991F 16.02 15.75 26.93 26.99 25.05 25.08 25.09 25.12 37.62 34.49

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Cuauhtémoc CHC 115

230

115

Delicias DEL 115

Cuauhtémoc II CUD

Delicias II DED 115

Delphi Auto Motive System DEJ 115

Delphi Sistemas de Energía DET 115

Diagonal DIA 115

DGD

115

Dinamita DIN 115

Divisadero DVS 115

El Encino ENO

400

230

230

115

115

División del Norte DDN

Dunas DUN

Durango I DGU 115

230Durango II

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 212: Catalogo 2011-2020 r010212 Corto Circuito

212

Coordinación de Planificación

ÁREA NORTE

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 23.30 23.35 21.26 21.29 21.29 21.33 32.47 32.491F 27.47 27.52 25.36 25.38 25.40 25.43 39.34 35.353F 1.03 1.03 1.04 1.03 1.04 1.04 1.04 1.04 1.04 1.041F 0.67 0.67 0.67 0.67 0.67 0.67 0.67 0.67 0.67 0.673F 9.19 8.97 10.02 10.03 9.83 10.26 10.26 10.27 11.01 11.151F 6.68 6.49 7.17 7.18 7.10 7.33 7.24 7.25 7.65 7.683F 3.48 3.24 3.37 3.37 3.35 3.43 3.43 3.43 3.51 3.521F 2.26 2.10 2.17 2.17 2.16 2.20 2.18 2.18 2.22 2.233F 16.79 16.78 16.39 16.90 19.88 19.89 19.89 24.83 23.66 19.751F 15.36 15.36 15.14 15.42 16.09 16.09 16.09 36.02 18.65 16.033F 3.34 3.35 3.35 3.31 3.33 3.35 3.35 3.35 3.36 3.251F 2.17 2.31 2.31 2.30 2.30 2.31 2.31 2.31 2.31 2.283F 1.09 1.08 1.10 1.11 1.10 1.10 1.10 1.10 1.12 1.121F 0.72 0.72 0.72 0.73 0.72 0.73 0.73 0.73 0.73 0.733F 5.47 5.47 5.47 5.42 5.46 5.49 5.49 5.49 5.51 5.161F 3.55 3.58 3.58 3.57 3.58 3.59 3.59 3.59 3.60 3.343F 8.58 8.58 8.48 8.61 9.29 9.29 9.29 9.99 9.81 9.241F 6.21 6.21 6.18 6.22 6.24 6.25 6.25 7.54 6.49 6.233F 11.34 11.34 11.62 11.25 11.85 11.85 11.86 11.87 11.87 11.871F 9.51 9.51 9.88 9.65 10.03 10.04 10.03 10.04 10.04 10.043F 11.86 11.46 13.27 13.29 12.95 14.10 14.10 14.12 15.55 15.971F 9.41 8.97 10.44 10.46 10.29 11.09 10.75 10.76 11.83 12.023F 9.08 9.08 9.14 9.12 9.94 9.94 9.94 10.21 10.04 5.471F 6.83 6.83 6.93 6.84 6.23 6.23 6.23 6.69 6.26 3.243F 10.01 9.12 12.69 12.72 9.04 9.06 9.06 9.07 12.20 12.201F 10.34 9.56 12.62 12.81 7.15 7.08 7.24 7.24 9.46 9.663F 11.31 10.72 12.85 13.17 10.91 11.17 11.17 11.18 15.48 15.481F 11.52 11.02 12.81 13.20 9.44 9.50 9.78 9.78 12.61 12.773F 5.39 8.38 8.28 8.19 8.29 8.33 8.33 8.33 8.40 8.311F 3.56 5.78 5.70 5.68 5.71 5.72 5.72 5.72 5.77 5.723F 30.08 30.07 30.14 28.78 29.92 30.41 30.42 30.44 31.53 30.191F 36.02 35.19 35.25 33.92 35.05 35.50 35.51 35.53 37.49 35.223F 9.62 9.61 9.72 9.66 10.53 10.53 10.53 11.06 10.85 10.531F 7.28 7.28 7.45 7.31 6.87 6.87 6.87 7.49 6.95 6.733F 10.87 10.76 10.77 11.27 11.46 11.52 11.52 11.53 11.59 11.541F 7.72 7.70 7.71 7.89 7.97 7.99 7.99 7.99 8.02 8.00

FUH

Franckie FRC 115

115

115

Fuentes FTS

Fundilag Hierro

115

Francisco Zarco FZA 115

Francisco Villa FVL

Ford Maniobras FOD 115

115

230

Fox - Con FOX

Eticon Endo ETI 115

Fibras de Durango FDD 115

Escalón ECL 115

Escuadrón 201 EDU 115

Electro-Lux LUX 115

Emiliano Zapata EZT 115

El Saucito ELS 115

El Sauz ESZ 115

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

El Encino II ENOII 230

El Salto ESA 115

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 213: Catalogo 2011-2020 r010212 Corto Circuito

213

Coordinación de Planificación

ÁREA NORTE

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 3.12 3.12 3.18 3.20 3.22 3.23 3.23 3.24 3.25 3.251F 1.99 1.98 1.98 1.98 2.00 2.02 2.02 2.02 2.16 2.163F 1.29 1.34 1.33 1.33 1.33 1.33 1.34 1.341F 0.46 0.68 0.68 0.68 0.68 0.68 0.68 0.683F 9.64 9.64 9.68 9.68 10.61 10.61 10.61 10.88 10.70 5.081F 7.43 7.43 7.53 7.44 6.73 6.73 6.73 7.26 6.75 3.013F 4.58 4.55 4.79 4.85 4.81 4.82 4.82 4.82 4.98 5.001F 3.02 3.00 3.12 3.16 3.14 3.15 3.15 3.15 3.21 3.203F 16.03 16.01 16.09 14.89 15.87 16.09 16.10 16.11 16.16 16.201F 17.54 17.51 17.58 16.45 17.41 17.58 17.58 17.60 18.05 17.653F 32.13 32.12 32.20 30.66 31.95 32.51 32.52 32.55 33.80 32.261F 41.28 40.20 40.28 38.55 40.02 40.61 40.62 40.64 40.44 40.233F 10.86 10.85 10.71 10.90 11.91 11.91 11.91 12.92 12.64 11.851F 8.38 8.38 8.32 8.40 8.57 8.57 8.57 10.45 8.93 8.553F 0.65 0.65 0.65 0.65 0.67 0.72 0.72 0.72 0.73 0.731F 0.46 0.46 0.46 0.46 0.47 0.50 0.50 0.50 0.50 0.523F 1.70 1.70 1.71 1.70 1.71 1.71 1.71 1.71 1.71 1.711F 1.08 1.08 1.09 1.08 1.09 1.09 1.09 1.09 1.09 1.093F 7.09 7.09 7.17 7.02 7.26 7.26 7.26 7.27 7.27 7.271F 5.07 5.07 5.18 5.11 5.21 5.22 5.22 5.22 5.22 5.223F 9.44 9.32 10.34 10.36 10.13 10.18 10.18 10.19 10.96 10.961F 6.89 6.80 7.40 7.41 7.32 7.34 7.34 7.34 7.67 7.613F 3.33 3.33 3.59 3.59 3.57 3.57 3.57 3.57 3.68 3.681F 2.27 2.27 2.38 2.38 2.37 2.37 2.37 2.37 2.41 2.403F 25.23 25.23 25.28 24.31 25.12 25.47 25.47 25.49 26.25 25.311F 25.59 25.59 25.63 24.92 25.52 25.76 25.76 25.77 26.79 25.613F 14.68 14.68 14.69 14.43 14.72 14.84 14.85 14.85 15.07 14.611F 11.24 11.23 11.23 11.12 11.24 11.29 11.29 11.30 11.45 11.093F 12.74 12.74 12.56 12.80 14.13 14.13 14.13 14.64 14.31 13.731F 11.48 11.48 11.40 11.51 11.22 11.22 11.21 12.30 11.30 11.033F 1.40 1.40 1.13 1.13 2.10 2.10 2.11 2.11 2.11 2.111F 0.89 0.89 0.73 0.73 1.38 1.38 1.38 1.38 1.38 1.383F 4.71 4.71 6.04 5.93 7.00 7.00 7.01 7.01 7.01 7.011F 3.19 3.19 4.23 4.18 4.92 4.93 4.93 4.93 4.93 4.933F 11.60 11.59 11.60 12.11 12.32 12.39 12.39 12.40 12.48 12.401F 8.31 8.41 8.41 8.58 8.66 8.68 8.68 8.69 8.72 8.67

115

115

115

Independencia IDP 115

Industrial Juárez INJ 115

Industrias Centauro ICE

Industrias Lajat INL

Industrial Minera México MRT

Haciendas HAC 115

400

115

Hércules Potencia HCP

Iberdrola Energía La Laguna IBR

Guadalupe Victoria GVR 115

Guadiana GDN 115

Granjero GJO 115

Guachochi GCC 115

230

115Gómez Palacio GPL

Géminis GEM 115

General Trias GTR 115

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Galeana GNA 115

Gamon Lake GML 115

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 214: Catalogo 2011-2020 r010212 Corto Circuito

214

Coordinación de Planificación

ÁREA NORTE

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 14.20 14.19 14.67 14.28 16.36 16.36 16.36 18.38 17.84 16.341F 11.94 11.93 12.81 11.97 10.12 10.12 10.12 11.73 10.46 9.463F 7.69 7.69 8.34 8.15 8.62 8.62 8.63 8.63 8.63 8.631F 5.69 5.69 6.29 6.19 6.46 6.47 6.47 6.47 6.47 6.473F 9.99 9.73 10.97 10.99 10.75 11.39 11.39 11.40 12.33 12.701F 7.45 7.20 8.07 8.08 7.98 8.37 8.21 8.22 8.78 8.983F 4.22 4.22 4.33 4.37 4.71 4.76 4.53 4.54 5.07 5.091F 2.76 2.76 2.77 2.78 3.06 3.10 2.91 2.91 4.64 4.653F 15.45 15.05 15.07 14.70 15.07 15.18 15.18 15.19 15.40 15.171F 12.00 11.55 11.56 11.37 11.56 11.60 11.61 11.61 11.75 11.603F 6.40 6.41 6.61 6.39 6.63 6.63 6.66 6.66 6.67 6.671F 4.98 4.99 5.39 5.22 5.39 5.44 5.41 5.41 5.41 5.413F 11.21 11.22 12.19 11.23 12.21 12.21 12.25 12.26 12.27 12.261F 9.17 9.18 10.62 9.91 10.63 10.67 10.65 10.66 10.66 10.663F 12.56 12.56 13.07 12.55 13.40 13.40 13.42 13.43 13.44 13.431F 11.02 11.03 11.91 11.49 12.13 12.16 12.15 12.15 12.15 12.153F 3.36 3.32 3.44 3.60 3.46 3.54 3.54 3.54 3.68 3.681F 2.50 2.49 2.53 2.61 2.54 2.55 2.55 2.55 2.61 2.633F 3.47 3.47 3.51 3.53 3.54 3.54 3.54 3.54 3.531F 2.21 2.21 2.22 2.23 2.23 2.23 2.23 2.23 2.233F 9.74 9.74 9.81 9.78 10.73 10.73 10.73 11.06 10.87 5.401F 7.44 7.44 7.57 7.46 6.74 6.74 6.74 7.28 6.77 3.203F 4.07 3.99 4.24 4.27 4.00 5.04 5.04 5.04 5.59 5.591F 2.85 2.82 2.92 2.94 2.70 2.97 3.65 3.65 3.89 3.903F 0.75 0.75 0.76 0.76 0.78 0.85 0.85 0.85 0.86 0.861F 0.52 0.52 0.52 0.53 0.53 0.57 0.57 0.57 0.58 0.613F 0.49 0.49 0.49 0.49 0.49 0.45 0.45 0.45 0.45 0.451F 0.36 0.36 0.36 0.36 0.36 0.34 0.34 0.34 0.34 0.343F 12.07 12.07 11.92 12.11 13.14 13.14 13.14 13.61 13.35 12.991F 10.32 10.32 10.25 10.34 10.48 10.48 10.47 11.23 10.57 10.413F 24.44 24.41 24.46 23.52 24.37 24.68 24.69 24.70 25.34 24.601F 23.45 23.15 23.18 22.53 23.13 23.31 23.32 23.33 24.03 23.243F 2.83 2.80 2.91 3.18 3.04 3.04 3.04 3.04 3.17 3.171F 1.96 1.95 1.99 2.13 1.98 2.01 2.02 2.02 2.07 2.043F 6.24 6.45 6.45 5.97 6.02 6.46 6.46 6.46 6.49 6.351F 5.89 6.04 6.05 4.22 5.79 6.05 6.05 6.05 6.07 5.99

115

115

115

La Ciénega CIE 115

La Cuesta LCU 115

La Perla Minas de Fierro LPL

La Popular PPR

La Laguna LGA

Juárez JUA 115

115

115

Kilómetro 88 KOO

La Catedral LCA

Jiménez JEZ 115

Jimulco JIM 115

230

115

Jerónimo Ortiz JOM

Jardín JAR 115

400

Jabil JCI 115

Janos JOS 115

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Insurgentes IGS 115

International Wire INT 115

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 215: Catalogo 2011-2020 r010212 Corto Circuito

215

Coordinación de Planificación

ÁREA NORTE

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 7.68 7.71 7.72 7.67 7.76 7.83 7.83 7.84 7.86 7.651F 5.15 5.53 5.53 5.52 5.55 5.57 5.57 5.57 5.58 5.513F 13.43 13.43 13.90 13.26 13.93 13.94 13.96 13.97 13.98 13.971F 16.24 16.24 16.73 16.08 16.76 16.77 16.79 16.80 16.80 16.803F 11.83 11.83 11.67 11.87 12.97 12.98 12.98 13.85 13.54 12.901F 9.61 9.61 9.54 9.63 9.86 9.86 9.86 11.45 10.14 9.833F 0.79 0.80 0.80 0.79 0.79 0.80 0.80 0.80 0.80 0.791F 0.54 0.55 0.55 0.53 0.54 0.55 0.55 0.55 0.55 0.543F 24.20 24.17 24.22 23.30 24.13 24.44 24.44 24.46 25.09 24.361F 23.09 22.80 22.83 22.20 22.78 22.96 22.96 22.97 23.66 22.883F 9.86 9.83 9.84 10.14 10.30 10.37 10.37 10.38 10.43 10.361F 6.82 7.00 7.00 7.10 7.16 7.18 7.18 7.18 7.20 7.183F 19.95 19.92 19.95 19.32 19.89 20.09 20.10 20.11 20.53 20.041F 17.22 17.05 17.07 16.71 17.04 17.14 17.14 17.14 17.52 17.103F 5.39 5.25 5.71 5.77 5.28 5.34 5.34 5.35 6.16 6.161F 4.01 3.95 4.16 4.19 3.72 3.73 3.77 3.77 4.12 4.143F 5.86 5.84 5.85 5.79 5.85 5.87 5.87 5.87 5.90 5.871F 3.87 3.86 3.86 3.84 3.87 3.87 3.87 3.87 3.88 3.873F 15.53 15.51 15.55 15.47 15.38 15.56 15.56 15.58 15.80 15.621F 15.89 16.01 16.04 15.98 15.91 16.04 16.05 16.06 16.25 16.103F 11.24 11.24 11.07 11.29 12.48 12.48 12.48 13.81 13.45 12.411F 8.69 8.69 8.63 8.71 8.77 8.77 8.77 11.56 9.25 8.743F 10.61 10.60 10.46 10.64 11.61 11.61 11.61 12.60 12.32 11.561F 8.13 8.12 8.07 8.14 8.31 8.31 8.31 10.11 8.66 8.293F 11.46 11.46 11.32 11.51 12.49 12.49 12.49 12.90 12.65 12.281F 9.51 9.50 9.45 9.52 9.51 9.51 9.50 10.19 9.57 9.423F 2.77 2.76 2.60 2.74 2.72 2.72 2.72 2.72 2.78 2.781F 1.81 1.80 1.37 1.75 1.74 1.74 1.74 1.74 1.76 1.763F 0.63 0.63 0.63 0.63 0.63 0.56 0.56 0.56 0.56 0.561F 0.43 0.43 0.44 0.43 0.44 0.40 0.40 0.40 0.40 0.403F 3.67 3.66 3.47 3.75 3.72 3.72 3.72 3.73 3.90 3.901F 2.43 2.43 2.25 2.46 2.45 2.45 2.45 2.45 2.52 2.523F 2.02 2.32 2.31 2.30 2.31 2.31 2.31 2.31 2.32 2.311F 1.27 1.46 1.45 1.45 1.46 1.46 1.46 1.46 1.46 1.463F 11.50 11.49 11.50 12.00 12.21 12.28 12.28 12.29 12.37 12.281F 8.23 8.32 8.33 8.49 8.57 8.59 8.59 8.60 8.63 8.57

115

115

115

López Mateos LZM 115

Los Altares ATR 115

Mapimí MAP

Maq. Conf. de Ropa Lajat MCL

Manitoba MNT

Lexmark LEX 115

115

115

Lexmark II LEX2

Libertad LTD

León Guzmán LGM 115

Lerdo LED 230

Lala LAL 115

Lázaro Cárdenas LCS 115

Laguna II LAD 115

Laguna Seca LSC 115

Lagos LAG 115

Laguna del Rey LDR 115

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

La Rosita LRT 115

La Trinidad TND 230

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 216: Catalogo 2011-2020 r010212 Corto Circuito

216

Coordinación de Planificación

ÁREA NORTE

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 8.75 8.74 8.64 8.77 9.48 9.48 9.48 10.22 10.03 9.441F 6.35 6.35 6.32 6.36 6.39 6.39 6.39 7.75 6.64 6.383F 10.87 10.76 10.77 11.27 11.46 11.52 11.52 11.53 11.59 11.541F 7.72 7.70 7.71 7.89 7.97 7.99 7.99 7.99 8.02 8.003F 12.81 12.87 12.88 12.42 12.65 12.93 12.93 12.94 13.05 4.961F 10.14 12.97 12.98 12.67 12.83 13.02 13.02 13.02 13.09 3.213F 3.93 3.98 3.98 3.85 3.87 3.98 3.98 3.98 3.99 3.911F 2.80 2.86 2.86 2.61 2.82 2.86 2.86 2.86 2.86 2.843F 10.34 10.33 10.19 10.37 11.36 11.36 11.36 12.53 12.24 11.311F 7.83 7.83 7.78 7.85 8.01 8.01 8.01 10.26 8.45 7.993F 2.36 2.36 2.41 2.56 2.54 2.54 2.54 2.55 2.90 2.901F 1.53 1.53 1.55 1.65 1.65 1.65 1.65 1.65 1.84 1.843F 5.77 5.62 6.14 6.21 5.65 5.72 5.72 5.72 6.66 6.661F 4.37 4.30 4.54 4.59 4.03 4.04 4.08 4.09 4.50 4.523F 2.06 2.02 2.15 2.17 2.04 2.04 2.04 2.04 2.15 2.151F 1.38 1.37 1.41 1.43 1.32 1.32 1.33 1.33 1.38 1.383F 3.18 3.13 3.28 3.72 3.53 3.53 3.53 3.53 3.70 3.701F 2.28 2.26 2.32 2.55 2.32 2.38 2.39 2.39 2.48 2.413F 1.40 1.39 1.42 3.46 3.32 3.35 3.35 3.35 3.51 3.511F 0.90 0.89 0.90 2.60 2.54 2.55 2.55 2.55 2.61 2.623F 11.39 14.68 14.69 14.14 14.41 14.75 14.75 14.76 14.99 14.781F 8.35 11.74 11.75 11.12 11.63 11.77 11.77 11.77 11.94 11.783F 1.42 1.42 1.44 1.44 1.50 1.51 1.46 1.46 1.58 1.581F 0.92 0.92 0.92 0.92 0.97 0.97 0.93 0.93 1.14 1.143F 1.17 1.16 1.20 1.20 1.16 1.16 1.16 1.16 1.20 1.201F 0.78 0.77 0.79 0.79 0.76 0.76 0.76 0.76 0.78 0.783F 0.49 0.49 0.49 0.49 0.49 0.44 0.44 0.44 0.44 0.441F 0.36 0.36 0.36 0.36 0.36 0.34 0.34 0.34 0.34 0.343F 14.26 14.27 13.96 14.22 14.33 14.33 14.34 14.58 14.281F 11.10 11.10 10.97 11.08 11.12 11.13 11.13 11.31 11.103F 4.46 4.50 4.51 4.52 4.52 4.55 4.70 4.711F 2.68 2.67 2.70 2.72 2.71 2.74 2.98 2.993F 9.46 9.36 10.62 10.84 11.08 11.18 11.18 11.38 11.45 11.571F 6.45 6.39 6.29 6.36 6.47 6.55 6.51 6.61 7.35 7.393F 10.00 9.94 10.60 10.71 10.84 10.89 10.89 10.98 11.02 11.071F 7.98 7.05 7.00 7.04 7.12 7.17 8.04 8.12 8.69 8.72

230

115

Moctezuma MCZ

Miravalle MVL 115

400

Minera Hércules HCL 230

Minera Mexicana La Ciénega MLC 115

Minera Autlán MIA 115

Minera Bismark BIS 115

115

Mina Naica MNA 115

Mesteñas MTA

Meoqui MOQ 115

230

Médanos MED 115

Menonitas MEN 115

Matamoros MAT 115

Mayran MAY 115

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Masa MAS 115

Master Trim de México MTR 115

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 217: Catalogo 2011-2020 r010212 Corto Circuito

217

Coordinación de Planificación

ÁREA NORTE

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 1.82 1.82 1.84 1.85 1.91 1.92 1.88 1.88 1.96 1.971F 1.15 1.15 1.15 1.16 1.20 1.21 1.18 1.18 1.38 1.383F 10.87 10.76 10.77 11.27 11.46 11.52 11.52 11.53 11.59 11.541F 7.72 7.70 7.71 7.89 7.97 7.99 7.99 7.99 8.02 8.003F 13.32 13.14 13.16 13.90 14.19 14.28 14.29 14.30 14.40 14.321F 9.86 9.84 9.85 10.12 10.26 10.29 10.29 10.29 10.34 10.303F 8.46 8.25 9.14 9.16 8.99 9.47 9.47 9.48 10.10 10.231F 6.10 5.92 6.51 6.52 6.45 6.72 6.61 6.61 6.98 7.013F 1.40 1.39 1.42 3.47 3.33 3.36 3.36 3.36 3.52 3.521F 0.90 0.90 0.90 2.62 2.55 2.56 2.56 2.56 2.63 2.633F 1.38 1.38 1.40 1.45 1.44 1.44 1.44 1.44 1.64 1.641F 0.90 0.90 0.91 0.94 0.94 0.94 0.94 0.94 1.04 1.043F 14.21 14.19 14.23 13.01 14.10 14.27 14.27 14.28 14.52 14.321F 13.50 13.52 13.55 12.40 13.47 13.57 13.58 13.58 13.79 13.603F 22.68 22.50 22.55 21.70 22.68 22.92 22.93 22.95 23.33 22.971F 21.08 20.90 20.94 20.14 21.03 21.16 21.17 21.18 21.51 21.183F 0.91 0.91 0.92 0.94 0.94 0.94 0.94 0.94 1.02 1.021F 0.61 0.61 0.61 0.62 0.62 0.62 0.62 0.62 0.66 0.663F 11.04 10.74 12.25 12.27 11.97 12.62 12.62 12.63 13.78 14.431F 8.36 8.07 9.14 9.15 9.02 9.42 9.26 9.27 9.95 10.383F 1.06 1.05 1.07 1.39 1.17 1.17 1.17 1.17 1.19 1.191F 0.71 0.70 0.71 0.86 0.73 0.73 0.73 0.73 0.74 0.733F 5.50 5.48 5.89 6.04 6.22 6.40 6.39 6.43 6.44 6.501F 3.56 3.54 3.58 3.64 3.82 3.97 3.89 3.91 5.82 5.863F 7.51 7.49 7.86 7.98 8.16 8.30 8.27 8.30 8.36 8.411F 5.43 5.41 5.45 5.52 5.72 5.88 5.79 5.81 7.87 7.903F 1.31 1.31 1.32 1.31 1.32 1.03 1.03 1.03 1.03 1.031F 0.84 0.84 0.84 0.84 0.84 0.67 0.67 0.67 0.67 0.673F 1.88 1.86 1.91 2.35 2.27 2.27 2.27 2.27 2.34 2.341F 1.27 1.26 1.28 1.41 1.34 1.36 1.36 1.36 1.39 1.373F 11.30 11.18 12.65 12.67 12.30 12.34 12.34 12.35 13.52 13.301F 8.58 8.49 9.43 9.44 9.27 9.29 9.29 9.29 9.83 9.613F 0.71 0.71 0.72 1.33 0.76 0.76 0.76 0.76 0.77 0.771F 0.50 0.50 0.50 0.82 0.50 0.51 0.51 0.51 0.51 0.513F 13.66 13.66 13.41 13.73 15.55 15.55 15.55 18.02 17.42 15.461F 11.31 11.31 11.20 11.34 11.69 11.69 11.69 17.88 12.76 11.66

OTV

Ocampo OCA 115

115

115

Ojinaga OJI

Oriente XXI

Nuevo Ideal NUI 115

Oasis OAS 115

Nueva Holanda NHO 115

Nuevo Casas Grandes NCG

230

115

Nicolás Bravo NCB 115

Nombre de Dios NDD 115

230

115Nazas NAZ

Naica NAC 115

Namiquipa NAM 115

Motores John Deere JOD 115

Motorola de Mexico MOT 115

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Monteverde MTV 115

Montiac MON 115

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 218: Catalogo 2011-2020 r010212 Corto Circuito

218

Coordinación de Planificación

ÁREA NORTE

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 5.87 5.87 5.88 5.81 5.88 5.92 5.92 5.93 5.95 5.951F 3.91 3.99 3.99 3.97 4.00 4.01 4.01 4.01 4.02 4.023F 0.81 0.81 0.81 0.81 0.81 0.81 0.81 0.81 0.81 0.801F 0.54 0.54 0.54 0.54 0.54 0.54 0.54 0.54 0.54 0.543F 0.80 0.82 0.81 0.81 0.81 0.81 0.82 0.821F 0.41 0.55 0.55 0.55 0.55 0.55 0.55 0.553F 8.77 8.66 9.54 9.56 9.36 9.41 9.41 9.41 10.07 10.091F 6.32 6.24 6.75 6.76 6.68 6.70 6.70 6.70 6.97 6.943F 1.42 1.42 1.44 1.44 1.50 1.51 1.46 1.46 1.58 1.581F 0.92 0.92 0.92 0.92 0.97 0.97 0.93 0.93 1.14 1.143F 12.23 12.14 13.88 13.89 13.43 13.46 13.46 13.47 14.90 14.911F 9.64 9.56 10.79 10.80 10.56 10.57 10.58 10.58 11.30 11.183F 10.51 10.43 11.69 11.70 11.37 11.40 11.40 11.41 12.41 9.281F 7.88 7.82 8.62 8.62 8.47 8.49 8.49 8.49 8.94 6.443F 14.93 14.93 14.71 15.00 16.52 16.52 16.52 17.29 16.88 16.381F 15.26 15.26 15.11 15.30 15.87 15.87 15.87 17.50 16.10 15.793F 13.83 13.82 13.56 13.90 15.77 15.78 15.78 18.07 17.46 15.661F 11.46 11.46 11.35 11.49 11.64 11.64 11.64 17.48 12.57 11.593F 1.79 1.78 1.82 1.82 1.95 2.50 2.50 2.50 2.57 2.571F 1.22 1.22 1.23 1.24 1.28 1.66 1.67 1.67 1.70 2.063F 0.99 0.99 0.99 0.98 0.99 0.99 0.99 0.99 0.99 0.981F 0.64 0.65 0.65 0.65 0.65 0.65 0.65 0.65 0.65 0.653F 0.99 0.99 0.99 0.98 0.99 0.99 0.99 0.99 0.99 0.981F 0.64 0.65 0.65 0.65 0.65 0.65 0.65 0.65 0.65 0.653F 11.50 11.49 11.50 12.00 12.21 12.28 12.28 12.29 12.37 12.281F 8.23 8.32 8.33 8.49 8.57 8.59 8.59 8.60 8.63 8.573F 8.06 8.06 8.07 7.97 8.06 8.11 8.11 8.11 8.17 7.401F 5.45 5.52 5.52 5.49 5.52 5.53 5.53 5.53 5.56 4.963F 9.20 9.19 10.43 9.27 11.42 11.42 11.42 11.83 11.40 11.171F 7.60 7.60 9.06 7.63 5.87 5.87 5.87 6.66 5.86 5.583F 15.15 15.14 15.71 15.25 17.65 17.66 17.66 20.10 19.46 17.621F 13.09 13.09 14.20 13.14 10.87 10.87 10.87 12.77 11.28 10.083F 9.13 9.12 9.02 9.15 9.89 9.89 9.89 10.69 10.48 9.851F 6.71 6.71 6.67 6.72 6.84 6.84 6.84 8.22 7.12 6.823F 1.55 1.55 1.55 1.55 1.55 1.55 1.55 1.55 1.55 1.551F 0.97 0.97 0.97 0.97 0.97 0.97 0.97 0.97 0.97 0.97

Pedriceña PDA

115

115

115

Paso del Norte PNR

Patria PAT

115

230

Parras PRA 115

115

115

Parras Cone de México PCO

Parras de La Laguna PDL

Paso del Águila AGL

Parque de Tecnología Electrónica FlextronicFLE 115

Parral PAR 115

Papelera de Chihuahua PCH 115

Parque PQE 115

Palomas PMS 115

Paneles Ponderosa PPO 115

Palmarejo PMC 115

Palomar PLM 115

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Paila PLA 230

Paila PLA 115

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 219: Catalogo 2011-2020 r010212 Corto Circuito

219

Coordinación de Planificación

ÁREA NORTE

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 8.72 8.71 8.73 8.11 8.67 8.73 8.73 8.74 8.81 8.751F 6.82 6.84 6.84 6.34 6.82 6.84 6.84 6.85 6.88 6.853F 22.59 22.58 22.62 21.85 22.51 22.80 22.81 22.82 23.40 22.261F 21.18 21.01 21.03 20.55 20.96 21.13 21.13 21.14 21.77 20.513F 3.50 3.57 3.57 3.42 3.43 3.57 3.57 3.57 3.58 3.541F 2.65 2.68 2.68 2.25 2.63 2.68 2.68 2.68 2.68 2.673F 3.63 3.62 4.50 4.96 4.91 4.92 4.92 4.92 5.11 5.111F 2.41 2.40 3.03 3.41 3.39 3.39 3.39 3.39 3.47 3.453F 1.68 1.68 1.68 1.68 1.71 1.71 1.71 1.73 1.73 1.701F 1.07 1.07 1.07 1.07 1.07 1.07 1.07 1.11 1.08 1.073F 1.65 1.64 1.67 1.67 1.78 2.22 2.22 2.22 2.28 2.281F 1.12 1.11 1.12 1.13 1.17 1.47 1.47 1.47 1.50 1.773F 1.98 1.98 2.07 2.31 2.29 2.29 2.29 2.29 3.31 3.311F 1.30 1.29 1.33 1.49 1.48 1.48 1.48 1.48 2.11 2.103F 3.33 3.33 3.45 3.76 3.73 3.73 3.73 3.73 5.38 5.381F 2.28 2.27 2.33 2.57 2.56 2.56 2.56 2.56 3.66 3.643F 0.79 0.80 0.80 0.79 0.79 0.80 0.80 0.80 0.80 0.791F 0.54 0.54 0.54 0.53 0.54 0.54 0.54 0.54 0.55 0.543F 7.62 7.62 7.74 7.56 7.85 7.85 7.85 7.86 7.86 7.861F 5.55 5.55 5.71 5.62 5.75 5.76 5.76 5.76 5.76 5.763F 9.99 9.99 9.86 10.03 10.91 10.91 10.91 11.90 11.64 10.871F 7.51 7.51 7.46 7.52 7.67 7.67 7.67 9.46 8.02 7.653F 10.69 10.69 10.55 10.73 11.71 11.71 11.71 12.69 12.41 11.651F 8.22 8.21 8.16 8.23 8.40 8.40 8.40 10.19 8.74 8.383F 13.15 13.14 12.80 13.30 18.13 18.14 18.14 17.83 17.52 17.981F 12.10 12.09 12.06 12.18 9.09 9.09 9.09 11.02 8.96 9.003F 15.36 15.35 15.08 15.45 17.59 17.59 17.59 18.39 17.86 17.271F 14.54 14.53 14.44 14.59 13.24 13.24 13.24 13.30 13.36 13.093F 22.59 22.58 22.62 21.85 22.51 22.80 22.81 22.82 23.40 22.261F 21.18 21.01 21.03 20.55 20.96 21.13 21.13 21.14 21.77 20.513F 14.13 14.12 14.14 14.22 14.51 14.63 14.64 14.65 14.80 14.361F 10.39 10.50 10.51 10.53 10.65 10.69 10.69 10.69 10.78 10.413F 3.24 3.21 3.32 3.39 3.26 3.32 3.32 3.32 3.44 3.441F 2.30 2.29 2.33 2.38 2.31 2.32 2.32 2.32 2.37 2.403F 11.94 11.94 12.01 12.00 13.34 13.34 13.34 14.03 13.69 13.351F 9.91 9.91 10.10 9.94 9.40 9.40 9.40 10.54 9.49 9.26

RVR

Revolución REV 115

115

115

Río Florido RIF

Rivereña

115

Renault RNL 115

Reforma REA

Rayón RAY 115

115

230

RCA (Thompson TV de México) RCA

Química del Rey QRY 115

Quince de Octubre QDO 115

230

115Quevedo QEV

Porvenir PRR 115

Puerto Justo PTJ 115

Pilar PLR 115

Pondercel POE 115

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Peñoles PEL 230

Phillips Display de México PHI 115

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 220: Catalogo 2011-2020 r010212 Corto Circuito

220

Coordinación de Planificación

ÁREA NORTE

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 11.30 11.30 11.16 11.34 12.29 12.29 12.29 12.94 12.68 12.221F 9.22 9.22 9.16 9.24 9.44 9.44 9.44 10.55 9.62 9.413F 12.05 11.95 13.63 13.65 13.20 13.25 13.25 13.26 14.63 10.461F 9.39 9.31 10.47 10.47 10.25 10.27 10.27 10.27 10.95 7.413F 2.78 2.77 2.85 3.07 3.05 3.05 3.05 3.05 4.06 4.061F 1.86 1.86 1.89 2.05 2.04 2.04 2.04 2.04 2.68 2.673F 21.70 21.68 21.72 20.99 21.63 21.88 21.88 21.90 22.42 21.791F 19.81 19.59 19.61 19.17 19.56 19.69 19.69 19.70 20.24 19.623F 11.53 11.52 11.35 11.58 12.84 12.84 12.84 14.24 13.87 12.761F 8.98 8.98 8.91 9.00 9.06 9.06 9.06 12.08 9.58 9.033F 20.96 20.93 19.31 21.35 26.10 26.12 26.12 29.94 24.32 26.101F 26.87 26.83 24.80 27.28 31.41 31.43 31.43 37.46 28.67 31.423F 20.07 20.03 20.25 20.46 24.86 24.89 24.89 23.31 24.87 29.461F 24.04 24.01 24.20 24.40 27.77 27.80 27.79 25.72 27.82 36.023F 1.72 1.72 1.74 1.74 1.75 1.76 1.75 1.76 1.76 1.761F 1.09 1.08 1.08 1.08 1.09 1.09 1.09 1.09 1.13 1.133F 1.28 1.32 1.31 1.31 1.31 1.31 1.33 1.331F 0.27 0.27 0.27 0.27 0.27 0.27 0.27 0.273F 2.27 2.27 2.26 2.27 2.31 2.31 2.31 2.37 2.36 2.311F 1.44 1.44 1.44 1.44 1.45 1.45 1.45 1.52 1.47 1.453F 6.63 6.63 6.57 6.65 7.07 7.07 7.07 7.61 7.50 7.051F 4.61 4.61 4.59 4.62 4.68 4.68 4.68 5.58 4.87 4.673F 6.14 6.25 6.25 5.94 5.99 6.26 6.26 6.26 6.29 6.081F 4.88 5.05 5.05 4.32 4.94 5.06 5.06 5.06 5.07 4.983F 2.07 2.31 2.29 2.29 2.29 2.29 2.37 2.371F 1.42 1.48 1.47 1.47 1.47 1.47 1.50 1.493F 0.97 0.97 3.22 3.50 3.47 3.47 3.47 3.47 3.57 3.571F 0.64 0.64 2.38 2.43 2.42 2.42 2.42 2.42 2.46 2.453F 2.27 2.25 2.31 2.32 2.53 3.55 3.55 3.55 3.69 3.691F 1.59 1.58 1.61 1.62 1.70 2.46 2.47 2.47 2.54 3.463F 0.74 0.74 0.75 0.75 0.77 0.84 0.84 0.84 0.85 0.851F 0.52 0.52 0.52 0.52 0.53 0.57 0.57 0.57 0.57 0.603F 2.50 2.47 2.55 2.55 2.82 4.14 4.14 4.14 4.34 4.331F 1.77 1.76 1.79 1.81 1.91 2.95 2.95 2.95 3.05 4.50

Santiago SGO 115

Santa Bárbara BBA 115

Santa María del Oro SMO 115

115

San Ignacio SIG 115

San Isidro SID 115

San Pedro SPD 115

San Pedro Potencia MSP

230

230

115

San Francisco del Oro SFO 115

Samalayuca Sur SYS

San Buenaventura SBV

Salvarcar SVC 115

Samalayuca SYC 230

Ruiz Cortinez RCS 115

Sacramento SCT 115

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Robert Bosch ROB 115

Robinson RNN 115

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 221: Catalogo 2011-2020 r010212 Corto Circuito

221

Coordinación de Planificación

ÁREA NORTE

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 1.70 1.68 1.75 1.75 1.68 2.71 2.71 2.71 2.88 2.881F 1.12 1.11 1.13 1.15 1.10 1.81 1.82 1.82 1.89 3.493F 2.55 2.52 2.60 2.60 2.88 4.27 4.27 4.27 4.49 4.491F 1.81 1.81 1.83 1.85 1.96 3.06 3.07 3.07 3.18 4.773F 0.96 0.96 0.96 0.96 0.96 0.80 0.80 0.80 0.80 0.801F 0.63 0.63 0.63 0.63 0.63 0.53 0.53 0.53 0.53 0.533F 24.69 24.70 24.70 25.24 23.58 24.621F 24.97 24.98 24.98 25.52 23.86 24.903F 1.31 1.31 1.07 1.07 1.90 1.90 1.91 1.91 1.91 1.911F 0.83 0.83 0.69 0.69 1.24 1.25 1.25 1.25 1.25 1.253F 11.90 12.01 12.02 12.19 12.44 12.51 12.52 12.52 12.61 12.531F 8.52 8.66 8.66 8.69 8.81 8.83 8.83 8.84 8.88 8.843F 8.23 8.23 8.34 8.15 8.46 8.46 8.47 8.47 8.47 8.471F 6.12 6.12 6.26 6.17 6.32 6.33 6.32 6.32 6.32 6.323F 11.26 10.89 12.53 12.55 12.24 13.26 13.26 13.28 14.53 14.901F 8.79 8.40 9.68 9.69 9.55 10.24 9.95 9.96 10.87 11.023F 11.55 11.46 13.01 13.02 12.61 12.65 12.65 12.66 13.91 14.191F 8.89 8.82 9.86 9.86 9.66 9.68 9.68 9.68 10.28 10.333F 13.87 13.85 13.86 14.74 15.06 15.16 15.17 15.19 15.29 15.191F 10.41 10.56 10.58 10.89 11.02 11.06 11.06 11.07 11.12 11.063F 10.94 10.94 10.97 10.99 12.10 12.10 12.10 12.60 12.31 12.111F 8.95 8.95 9.07 8.98 8.63 8.64 8.64 9.56 8.69 8.553F 12.67 12.66 12.14 12.81 18.26 18.27 18.27 19.19 17.68 18.201F 11.42 11.42 11.13 11.50 13.05 13.05 13.05 22.28 12.80 13.033F 17.11 17.10 16.70 17.22 20.34 20.35 20.35 25.62 24.37 20.201F 15.84 15.84 15.61 15.90 16.61 16.62 16.62 39.50 19.41 16.553F 11.50 11.49 11.50 12.00 12.21 12.28 12.28 12.29 12.37 12.281F 8.23 8.32 8.33 8.49 8.57 8.59 8.59 8.60 8.63 8.573F 11.08 10.32 10.33 10.37 10.56 10.61 10.62 10.62 10.69 10.631F 7.84 7.24 7.25 7.23 7.33 7.34 7.34 7.34 7.37 7.353F 15.62 15.59 15.62 16.55 16.95 17.08 17.09 17.11 17.26 17.091F 12.01 12.20 12.22 12.56 12.74 12.80 12.80 12.80 12.88 12.76

Torreón Oriente TOT 115

The House of Lajat THL 115

Torreón TRR 115

Tecnológico TNG 115

Terranova TER

230

115

Tabalaopa TBP 115

Takata TAK 115

Subestación Cerro del Mercado SDM 115

Superior Industries de México SIN 115

Sombrerete SOM 115

Subestación Cementos SCE 115

Santiago Papasquiaro SGP 115

SE Cereso CCC NORTE III SCER 230

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

230

115Santiago II SGD

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 222: Catalogo 2011-2020 r010212 Corto Circuito

222

Coordinación de Planificación

ÁREA NORTE

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 7.94 7.94 7.97 7.84 8.12 8.20 8.21 8.23 8.30 8.261F 6.66 6.89 6.92 6.84 7.00 7.04 7.04 7.05 7.10 7.113F 14.33 14.32 14.36 13.43 14.17 14.37 14.37 14.40 14.58 14.491F 12.62 13.29 13.32 12.77 13.21 13.33 13.33 13.35 13.47 13.633F 19.58 19.53 19.57 21.81 22.51 22.73 22.75 22.79 23.01 22.831F 16.74 17.16 17.19 18.23 18.62 18.73 18.73 18.75 18.88 18.803F 13.87 13.87 13.62 13.95 15.76 15.77 15.77 17.48 16.94 15.621F 11.54 11.53 11.43 11.57 11.47 11.47 11.47 15.64 12.08 11.413F 2.11 2.09 2.16 2.17 2.10 2.10 2.10 2.10 2.16 2.161F 1.44 1.43 1.45 1.49 1.41 1.43 1.43 1.43 1.46 1.443F 1.55 1.57 1.57 1.54 1.54 1.57 1.57 1.57 1.57 1.561F 1.05 1.05 1.05 0.98 1.04 1.05 1.05 1.05 1.05 1.053F 12.53 12.52 12.07 12.66 16.07 16.08 16.08 16.70 15.57 16.031F 11.46 11.45 11.24 11.53 11.60 11.60 11.60 14.97 11.36 11.593F 14.57 14.57 14.35 14.63 16.13 16.14 16.14 16.86 16.45 16.011F 14.39 14.38 14.25 14.43 14.85 14.85 14.85 16.57 15.03 14.783F 2.06 2.05 2.08 2.09 2.09 2.09 2.09 2.10 2.10 2.101F 1.32 1.29 1.29 1.29 1.29 1.30 1.32 1.32 1.34 1.343F 13.96 13.95 13.97 14.35 14.66 14.76 14.77 14.78 14.91 14.671F 10.28 10.41 10.42 10.54 10.67 10.71 10.71 10.71 10.78 10.583F 9.07 5.82 6.19 6.19 6.10 6.10 6.10 6.11 6.38 6.281F 6.58 3.97 4.16 4.16 4.13 4.13 4.13 4.13 4.23 4.173F 14.33 9.46 9.11 9.05 9.18 9.22 9.22 9.22 9.31 9.211F 11.07 6.60 6.33 6.35 6.40 6.41 6.41 6.41 6.47 6.413F 2.35 2.35 1.67 1.66 5.23 5.23 5.24 5.24 5.25 5.241F 1.50 1.50 1.07 1.06 3.91 3.91 3.91 3.92 3.92 3.913F 4.57 4.56 4.58 4.59 4.59 4.591F 3.14 3.14 3.14 3.15 3.15 3.143F 5.60 5.59 5.61 5.61 5.62 5.611F 4.33 4.33 4.33 4.34 4.34 4.343F 2.16 2.16 2.19 2.19 2.20 2.20 2.20 2.21 2.21 2.211F 1.39 1.36 1.36 1.36 1.36 1.36 1.39 1.39 1.41 1.413F 11.94 11.85 13.52 13.53 13.09 13.11 13.11 13.12 14.47 13.981F 9.48 9.41 10.61 10.62 10.38 10.39 10.40 10.40 11.09 10.673F 9.25 9.24 9.29 9.28 10.13 10.14 10.14 10.38 10.21 10.251F 7.04 7.04 7.14 7.06 6.41 6.41 6.41 6.89 6.43 6.65

Werner WER

Villa Ahumada VAH 115

115

115

Vitromex VTM

230

115

Valles de Chihuahua VDC 115

115

115

Vergel VER

Vicente Guerrero VGR

Vicente Guerrero II VGD

Valle Esperanza VES 115

Valle Verde VVE 115

230

115Valle de Juárez VJZ

Tres Hermanos THS 115

Tres Manantiales TRM 115

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

400

230

115

Torres TOR 115

Torreón Sur TRS

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 223: Catalogo 2011-2020 r010212 Corto Circuito

223

Coordinación de Planificación

ÁREA NORTE

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 6.24 6.05 6.67 6.75 6.10 6.18 6.18 6.18 7.30 7.301F 4.83 4.74 5.04 5.09 4.41 4.42 4.48 4.48 4.99 5.023F 10.87 10.76 10.77 11.27 11.46 11.52 11.52 11.53 11.59 11.541F 7.72 7.70 7.71 7.89 7.97 7.99 7.99 7.99 8.02 8.003F 1.22 1.32 1.32 1.32 1.32 1.32 1.32 1.32 1.32 1.321F 0.77 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.833F 13.82 13.81 13.60 13.88 15.33 15.33 15.33 16.35 15.94 15.231F 12.28 12.27 12.17 12.31 12.66 12.66 12.66 14.76 13.00 12.61

Yermo YMO 115

Zaragoza ZZA 115

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Wrangler Chihuahua WDC 115

Wrangler de México WDT 115

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____

Page 224: Catalogo 2011-2020 r010212 Corto Circuito

224

Coordinación de PlanificaciónESTUDIO DE CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

ÁREA NORESTE

ÁREANORESTE

______________Catálogo de Corto Circuito 2011-2020 _______Catálogo de Corto Circuito 2011-2020_____

Page 225: Catalogo 2011-2020 r010212 Corto Circuito

225

Coordinación de PlanificaciónRED ELÉCTRICA PRINCIPAL 2011

ÁREA NORESTE

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 226: Catalogo 2011-2020 r010212 Corto Circuito

226

Coordinación de PlanificaciónRED ELÉCTRICA PRINCIPAL 2020

ÁREA NORESTE

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 227: Catalogo 2011-2020 r010212 Corto Circuito

227

Coordinación de PlanificaciónADICIONES Y RETIROS DE GENERACIÓN

ÁREA NORESTE

ADICIONES:

Nombre de la Central Año Capacidad

Noreste (Escobedo) (CC) 2016 1,034 MW

Noreste II(Monterrey) (CC) 2018 520 MW

Noreste III(Monterrey) (CC/NTG) 2018 520 MW

RETIROS:

Nombre de la Central Año Capacidad

Universidad (TG) U1 y U2 2010 24 MW

Fundidora (TG) U1 2010 12 MW

Tecnológico (DTG) U1 2010 26 MW

Monclova (TG) U1 y U2 2010 48 MW

Huinalá (CC) U1-U5 2016 378 MW

Altamira (TC) U3 y U4 2018 500 MW

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 228: Catalogo 2011-2020 r010212 Corto Circuito

228

Coordinación de PlanificaciónADICIONES Y RETIROS DE GENERACIÓN

ÁREA NORESTE

Para 2015, los niveles de corto circuito trifásico y monofásico en la S.E. Escobedo 115 kV incrementan

considerablemente alcanzando valores de 36.89 kA y 39.94 kA, respectivamente. Esto se debe a la entrada en

operación del segundo banco 400/115 kV como parte de la red asociada al ciclo combinado Noreste (Escobedo),

programado en 2016, cuyo alcance contempla el cambio de todos los interruptores en 115 y 400 kV que rebasen su

capacidad interruptiva a causa de la central.

En las barras A y B de la S.E. Monterrey Potencia 115 kV los niveles de corto circuito trifásico y monofásico aumentan

con la entrada en operación del ciclo combinado Noreste II y III(Monterrey) en 2018. El incremento neto en la corriente

de falla es de 9.56 kA monofásica y 7.71 kA trifásica.

El retiro de las unidades tres y cuatro de la central Altamira en 2018 provoca un descenso en los niveles de corto

circuito trifásico y monofásico de la S.E. Altamira 400 kV. La reducción es de 3.33 kA para el trifásico y de 1.8 kA para

el monofásico.

El retiro, en 2016, de las cinco unidades del ciclo combinado en Huinalá origina una disminución en los niveles de corto

circuito trifásico y monofásico (1.85 kA y 2.7 kA respectivamente) en la S.E. Huinalá 230 kV.

La entrada en operación de los nuevos proyectos de generación en 2011 – 2020 provocan que se alcance el límite de

capacidad interruptiva únicamente en S.E. Monterrey Potencia 115 kV en 2018. En el resto de subestaciones del área

no se presentan problemas de este tipo.

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 229: Catalogo 2011-2020 r010212 Corto Circuito

229

Coordinación de PlanificaciónADICIONES Y RETIROS DE GENERACIÓN

ÁREA NORESTE

Para evitar rebasar la capacidad interruptiva del equipo instalado en la subestación Monterrey Potencia, que implicaría

el cambio de prácticamente toda la subestación de 115 kV por ser en SF6, se revisará la posibilidad de reubicar la

generación programada para 2018 correspondiente a los dos ciclos combinados o quizá sólo sea necesario la

reubicación de uno, en otro punto de la zona Monterrey.

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 230: Catalogo 2011-2020 r010212 Corto Circuito

230

Coordinación de PlanificaciónPRINCIPALES PROYECTOS DE TRANSMISIÓN Y TRANSFORMACIÓN

ÁREA NORESTE

Proyecto Año Nivel de tensión

Anáhuac Potencia Bco. 2 2013 400/115 kV

Guerreño Bco. 1 2013 400/138 kV

Monclova Bco. 4 2014 230/115 kV

Regiomontano Bco. 1 2015 400/115 kV

Derramadero Bco. 1 2015 400/115 kV

San Jerónimo Potencia Bco. 2 2015 400/115 kV

Escobedo Bco. 4 2015 400/115 kV

Champayán – Güemez - Regiomontano 2016 400 kV

Piedras Negras Potencia – Acuña Dos 2016 230 kV

Tamos Bco. 2 2016 400/115 kV

Las Glorias Bco. 2 2016 400/115 kV

Güemez Bco. 2 2017 400/115 kV

Tecnológico Bco. 2 2017 400/115 kV

Huinalá – Tecnológico 2018 400 kV

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 231: Catalogo 2011-2020 r010212 Corto Circuito

231

Coordinación de PlanificaciónPRINCIPALES PROYECTOS DE TRANSMISIÓN Y TRANSFORMACIÓN

ÁREA NORESTE

En 2013 el nivel de corto circuito trifásico y monofásico en la S.E. Anáhuac Potencia en 115 kV alcanzará valores de

18.18 kA y 23.74 kA, respectivamente, esto debido a la entrada en operación del segundo banco de transformadores

400/115 kV en esta subestación. Para este año, también se tiene programada la subestación Guerreño: transformación

400/138 kV en la zona Reynosa. Esta obra ocasionará mayores niveles de corriente de falla en las subestaciones

involucradas con la red asociada al proyecto, los incrementos más significativos se presentan en: Delnosa II (7.66 kA

trifásica y 6.68 kA monofásica), Aztlán (5.32 kA trifásica y 5.06 kA monofásica), Jarachina (4.54 kA trifásica y 4.21 kA

monofásica) y Juárez (6.41 kA trifásica y 6.61 kA monofásica).

Para 2014, la obra Monclova Bco. 4 230/115 kV provoca un ligero incremento en el valor de corto circuito de la barra de

115 kV de S.E. Monclova. Los valores de corto circuito trifásico (3F) y monofásico (1F) calculados para esta

subestación son de 11.13 kA y 13.16 kA respectivamente.

En las zonas Saltillo y Monterrey los niveles de corto circuito incrementan a consecuencia de la entrada en operación

de cuatro bancos de transformación de potencia 400/115 kV en 2015: Derramadero Bco. 1, Regiomontano Bco. 1,

San Jerónimo Potencia Bco. 2 y Escobedo Bco. 2. Las subestaciones donde se detectan aumentos más significativos

en el valor de corriente de falla son: Saltillo 115 kV llegando a 24.42 kA (3F) y 25.54 kA (1F),Agua Nueva presenta

10.05 kA (3F) y 7.26 kA (1F), mientras que en San Jerónimo Potencia y Escobedo, ambos en 115 kV, se tienen valores

de 35.28 kA (3F) / 36.96 kA (1F) y 36.89 kA (3F) / 39.94 kA (1F).

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 232: Catalogo 2011-2020 r010212 Corto Circuito

232

Coordinación de PlanificaciónPRINCIPALES PROYECTOS DE TRANSMISIÓN Y TRANSFORMACIÓN

ÁREA NORESTE

En 2016, los proyectos de transmisión Champayan – Güemez - Regiomontano en 400 kV y el tendido del segundo

circuito en 230 kV Piedras Negras Potencia – Acuña Dos producirán una mayor corriente de corto circuito,

principalmente, en S.E. Huinalá 400 kV [29.06 kA (3F) y 33.55 kA (1F)] y en la S.E. Acuña Dos 138 kV [4.56 kA (3F) y

3.70 kA (1F)]. En este año también entran en operación los proyectos de transformación 400/115 kV Tamos Bco. 2 y

Las Glorias Bco. 2, con lo cual incrementan los valores de corriente de falla en la S.E. Tamos 115 kV, los cuales

llegarán a 26.54 kA (3F) y 23.52 kA (1F), mientras que en la S.E. Las Glorias el nivel de corto circuito quedará en 39.84

kA (3F) y 39.31 kA (1F).

Los segundos bancos de transformación 400/115 kV en las subestaciones Güemez y Tecnológico programados para

2017, originan un aumento en los valores de corto circuito trifásico y monofásico. De manera puntual se tiene: Güemez

115 kV pasa de 12.90 kA a 15.07 kA (3F) y de 13.21 kA a 14.46 kA (1F); mientras que en Tecnológico 115 kV el

aumento es de 30.76 a 36.60 kA (3F) y de 29.64 a 37.48 kA (1F).

En 2018, la línea de transmisión programada Huinalá – Tecnológico ocasionará incrementos en la magnitud de corriente

de corto circuito trifásico y monofásico, principalmente de la S.E. Tecnológico 400 kV. Los gradientes son de 5.17 kA

(3F) y 4.77 kA (1F). En resumen, para las obras de transmisión programadas para 2010 – 2020 no se observa que se

rebase la capacidad interruptiva de los equipos que conforman las redes de transmisión y subtransmisión del área

Noreste.

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 233: Catalogo 2011-2020 r010212 Corto Circuito

233

Coordinación de Planificación

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 8.93 8.93 8.93 9.78 9.78 10.63 10.63 10.69 10.69 10.69

1F 8.88 8.89 8.90 9.65 9.66 11.16 11.16 11.20 11.20 11.20

3F 3.28 3.28 3.28 3.33 3.33 3.94 3.94 3.94 3.94 3.94

1F 2.54 2.54 2.54 2.57 2.57 2.98 2.98 2.98 2.98 2.98

3F 3.51 3.51 3.51 3.56 3.56 4.56 4.56 4.56 4.56 4.56

1F 2.91 2.91 2.91 2.94 2.94 3.70 3.70 3.70 3.70 3.70

3F 14.07 14.07 14.45 14.45 14.46 14.67 14.68 14.94 14.94 14.94

1F 13.05 13.05 13.94 13.94 13.95 14.09 14.10 14.26 14.26 14.26

3F 15.33 15.32 16.04 16.04 16.04 16.12 16.13 16.25 16.25 16.25

1F 17.34 17.33 18.04 18.04 18.04 18.11 18.12 18.22 18.22 18.22

3F 16.43 16.41 18.10 18.10 18.10 18.16 18.17 18.26 18.26 18.26

1F 18.79 18.77 20.24 20.24 20.24 20.29 20.30 20.38 20.38 20.38

3F 7.62 7.62 7.62 7.62 10.05 10.10 10.12 10.18 10.18 10.18

1F 5.39 5.39 5.39 5.39 7.26 7.27 7.28 7.31 7.30 7.30

3F 15.74 15.73 15.74 15.73 15.80 16.04 16.69 17.49 17.49 17.49

1F 11.26 11.25 11.26 11.26 11.29 11.37 11.75 12.05 12.05 12.05

3F 21.48 21.48 21.49 21.48 21.85 22.05 22.05 22.39 22.39 22.39

1F 23.48 23.48 23.48 23.48 23.78 23.93 23.94 24.20 24.20 24.20

3F 5.79 5.79 5.79 5.82 5.82 5.83 5.83 5.70 5.70 5.70

1F 4.51 4.51 4.52 4.53 4.53 4.53 4.53 4.44 4.44 4.44

3F 2.48 2.48 2.48 2.48 2.48 2.48 2.51 2.53 2.53 2.53

1F 1.77 1.77 1.77 1.77 1.77 1.77 1.79 1.80 1.80 1.80

3F 15.96 15.96 15.96 15.95 15.98 20.02 20.03 21.51 21.51 21.51

1F 11.24 11.24 11.25 11.24 11.26 14.19 14.19 15.10 15.10 15.10

3F 14.29 14.29 14.29 14.28 15.97 16.10 16.12 16.34 16.27 16.27

1F 11.38 11.38 11.38 11.37 12.32 12.38 12.38 12.50 12.44 12.44

3F 27.39 27.47 27.53 27.52 27.53 27.99 28.10 24.77 24.82 24.83

1F 27.67 27.73 27.82 27.81 24.79 24.67 24.72 22.92 22.95 22.96

3F 20.84 20.89 20.93 20.92 20.93 21.10 21.13 20.35 20.37 20.37

1F 24.43 24.47 24.51 24.51 24.14 24.21 24.23 23.55 23.56 23.57

3F 26.46 26.49 26.60 26.60 26.60 26.93 26.95 26.77 26.78 26.79

1F 29.24 29.26 29.36 29.36 29.27 29.51 29.53 29.43 29.44 29.44

3F 5.86 5.86 5.86 6.49 6.49 6.54 6.54 6.57 6.57 6.57

1F 4.90 4.91 4.91 5.35 5.35 5.38 5.38 5.39 5.39 5.39

3F 9.38 9.38 9.39 9.39 9.40 9.58 9.59 9.75 9.76 9.76

1F 7.88 7.90 7.91 7.94 7.95 8.04 8.04 8.12 8.12 8.12

115

400

Altamirano ATR

Altos Hornos de México S.A. AHM

115

115

Almacentro

Alpes

ALE

ALP

400

230Altamira ALT

115

Álcali Maniobras ACM 115

Allende Dos AED 138

Allende ALN 115

400

AERAeropuerto 230

138

Agua Nueva AGN 115

Agua y Drenaje de MTY AAD 115

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Acero AEO 115

Acuña AUA 138

Acuña II AUD 138

ÁREA NORESTE

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 234: Catalogo 2011-2020 r010212 Corto Circuito

234

Coordinación de Planificación

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 4.36 4.36 4.36 4.36 4.36 4.59 4.59 4.63 4.63 4.63

1F 2.80 2.80 2.80 2.80 2.80 2.90 2.90 2.91 2.91 2.91

3F 2.74 2.74 2.75 2.77 2.77 3.10 3.10 3.10 3.10 3.10

1F 3.26 3.26 3.26 3.28 3.28 3.61 3.61 3.61 3.61 3.61

3F 2.34 2.34 2.34 2.34 2.34 2.34 2.34 2.40 2.40 2.40

1F 1.61 1.61 1.61 1.61 1.61 1.61 1.61 1.63 1.63 1.63

3F 17.07 17.10 17.18 17.16 17.20 17.32 17.42 16.91 16.93 16.95

1F 15.20 15.23 16.15 16.13 16.09 16.15 16.21 15.98 15.99 16.00

3F 11.91 11.91 18.18 18.18 18.19 18.24 18.27 18.09 18.10 18.10

1F 15.15 15.16 23.74 23.75 23.75 23.81 23.84 23.65 23.66 23.66

3F 13.90 13.90 14.10 14.10 14.10 14.21 14.21 14.34 14.34 14.34

1F 15.70 15.70 16.00 16.00 16.00 16.09 16.10 16.21 16.21 16.21

3F 16.76 16.71 16.72 16.72 16.72 16.77 16.77 16.83 16.83 16.83

1F 21.27 21.21 21.24 21.24 21.24 21.29 21.29 21.36 21.36 21.36

3F 1.98 1.98 2.68 2.68 2.68 2.68 2.68 2.68 2.68 2.68

1F 1.35 1.35 1.70 1.75 1.75 1.75 1.75 1.75 1.75 1.75

3F 12.85 12.83 14.87 14.87 14.88 14.92 14.92 15.00 15.00 15.00

1F 11.41 11.40 12.59 12.59 12.59 12.62 12.62 12.65 12.65 12.65

3F 6.19 6.20 6.20 6.20 6.20 6.66 6.67 6.75 6.75 6.75

1F 3.95 3.95 3.95 3.95 3.95 4.16 4.16 4.18 4.18 4.18

3F 19.27 19.27 19.28 19.27 19.63 19.82 19.83 20.16 20.16 20.16

1F 18.67 18.67 18.67 18.67 18.90 19.02 19.03 19.23 19.23 19.23

3F 4.28 4.28 4.28 4.28 4.28 4.29 4.29 4.29 4.29 4.29

1F 4.29 4.29 4.30 4.30 4.30 4.30 4.30 4.30 4.30 4.30

3F 4.78 4.78 4.79 4.79 4.79 4.79 4.79 5.19 5.19 5.19

1F 4.71 4.71 4.71 4.71 4.71 4.72 4.72 5.02 5.02 5.02

3F 11.15 11.15 11.17 11.17 11.17 11.19 11.19 13.45 13.45 13.45

1F 12.40 12.40 12.41 12.41 12.41 12.43 12.43 14.57 14.57 14.57

3F 1.39 1.40 2.23 2.23 2.23 2.24 2.24 2.24 2.47 2.24

1F 0.94 0.95 1.14 1.14 1.14 1.14 1.14 1.14 1.17 1.14

3F 2.74 2.74 3.32 3.32 3.32 3.33 3.33 3.32 3.32 3.32

1F 1.84 1.84 2.14 2.18 2.18 2.18 2.18 2.18 2.18 2.18

3F 9.39 9.38 14.70 14.70 14.71 14.75 14.75 14.82 14.82 14.82

1F 7.60 7.60 12.66 12.66 12.66 12.69 12.69 12.72 12.72 12.72

3F 3.00 3.00 3.00 3.00 3.00 3.06 3.16 3.16 3.16 3.16

1F 2.01 2.01 2.01 2.01 2.01 2.03 2.06 2.06 2.06 2.06

Anáhuac ANH 138

Amistad AMI 138

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

America AEA 115

Ánimas ANI 115

Anzalduas ANZ 138

400

115

400

230

115

400

230

138

115Atlapexco APX

Apodaca APO 115

Arco Vial ARV

115

Aztlan AZT 138

Barretal BET 115

Aztecas ATS

Anáhuac Potencia ANP

Anáhuac Tamaulipas Potencia ATP

Arroyo del Coyote ADC

ÁREA NORESTE

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 235: Catalogo 2011-2020 r010212 Corto Circuito

235

Coordinación de Planificación

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 20.26 20.28 20.31 20.31 20.31 20.50 20.51 20.46 20.47 20.47

1F 16.02 16.03 16.04 16.04 16.03 16.11 16.11 16.17 16.18 16.18

3F 1.65 1.65 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78

1F 1.09 1.09 1.15 1.15 1.15 1.15 1.15 1.15 1.15 1.15

3F 13.01 13.02 13.02 13.01 14.72 14.83 14.85 15.02 14.98 14.98

1F 10.63 10.63 10.63 10.63 11.55 11.60 11.60 11.71 11.66 11.66

3F 19.20 15.42 15.42 15.42 15.31 14.18 14.19 14.52 14.52 14.52

1F 15.92 13.39 13.39 13.39 13.33 12.39 12.40 12.57 12.57 12.57

3F 8.88 8.88 8.88 8.87 9.58 9.63 9.64 9.71 9.69 9.69

1F 6.40 6.40 6.40 6.40 6.70 6.72 6.72 6.76 6.74 6.74

3F 2.15 2.15 2.16 2.16 2.16 2.15 2.15 2.16 2.16 2.16

1F 1.72 1.72 1.72 1.72 1.72 1.72 1.72 1.72 1.72 1.72

3F 4.24 4.24 4.33 4.33 4.33 4.34 4.34 4.37 4.37 4.37

1F 2.95 2.95 2.98 2.98 2.98 2.98 2.98 2.99 2.99 2.99

3F 8.55 8.55 8.55 8.55 8.55 8.57 8.57 9.75 9.75 9.75

1F 7.94 7.94 7.94 7.94 7.94 7.95 7.95 8.70 8.71 8.71

3F 15.84 15.86 15.86 15.85 17.02 17.18 17.20 17.63 17.37 17.37

1F 13.34 13.36 13.36 13.36 13.94 14.02 14.03 14.41 14.10 14.10

3F 20.91 20.90 20.96 20.96 20.97 21.28 21.28 21.54 21.56 21.56

1F 24.31 24.31 24.36 24.36 24.37 24.65 24.66 24.96 24.98 24.98

3F 10.59 10.60 10.60 10.59 11.39 11.54 11.56 12.41 11.74 11.73

1F 10.19 10.19 10.20 10.18 10.76 10.85 10.86 12.13 10.97 10.97

3F 22.88 22.91 22.92 22.89 25.75 26.12 26.17 27.40 26.58 26.58

1F 25.00 25.04 25.05 25.02 27.45 27.73 27.77 30.02 28.08 28.07

3F 23.92 23.92 23.93 23.87 23.95 24.88 24.91 26.53 26.53 26.53

1F 17.30 17.30 17.30 17.27 17.34 17.78 17.79 18.49 18.49 18.49

3F 3.38 3.38 3.75 3.75 3.75 3.75 3.75 3.75 3.75 3.75

1F 2.39 2.39 2.54 2.54 2.54 2.54 2.54 2.54 2.54 2.54

3F 9.25 9.26 9.26 9.25 9.59 9.71 9.72 10.10 9.86 9.86

1F 7.28 7.28 7.29 7.28 7.44 7.49 7.50 7.80 7.55 7.55

3F 5.68 5.68 6.83 6.83 6.83 6.84 6.84 6.82 6.82 6.82

1F 4.55 4.55 5.11 5.12 5.12 5.12 5.12 5.12 5.12 5.12

3F 19.79 19.79 19.80 19.79 19.92 20.43 20.45 21.60 21.60 21.60

1F 13.24 13.24 13.24 13.24 13.30 13.49 13.50 13.97 13.97 13.97

3F 10.11 7.58 7.59 7.59 7.59 7.59 7.59 7.60 7.60 7.60

1F 9.12 6.52 6.53 6.53 6.53 6.53 6.53 6.54 6.54 6.54

Brisas BRI 115

RDN 115

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Basf BSF 115

Bravo Dos BRA 115

Campestre CPR 138

Capellanía CAP 115

IMS 115

CYN 115

CAM 138

115

115

Cementos Anáhuac CAU 115

Cedros CED

Carbón Dos CBD 400

230

Cementos Mexicanos

Central

Celulosa CEL

CEM

CEN

115

138

C.C.C Dulces Nombres

C.M.I.M.(IMIS)

Cadereyta

Camargo

Cementos Apasco APC 230

Cementos Mexicanos CMV 115

ÁREA NORESTE

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 236: Catalogo 2011-2020 r010212 Corto Circuito

236

Coordinación de Planificación

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 2.93 2.93 2.93 2.93 2.93 2.96 2.96 2.97 2.97 2.97

1F 2.02 2.02 2.02 2.02 2.02 2.04 2.04 2.04 2.04 2.04

3F 2.47 2.49 2.58 2.58 2.58 2.60 2.60 2.60 2.60 2.60

1F 1.63 1.63 1.67 1.67 1.67 1.02 1.02 1.02 1.02 1.02

3F 4.20 4.20 4.20 4.20 4.19 4.20 4.20 4.21 4.21 4.21

1F 3.67 3.67 3.67 3.67 3.66 3.67 3.67 3.68 3.68 3.68

3F 16.59 16.61 16.73 16.73 16.73 18.20 18.21 17.96 17.98 17.97

1F 12.97 12.98 13.03 13.03 12.99 13.84 13.85 13.75 13.76 13.76

3F 32.34 32.40 32.46 32.45 32.44 33.37 33.47 31.31 31.36 31.39

1F 31.77 31.81 31.95 31.94 31.22 31.88 31.95 30.61 30.64 30.66

3F 19.86 19.91 19.92 19.89 22.00 22.26 22.30 23.03 22.59 22.59

1F 18.92 18.98 18.99 18.97 20.33 20.48 20.50 21.38 20.67 20.66

3F 19.33 19.37 19.38 19.36 21.24 21.49 21.53 22.22 21.80 21.80

1F 18.05 18.10 18.11 18.09 19.26 19.39 19.41 20.20 19.56 19.56

3F 16.36 16.38 16.38 16.36 18.65 18.84 18.87 19.21 19.08 19.08

1F 14.63 14.65 14.65 14.64 16.03 16.13 16.14 16.46 16.24 16.24

3F 10.40 9.57 9.58 9.58 9.58 9.59 9.59 9.61 9.61 9.61

1F 10.26 9.52 9.53 9.53 9.53 9.54 9.54 9.55 9.55 9.55

3F 5.05 5.05 5.05 5.05 5.05 5.06 5.06 5.39 5.39 5.39

1F 5.39 5.39 5.39 5.39 5.39 5.39 5.39 5.66 5.66 5.66

3F 8.55 8.55 8.55 8.55 8.55 8.57 8.57 9.43 9.43 9.43

1F 9.26 9.26 9.26 9.26 9.26 9.27 9.27 9.96 9.96 9.96

3F 7.13 7.13 7.13 7.13 7.12 7.51 8.19 8.19 8.19 8.19

1F 5.70 5.70 5.70 5.70 5.69 5.93 6.17 6.17 6.17 6.17

3F 1.32 1.32 1.32 1.32 1.37 1.37 1.37 1.38 1.38 1.38

1F 0.84 0.84 0.84 0.84 0.87 0.87 0.87 0.87 0.87 0.87

3F 19.02 19.01 19.02 19.02 19.36 19.55 19.55 19.87 19.88 19.88

1F 18.24 18.24 18.24 18.24 18.46 18.57 18.58 18.77 18.77 18.77

3F 18.07 18.05 18.06 18.05 18.08 18.40 19.56 20.67 20.67 20.67

1F 13.37 13.36 13.36 13.36 13.39 13.51 14.27 14.73 14.73 14.73

3F 20.25 20.28 20.34 20.34 20.34 20.87 20.88 20.60 20.61 20.61

1F 17.75 17.77 17.80 17.80 17.78 18.00 18.01 17.87 17.88 17.88

3F 19.35 19.36 19.40 19.40 19.40 19.60 19.60 19.91 19.92 19.92

1F 16.82 16.82 16.84 16.84 16.83 16.93 16.94 17.26 17.26 17.26

3F 1.83 1.83 1.83 1.84 1.85 1.85 1.85 1.85 1.85 1.85

1F 1.22 1.22 1.22 1.23 1.23 1.23 1.23 1.23 1.23 1.23Cuatro Ciénegas CCE 115

Ciudad Industrial CID

Ciudad Victoria CDV

Contry CNY 115

Crioinfra CRY 115

Cto de Maniobras ETK ETK 115

138

115

Concepción del Oro CDO 115

Conek CNK 115

Cifunsa CIF 115

Cima CMA 138

230

Champayán CPY 115

Chrysler P. Motores CYM 115

Cibiosa CIB 115

Cerro Azul Dos CDO 115

Cerro Prieto CEP 115

Chairel CHR 115

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Cerralvo CER 115

ÁREA NORESTE

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 237: Catalogo 2011-2020 r010212 Corto Circuito

237

Coordinación de Planificación

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 10.06 10.05 10.81 10.81 10.81 10.85 10.85 10.91 10.91 10.91

1F 9.54 9.53 10.14 10.14 10.15 10.17 10.17 10.20 10.20 10.20

3F 14.34 14.32 17.90 17.90 17.91 17.97 17.97 18.08 18.08 18.08

1F 15.22 15.21 18.43 18.43 18.43 18.48 18.48 18.55 18.55 18.55

3F 19.70 19.75 19.76 19.73 21.84 22.10 22.14 22.86 22.43 22.42

1F 18.73 18.78 18.79 18.77 20.13 20.28 20.30 21.17 20.46 20.46

3F 7.25 7.22 14.88 14.88 14.88 14.92 14.92 14.98 14.98 14.98

1F 5.51 5.50 12.18 12.18 12.18 12.20 12.20 12.22 12.22 12.22

3F 5.82 5.82 5.82 5.82 5.82 6.23 6.23 6.30 6.30 6.30

1F 3.67 3.67 3.67 3.67 3.68 3.86 3.86 3.88 3.88 3.88

3F 10.23 10.41 10.51 10.74 10.74 10.74

1F 8.56 8.64 8.69 8.81 8.80 8.80

3F 21.33 21.57 21.65 21.95 21.93 21.93

1F 20.42 20.57 20.62 20.83 20.79 20.79

3F 5.38 5.38 5.61 5.61 5.61 5.62 5.62 5.64 5.64 5.64

1F 3.74 3.74 3.82 3.82 3.82 3.82 3.82 3.83 3.83 3.83

3F 7.81 7.81 7.81 7.31 7.31 7.40 7.41 7.54 7.54 7.54

1F 4.76 4.76 4.76 4.53 4.53 4.57 4.57 4.61 4.61 4.61

3F 7.94 7.94 7.94 7.42 7.43 7.52 7.52 7.66 7.66 7.66

1F 4.85 4.85 4.85 4.61 4.61 4.65 4.65 4.69 4.69 4.69

3F 3.86 3.86 3.97 3.97 3.97 4.03 4.03 4.02 4.02 4.02

1F 2.48 2.48 2.52 2.52 2.51 2.54 2.54 2.54 2.54 2.54

3F 1.88 1.88 2.52 2.52 2.52 2.52 2.52 2.52 2.52 2.52

1F 1.45 1.45 1.63 1.84 1.84 1.84 1.84 1.84 1.84 1.84

3F 10.22 10.22 10.22 10.21 13.57 13.66 13.69 13.82 13.80 13.80

1F 7.64 7.64 7.64 7.64 10.12 10.16 10.17 10.23 10.21 10.21

3F 5.19 5.19 5.28 5.28 5.28 5.48 5.49 5.46 5.46 5.46

1F 3.36 3.36 3.39 3.39 3.39 3.49 3.49 3.48 3.48 3.48

3F 14.91 14.91 14.91 14.91 15.46 15.62 15.62 15.96 15.96 15.96

1F 10.83 10.83 10.83 10.83 11.10 11.16 11.17 11.28 11.28 11.28

3F 6.20 6.21 6.23 6.22 6.43 6.48 6.54 6.62 6.62 6.62

1F 3.99 4.01 4.01 4.00 4.23 4.24 4.27 4.29 4.29 4.29

3F 2.16 2.16 2.55 2.55 2.55 2.56 2.56 2.55 2.55 2.55

1F 2.12 2.12 1.75 2.40 2.40 2.40 2.40 2.40 2.40 2.40

3F 16.21 16.21 16.22 16.21 16.31 15.95 15.96 16.57 16.57 16.57

1F 13.21 13.21 13.21 13.21 13.28 13.03 13.04 13.32 13.32 13.32Electrodos ELE 230

Cumbres CUF

Dirona y Forja DFO

Ébano

Derramadero DER

EBN

El Lechugal LEC 115

El Salero SRO 400

El Salto(Camilo Arriaga) STO 115

El Abra ABR 115

El Alamo ALM 115

El Coco COC 115

Díaz Ordaz DOR 138

Dirona DIR 115

115

115

Denso DSO 115

400

115

138

De Acero DEA 115

Delphi Delco ( Delnosa II ) DEL 138

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

230

ÁREA NORESTE

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 238: Catalogo 2011-2020 r010212 Corto Circuito

238

Coordinación de Planificación

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 3.74 3.68 3.73 3.73 3.73 3.73 3.73 3.73 3.73 3.73

1F 2.46 2.42 2.44 2.44 2.44 2.44 2.44 2.44 2.44 2.44

3F 22.69 22.71 22.76 22.76 22.76 23.06 23.07 23.52 23.53 23.53

1F 19.60 19.61 19.64 19.64 19.62 19.77 19.77 20.31 20.32 20.32

3F 21.83 21.83 21.87 21.85 22.03 27.02 27.07 30.56 30.57 30.57

1F 21.44 21.45 21.48 21.46 22.34 29.46 29.51 32.65 32.66 32.65

3F 20.04 20.04 20.06 20.04 20.70 21.05 21.07 22.03 22.02 22.02

1F 19.01 19.01 19.02 19.02 19.81 20.12 20.14 20.74 20.73 20.73

3F 28.18 28.18 28.19 28.18 36.89 39.45 39.49 41.42 41.42 41.41

1F 29.80 29.80 29.81 29.80 39.94 43.06 43.09 44.73 44.73 44.73

3F 2.91 2.91 2.91 2.91 2.91 2.91 2.91 2.91 2.91 2.91

1F 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78 1.78

3F 15.89 15.87 15.87 15.87 15.82 16.06 17.52 18.42 18.42 18.42

1F 12.85 12.84 12.84 12.84 12.84 12.95 14.23 14.74 14.74 14.74

3F 6.19 6.19 6.19 6.19 6.52 6.60 6.60 6.65 6.65 6.65

1F 4.12 4.12 4.12 4.12 4.27 4.30 4.30 4.32 4.32 4.32

3F 5.36 5.36 5.42 5.42 5.42 5.43 5.43 5.53 5.53 5.53

1F 4.53 4.53 4.56 4.56 4.56 4.57 4.57 4.62 4.62 4.62

3F 22.35 22.34 22.35 22.35 22.82 23.31 23.67 25.26 25.26 25.26

1F 20.74 20.73 20.73 20.73 21.04 21.32 21.56 22.47 22.47 22.47

3F 19.21 19.20 19.21 19.20 19.42 19.78 20.33 21.51 21.51 21.51

1F 15.25 15.24 15.24 15.24 15.35 15.50 15.83 16.34 16.34 16.34

3F 10.70 10.70 10.71 10.71 10.73 10.96 10.97 11.19 11.19 11.19

1F 9.53 9.56 9.56 9.61 9.62 9.76 9.76 9.88 9.88 9.88

3F 10.37 10.37 10.38 10.38 10.39 10.51 10.51 10.62 10.62 10.62

1F 11.80 11.86 11.86 11.95 11.96 12.07 12.07 12.17 12.17 12.17

3F 10.92 10.92 10.92 11.43 11.44 11.67 11.67 11.74 11.74 11.74

1F 13.21 13.23 13.23 13.78 13.79 14.06 14.06 14.12 14.13 14.13

3F 10.00 10.00 10.01 10.53 10.53 10.58 10.58 10.55 10.55 10.55

1F 8.98 8.98 8.98 9.49 9.49 9.54 9.54 9.51 9.51 9.51

3F 17.93 17.91 17.92 17.92 18.02 18.33 19.10 20.15 20.15 20.15

1F 13.42 13.41 13.41 13.41 13.47 13.58 14.05 14.48 14.48 14.48

3F 26.38 26.38 26.40 25.95 26.03 27.34 27.36 30.02 30.02 30.02

1F 19.70 19.70 19.70 19.36 19.43 20.08 20.09 21.60 21.60 21.60

3F 19.05 19.07 19.08 19.06 21.56 21.82 21.86 22.50 22.15 22.14

1F 18.26 18.27 18.28 18.27 19.95 20.10 20.12 20.93 20.28 20.28

Galvak GVK 115

General Motor de México GMO 115

Frontera FRO

400

230

115

Fuente FUE 138

Fundidora FUN 115

Falcón Mexicano FAM 138

Faro FAR 230

Félix U. Gómez FUG 115

Esperanzas ESP 115

Estanzuela ETZ 115

Estrella ETR 115

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Empalme EML 138

Enertek ETK 115

Escobedo ESC

400

230

115

ÁREA NORESTE

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 239: Catalogo 2011-2020 r010212 Corto Circuito

239

Coordinación de Planificación

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 6.53 6.53 6.53 7.04 7.05 7.07 7.08 7.10 7.10 7.10

1F 5.55 5.55 5.55 5.89 5.89 5.91 5.91 5.92 5.92 5.92

3F 9.93 9.92 9.92 9.92 9.90 10.00 10.54 10.86 10.86 10.86

1F 6.43 6.43 6.43 6.43 6.43 6.45 6.76 6.87 6.87 6.87

3F 10.08 10.08 10.09 10.09 10.00 13.34 13.35 13.36 13.36 13.36

1F 8.10 8.10 8.11 8.11 8.05 10.53 10.57 10.58 10.58 10.58

3F 11.84 11.84 11.84 11.84 11.81 12.90 15.07 15.07 15.07 15.08

1F 12.10 12.10 12.11 12.11 12.07 13.21 14.46 14.46 14.46 14.46

3F 13.17 13.17 13.18 13.33 13.33 13.53 13.53 13.53

1F 12.62 12.62 12.63 12.73 12.73 12.85 12.85 12.85

3F 20.91 20.91 20.91 21.01 21.01 21.15 21.15 21.15

1F 21.09 21.08 21.09 21.16 21.16 21.25 21.25 21.25

3F 6.92 6.92 6.92 6.92 7.34 7.44 7.44 7.50 7.50 7.50

1F 5.10 5.10 5.10 5.10 5.33 5.38 5.38 5.40 5.40 5.40

3F 1.20 1.21 2.10 2.10 2.10 2.12 2.12 2.12 2.41 2.12

1F 0.81 0.82 1.00 1.00 1.00 1.00 1.00 1.00 1.04 1.00

3F 6.55 6.55 6.55 6.55 6.52 6.55 6.55 6.58 6.58 6.58

1F 6.65 6.65 6.65 6.65 6.63 6.65 6.65 6.67 6.67 6.67

3F 1.60 1.60 1.67 1.67 1.67 1.67 1.67 1.67 1.67 1.67

1F 1.05 1.05 1.07 1.07 1.07 1.07 1.07 1.07 1.07 1.07

3F 26.14 26.14 26.21 26.19 26.31 29.06 29.10 33.71 33.72 33.72

1F 30.51 30.51 30.57 30.55 30.87 33.55 33.62 38.51 38.52 38.52

3F 27.70 27.69 27.71 27.69 27.74 25.89 25.92 27.69 27.68 27.68

1F 33.10 33.07 33.09 33.07 33.14 30.44 30.47 32.19 32.19 32.19

3F 42.91

1F 50.03

3F 32.32 32.32 32.31 30.65 30.30 30.33 31.63 31.63 31.63

1F 35.38 35.39 35.38 33.84 33.36 33.39 34.48 34.48 34.47

3F 27.70 27.70 27.69 27.33 23.93 23.96 24.92 24.92 24.92

1F 31.19 31.19 31.19 30.86 26.25 26.27 27.06 27.06 27.06

3F 15.24 15.24 15.25 15.10 15.12 15.56 15.56 16.39 16.39 16.39

1F 9.94 9.94 9.95 9.86 9.88 10.04 10.04 10.41 10.41 10.41

3F 9.91 9.54 9.57 9.57 9.57 9.58 9.58 9.59 9.59 9.59

1F 9.10 8.81 8.83 8.83 8.83 8.83 8.83 8.84 8.84 8.84

3F 14.51 14.53 14.59 14.59 14.59 15.40 15.41 15.23 15.24 15.24

1F 11.03 11.04 11.07 11.07 11.05 11.45 11.45 11.39 11.39 11.39

115

400

138

Güemez GUE

Guerreño GRR

115

HUI-B 115

Industrias Monterrey IMO 115

115

400

230

115

HUI

Huinalá

Huertas HUS 115

Infonavit INV 138

Infonavit INF 115

Huichihuayán HUH

HUI-A

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Granjas GRA 115

Guadalupe GPE 115

400

Hidalgo HID 115

Huejutla HJD 115

ÁREA NORESTE

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 240: Catalogo 2011-2020 r010212 Corto Circuito

240

Coordinación de Planificación

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 11.41 11.40 15.94 15.94 15.95 16.00 16.00 16.08 16.08 16.08

1F 10.47 10.46 14.67 14.67 14.67 14.70 14.70 14.74 14.74 14.74

3F 9.67 5.60 5.64 5.64 5.64 5.64 5.64 5.64 5.64 5.64

1F 8.36 3.99 4.00 4.00 4.00 4.00 4.00 4.00 4.00 4.00

3F 1.40 1.40 1.40 1.40 1.40 1.41 1.43 1.43 1.43 1.43

1F 0.91 0.91 0.91 0.91 0.91 0.91 0.92 0.92 0.92 0.92

3F 11.06 11.05 17.46 17.46 17.46 17.53 17.53 17.62 17.62 17.62

1F 9.56 9.55 16.16 16.16 16.16 16.19 16.20 16.25 16.25 16.25

3F 20.79 20.81 20.85 20.85 20.85 21.06 21.07 22.65 22.66 22.66

1F 16.72 16.73 16.75 16.75 16.73 16.82 16.83 18.56 18.57 18.57

3F 22.50 22.50 22.51 22.33 22.40 23.54 23.55 25.70 25.70 25.70

1F 16.44 16.44 16.44 16.36 16.40 16.97 16.97 18.43 18.43 18.43

3F 17.15 17.15 17.16 17.14 17.99 18.16 18.19 18.51 18.37 18.37

1F 14.49 14.49 14.49 14.49 14.92 15.00 15.01 15.19 15.09 15.09

3F 21.44 19.80 19.79 19.78 15.16 15.07 15.08 15.39 15.39 15.39

1F 15.56 14.59 14.60 14.60 11.19 11.13 11.14 11.25 11.25 11.25

3F 21.92 21.87 21.68 21.68 20.83 21.34 21.57 22.44 22.44 22.44

1F 15.07 15.05 15.07 15.07 14.68 14.94 15.07 15.40 15.40 15.40

3F 1.92 1.92 1.92 1.92 1.91 1.92 1.92 1.92 1.92 1.92

1F 1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.25

3F 8.61 8.61 8.62 8.62 8.62 8.63 8.63 9.82 9.82 9.82

1F 8.05 8.05 8.05 8.05 8.05 8.06 8.06 8.82 8.82 8.82

3F 24.95 24.97 25.03 25.03 25.03 25.36 25.37 26.06 26.07 26.07

1F 21.86 21.88 21.91 21.91 21.88 22.05 22.05 22.96 22.96 22.96

3F 11.53 11.53 11.54 11.53 11.23 11.52 11.53 11.82 11.82 11.82

1F 9.49 9.49 9.49 9.49 9.29 9.33 9.33 9.47 9.47 9.47

3F 8.42 8.42 8.42 8.42 8.37 8.41 8.42 8.46 8.46 8.46

1F 11.07 11.07 11.07 11.07 11.01 11.06 11.06 11.11 11.11 11.11

3F 10.85 10.85 10.86 10.86 10.88 11.33 11.33 11.59 11.59 11.59

1F 7.67 7.67 7.68 7.68 7.71 7.95 7.96 8.05 8.05 8.05

3F 1.26 1.26 1.39 1.39 1.39 1.39 1.39 1.39 1.39 1.39

1F 1.00 1.00 0.92 1.06 1.06 1.06 1.06 1.06 1.06 1.06

3F 18.56 18.56 18.56 18.55 18.60 20.20 20.23 22.21 22.22 22.22

1F 16.45 16.45 16.45 16.45 16.52 18.48 18.50 19.73 19.73 19.73

3F 27.43 27.43 27.43 27.42 27.48 39.84 39.88 43.19 43.20 43.20

1F 26.02 26.02 26.02 26.01 26.07 39.31 39.34 41.76 41.76 41.76115

Lago LAG

Laguna del Conejo LDC

Lajas LAJ

Las Glorias GLO

Lampazos LAM 400

Las Cruces CCX 115

400

138

115

400

115

Kohler Sanimex KOH 115

La Silla SLL 115

Ladrillera LDA 115

FIN 115

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Jarachina JRA 138

Jardín JAD 138

Jiménez JIZ 115

Kemet de México KMT 115

Kimberly Clark (Sal) KYC 115

Juárez JUZ 138

Kaltex Fibers ( Finacril )

ÁREA NORESTE

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 241: Catalogo 2011-2020 r010212 Corto Circuito

241

Coordinación de Planificación

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 16.63 16.64 16.65 16.64 16.64 16.69 16.72 16.71 16.75 16.81

1F 17.33 17.35 17.36 17.34 17.33 17.37 17.39 17.41 17.44 17.48

3F 8.07 8.07 8.09 8.09 8.09 8.10 8.10 8.12 8.12 8.12

1F 7.74 7.74 7.75 7.75 7.75 7.75 7.75 7.76 7.76 7.76

3F 9.81 9.81 9.83 9.83 9.83 9.84 9.84 9.85 9.85 9.85

1F 10.16 10.16 10.17 10.17 10.17 10.18 10.18 10.19 10.19 10.19

3F 16.73 16.73 16.73 16.73 17.94 18.19 18.21 18.83 18.83 18.83

1F 12.09 12.09 12.09 12.09 12.80 12.89 12.91 13.13 13.13 13.13

3F 6.57 6.57 6.57 6.57 6.56 6.88 7.45 7.45 7.45 7.45

1F 5.11 5.11 5.11 5.11 5.11 5.30 5.49 5.49 5.49 5.49

3F 6.32 6.32 6.32 6.32 6.29 6.32 6.32 6.34 6.34 6.34

1F 6.44 6.44 6.44 6.44 6.42 6.43 6.43 6.45 6.45 6.45

3F 1.88 1.88 2.77 2.77 2.77 2.77 2.77 2.76 2.76 2.76

1F 1.39 1.39 1.77 1.92 1.92 1.92 1.92 1.92 1.92 1.92

3F 3.52 3.52 3.52 3.52 3.52 3.52 3.52 3.53 3.53 3.53

1F 2.59 2.59 2.59 2.59 2.59 2.59 2.59 2.60 2.60 2.60

3F 8.86 8.60 8.62 8.62 8.62 8.63 8.63 8.65 8.65 8.65

1F 8.58 8.33 8.34 8.34 8.34 8.35 8.35 8.36 8.36 8.36

3F 10.88 9.93 9.95 9.95 9.95 9.96 9.96 9.97 9.97 9.97

1F 11.02 10.10 10.11 10.11 10.11 10.12 10.12 10.13 10.13 10.13

3F 4.36 4.36 4.36 4.36 4.49 4.50 4.50 4.52 4.52 4.52

1F 2.83 2.83 2.83 2.83 2.88 2.88 2.88 2.89 2.88 2.88

3F 19.18 19.16 19.17 19.17 19.26 19.62 20.61 21.84 21.84 21.84

1F 14.62 14.62 14.62 14.62 14.67 14.81 15.46 15.98 15.98 15.98

3F 1.94 1.94 3.21 3.21 3.21 3.21 3.21 3.21 3.21 3.21

1F 1.39 1.39 2.04 2.16 2.16 2.16 2.16 2.16 2.16 2.16

3F 3.09 3.09 4.76 4.76 4.76 4.76 4.76 4.76 4.76 4.76

1F 1.96 1.96 3.11 3.13 3.13 3.13 3.13 3.13 3.13 3.13

3F 11.34 10.06 10.18 10.18 10.18 10.19 10.19 10.20 10.20 10.20

1F 10.07 8.54 8.60 8.60 8.60 8.61 8.61 8.62 8.62 8.62

3F 11.24 11.21 11.23 11.23 11.23 11.26 11.26 11.28 11.28 11.28

1F 11.26 11.24 11.25 11.25 11.26 11.27 11.27 11.29 11.29 11.29

3F 12.62 12.53 12.60 12.60 12.60 12.62 12.62 12.64 12.64 12.64

1F 14.03 13.90 13.96 13.96 13.96 13.98 13.98 13.99 13.99 13.99

3F 9.28 8.80 8.82 8.82 8.82 8.82 8.82 8.83 8.84 8.84

1F 8.36 7.99 8.00 8.00 8.00 8.01 8.01 8.01 8.01 8.01

138

138

Lauro Villar LVI

Llano Grande LLG

Mante MAN

Manuel MUL

Matamoros Sur MMS

Matamoros Potencia MMP

115

115

Matamoros MTM 138

230

138

Llanos LLS 115

Loma Larga LOL 115

Libramiento LIB 115

Linares LSN 115

230

Leona LEO 115

Libertad (Montemorelos) LBE 115

Libertad (Victoria) LBT 115

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Las Mesas MES 400

230

138

ÁREA NORESTE

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 242: Catalogo 2011-2020 r010212 Corto Circuito

242

Coordinación de Planificación

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 16.54 16.53 16.54 16.54 16.62 16.97 16.99 17.78 17.78 17.78

1F 10.70 10.70 10.71 10.70 10.74 10.87 10.88 11.17 11.17 11.17

3F 14.72 14.72 14.72 14.57 14.59 14.97 14.98 15.53 15.53 15.53

1F 9.95 9.95 9.95 9.89 9.91 10.07 10.07 10.27 10.27 10.27

3F 14.31 14.31 14.32 14.18 14.21 14.59 14.59 15.32 15.32 15.32

1F 9.24 9.24 9.24 9.17 9.18 9.32 9.33 9.64 9.64 9.64

3F 12.95 12.93 13.99 13.99 13.99 14.02 14.03 14.08 14.08 14.08

1F 11.94 11.93 12.53 12.53 12.53 12.55 12.55 12.58 12.58 12.58

3F 10.45 10.45 10.46 10.91 10.91 10.95 10.95 10.88 10.88 10.88

1F 9.27 9.27 9.27 9.64 9.64 9.67 9.67 9.62 9.62 9.62

3F 4.04 4.03 4.09 4.09 4.09 4.10 4.10 4.14 4.14 4.14

1F 2.89 2.89 2.92 2.92 2.92 2.92 2.92 2.93 2.93 2.93

3F 6.96 7.00 7.01 7.01 7.01 7.05 7.06 6.99 6.99 6.99

1F 4.99 5.00 5.03 5.03 5.02 4.59 4.59 4.57 4.57 4.57

3F 20.21 18.74 18.73 18.73 14.53 14.45 14.46 14.75 14.75 14.75

1F 14.41 13.58 13.59 13.58 10.58 10.53 10.54 10.64 10.64 10.64

3F 8.98 8.98 8.98 8.98 9.70 9.87 9.87 9.99 9.99 9.99

1F 5.89 5.89 5.89 5.89 6.19 6.26 6.27 6.30 6.30 6.30

3F 12.22 12.22 12.23 11.44 11.45 11.69 11.69 12.04 12.04 12.04

1F 7.85 7.85 7.86 7.42 7.44 7.53 7.53 7.65 7.65 7.65

3F 0.80 0.80 1.11 1.11 1.11 1.12 1.12 1.12 1.19 1.12

1F 0.55 0.55 0.62 0.62 0.62 0.62 0.62 0.62 0.63 0.62

3F 9.23 9.23 9.23 9.25 9.26 9.35 9.35 9.44 9.44 9.44

1F 9.21 9.36 9.36 9.63 9.64 9.72 9.72 9.78 9.78 9.78

3F 9.10 9.10 9.10 11.13 11.14 11.40 11.40 11.46 11.46 11.46

1F 10.25 10.28 10.28 13.16 13.17 13.47 13.47 13.53 13.53 13.53

3F 1.85 1.85 1.85 1.85 1.85 1.85 1.85 1.86 1.86 1.86

1F 1.21 1.21 1.21 1.21 1.21 1.21 1.21 1.21 1.21 1.21

3F 23.33 23.33 23.38 23.36 23.45 26.70 26.74 31.82 31.82 31.82

1F 24.29 24.29 24.32 24.31 24.62 27.78 27.83 34.14 34.15 34.15

3F 39.56 39.56 39.59 39.05 39.25 42.90 42.95 50.66 50.66 50.66

1F 37.84 37.84 37.86 37.41 37.63 40.77 40.82 50.38 50.38 50.38

3F 39.56 39.56 39.59 39.52 39.72 43.45 43.51 52.61 52.61 52.61

1F 37.84 37.84 37.86 37.81 38.04 41.26 41.30 53.04 53.04 53.04

3F 10.09 10.09 10.09 10.09 11.81 11.89 11.90 12.01 11.98 11.98

1F 7.40 7.41 7.41 7.40 8.45 8.48 8.49 8.53 8.51 8.51

115

115

Montemorelos MTN

MTPB

Morelos MRL

Monterrey Potencia

Monclova MON

115

115

MTP 400

MTPA 115

Modelo MOD 115

Molango MOL 115

230

Minera Autlán MIA 230

Misiones LMS 115

Mitras MIT 115

México MEX 138

Micare MCR 138

Miguel Alemán MIG 138

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Metrorey Cuauhtémoc MCU 115

Metrorey Lincoln MLI 115

Metrorey Munich MUC 115

ÁREA NORESTE

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 243: Catalogo 2011-2020 r010212 Corto Circuito

243

Coordinación de Planificación

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 6.44 6.45 8.80 8.80 8.80 8.82 8.82 8.78 8.78 8.79

1F 5.41 5.42 7.10 7.13 7.14 7.14 7.14 7.13 7.13 7.13

3F 1.96 1.96 1.96 1.96 1.96 1.96 1.96 1.96 1.96 1.96

1F 1.44 1.44 1.44 1.44 1.44 1.44 1.44 1.44 1.44 1.44

3F 4.22 4.22 4.22 4.29 4.29 4.33 4.33 4.34 4.34 4.34

1F 3.15 3.15 3.15 3.18 3.18 3.19 3.19 3.20 3.20 3.20

3F 2.77 2.79 2.90 2.90 2.90 2.93 2.93 2.92 2.93 2.92

1F 1.84 1.85 1.90 1.90 1.90 1.09 1.09 1.09 1.09 1.09

3F 13.98 13.98 13.99 13.99 13.99 14.05 14.05 14.08 14.08 14.08

1F 13.70 13.70 13.71 13.71 13.71 13.76 13.76 13.71 13.71 13.71

3F 10.75 10.75 10.76 10.87 10.87 10.90 10.90 10.47 10.47 10.47

1F 11.31 11.31 11.31 11.40 11.40 11.42 11.42 10.86 10.86 10.86

3F 3.11 3.11 3.11 3.11 3.24 3.24 3.24 3.25 3.25 3.25

1F 1.98 1.98 1.98 1.98 2.04 2.04 2.04 2.04 2.04 2.04

3F 6.63 6.63 6.63 6.26 6.27 6.34 6.34 6.43 6.43 6.43

1F 3.99 3.99 3.99 3.83 3.83 3.85 3.85 3.88 3.88 3.88

3F 18.52 18.54 18.59 18.59 18.59 18.79 18.80 18.68 18.68 18.69

1F 15.70 15.71 15.73 15.73 15.71 15.79 15.80 15.75 15.75 15.75

3F 18.96 18.95 18.96 18.96 19.29 19.47 19.48 19.79 19.79 19.79

1F 18.12 18.12 18.12 18.12 18.33 18.44 18.44 18.63 18.63 18.63

3F 20.85 20.85 20.89 20.87 20.99 24.63 24.67 28.14 28.15 28.15

1F 20.43 20.44 20.46 20.45 20.91 24.90 24.93 27.91 27.91 27.91

3F 41.20 41.21 41.24

1F 41.69 41.69 41.72

3F 33.52 33.62 35.74 35.77 39.23 39.23 39.23

1F 31.86 32.06 33.85 33.88 36.46 36.46 36.46

3F 30.23 30.30 32.01 32.03 34.61 34.62 34.62

1F 28.90 29.07 30.55 30.56 32.46 32.46 32.46

3F 23.41 23.41 23.42 23.41 23.58 24.30 24.34 25.98 25.98 25.98

1F 16.26 16.26 16.26 16.26 16.35 16.65 16.66 17.37 17.37 17.37

3F 8.43 8.42 9.34 9.34 9.34 9.36 9.36 9.39 9.39 9.39

1F 6.52 6.51 6.93 6.93 6.93 6.94 6.94 6.95 6.95 6.95

3F 6.46 6.46 6.46 6.46 6.46 6.48 6.48 6.49 6.49 6.49

1F 6.42 6.42 6.43 6.43 6.43 6.44 6.44 6.45 6.45 6.45

3F 5.51 5.51 5.51 5.51 5.51 5.52 5.52 5.52 5.52 5.52

1F 6.45 6.45 6.45 6.45 6.45 6.46 6.46 6.46 6.46 6.46

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Museo MSO 115

Muzquiz MUZ 115

115

115

115

400

115

115

Nava NAV

230

138

Navidad NVD 115

Navistar (Camiones) NAS 115

230

115

Nadadores

Naranjo

NAD

NRJ

Nicolás

NIC

NICA

Nueva Rosita NUR

NICB 115

Nogalar NOG 115

Norte NRE 138

Negromex NEM 115

Nemak NEK

ÁREA NORESTE

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 244: Catalogo 2011-2020 r010212 Corto Circuito

244

Coordinación de Planificación

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 8.97 8.97 8.97 8.97 8.97 8.99 8.99 10.20 10.20 10.20

1F 8.70 8.70 8.71 8.71 8.71 8.72 8.72 9.54 9.54 9.54

3F 5.65 5.60 5.77 5.77 5.77 5.77 5.77 5.78 5.78 5.78

1F 3.95 3.93 3.99 3.99 3.99 3.99 3.99 3.99 3.99 3.99

3F 7.19 7.19 7.19 7.19 7.18 7.57 8.26 8.26 8.27 8.27

1F 5.76 5.76 5.76 5.76 5.75 5.99 6.24 6.24 6.24 6.24

3F 16.39 16.39 16.39 16.39 17.53 17.77 17.79 18.38 18.38 18.38

1F 11.77 11.77 11.77 11.77 12.43 12.52 12.53 12.74 12.74 12.74

3F 1.72 1.72 1.72 1.72 1.72 1.74 1.77 1.77 1.77 1.77

1F 1.11 1.11 1.11 1.11 1.11 1.12 1.13 1.13 1.13 1.13

3F 7.69 7.69 7.70 7.70 7.70 7.71 7.71 8.61 8.61 8.61

1F 6.82 6.82 6.83 6.83 6.83 6.83 6.83 7.35 7.35 7.35

3F 8.04 8.04 8.04 8.04 8.02 8.51 9.40 9.40 9.40 9.40

1F 6.69 6.69 6.70 6.70 6.69 7.02 7.35 7.35 7.35 7.35

3F 10.62 9.41 9.43 9.43 9.43 9.44 9.44 9.45 9.45 9.45

1F 10.13 8.99 9.00 9.00 9.00 9.01 9.01 9.01 9.01 9.01

3F 19.86 19.86 19.87 19.86 22.40 22.86 22.89 24.15 24.16 24.16

1F 15.74 15.73 15.74 15.74 17.75 17.95 18.00 18.57 18.57 18.57

3F 9.29 9.27 9.84 9.84 9.84 9.86 9.86 9.88 9.88 9.88

1F 7.16 7.15 7.38 7.38 7.38 7.39 7.39 7.39 7.39 7.39

3F 4.09 4.11 4.17 4.17 4.17 4.29 4.29 4.28 4.28 4.28

1F 2.65 2.65 2.68 2.68 2.68 2.13 2.13 2.13 2.13 2.13

3F 12.22 12.22 12.23 11.03 11.04 11.26 11.26 11.57 11.57 11.57

1F 7.85 7.85 7.86 7.25 7.26 7.35 7.35 7.46 7.46 7.46

3F 6.67 6.67 7.17 7.17 7.17 7.79 7.80 7.75 7.84 7.75

1F 4.50 4.50 4.64 4.64 4.64 4.96 4.96 4.94 4.97 4.94

3F 20.01 20.01 20.02 19.76 19.81 20.56 20.57 22.04 22.04 22.04

1F 13.80 13.80 13.80 13.64 13.67 13.99 13.99 14.71 14.71 14.71

3F 16.05 16.06 16.10 16.10 16.10 16.27 16.28 16.17 16.17 16.17

1F 12.72 12.73 12.74 12.74 12.73 12.79 12.79 12.75 12.75 12.75

3F 20.60 20.60 20.61 20.33 20.38 21.18 21.19 22.75 22.75 22.75

1F 14.30 14.30 14.31 14.13 14.16 14.50 14.51 15.28 15.28 15.28

3F 7.02 6.99 15.54 15.54 15.54 15.59 15.59 15.65 15.65 15.65

1F 5.29 5.28 12.92 12.92 12.92 12.94 12.94 12.97 12.97 12.97

3F 40.40 40.38 40.41 40.38 41.16 43.03 43.17 48.88 48.89 48.89

1F 33.99 33.99 34.00 33.99 34.51 35.63 35.71 39.56 39.56 39.56

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Nuevo Laredo NUL 138

Nuevo Progreso NVP 138

Nuevo Santander NST 115

Nylon de México S.A. NYL 115

Obra de Toma OBT 115

Ojo Caliente OJC 138

Pánuco PAN 115

Olivo OVO 115

Oriente II OTE 138

Orión ORN 115

Parque Industrial PAI 138

Pemex PEM 115

Orizatlán ORZ

Ozuluama OZL

Papalera Maldonado PAM 115

Papeles Higiénicos PPI 115

Papeles Higiénicos PHI 115

138

115

P. Ind. Escobedo PIE 115

ÁREA NORESTE

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 245: Catalogo 2011-2020 r010212 Corto Circuito

245

Coordinación de Planificación

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 6.05 6.05 7.12 7.12 7.12 7.13 7.13 7.15 7.15 7.15

1F 4.45 4.45 5.06 5.06 5.06 5.07 5.07 5.07 5.07 5.07

3F 2.66 2.68 2.78 2.78 2.78 2.80 2.80 2.80 2.80 2.80

1F 1.76 1.77 1.81 1.81 1.81 1.07 1.07 1.07 1.07 1.07

3F 14.36 14.36 14.36 14.36 14.82 14.97 14.97 15.27 15.27 15.27

1F 10.43 10.43 10.43 10.43 10.65 10.70 10.71 10.81 10.81 10.81

3F 9.51 9.51 9.51 9.51 9.51 9.35 9.35 9.53 9.53 9.53

1F 7.98 7.97 7.98 7.98 7.98 7.88 7.88 7.97 7.97 7.97

3F 14.26 14.27 14.31 14.30 14.31 14.63 14.63 14.54 14.54 14.54

1F 8.88 8.88 8.89 8.89 8.88 9.00 9.00 8.98 8.98 8.98

3F 4.29 4.26 4.27 4.26 4.36 4.38 4.41 4.45 4.45 4.45

1F 2.65 2.65 2.65 2.64 2.74 2.75 2.76 2.77 2.76 2.77

3F 12.07 12.07 12.07 12.07 12.08 13.83 13.83 14.19 14.19 14.19

1F 8.75 8.75 8.75 8.75 8.76 9.77 9.77 9.91 9.91 9.91

3F 19.70 19.72 19.76 19.75 19.76 19.95 19.96 20.39 20.40 20.40

1F 15.74 15.75 15.76 15.76 15.75 15.83 15.84 16.30 16.30 16.30

3F 13.00 12.97 14.87 14.87 14.88 14.92 14.92 15.00 15.00 15.00

1F 11.36 11.35 12.43 12.43 12.43 12.45 12.45 12.48 12.48 12.48

3F 9.22 9.22 9.22 10.26 10.26 10.31 10.31 10.28 10.29 10.29

1F 7.81 7.81 7.81 9.22 9.22 9.26 9.26 9.25 9.25 9.25

3F 8.03 8.03 8.04 8.04 8.04 10.81 10.81 10.83 10.83 10.83

1F 7.18 7.18 7.18 7.18 7.18 9.88 9.88 9.89 9.89 9.89

3F 11.15 11.15 11.15 11.15 11.15 12.11 12.11 12.09 12.09 12.09

1F 11.04 11.04 11.05 11.05 11.05 12.29 12.29 12.27 12.27 12.27

3F 5.86 5.86 5.87 5.86 5.87 6.28 6.28 6.36 6.36 6.36

1F 3.71 3.71 3.71 3.71 3.71 3.90 3.90 3.92 3.92 3.92

3F 9.69 6.85 6.91 6.91 6.91 6.91 6.91 6.92 6.92 6.92

1F 8.16 5.11 5.13 5.13 5.13 5.13 5.13 5.13 5.13 5.13

3F 16.41 16.40 16.43 16.42 16.47 17.46 17.54 21.68 21.69 21.69

1F 16.00 16.00 16.01 16.00 16.47 17.14 17.62 21.07 21.08 21.08

3F 30.36 30.34 30.36 30.35 31.22 32.16 32.84 35.99 36.00 36.00

1F 36.95 36.92 36.94 36.93 37.94 38.86 39.65 42.86 42.86 42.86

3F 24.10 24.13 24.22 24.22 24.22 24.52 24.53 24.36 24.37 24.37

1F 24.13 24.15 24.21 24.21 24.15 24.32 24.34 24.25 24.26 24.26

3F 17.13 17.14 17.20 17.20 17.20 17.83 17.84 17.70 17.71 17.71

1F 11.64 11.64 11.66 11.66 11.65 11.92 11.92 11.89 11.89 11.89

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Pemex Criogenica PXC 138

Pemex Naranjos NRJ 115

Pemex Pta. Satélite PSP 115

Pemex Cadereyta PCD 230

Pemex Refinería Madero RMA 115

Peñasquito PQO 400

Pesquería PQA 115

Petrocel S.A. PTC 115

Petrolera PER 138

Pimsa PMA 115

Planta II PTA 138

400

Piedras Negras PNE 138

230

138

Piedras Negras Potencia PNG

115

Policyd PLC 115

Polvorín POL 115

Plaza PZA

ÁREA NORESTE

_______Catálogo de Corto Circuito 2011-2020_____ _____

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

Page 246: Catalogo 2011-2020 r010212 Corto Circuito

246

Coordinación de Planificación

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 17.56 17.56 17.57 17.56 17.66 18.06 18.08 18.97 18.97 18.97

1F 11.49 11.49 11.49 11.49 11.53 11.68 11.69 12.03 12.03 12.03

3F 6.09 6.09 6.10 6.10 6.10 6.05 6.05 6.11 6.11 6.11

1F 5.40 5.40 5.41 5.41 5.41 5.38 5.38 5.41 5.41 5.41

3F 5.64 5.64 5.64 5.64 5.64 5.62 5.62 5.65 5.65 5.65

1F 6.35 6.35 6.36 6.36 6.36 6.34 6.34 6.36 6.36 6.36

3F 22.77 22.79 22.84 22.84 22.84 23.10 23.12 24.25 24.26 24.26

1F 19.05 19.06 19.08 19.08 19.06 19.18 19.19 20.53 20.53 20.53

3F 7.68 7.68 7.68 7.19 7.20 7.29 7.29 7.42 7.42 7.42

1F 4.67 4.67 4.67 4.45 4.46 4.49 4.49 4.53 4.53 4.53

3F 20.84 20.84 20.85 20.75 20.79 21.83 21.84 23.44 23.44 23.44

1F 14.71 14.71 14.71 14.67 14.70 15.19 15.20 16.09 16.09 16.09

3F 7.56 7.56 7.56 7.56 7.57 8.27 8.27 8.41 8.41 8.41

1F 4.97 4.97 4.97 4.97 4.97 5.31 5.31 5.35 5.35 5.35

3F 8.99 8.99 8.99 9.49 9.49 9.54 9.54 9.52 9.52 9.52

1F 7.81 7.81 7.81 8.29 8.29 8.32 8.32 8.31 8.31 8.31

3F 31.39 31.44 31.48 31.47 31.47 32.08 32.14 30.69 30.72 30.74

1F 35.62 35.66 35.71 35.70 35.54 36.07 36.13 34.90 34.93 34.95

3F 29.05 29.07 29.11 29.11 29.11 29.40 29.42 29.65 29.67 29.67

1F 28.90 28.92 28.95 28.95 28.92 29.11 29.12 29.50 29.51 29.51

3F 8.70 7.93 8.00 8.00 8.00 8.01 8.01 8.02 8.02 8.02

1F 6.94 6.19 6.22 6.22 6.22 6.22 6.22 6.22 6.22 6.22

3F 20.50 20.56 20.57 20.55 22.69 22.98 23.02 23.80 23.33 23.33

1F 19.80 19.88 19.88 19.87 21.29 21.45 21.48 22.43 21.66 21.66

3F 16.71 16.71 16.75 16.72 17.11 17.90 18.01 18.91 18.92 18.91

1F 14.72 14.74 14.76 14.74 15.55 16.02 16.09 16.60 16.57 16.57

3F 27.55 27.56 27.58 27.54 29.81 30.28 30.35 31.27 30.87 30.87

1F 30.97 30.99 31.01 30.98 33.03 33.42 33.48 34.42 33.91 33.90

3F 2.01 2.01 2.20 2.20 2.20 2.20 2.20 2.19 2.19 2.19

1F 1.34 1.34 1.42 1.43 1.43 1.43 1.43 1.42 1.42 1.42

3F 14.43 14.44 14.47 14.47 14.47 14.81 14.81 14.71 14.72 14.72

1F 8.99 8.99 9.00 9.00 8.99 9.12 9.12 9.09 9.10 9.10

3F 6.98 6.98 6.98 7.39 7.39 7.43 7.43 7.45 7.45 7.45

1F 6.06 6.06 6.06 6.33 6.33 6.35 6.35 6.36 6.36 6.36

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Praxiar PAX 115

Presa El Cuchillo PCU

230

115

Primex PNX 115

Prolamsa POM 115

Prolec PLE 115

Pta. de Tratamiento de Aguas ResidualesRNE 115

Ramos Arizpe RRA 115

400

115

Ramos Arizpe Potencia RAP

Puente Internacional PUI 138

Puerto Altamira PAE

400

115

Química Fluor QFL 138

Rayón RAY 115

115

115

Refinería Madero RMA

Regidores REG

ÁREA NORESTE

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 247: Catalogo 2011-2020 r010212 Corto Circuito

247

Coordinación de Planificación

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 13.72 19.46 19.49 21.02 21.02 21.02

1F 11.51 16.94 16.96 17.80 17.80 17.80

3F 28.42 30.03 30.24 31.50 31.50 31.50

1F 26.05 28.06 28.22 28.98 28.98 28.98

3F 13.37 13.35 15.82 15.82 15.82 15.87 15.88 15.96 15.96 15.96

1F 12.45 12.44 14.05 14.05 14.06 14.08 14.08 14.13 14.13 14.13

3F 11.39 11.38 13.05 13.05 13.06 13.09 13.09 13.14 13.14 13.14

1F 10.03 10.03 11.00 11.00 11.01 11.02 11.02 11.05 11.05 11.05

3F 18.36 18.36 18.36 18.36 18.48 18.89 18.92 19.91 19.91 19.91

1F 12.08 12.08 12.08 12.08 12.13 12.29 12.29 12.69 12.69 12.69

3F 23.78 23.77 23.78 23.77 25.27 25.87 26.08 27.90 27.90 27.90

1F 20.57 20.56 20.57 20.57 21.69 21.98 22.13 23.05 23.05 23.05

3F 14.32 14.31 14.81 14.81 14.81 14.86 14.86 14.94 14.94 14.94

1F 15.48 15.47 15.88 15.87 15.88 15.92 15.92 15.98 15.98 15.98

3F 16.16 15.99 17.93 17.93 17.93 17.97 17.97 18.02 18.02 18.02

1F 18.21 18.05 19.82 19.82 19.82 19.85 19.85 19.90 19.90 19.90

3F 9.21 9.16 11.69 11.69 11.69 11.71 11.71 11.74 11.74 11.74

1F 7.54 7.51 9.34 9.34 9.34 9.35 9.35 9.36 9.36 9.36

3F 20.51 20.51 20.57 20.57 20.58 20.86 20.87 21.10 21.12 21.12

1F 23.61 23.61 23.67 23.67 23.68 23.93 23.93 24.18 24.20 24.20

3F 19.71 19.70 19.72 19.72 19.73 19.85 19.85 19.94 19.95 19.95

1F 24.36 24.36 24.38 24.40 24.40 24.53 24.53 24.62 24.63 24.63

3F 13.33 13.33 13.34 13.23 13.23 13.27 13.28 13.16 13.16 13.16

1F 15.25 15.25 15.25 15.10 15.10 15.14 15.14 15.02 15.02 15.02

3F 3.87 3.87 3.89 3.89 3.89 3.89 3.89 3.98 3.98 3.98

1F 2.78 2.78 2.79 2.79 2.79 2.79 2.79 2.82 2.82 2.82

3F 1.89 1.89 2.05 2.05 2.05 2.05 2.05 2.05 2.05 2.05

1F 1.25 1.25 1.32 1.33 1.33 1.33 1.33 1.33 1.33 1.33

3F 4.59 4.59 4.59 4.59 4.59 4.59 4.59 4.60 4.60 4.60

1F 4.63 4.63 4.63 4.63 4.63 4.63 4.63 4.64 4.64 4.64

3F 1.43 1.43 1.43 1.43 1.43 1.45 1.45 1.45 1.45 1.45

1F 0.96 0.96 0.96 0.96 0.96 0.98 0.98 0.98 0.98 0.98

3F 22.23 22.21 22.22 22.22 22.68 23.17 23.52 25.10 25.10 25.10

1F 20.54 20.53 20.54 20.53 20.84 21.11 21.34 22.24 22.24 22.24

3F 3.94 3.94 3.94 3.94 3.93 3.94 3.94 3.95 3.95 3.95

1F 3.37 3.37 3.37 3.37 3.36 3.37 3.37 3.37 3.37 3.37

400RGMRegiomontano

Riel RIE 115

Río RIO 115

230

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

115

Reynosa REY 138

Reynosa Centro RYC 138

RIBRío Bravo

230

138

Río Salado SDO 138

138

Río Bravo Pte. RBP 138

400

Río Escondido REC

Río Verde RVE 115

Sabinas SAB 115

Sabinas Hidalgo SAH 115

Sabino SSB 115

Salitrillo SLT 115

ÁREA NORESTE

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 248: Catalogo 2011-2020 r010212 Corto Circuito

248

Coordinación de Planificación

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 10.85 10.86 10.86 10.84 11.82 11.98 12.00 12.36 12.18 12.18

1F 10.44 10.45 10.45 10.44 11.21 11.31 11.32 11.74 11.43 11.43

3F 19.78 19.80 19.81 19.78 24.42 24.75 24.80 25.25 25.18 25.17

1F 21.22 21.23 21.24 21.22 25.54 25.79 25.82 26.39 26.09 26.09

3F 23.01 22.99 23.01 23.00 23.37 23.89 24.53 26.26 26.26 26.26

1F 20.46 20.45 20.46 20.45 20.69 20.96 21.40 22.33 22.33 22.33

3F 7.26 7.26 7.26 7.26 7.73 7.83 7.84 7.91 7.91 7.91

1F 4.61 4.61 4.61 4.61 4.79 4.84 4.84 4.86 4.86 4.86

3F 0.76 0.76 0.76 0.76 0.76 0.77 0.78 0.78 0.78 0.78

1F 0.52 0.52 0.52 0.52 0.52 0.52 0.52 0.52 0.52 0.52

3F 16.78 16.78 16.80 16.79 16.92 17.97 18.04 21.47 21.48 21.48

1F 16.19 16.18 16.20 16.19 17.01 17.74 18.03 20.68 20.68 20.68

3F 29.38 29.37 29.38 29.37 35.28 36.43 36.51 39.83 39.84 39.84

1F 29.17 29.16 29.18 29.17 36.96 37.82 38.05 40.70 40.70 40.70

3F 9.60 9.60 9.60 9.60 9.61 9.77 9.78 10.01 10.01 10.01

1F 6.10 6.10 6.10 6.10 6.11 6.17 6.17 6.25 6.25 6.25

3F 4.58 4.56 4.56 4.55 3.78 3.77 3.78 3.79 3.79 3.79

1F 2.68 2.67 2.67 2.67 2.25 2.25 2.25 2.26 2.26 2.26

3F 1.20 1.20 1.20 1.20 1.22 1.22 1.22 1.22 1.22 1.22

1F 0.76 0.76 0.76 0.76 0.77 0.77 0.77 0.77 0.77 0.77

3F 26.10 26.09 26.04 26.03 25.65 26.34 26.77 28.25 28.26 28.26

1F 18.53 18.53 18.55 18.55 18.36 18.68 18.93 19.53 19.53 19.53

3F 7.10 7.10 7.10 7.10 7.15 7.18 7.18 7.22 7.22 7.22

1F 4.71 4.71 4.71 4.71 4.73 4.73 4.73 4.75 4.75 4.75

3F 31.03 31.03 31.05 30.43 30.54 32.36 32.40 36.19 36.19 36.19

1F 24.65 24.65 24.66 24.14 24.23 25.26 25.28 27.71 27.71 27.71

3F 9.54 9.30 9.29 9.29 6.47 6.26 6.26 6.32 6.32 6.32

1F 5.86 5.78 5.78 5.78 4.10 4.01 4.01 4.02 4.02 4.02

3F 9.77 9.24 9.32 9.32 9.32 9.33 9.33 9.34 9.34 9.34

1F 8.41 7.82 7.86 7.86 7.86 7.86 7.86 7.87 7.87 7.87

3F 8.24 8.24 8.24 8.24 8.85 8.99 8.99 9.09 9.09 9.09

1F 5.33 5.33 5.33 5.33 5.58 5.63 5.64 5.66 5.66 5.66

3F 25.80 25.80 25.82 25.59 25.67 27.18 27.21 30.11 30.11 30.11

1F 19.76 19.76 19.76 19.64 19.70 20.52 20.54 22.71 22.71 22.71

3F 13.28 13.29 13.37 13.37 13.37 14.25 14.26 14.14 14.15 14.14

1F 9.07 9.07 9.09 9.09 9.08 9.51 9.52 9.49 9.49 9.49

San Bernabé BER 115

San Fernando FND 115

400

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

230

115

San Agustín AUS 115

Saltillo SAL

115

San Jorge JOR 115

San Juan JAN 115

San Jerónimo Potencia JEP

San Roberto ROB 115

San Roque ROQ 115

Santa Catarina CAT 115

Santo Domingo DON 115

San Marcos MCO 115

Sendero Nacional SEN 138

Solidaridad SRD 115

Sto.Domingo Viejo DVP 115

Tamaulipas TAM 115

ÁREA NORESTE

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 249: Catalogo 2011-2020 r010212 Corto Circuito

249

Coordinación de Planificación

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 1.19 1.19 1.24 1.24 1.24 1.24 1.24 1.24 1.24 1.24

1F 0.78 0.78 0.80 0.80 0.80 0.80 0.80 0.80 0.80 0.80

3F 2.59 2.59 2.90 2.90 2.90 2.90 2.90 2.89 2.89 2.90

1F 1.76 1.76 1.91 1.91 1.91 1.91 1.91 1.91 1.91 1.91

3F 20.85 20.92 20.98 20.97 20.98 21.38 21.48 19.83 19.87 19.88

1F 17.37 17.41 17.46 17.46 16.63 16.00 16.04 15.40 15.42 15.42

3F 19.59 19.63 20.04 20.04 20.04 26.54 26.58 25.99 26.06 26.01

1F 17.38 17.40 17.62 17.62 17.50 23.52 23.54 23.23 23.27 23.24

3F 13.04 13.08 13.10 13.10 13.10 13.27 13.28 13.01 13.02 13.02

1F 11.88 11.90 11.92 11.92 11.88 11.76 11.76 11.62 11.62 11.62

3F 23.96 24.01 24.10 24.10 24.10 25.00 25.02 24.59 24.60 24.60

1F 24.58 24.62 24.69 24.69 24.64 25.17 25.19 24.89 24.90 24.90

3F 14.68 14.68 14.68 14.68 16.02 16.25 16.27 16.90 16.90 16.90

1F 10.48 10.47 10.48 10.48 11.33 11.41 11.43 11.66 11.66 11.66

3F 14.80 14.82 14.88 14.88 14.88 15.60 15.60 15.43 15.43 15.43

1F 11.41 11.42 11.44 11.44 11.42 11.77 11.77 11.70 11.71 11.71

3F 16.18 16.17 16.20 16.18 16.21 17.16 17.32 22.49 22.49 22.49

1F 15.36 15.35 15.37 15.36 15.64 16.24 17.08 21.85 21.86 21.86

3F 30.12 30.05 30.06 30.05 29.89 30.76 36.60 40.77 40.77 40.77

1F 29.14 29.09 29.10 29.09 29.07 29.64 37.48 41.22 41.22 41.22

3F 1.36 1.37 2.17 2.17 2.17 2.20 2.20 2.19 3.07 2.19

1F 0.27 0.27 0.74 0.74 0.74 0.74 0.74 0.74 0.78 0.74

3F 5.18 5.18 5.18 5.18 5.18 5.37 5.70 5.70 5.70 5.70

1F 3.77 3.77 3.77 3.77 3.77 3.87 3.96 3.96 3.96 3.97

3F 23.82 23.82 23.83 22.63 22.69 23.57 23.59 25.00 25.00 25.00

1F 17.48 17.48 17.49 16.73 16.79 17.23 17.24 17.86 17.86 17.86

3F 11.98 11.99 12.01 12.01 12.01 12.28 12.28 12.20 12.20 12.20

1F 8.22 8.23 8.24 8.24 8.23 8.33 8.33 8.31 8.31 8.31

3F 14.43 14.43 14.43 14.43 14.45 14.82 14.83 15.37 15.37 15.37

1F 9.87 9.87 9.87 9.87 9.89 10.05 10.05 10.26 10.26 10.26

3F 5.78 5.78 6.01 6.01 6.01 6.02 6.02 6.06 6.06 6.06

1F 4.10 4.10 4.18 4.18 4.18 4.19 4.19 4.20 4.20 4.20

3F 21.67 21.66 21.67 21.67 22.93 23.42 23.59 25.07 25.07 25.07

1F 17.84 17.84 17.84 17.84 18.70 18.92 19.02 19.70 19.70 19.70

3F 8.30 8.31 10.98 10.98 10.98 11.00 11.01 10.95 10.95 10.95

1F 7.90 7.90 9.67 9.75 9.75 9.76 9.77 9.74 9.74 9.74

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Tamazunchale TZE 115

Tambaca TBC 115

400

Tampiquito TPQ 115

Tancol TCL 115

400

115

230

115

Tamos TMS

Tampico TPC

115

Tempoal TED 115

Tierra Nueva TNV 115

Tecnológico TEC

Topochico THO 115

Universidad UNIT 115

Universidad UNI 115

Valadeces VDL 138

Valle VLL 115

Valle Alto VAL 115

ÁREA NORESTE

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 250: Catalogo 2011-2020 r010212 Corto Circuito

250

Coordinación de Planificación

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 3.74 3.68 3.72 3.72 3.72 3.73 3.73 3.73 3.73 3.73

1F 2.46 2.42 2.44 2.44 2.44 2.44 2.44 2.44 2.44 2.44

3F 29.73 29.70 29.72 29.71 30.55 31.45 32.09 35.10 35.11 35.10

1F 35.30 35.28 35.30 35.29 36.20 37.04 37.76 40.65 40.66 40.66

3F 24.67 24.02 24.03 24.02 24.21 24.47 24.50 25.82 25.82 25.82

1F 17.58 17.20 17.20 17.20 17.31 17.40 17.41 17.98 17.98 17.98

3F 8.24 8.25 10.88 10.88 10.88 10.90 10.91 10.85 10.85 10.85

1F 7.79 7.79 9.56 9.61 9.61 9.62 9.63 9.60 9.60 9.60

3F 16.54 16.53 16.54 16.54 16.62 16.97 16.99 17.78 17.78 17.78

1F 10.70 10.70 10.71 10.70 10.74 10.87 10.88 11.17 11.17 11.17

3F 2.31 2.31 2.31 2.31 2.31 2.35 2.41 2.41 2.41 2.41

1F 1.52 1.52 1.52 1.52 1.51 1.53 1.54 1.54 1.54 1.54

3F 22.89 22.89 22.95 22.91 23.13 25.30 25.39 27.93 27.95 27.94

1F 23.04 23.05 23.09 23.07 23.54 25.31 25.41 27.16 27.15 27.15

3F 21.90 21.90 21.93 21.90 22.27 23.05 23.09 24.20 24.13 24.12

1F 24.53 24.53 24.55 24.53 24.93 25.67 25.71 26.66 26.58 26.58

3F 23.33 23.33 23.34 23.34 23.91 24.21 24.22 24.76 24.76 24.76

1F 27.41 27.40 27.41 27.41 27.96 28.25 28.26 28.75 28.75 28.75

3F 3.27 3.27 3.27 3.27 3.26 3.27 3.32 3.35 3.35 3.35

1F 2.31 2.31 2.31 2.31 2.31 2.31 2.35 2.36 2.36 2.36

3F 16.10 16.09 16.10 16.10 16.30 16.41 16.41 16.60 16.60 16.60

1F 14.18 14.18 14.18 14.18 14.28 14.34 14.34 14.44 14.44 14.44

3F 15.56 15.56 15.57 15.57 15.76 15.86 15.86 16.04 16.04 16.04

1F 13.45 13.45 13.45 13.45 13.55 13.60 13.60 13.68 13.68 13.68

3F 1.31 1.31 1.79 1.79 1.79 1.79 1.79 1.79 1.79 1.79

1F 0.90 0.90 1.13 1.16 1.16 1.16 1.16 1.16 1.16 1.16

3F 7.40 7.40 7.40 8.43 8.44 8.52 8.53 8.56 8.56 8.56

1F 6.90 6.91 6.91 7.83 7.84 7.90 7.90 7.92 7.92 7.92

3F 11.38 11.38 11.38 11.37 12.57 12.65 12.67 12.79 12.76 12.76

1F 8.71 8.72 8.72 8.71 9.30 9.33 9.33 9.40 9.37 9.37

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Valle Hermoso VHE 138

Valle Oriente VOT 115

Valle Soleado VSL 115

400

230

115

Villa de García VDG

Valles VES 115

Vidriera Monterrey VMO 115

Villa de Casas VDC 115

Villa de Santiago VDS 115

Vitro Flotado S.A. VIF 115

Vitroflex S.A. VFL 115

Xicotencatl XIC 115

Xochipilli XOC 115

Zapaliname ZPL 115

ÁREA NORESTE

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____

Page 251: Catalogo 2011-2020 r010212 Corto Circuito

251

Coordinación de Planificación

ÁREA BAJA CALIFORNIA

ESTUDIO DE CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____

_______

Page 252: Catalogo 2011-2020 r010212 Corto Circuito

252

Coordinación de Planificación

ÁREA BAJA CALIFORNIA

SUBDIRECCIÓN DE PROGRAMACIÓN

COORDINACIÓN DE PLANIFICACIÓN

RED ELÉCTRICA PRINCIPAL

ÁREA BAJA CALIFORNIA NORTE

2011

Ciprés

Lomas

El Rubí

Panamericana

Tijuana I

RumorosaHerradura

Toyota

Metrópoli

1 x 150 MW

2 x 248 MW

2 x 160 MW

2 x 30 MW

Rosita

CCM489 MW

Wisteria

Orizaba

Packard

Aeropuerto II

Cetys

Mexicali Oriente

González

Tecnológico

Taboada

Mexicali II

Ruíz

Hidalgo

Parque IndSan Luis

OPera

ció

n inic

ial en 161 k

V

100 MW

220 MW

2 x 37.5 MW

1 x 30 MW

Río Nuevo

Centro

Santa

Chapultepec

Imperial Valley(E.U.A.)

Miguel

Potencia

Siderúrgica

Potencia

(E.U.A.)

277 MW

CerroPrieto IV

CerroPrieto I

CerroPrieto II

CerroPrieto III

Ais

lada e

n 2

30 k

V

Ortega II

Isabel

Sánchez

JuárezPresidente

TDM625 MW

Intergen470MW

Xochimilco

Nacozari

Cortines

1 x 225 MVA230/115 kV

1 x 225 MVA230/69 kV

2 x 100 MVA230/69 kV

3 x 100 MVA230/69 kV

2 x 100 MVA230/69 kV

1 x 225 MVA230/69 kV 1 x 225 MVA

230/161 kV

2 x 100 MVA230/161 kV

1 x 225 MVA230/161 kV

1 x 100 MVA230/161 kV

1 x 225 MVA

230/161 kV

220 MW

INFORMACIÓN RESERVADA DEACUERDO CON LA LEY FEDERAL DETRANSPARENCIA Y ACCESO A LA

INFORMACIÓN PÚBLICAGUBERNAMENTAL

RED ELÉCTRICA PRINCIPAL 2011

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 253: Catalogo 2011-2020 r010212 Corto Circuito

253

Coordinación de Planificación

ÁREA BAJA CALIFORNIA

SUBDIRECCIÓN DE PROGRAMACIÓN

COORDINACIÓN DE PLANIFICACIÓN

El Rubí1 x 225 MVA230/69 kV

Panamericana

2 x 100 MVA230/69 kV

Tijuana I

Rumorosa1 x 100 MVA

230/69 kV

Herradura2 x 225 MVA

230/115 KV

Toyota

Metrópoli

Presidente Juárez

La Rosita1 x 225 MVA230/161 kV

CC Mexicali489 MW

Wisteria2 x 40 MVA230/13.8 kV

Orizaba

21 MVAR

Packard2 x 40 MVA161/13.8 kV

2 x 40 MVA161/13.8 kV

Nacozari

Aeropuerto2 x 40 MVA230/13.8 kV

Cetys1 x 100 MVA 230/161 kV2 x 40MVA 230/13.8 kV1 x 40MVA 161/34.5 kV

Mexicali Oriente2 x 40 MVA 161/13.8 kV1 x 50MVA 161/34.5 kV

González Ortega II2 x 40 MVA 161/13.8 kV1 x 50 MVA 161/34.5 kV

Tecnológico2 x 50 MVA230/34.5 kV2 x 40 MVA230/13.8 kV

S. Taboada2 x 40 MVA230/13.8 kV

Mexicali II3 x 100 MVA230/161 kV1 x 40 MVA230/13.8 kV3 x 37.5 MVA161/34.5 kV1x 26 MW2 x18 MW

21 MVAR

Ruíz Cortines2 x 75 MVA

31.5 MVAR

Hidalgo1 x 40MVA1 x 30MVA

P.Ind.S.Luis2 x 50 MVA

230/161/34.5 kV1 x 225 MVA230/161 kV

Ais

lada E

n 2

30 k

V

Opera

ción I

nic

ial 161 k

V

CerroPrieto IV

100 MW

220 MW

220 MW

Cerro Prieto I2 x 37.5 MW1 x 30 MW1 x 30 MVA161/13.8 kV

INFORMACIÓN RESERVADA DEACUERDO CON LA LEY FEDERAL DETRANSPARENCIA Y ACCESO A LA

INFORMACIÓN PÚBLICAGUBERNAMENTAL

Río Nuevo1 x 30 MVA161/13.8 kV1 x 40 MVA161/13.8 kV

RED ELÉCTRICA PRINCIPAL

ÁREA BAJA CALIFORNIA NORTE

2020

Centro1 x 225 MVA230/161 kV2 x 40 MVA161/13.8 kV2 x 38 MVA161/34.5 kV

Santa Isabel2 x 40MVA 161/13.8 kV1 x 50MVA 161/34.5 kV

161/34.5 kV

Chapultepec2 x 50 MVA230/34.5 kV

161/13.8 kV

Imperial Valley

(E.U.A.)

Otay

Potencia

Siderúrgica

Potencia

(E.U.A.)

1 X 40 MVA

230/13.8 kV

2 x 40MVA230/13.8 kV

1 x 50 MVA

Cerro Prieto V

2 x 40 MVA230/13.8 kV

2 x 40 MVA161/13.8 kV

2 x 40 MVA230/13.8 kV

Xochimilco

Centenario

Carranza

Valle de Puebla

CerroPrieto II

CerroPrieto III

100 MW

San Luis Rey

1 x 40 MVA161/13.8 kV

1 x 225 MVA230/115 kV

2 x 40 MVA230/13.8 kV

Cachanilla

EstaciónAsíncrona

300 MWCucapah

A Seis de Abril(Zona Caborca)

Ciprés2 x 100 MVA230/115 kVLomas

1 x 100 MVA230/115 kV

1 x 225 MVA230/115 kV

BC III294 MW

1 x 40 MVA161/34.5 kV

Cañón1 x 100 MVA230/115 kV

200/-75 MVARCEV

BC IV565 MW

Tend. Primer Circuito

Operació

n Inic

ial 2

30 kV

Rumorosa I,II,III300 MW

Santa Isabel

230/161 kV225 MVA

1 x 150 MW

2 x 248 MW

2 x 160 MW2 x 30 MW

277 MW

1 x 225 MVA230/115 kV

Potencia

2 x 375 MVA400/230 KV

1 x 375 MVA400/230 KV

TDM625 MW

Intergen470MW

RED ELÉCTRICA PRINCIPAL 2020

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 254: Catalogo 2011-2020 r010212 Corto Circuito

254

Coordinación de Planificación

ÁREA BAJA CALIFORNIA

ADICIONES:

Nombre de la Central Año Capacidad

Baja California II Fase I (TG) 2013 124 MW

Baja California III (CC) 2013 294 MW

Baja California II (CC) 2014 276 MW

Rumorosa I y II (EO) 2014 200 MW

Rumorosa III (EO) 2015 100 MW

Mexicali (GEO) 2017 100 MW

Baja California IV (CC) 2019 565 MW

RETIROS:

Nombre de la Central Año Capacidad

Cerro Prieto I (GEO) U3 2012 37.5 MW

Mexicali (DTG) U1, U2 y U3 2014 62 MW

Cerro Prieto I (GEO) U4 2014 37.5 MW

Tijuana 1 y 2 (TG) 2017 60 MW

ADICIONES Y RETIROS DE GENERACIÓN

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 255: Catalogo 2011-2020 r010212 Corto Circuito

255

Coordinación de Planificación

La corriente de corto circuito en las subestaciones Imperial Valley y Otay Mesa que forman parte del sistema eléctrico

de Estados Unidos de América (EUA) es de 32 y 29 kA para el 2011 respectivamente, mientras que en Tijuana I y La

Rosita presentan valores de 29 kA y 30 kA respectivamente, sin embargo, el equivalente utilizado para el WECC en

este estudio es el proporcionado por SDG&E en 2003, este equivalente se mantuvo constante durante todo el periodo

de planificación por lo que estos valores se incrementarán considerablemente a través de los años, ya que se han

programado un número considerable de proyectos de generación en la zona fronteriza, impactando los niveles de corto

circuito en el sistema eléctrico de Baja California, principalmente en las subestaciones de Tijuana I y La Rosita.

Se realizó una sensitividad considerando una interconexión asíncrona (separación mediante dispositivos BtB) entre el

área Baja California y el sistema del WECC y se observa que los niveles de corto circuito en las subestaciones

disminuyen considerablemente a 16 kA en Tijuana I , 20 kA en Presidente Juárez y 18 kA en La Rosita.

En la zona Tijuana se tiene una gran concentración de generación en la Central Presidente Juárez, en 2013 se han

programado tres unidades turbogas en la misma central en el nivel de 115 kV. Los niveles de falla en 230 kV en la SE

Presidente Juárez es de 39.6 KA en el año horizonte.

Las SE s Tijuana I y Metrópoli Potencia presentan valores de corto circuito en la red de 69 kV mayores a 35 kA, sin

embargo, estos valones disminuyen considerablemente con el cambio de tensión de operación de la zona Tijuana de

69 kV a 115 kV. Para esta zona, se ha programado el retiro de las pequeñas unidades turbogas en la central Presidente

Juárez en el 2017.

ÁREA BAJA CALIFORNIA

ADICIONES Y RETIROS DE GENERACIÓN

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 256: Catalogo 2011-2020 r010212 Corto Circuito

256

Coordinación de Planificación

Actualmente en la zona Ensenada no se ha instalado un proyecto de generación, sin embargo, se tiene programado la

adición de generación en el sitio La Jovita ubicado al norte de la ciudad de Ensenada en 2013 en el nivel de 230 kV,

muy cercano a este sitio en el 2019 se incorporan 565 MW de generación, que incrementa la corriente de corto circuito

hasta 22 kA en la subestación La Jovita, mientras las subestaciones Lomas y Ciprés presentan valores de 8 kA en 230

kV para el año horizonte. Los valores máximo en 115 kV se presentan en las SE s Ensenada con 10 kA y Ciprés con

13 kA, siendo este último valor el más alto para esta zona durante el periodo de estudio.

En la zona Mexicali, existen dos sitios de gran concentración de generación, el primero localizado en el campo

geotérmico de Cerro Prieto con una gran cantidad de unidades geotérmicas y el segundo en la cercanías de la

subestación La Rosita.

La SE La Rosita presenta los valores máximos de corto circuito de la zona con 35 kA al año horizonte en 230 kV. Las

SE s Mexicali II y Cerro Prieto I presentan valores de 24 y 16 kA respectivamente en el nivel de 161 kV. Para esta zona,

se ha programado el retiro de las tres unidades turbogas de la Central Turbogas Mexicali en 2014, adicionalmente se

retira la unidad 3 de la Central Cerro Prieto I.

ÁREA BAJA CALIFORNIA

ADICIONES Y RETIROS DE GENERACIÓN

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 257: Catalogo 2011-2020 r010212 Corto Circuito

257

Coordinación de PlanificaciónPRINCIPALES PROYECTOS DE TRANSMISIÓN Y TRANSFORMACIÓN

ÁREA BAJA CALIFORNIA

Proyecto Año Nivel de tensión

La Jovita entronque Presidente Juárez – Ciprés 2012 230 kV

Rumorosa Eólico – La Herradura 2013 230 kV

Santa Isabel Potencia Banco 1 y red de transmisión asociada 2014 230 kV

Interconexión asíncrona BC-SIN (Cucapah) 2015 230 kV

Cambio de tensión de 69 kV a 115 kV de la zona Tijuana Fase1 2016 115 kV

Cañon banco 1 2017 230 kV

Cambio de tensión de 69 kV a 115 kV de la zona Tijuana Fase 2 2018 115 kV

Red asociada a Baja California IV (Ensenada) 2018 400 kV

La zona Tijuana presenta los niveles de corto circuito más altos del sistema, Presidente Juárez, Tijuana y La Rosita

tienen los mayores valores en 230 kV con 34.4, 28.7 y 30 kA respectivamente, mientras que Tijuana I, Metrópoli

Potencia, Panamericana Potencia presentan valores de 37.4, 35.3 y 34.9 kA en 69 kV respectivamente.

En la zona Tijuana es relevante el cambio de tensión de operación de la red de subtransmisión de 69 kV a 115 kV, en la

parte oriente y sur de la ciudad de Tijuana en 2016 y 2018, en el año horizonte solamente la parte central colindante

con la frontera de EUA estará operando en 69 kV.

Con el cambio de tensión de operación, se reducen los niveles de corto circuito de las subestaciones que continúan

operando en 69 kV. Los valores máximos que se presentan en las subestaciones operando en 115 kV son en Metrópoli

Potencia y Tijuana I con 25 y 27 kA respectivamente.

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 258: Catalogo 2011-2020 r010212 Corto Circuito

258

Coordinación de Planificación

Los proyectos relevantes para la zona Ensenada consideran la incorporación de la red de transmisión asociada a la

generación Baja California III y IV al norte de la ciudad, esto incrementa en forma importante los valores de la corriente

de corto circuito de la parte norte de la ciudad de Ensenada, alcanzando valores al horizonte de 22.1 kA en la SE La

Jovita en 230 kV. Los valores máximos en el nivel de 115 kV se obtienen en la SE Ciprés con 12.9 kA.

Para el suministro de los poblados al sur de la ciudad de Ensenada, se ha programado una nueva subestación

denominada Cañón de 100 MVA de capacidad.

En la zona Mexicali, se ha programado la interconexión del área Baja California con el Sistema Interconectado Nacional

(SIN), adicionando la subestación Cucapah y una reconfiguración de la red de 230 kV de la parte sur de la ciudad de

Mexicali. Adicionalmente, se incorpora la nueva SE Santa Isabel Potencia con 225 MVA de capacidad y se realizan

modificaciones a la topología de la red de transmisión hacia el poniente de la ciudad de Mexicali.

La máxima corriente de corto circuito se presenta en la subestación La Rosita con 35 kA en 230 kV, mientras que en las

subestaciones Mexicali II y Cucapah presentan valores de 22 y 20 kA respectivamente en el mismo nivel de tensión. En

las SE s operadas en 161 kV, el valor mas alto se presenta en la Se Mexicali II con 24 kA.

El proyecto más relevante para la zona San Luis Río Colorado es la formación de un anillo en 161 kV en la ciudad y el

reforzamiento mediante un segundo circuito entre las SE s Cerro Prieto II y Parque Industrial San Luis, las mayores

corrientes de corto circuito se presentan en las SE s Chapultepec con 9 kA en 230 kV y Parque industrial San Luis con

8 kA en 161 kV. Es importante mencionar que se esta explorando la posibilidad de que en un futuro se incorpore

generación en esta zona.

ÁREA BAJA CALIFORNIA

PRINCIPALES PROYECTOS DE TRANSMISIÓN Y TRANSFORMACIÓN

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 259: Catalogo 2011-2020 r010212 Corto Circuito

259

Coordinación de Planificación

ÁREA BAJA CALIFORNIA

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 8.91 8.73 8.73 8.82 8.85 10.60 10.70 10.70 10.72 10.72

1F 6.90 6.76 6.76 6.82 6.85 8.22 8.26 8.26 8.27 8.27

3F 15.88 16.18 16.18

1F 14.06 14.22 14.22

3F 23.57 23.87 23.94 24.31 24.62 21.59 21.48

1F 17.18 17.44 17.47 17.60 18.24 16.05 14.66

3F 11.71 11.89 11.91 12.00 9.42 9.21 9.20 7.84 7.87 7.87

1F 7.48 7.62 7.62 7.65 5.44 5.34 4.46 2.89 2.90 2.90

3F 17.86 17.96 18.02 18.28 18.28 18.35 18.35

1F 15.48 15.60 15.65 15.79 15.79 15.82 15.82

3F 2.65 2.65 2.87 2.87

1F 2.51 2.51 2.65 2.65

3F 2.38 2.38 2.39 2.43 2.43 2.43 4.46 4.46 4.76 4.76

1F 1.66 1.66 1.67 1.68 1.68 1.68 4.89 4.90 5.13 5.13

3F 7.47 8.53 8.43 8.86 8.95 8.95

1F 5.82 6.26 6.21 6.38 6.41 6.41

3F 14.61 14.77 14.80 14.95

1F 9.38 9.50 9.51 9.55

3F 9.74 9.74 10.14 10.15 10.86 11.05 11.05 11.06 11.06

1F 7.53 7.53 7.74 7.75 8.38 8.46 8.46 8.47 8.47

3F 26.95 26.92 26.93 29.33 29.56 29.59 29.89 29.90 30.11 30.11

1F 28.96 28.92 28.93 31.46 31.67 31.70 31.93 31.94 32.10 32.10

3F 7.67 7.67 7.75 8.12 8.12 8.12 8.21 8.20 9.13 9.13

1F 7.48 7.48 7.53 7.78 7.78 7.78 7.90 7.87 8.46 8.46

3F 12.69 12.69 13.34 13.77 13.79 13.90 13.90 13.94 13.94

1F 9.34 9.34 9.75 10.13 10.14 10.18 10.18 10.19 10.19

3F 15.77 15.75 15.76 16.95 17.04 17.07 17.30 17.31 17.37 17.37

1F 14.27 14.25 14.25 15.42 15.52 15.53 15.67 15.68 15.71 15.71

3F 18.62 18.66 18.66 20.38 20.47 20.37 20.85 20.85 20.90 20.90

1F 17.14 17.16 17.15 18.74 18.86 18.78 19.07 19.07 19.10 19.10

3F 14.16 14.28 14.27 14.94 14.96 14.94 15.86 15.86 15.88 15.88

1F 15.16 15.26 15.26 15.80 15.82 15.81 16.87 16.87 16.88 16.88

3F 15.58 15.65 15.64 15.72 17.49 17.58 17.80 17.80 17.84 17.84

1F 15.90 16.08 16.06 16.16 18.02 18.09 18.25 18.25 18.28 18.28230Cerro Prieto II CPD

115

230

Cementos California

Centenario

CEC

CEO

230

161

161

Centro CRO

Cerro Prieto I CPU

Cañon KON

Cárdenas CNA

69

Carranza CZA 161

CC Mexicali LRP 230

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Aeropuerto II APD 230

115

69

American Optical AMO

69

230

230

115

115

Bombeo Presa PB1

Cachanilla CAA

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 260: Catalogo 2011-2020 r010212 Corto Circuito

260

Coordinación de Planificación

ÁREA BAJA CALIFORNIA

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 15.75 15.77 15.77 15.82 17.54 17.66 17.87 17.87 17.91 17.91

1F 16.09 16.18 16.17 16.22 18.05 18.15 18.30 18.30 18.33 18.33

3F 12.79 12.71 12.71 13.23 13.24 13.37 12.97 12.97 12.98 12.98

1F 13.02 12.92 12.92 13.30 13.31 13.44 12.85 12.85 12.86 12.86

3F 14.74 14.74 14.75 14.75

1F 15.24 15.24 15.25 15.25

3F 9.13 8.91 8.91 9.03 9.04 11.48 11.60 11.60 11.62 11.62

1F 7.22 7.02 7.02 7.11 7.14 9.16 9.22 9.22 9.23 9.23

3F 14.43 14.32 14.31 15.28 15.32 15.67 16.06 16.06 16.09 16.09

1F 12.77 12.59 12.59 13.31 13.35 13.75 13.97 13.97 13.98 13.98

3F 7.78 8.14 8.11 8.14 8.51 8.52 8.59 8.59 8.60 8.60

1F 6.13 6.33 6.32 6.33 6.54 6.54 6.57 6.57 6.58 6.58

3F 5.69 5.69 5.75 6.29 6.29 6.29 6.31 6.31 7.85 7.85

1F 5.98 5.98 6.03 6.53 6.54 6.54 6.71 6.71 7.93 7.93

3F 9.15 9.15 9.26 9.80 9.80 9.82 9.99 10.01 11.44 11.44

1F 10.56 10.56 10.66 11.20 11.20 11.21 11.53 11.55 12.87 12.87

3F 7.36 8.39 8.29 8.70 8.79 8.79

1F 5.70 6.12 6.08 6.23 6.26 6.26

3F 19.86 19.98 20.29 20.29 20.36 20.36

1F 17.96 18.12 18.31 18.31 18.35 18.35

3F 10.40 10.42 11.65 11.80 11.80

1F 7.51 7.53 8.03 8.08 8.08

3F 13.12 13.13 13.16 13.27 13.28

1F 8.30 8.30 8.31 8.34 8.34

3F 5.14 5.16 5.66 5.71 5.71

1F 3.42 3.44 3.61 3.62 3.62

3F 3.47 3.47 3.47 3.48 3.48

1F 2.22 2.22 2.22 2.22 2.22

3F 11.24 11.13 13.73 14.00 14.00

1F 9.64 9.58 10.99 11.11 11.11

3F 11.94 11.94 11.95 12.07 12.09 2.11 2.11 2.13 2.14 2.14

1F 7.93 7.93 7.94 7.99 7.99 0.62 0.62 0.62 0.62 0.62

3F 17.43 17.43 17.62 18.42 18.45 18.39 18.39 18.16 18.93 18.93

1F 16.38 16.38 16.50 16.97 16.93 16.91 16.71 16.52 16.94 16.94

3F 30.42 30.46 30.63 31.30 31.35 30.87 30.86 28.94 29.50 29.50

1F 30.21 30.26 30.37 30.81 30.49 30.20 29.16 27.72 28.06 28.06

CES

Durazno

115

161

161

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

230

115

Cerro Prieto III CPT

Cerro Prieto V CPV

Cetys CTY

Chapultepec CHQ

Ciprés CIP

Cosae Punta Bandera

230

161

230

230

115

69

115

69

115

Cucapáh CUC 230

DRA

El Encinal END

El Florido FLO

69

230

69

El Rubí RUB

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 261: Catalogo 2011-2020 r010212 Corto Circuito

261

Coordinación de Planificación

ÁREA BAJA CALIFORNIA

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 7.94 7.94 8.03 8.42 8.42 8.42 8.49 8.48 9.47 9.47

1F 8.11 8.11 8.17 8.47 8.47 8.46 8.57 8.54 9.24 9.24

3F 7.67 7.67 7.75 8.12 8.12 8.12 8.19 8.18 9.09 9.09

1F 7.57 7.57 7.62 7.88 7.88 7.88 7.97 7.94 8.54 8.54

3F 11.26 11.14 16.20 16.55 16.55

1F 9.16 9.10 12.84 12.99 12.99

3F 12.42 12.42 12.44 12.56 12.58

1F 9.16 9.16 9.17 9.22 9.22

3F 10.38 10.23 18.95 19.38 19.38

1F 8.04 7.96 16.85 17.07 17.07

3F 14.96 14.97 15.00 15.14 22.86

1F 10.57 10.57 10.58 10.63 16.84

3F 8.00 8.00 8.09 8.48 8.49 8.49 8.58 8.55 9.56 9.56

1F 8.08 8.08 8.14 8.43 8.44 8.44 8.56 8.49 9.18 9.18

3F 10.17 8.61 8.61 8.89 8.90 10.12 10.28 10.28 10.28 10.28

1F 8.02 6.54 6.54 6.67 6.68 7.78 7.84 7.84 7.85 7.85

3F 17.45 17.81 17.86 18.07 18.76 18.11 18.10 14.54 14.68 14.68

1F 11.45 11.74 11.75 11.81 9.57 9.32 7.22 4.10 4.10 4.10

3F 4.95 6.96 6.91 6.99 7.01 6.89 7.00 7.00 7.00 7.00

1F 3.63 5.46 5.43 5.46 5.47 5.41 5.46 5.46 5.46 5.46

3F 24.50 26.07 26.17 26.62 26.81 24.42 24.28 14.17 14.30 14.30

1F 17.38 18.80 18.84 19.00 18.15 16.74 9.31 3.45 3.45 3.45

3F 13.30 13.12 17.15 17.51 17.51

1F 11.58 11.51 14.01 14.17 14.17

3F 25.29 25.29 25.37 25.81 25.86

1F 21.85 21.85 21.90 22.15 22.17

3F 31.97 31.96 31.98 32.83 32.91 32.94 33.03 33.03 33.17 33.17

1F 32.45 32.44 32.46 33.25 33.31 33.33 33.39 33.39 33.49 33.49

3F 16.10 16.41 16.41

1F 14.18 14.34 14.34

3F 24.10 24.45 24.52 24.91 25.38 22.05 21.92

1F 17.65 17.95 17.98 18.13 18.97 16.44 14.85

3F 3.81 3.81 3.88 3.93 3.93 4.01 4.00 4.03 4.13 4.13

1F 2.48 2.48 2.50 2.51 2.51 2.53 2.54 2.54 2.57 2.57

3F 11.14 13.85 14.10 14.10

1F 8.98 10.35 10.45 10.45

Industrial INA

Jatay

La Encantada

JAT

LDA

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Ensenada EDA 115

Fábrica Monterrey FAM 115

115

69

GLL 115

115

69

Francisco Villa FCO

Frontera FTA

115

115

Gallo

115

69

115

69

Imperial Valley IVY 230

Hidalgo HGO 161

69

González Ortega GOR 161

Guerrero GER 69

Hipódromo HMO

Hyundai HYN

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 262: Catalogo 2011-2020 r010212 Corto Circuito

262

Coordinación de Planificación

ÁREA BAJA CALIFORNIA

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 7.78 7.78

1F 9.30 9.30

3F 14.53 14.53 14.59 15.69 15.96 16.03 16.03 16.32 19.32 19.32

1F 11.98 11.98 12.00 13.27 13.44 13.74 13.75 13.97 15.32 15.32

3F 14.92 15.15 20.48 21.16 21.16

1F 15.72 16.07 20.63 21.08 21.08

3F 24.87 24.87 24.94 25.57 25.68

1F 26.99 26.99 27.04 27.77 27.87

3F 6.84 6.84

1F 7.37 7.37

3F 8.69 8.69 8.69 8.70 8.70 19.75 19.75

1F 8.86 8.87 8.87 8.88 8.88 22.09 22.09

3F 9.31 9.41 9.42 12.02 11.97 12.83 13.02 13.02

1F 8.13 8.18 8.19 9.44 9.42 9.79 9.87 9.87

3F 17.73 18.11 18.11

1F 14.13 14.29 14.29

3F 24.18 24.38 24.45 24.85 24.90 22.54 20.85

1F 17.63 17.79 17.82 17.96 17.84 16.76 0.27

3F 28.83 28.79 28.80 31.93 32.24 32.28 32.68 32.69 32.98 32.98

1F 30.02 29.96 29.97 34.14 34.45 34.49 34.80 34.81 35.03 35.03

3F 15.39 15.39 15.39 17.82 17.89 17.88 18.10 18.10 18.15 18.15

1F 16.14 16.14 16.14 18.52 18.59 18.58 18.74 18.74 18.78 18.78

3F 16.31 16.63 16.63

1F 12.66 12.78 12.78

3F 17.81 17.88 17.92 18.13 18.16 16.17 15.51

1F 13.40 13.45 13.47 13.55 13.52 12.66 8.74

3F 5.68 5.68 5.73 6.18 6.18 6.18 6.18 6.19 7.71 7.71

1F 5.53 5.53 5.57 5.89 5.90 5.89 5.97 5.97 7.17 7.17

3F 8.43 8.43 8.52 8.96 8.96 8.95 9.01 9.02 10.14 10.14

1F 9.57 9.57 9.65 10.05 10.06 10.04 10.15 10.15 11.17 11.17

3F 2.56 2.56 2.56 2.58 2.58 2.39 2.39 2.40 2.42 2.42

1F 2.72 2.72 2.72 2.73 2.73 2.53 2.53 2.53 2.55 2.55

3F 5.85 5.85 5.90 6.11 6.11 6.12 6.38 6.38 6.94 6.94

1F 5.36 5.36 5.39 5.52 5.52 5.53 5.87 5.87 6.19 6.19

La Herradura HRA

La Jovita JOV

La Mesa LMS

Lago LGO

La Rosita ROA

115

69

Maneadero MND 115

161

115

69

230

115

69

230

Lomas LOS

400

230

La Joya LJY 115

230

115

69

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

400

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 263: Catalogo 2011-2020 r010212 Corto Circuito

263

Coordinación de Planificación

ÁREA BAJA CALIFORNIA

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 25.98 25.98 26.26 27.82 27.99 28.28 28.25 28.29 30.09 30.09

1F 23.73 23.73 23.89 24.91 25.00 25.97 25.93 25.93 26.92 26.92

3F 17.41 17.09 24.63 25.39 25.39

1F 18.33 18.15 25.28 25.81 25.81

3F 33.30 33.30 33.44 34.22 34.30

1F 35.32 35.32 35.43 36.09 36.15

3F 18.70 18.48 18.48 20.69 21.60 21.85 22.24 22.24 22.33 22.33

1F 16.85 16.63 16.63 19.04 20.35 20.73 20.98 20.98 21.04 21.04

3F 19.92 20.02 20.02 22.92 23.04 22.78 23.56 23.56 23.62 23.62

1F 20.44 20.51 20.50 23.59 23.84 23.52 24.12 24.13 24.17 24.17

3F 10.87 10.85 10.85 11.36 11.38 11.56 11.76 11.76 11.77 11.77

1F 8.67 8.63 8.63 8.92 8.94 9.10 9.18 9.18 9.18 9.18

3F 15.63 16.02 16.06 16.23 15.52 14.93 14.91 11.61 11.70 11.70

1F 10.05 10.35 10.36 10.41 8.70 8.45 6.44 3.53 3.54 3.54

3F 7.12 7.05 10.33 10.45 10.45

1F 4.91 4.89 7.22 7.26 7.26

3F 9.00 9.05 9.06 9.11 8.83

1F 5.21 5.23 5.24 5.25 5.13

3F 0.65 0.65 0.65 0.66 0.66 0.66 0.75 0.75 0.75 0.75

1F 0.48 0.48 0.48 0.48 0.48 0.48 0.56 0.56 0.56 0.56

3F 4.02 4.02 4.12 4.17 4.17 4.31 4.30 4.35 4.43 4.43

1F 2.60 2.60 2.64 2.65 2.65 2.69 2.69 2.70 2.72 2.72

3F 12.26 12.21 12.21 13.25 13.28 13.43 13.69 13.70 13.72 13.72

1F 9.84 9.77 9.77 10.56 10.59 10.72 10.84 10.84 10.85 10.85

3F 1.18 1.18 1.18 1.19 1.19 1.15 1.15 1.15 1.16 1.16

1F 0.90 0.90 0.90 0.90 0.90 0.88 0.88 0.88 0.89 0.89

3F 16.73 16.67 16.67 18.81 18.92 19.00 19.28 19.28 19.36 19.36

1F 14.25 14.19 14.20 16.31 16.44 16.52 16.67 16.67 16.71 16.71

3F 29.30 29.30 29.51 30.61 30.72 30.81 30.81 30.98 32.09 32.09

1F 23.53 23.53 23.62 24.11 24.15 24.30 24.27 24.42 24.87 24.87

3F 21.01 21.05 21.12 21.42 21.45 20.81 20.60 19.06 19.29 19.29

1F 15.20 15.22 15.24 15.35 15.36 15.11 4.71 4.65 4.66 4.66

3F 15.26 15.27 15.27 16.56 16.62 16.65 17.10 17.11 17.14 17.14

1F 13.34 13.31 13.31 14.25 14.33 14.35 14.60 14.60 14.62 14.62

3F 7.74 7.74 8.45 8.54 8.54 11.00 9.46 15.11 15.37 15.37

1F 6.51 6.51 7.02 7.06 7.06 8.05 6.72 11.13 11.22 11.22Panamericana Fraccionamiento PNM 115

Minera San Felipe MIN

Misión MSN

Otay Mesa OTAY 230

Pacífico PAF 69

Packard PKD 161

Nacozari NZI 161

Ojos Negros ONG 69

Orizaba OZA 230

115

69

115

115

MGI Industrias MGI

161

161

69México MXC

115

69

230

Metrópoli Potencia MEP

Mexicali II MXI

Mexicali Oriente MOE

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

230

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 264: Catalogo 2011-2020 r010212 Corto Circuito

264

Coordinación de Planificación

ÁREA BAJA CALIFORNIA

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 22.03 22.03 22.29 23.44 23.51 23.42 23.40 23.30 24.42 24.42

1F 20.85 20.85 21.02 21.71 21.75 21.74 21.50 21.46 22.10 22.10

3F 34.06 34.22 34.40 35.20 35.28 33.32 32.63 28.54 29.04 29.04

1F 34.84 34.99 35.12 35.69 35.71 34.16 31.74 29.05 29.40 29.40

3F 5.15 7.33 7.13 7.16 7.36 7.34 7.42 7.42 7.43 7.43

1F 4.64 6.40 6.23 6.25 6.37 6.36 6.40 6.40 6.40 6.40

3F 6.82 8.22 8.11 8.16 8.25 8.17 8.28 8.28 8.29 8.29

1F 6.89 8.27 8.15 8.19 8.26 8.21 8.28 8.28 8.29 8.29

3F 5.14 5.16 5.66 5.71 5.71

1F 3.42 3.44 3.61 3.62 3.62

3F 3.49 3.49 3.49 3.50 3.50

1F 2.23 2.23 2.23 2.24 2.24

3F 6.93 6.93 7.43 7.52 7.52 8.41 8.33 8.68 8.81 8.81

1F 5.29 5.29 5.58 5.61 5.61 5.95 5.92 6.05 6.09 6.09

3F 28.94 28.94 29.49 31.81 31.92 31.88 31.89 31.80 34.26 34.26

1F 34.40 34.40 34.96 37.20 37.30 37.34 37.34 37.26 39.58 39.58

3F 11.86 11.86 13.66 13.89 13.90 18.14 17.70 19.70 20.17 20.17

1F 13.70 13.70 16.26 16.47 16.48 20.64 20.20 22.06 22.45 22.45

3F 5.27 5.27 5.52 5.58 5.58 5.98 5.95 6.10 6.18 6.18

1F 3.64 3.64 3.76 3.77 3.77 3.90 3.89 3.93 3.96 3.96

3F 2.07 2.07 2.08 2.10 2.10 2.10 2.26 2.26 2.33 2.33

1F 1.53 1.53 1.54 1.55 1.55 1.55 1.70 1.70 1.73 1.73

3F 20.54 21.48 21.55 21.85 21.95 20.58 20.51 13.82 13.94 13.94

1F 13.82 14.63 14.65 14.75 13.35 12.68 8.28 3.62 3.63 3.63

3F 15.95 15.97 15.97 17.68 17.75 17.69 18.03 18.04 18.08 18.08

1F 13.53 13.53 13.53 15.05 15.12 15.08 15.26 15.26 15.28 15.28

3F 4.91 8.09 8.03 8.14 8.17 7.97 8.13 8.14 8.14 8.14

1F 3.53 6.48 6.45 6.50 6.52 6.41 6.49 6.49 6.49 6.49

3F 9.81 9.81 9.82 10.11 10.14 10.15 10.18 10.19 10.33 10.33

1F 8.39 8.39 8.39 8.57 8.59 8.60 8.61 8.62 8.68 8.68

3F 9.67 9.67 9.67 9.76 9.77 9.77 9.78 9.78 9.82 9.82

1F 12.84 12.84 12.84 12.94 12.95 12.96 12.97 12.97 13.01 13.01

3F 4.99 5.37 5.38 5.38 5.40 5.59 5.59

1F 5.27 5.81 5.82 5.82 5.84 5.98 5.98

3F 6.72 8.01 8.01 8.01 8.02 8.13 8.13

1F 6.86 9.20 9.20 9.20 9.21 9.31 9.31

230

115

Rumorosa Eólico RUE

230

69

Río RII

Rio Nuevo RIN

Ruíz Cortines RZC

Rumorosa RUM

PNU 115

Punta China PCH 115

PJZ

69

161

161

69

115

230

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

230

69

230

161

115

Panamericana Potencia PAP

Parque Industrial San Luis PID

Pemex PMX

Popotla POP

Presidente Juárez

115

Puerto Nuevo

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 265: Catalogo 2011-2020 r010212 Corto Circuito

265

Coordinación de Planificación

ÁREA BAJA CALIFORNIA

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 22.67 22.67 22.88 24.06 24.18 24.40 24.38 24.41 25.74 25.74

1F 19.28 19.28 19.38 20.05 20.11 20.73 20.71 20.70 21.33 21.33

3F 0.69 0.69 0.69 0.69 0.69 0.69 0.80 0.80 0.81 0.81

1F 0.51 0.51 0.51 0.51 0.51 0.51 0.61 0.61 0.61 0.61

3F 6.90 6.92 7.14 7.14 7.21 7.21 7.21 7.21

1F 5.46 5.47 5.59 5.59 5.62 5.62 5.62 5.62

3F 1.09 1.09 1.09 1.10 1.10 1.10 1.38 1.38 1.41 1.41

1F 0.77 0.77 0.77 0.77 0.77 0.77 1.07 1.07 1.08 1.08

3F 0.88 0.88 0.89 0.89 0.89 0.89 1.07 1.07 1.08 1.08

1F 0.62 0.62 0.62 0.62 0.62 0.62 0.78 0.78 0.79 0.79

3F 2.42 2.42 2.43 2.47 2.47 2.47 3.64 3.64 3.83 3.83

1F 1.74 1.74 1.75 1.76 1.76 1.76 3.20 3.20 3.29 3.29

3F 15.95 15.45 15.45 16.64 18.04 18.14 18.38 18.39 18.45 18.45

1F 13.09 12.60 12.60 13.60 15.40 15.46 15.59 15.59 15.62 15.62

3F 15.24 15.24 15.24 21.12 21.21 21.19 21.64 21.65 21.70 21.70

1F 13.17 13.16 13.16 20.28 20.38 20.37 20.65 20.66 20.69 20.69

3F 20.59 20.73 20.81 21.13 21.14 21.23 21.23

1F 18.55 18.71 18.79 18.98 18.98 19.03 19.03

3F 21.06 21.16 21.13 21.57 21.57 21.63 21.63

1F 21.07 21.18 21.16 21.47 21.47 21.51 21.51

3F 4.20 4.20 4.26 4.34 4.34 4.40 4.41 4.43 4.58 4.58

1F 2.79 2.79 2.81 2.84 2.84 2.85 2.86 2.87 2.91 2.91

3F 9.29 14.50 14.75 14.75

1F 6.52 10.73 10.82 10.82

3F 14.04 14.07 14.10 14.23 14.25 13.25

1F 8.89 8.91 8.92 8.95 8.94 8.50

3F 13.02 12.97 12.97 13.20 12.90 12.96 13.08 13.08 13.11 13.11

1F 10.48 10.46 10.46 10.65 10.30 10.33 10.38 10.39 10.40 10.40

3F 7.47 7.53 8.64 8.76 8.76

1F 5.45 5.49 5.94 5.97 5.97

3F 7.14 7.14 7.15 7.20 7.21

1F 4.54 4.54 4.55 4.57 4.57

3F 7.45 7.51 8.61 8.73 8.73

1F 5.43 5.47 5.91 5.95 5.95

3F 7.11 7.11 7.12 7.17 7.18

1F 4.52 4.52 4.52 4.54 4.54

115

115

115

San Luis Rey SLR

San Quintín SQN

San Simón SMN

San Vicente SVE

161

115

115

69

115

69

SIO

Siderúrgica de California CSC

Tecate TCT

Tecate II TCD

230

115

69

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Samsung SAM 230

San Felipe SAF 115

230

Sánchez Taboada STB 230

161Santa Isabel STA

Santa Isabel Potencia SIP

Sauzal SAZ

Seminario

230

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 266: Catalogo 2011-2020 r010212 Corto Circuito

266

Coordinación de Planificación

ÁREA BAJA CALIFORNIA

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 9.38 8.98 8.98 9.16 9.21 15.60 15.80 15.80 15.84 15.84

1F 7.10 6.74 6.74 6.86 6.94 12.82 12.92 12.92 12.94 12.94

3F 13.93 13.93 13.96 14.10 14.11 13.92 13.88 13.34 13.45 13.45

1F 9.21 9.21 9.22 9.26 9.26 9.20 5.96 5.88 5.90 5.90

3F 7.48 7.54 8.65 8.77 8.77

1F 5.46 5.50 5.94 5.98 5.98

3F 7.49 7.49 7.50 7.55 7.56

1F 4.80 4.80 4.81 4.83 4.83

3F 12.96 12.63 12.63 13.41 14.31 14.37 14.53 14.53 14.57 14.57

1F 9.90 9.61 9.61 10.19 11.16 11.20 11.26 11.27 11.28 11.28

3F 28.65 28.65 28.96 30.58 30.73 30.87 30.86 31.13 32.89 32.89

1F 26.96 26.96 27.16 28.18 28.25 28.68 28.60 28.98 29.99 29.99

3F 13.78 13.51 26.14 26.97 26.97

1F 12.23 12.07 28.35 28.99 28.99

3F 36.80 36.86 37.03 37.91 38.07 31.53 31.27

1F 37.44 37.51 37.62 38.27 38.31 32.83 31.91

3F 16.83 16.85 16.89 17.08 17.11 13.57 13.31

1F 18.95 18.97 19.00 19.17 19.18 15.86 15.29

3F 13.27 13.27 13.32 14.08 14.25 14.32 14.32 14.47 16.17 16.17

1F 10.15 10.15 10.17 10.85 10.93 11.11 11.11 11.20 11.84 11.84

3F 14.05 14.28 14.28

1F 11.21 11.31 11.31

3F 16.54 18.35 18.39 18.61 16.17 14.04 14.00

1F 10.76 12.17 12.18 12.25 10.25 8.84 7.01

3F 2.85 2.85 2.85 2.86 2.87 1.67 1.67 1.68 1.69 1.69

1F 1.92 1.92 1.92 1.92 1.92 0.74 0.74 0.74 0.74 0.74

3F 9.63 9.63 9.90 10.05 12.89 13.02 13.02 13.05 13.05

1F 7.10 7.10 7.27 7.45 9.82 9.87 9.87 9.88 9.88

3F 8.31 9.26 9.26

1F 8.04 8.65 8.65

3F 2.14 2.14 2.15 2.15 2.15 1.67 1.67 1.68 1.68 1.68

1F 1.54 1.54 1.54 1.54 1.54 1.04 1.04 1.04 1.05 1.05

3F 1.35 1.35 1.35 1.36 1.36 1.36 1.84 1.84 1.88 1.88

1F 0.95 0.95 0.95 0.95 0.95 0.95 1.48 1.48 1.50 1.50

3F 19.04 18.92 18.93 22.50 22.67 22.83 23.22 23.22 23.33 23.33

1F 16.81 16.70 16.71 20.95 21.19 21.38 21.63 21.63 21.69 21.69

Valle Trinidad TRI

Wisteria WIS

Valle de las Palmas VPM

Valle de Puebla VPU

TCR

Thomson THO

230

Valle Dorado VDO 115

Valle Guadalupe VLP 69

115

115

69

69

230

69

69A

230

Tijuana TJI

Toyota TOY

Universidad UND

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Tecnológico TEK 230

69

115

Tecolote TEE

Tecra

230

115

69

230

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 267: Catalogo 2011-2020 r010212 Corto Circuito

267

Coordinación de Planificación

ÁREA BAJA CALIFORNIA

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 17.66 17.51 17.51 19.89 20.31 20.49 20.82 20.83 20.90 20.90

1F 15.24 15.10 15.10 17.59 18.16 18.38 18.57 18.57 18.62 18.62

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Xochimilco XCO 230

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____

Page 268: Catalogo 2011-2020 r010212 Corto Circuito

268

Coordinación de Planificación

ÁREA BAJA CALIFORNIA SUR

ESTUDIO DE CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____

_______

Page 269: Catalogo 2011-2020 r010212 Corto Circuito

269

Coordinación de Planificación

ÁREA BAJA CALIFORNIA SUR

Loreto

Puerto Escondido

Villa InsurgentesVilla

Constitución

Santo

Domingo

Puerto San

Carlos

Las Pilas

El Palmar San José

del CaboDiesel Los cabos

Cabo San Lucas II

El Triunfo

Santiago

Cabo Real

La Paz

Olas Altas

Punta Prieta I

y II

Coromuel

Rofomex

Enlace en 230 kV

Enlace en 115 kV

Subestación en 115 kV

Combustión interna

Termoeléctrica convencional

Turbogás

Subestación en 230 kV

RED ELÉCTRICA PRINCIPAL 2011

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 270: Catalogo 2011-2020 r010212 Corto Circuito

270

Coordinación de Planificación

ÁREA BAJA CALIFORNIA SUR

Mújica

Laguneros

Vizcaíno

O c é a n o

P a c í f i c o

Golfo de

California

Jesús María

Bahía Asunción

Guerrero Negro I

ParadorBahía

de Los Ángeles

Nuevo Rosarito

Santa Rosaliíta

Puerto

Nuevo

San Roque

Bahía

Tortugas

Punta

Eugenia

Punta Prieta San Hipólito

La Bocana

Punta

Abreojos

Zapata

Rancho

El Silencio

Benito Juárez

Mulegé

Santa Rosalía

Tres

Vírgenes

San

Ignacio

Sonora

Díaz Ordaz

San

Bruno

Enlace en 115 kV

Subestación en 34.5 kV

Enlace en 34.5 kV

Subestación en 115 kV

Combustión interna

Geotermoeléctrica

RED ELÉCTRICA PRINCIPAL 2011

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 271: Catalogo 2011-2020 r010212 Corto Circuito

271

Coordinación de Planificación

ÁREA BAJA CALIFORNIA SUR

O c é a n o P a c í f i c o

Mújica

Vizcaíno

Golfo de CaliforniaJesús María

Bahía Asunción

Guerrero

Negro I

Parador Bahía

de Los Ángeles

Nuevo

Rosarito

Santa

Rosaliíta

Puerto Nuevo

San Roque

Bahía Tortugas

Punta Eugenia

Punta PrietaSan Hipólito

La Bocana

Punta

Abreojos

Zapata

Benito Juárez

Mulegé

Santa Rosalía

Tres

Vírgenes

San Ignacio

Mezquital

Sonora

MinaDíaz Ordaz

San Bruno

Enlace en 230 kV

Subestación en 34.5 kV

Enlace en 115 kV

Subestación en 115 kV

Combustión interna

Enlace submarino en 230 kV

HVDC Light

Bahía

Kino

El Infiernito

Loreto

Santo Domingo

Puerto San

Carlos

Rofomex

Las Pilas

Loreto

maniobras Puerto

Escondido

Insurgentes

Villa

Constitución

La Paz Coromuel

Punta Prieta

I y II

San José

del Cabo

Cabo San Lucas II

Diésel Los Cabos

Cabo Real

El Triunfo

Santiago

Olas Altas

Termoeléctrica convencional

Turbogás

Geotermoeléctrica

Enlace en 34.5 kV

Subestación en 230 kV

El Palmar

Camino Real

Monte

Real

Cabo Falso

RED ELÉCTRICA PRINCIPAL 2020

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 272: Catalogo 2011-2020 r010212 Corto Circuito

272

Coordinación de Planificación

ÁREA BAJA CALIFORNIA SUR

ADICIONES:

Nombre de la Central Año Capacidad

Guerrero Negro III (CI) 2011 11 MW

Santa Rosalía II (CI) 2012 15 MW

Baja California Sur III (CI) 2012 43 MW

Guerrero Negro IV (CI) 2013 7 MW

Baja California Sur IV (CI) 2013 43 MW

Santa Rosalía III (CI) 2014 11 MW

Baja California Sur V (CI) 2015 43 MW

Los Cabos I (TG) 2016 105 MW

Baja California Sur VI (CI) 2017 43 MW

Baja California Sur VII (CI) 2019 86 MW

Guerrero Negro V (CI) 2019 7 MW

RETIROS:

Nombre de la Central Año Capacidad

Santa Rosalía (CI) U9 y U10 2012 4.8 MW

Santa Rosalía (CI) U3, U4, U5 y U8 2013 6.2 MW

Los Cabos (DTG) U1, U2 y U3 2015 84.6 MW

CD. Constitución (DTG) 2017 33.2 MW

Punta Prieta II (TC) U1 y U2 2017 75 MW

La Paz (DTG) U1 y U2 2017 43 MW

ADICIONES Y RETIROS DE GENERACIÓN

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 273: Catalogo 2011-2020 r010212 Corto Circuito

273

Coordinación de Planificación

ÁREA BAJA CALIFORNIA SUR

En la zona La Paz, se incorporan los proyectos de generación Baja California Sur III, IV, V y VI en el sitio Coromuel en

230 kV, lo que provoca un incremento en la corriente de corto circuito en la SE Coromuel de 2.2 kA en 2011 a 6 kA al

año horizonte. Esta subestación es el punto de interconexión de los proyectos mencionados.

Se ha programado en la zona La Paz el retiro de cuatro unidades de generación en 2017, dos unidades en la central

Punta Prieta II y el retiro de la Central Punta Prieta I, ocasionando una disminución en la corriente de corto circuito de

6.9 kA a 6.2 kA en la SE Punta Prieta I y de 7.1 kA a 6.4 kA en la SE Punta Prieta II.

En la zona Constitución se retira la unidad turbogás existente en 2018, se observaría una reducción en la corriente de

corto circuito en las subestaciones Villa Constitución, Insurgentes y Loreto. Sin embargo, motivado por la interconexión

BCS-SIN con las adiciones de red de transmisión que inciden en la SE Villa Constitución, los valores de corto circuito

se incrementan de 3.4 kA a 5.9 kA.

En la zona Los Cabos sobresale la sustitución de las tres unidades turbogás en la Central diesel Los Cabos en 2016,

por tres unidades de similar capacidad, conservándose los valores de corto circuito en las subestaciones C.D. Los

Cabos, Cabo San Lucas II y Cabo Bello con 7.5 kA , 5 kA y 3.7 kA respectivamente.

En la zona Guerrero Negro se ha programado la entrada en operación de los Proyectos Guerrero Negro III, IV y V para

ser incorporados en la subestación Guerrero Negro II (vizcaíno) con un nivel de corto circuito de 5.4 kA en 34.5 kV. De

esta forma solo existirá un punto de generación ya que la Central Guerrero Negro I ha sido desmantelada, instalando

una unidad móvil para situación de emergencias.

ADICIONES Y RETIROS DE GENERACIÓN

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 274: Catalogo 2011-2020 r010212 Corto Circuito

274

Coordinación de Planificación

ÁREA BAJA CALIFORNIA SUR

En la zona Santa Rosalía se han programado los proyectos de Santa Rosalía II y III, posteriormente el retiro de todas

las unidades de la Central Santa Rosalía, por lo cual los valores de cortocircuito se incrementan ligeramente en las

subestaciones Mina con 3.9 kA y Tres Vírgenes con 2.7 kA.

Con las adiciones y retiros de generación programados en los sistemas que forman parte de BCS, los incrementos en

las corrientes de corto circuito no rebasan la capacidad interruptiva de los dispositivos de desconexión instalados en las

subestaciones que forman parte del sistema eléctrico.

ADICIONES Y RETIROS DE GENERACIÓN

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 275: Catalogo 2011-2020 r010212 Corto Circuito

275

Coordinación de PlanificaciónPRINCIPALES PROYECTOS DE TRANSMISIÓN Y TRANSFORMACIÓN

ÁREA BAJA CALIFORNIA SUR

Proyecto Año Nivel de tensión

Interconexión Guerrero Negro – Santa Rosalía 2014 115 kV

Los Cabos Banco 1 2015 230/115 kV

Central Diesel Los Cabos entq. El Palmar-Olas Altas 2015 230 kV

Interconexión SIN – BCS 2018 230 kV

Olas Altas Banco 2 2018 230/115 kV

Villa Constitución Banco 1 2018 230/115 kV

Loreto Maniobras CEV 2018 230 kV

La inclusión de nuevos proyectos de transmisión en el área Baja California Sur y cambios en la topología de la red

troncal son factores que influyen directamente en los resultados del estudio de corto circuito.

Con la interconexión de los sistemas aislados se incrementan los valores de corto circuito en las subestaciones

Vizcaíno, El Mezquital, Tres Vírgenes y Mina en 115 kV. El valor máximo de corriente de corto circuito se presenta en la

subestación Mina con 4.4 kA

Con la entrada de transformación en la subestación Diesel Los Cabos en 2015, se forma un anillo alterno en 230 kV en

la zona Los Cabos. En la SE El Palmar crecen los valores de corto circuito a 3.3 kA y en SE C.D. Los Cabos en 3.8 kA

en el nivel de 230 kV.

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 276: Catalogo 2011-2020 r010212 Corto Circuito

276

Coordinación de PlanificaciónPRINCIPALES PROYECTOS DE TRANSMISIÓN Y TRANSFORMACIÓN

ÁREA BAJA CALIFORNIA SUR

En 2018 se tiene programada la interconexión asíncrona del sistema Baja California Sur con el Sistema Interconectado

Nacional, lo cual implica un incremento en la corriente de corto circuito trifásica y monofásica en las subestaciones

existentes en los niveles de 115 y 230 kV que enlazan diversas subestaciones a través de su trayectoria como son

Mina con 4.4 kA, Villa Constitución con 3.4 y Olas Altas con 5.2 kA en el nivel de 230 kV.

En la SE Villa Constitución en 115 kV se tiene un valor de 5.2 kA y en 230 kV de 3.4 kA. En la SE Olas Altas se

alcanzan valores de 5.9 kA.

Los valores más altos de corto circuito en el sistema BCS se presentan en la SE Coromuel en 115 kV con 8.9 kA y C.D.

Los Cabos con 8.1 kA.

De los resultados de corto circuito obtenidos del área Baja California Sur se observa que todos los valores se

encuentran por debajo de las capacidades interruptivas de los equipos actualmente instalados. Por lo tanto se observa

que no existen violaciones en las capacidades interruptivas de los equipos.

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 277: Catalogo 2011-2020 r010212 Corto Circuito

277

Coordinación de Planificación

ÁREA BAJA CALIFORNIA SUR

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 0.63 0.63 0.70 0.78 0.78 0.78 0.78 0.86 0.86 0.86

1F 0.45 0.45 0.49 0.52 0.52 0.52 0.52 0.56 0.56 0.56

3F 4.02 4.02

1F 4.44 4.44

3F 0.24 0.24 0.27 0.43 0.43 0.43 0.43 0.58 0.58 0.58

1F 0.22 0.22 0.24 0.33 0.33 0.33 0.33 0.29 0.29 0.29

3F 0.54 0.54 0.60 0.78 0.78 0.78 0.78 1.24 1.24 1.24

1F 0.51 0.51 0.55 0.68 0.68 0.68 0.68 1.58 1.58 1.58

3F 0.15 0.15 0.15 0.16 0.16 0.16 0.16 0.16 0.16 0.16

1F 0.16 0.16 0.16 0.16 0.16 0.16 0.16 0.17 0.17 0.17

3F 0.22 0.22 0.23 0.25 0.25 0.25 0.25 0.28 0.28 0.28

1F 0.17 0.17 0.17 0.18 0.18 0.18 0.18 0.22 0.22 0.22

3F 0.96 0.96 1.09 1.25 1.25 1.25 1.25 1.35 1.36 1.36

1F 0.76 0.76 0.82 0.89 0.89 0.89 0.89 1.00 1.00 1.00

3F 0.96 0.96 1.09 1.25 1.25 1.25 1.25 1.36 1.36 1.36

1F 0.83 0.83 0.90 0.98 0.98 0.98 0.98 1.14 1.14 1.14

3F 4.60 4.66 4.70 4.71 4.76 4.70 4.73 4.53 5.34 5.34

1F 4.73 4.79 4.83 4.83 4.88 4.84 4.87 4.72 5.39 5.39

3F 2.80 2.32 2.42 2.54 2.65 2.65

1F 3.73 3.15 3.27 3.41 3.55 3.55

3F 5.00 5.09 5.12 5.12 5.12 4.66 4.79 4.89 5.04 5.04

1F 6.48 6.57 6.61 6.61 6.61 7.46 7.69 7.85 8.12 8.12

3F 3.86 3.94 3.94 3.94 4.16 3.48 3.55 3.57 3.56 3.56

1F 3.86 3.91 3.87 3.87 4.22 3.72 3.77 3.79 3.70 3.70

3F 3.63 3.71 3.72 3.72 3.84 3.28 3.34 3.35 3.36 3.36

1F 3.62 3.68 3.67 3.67 3.89 3.48 3.53 3.53 3.51 3.51

3F 4.38 4.38 4.90 3.92 4.01 4.06 4.14 4.14

1F 4.55 4.56 5.47 4.59 4.68 4.73 4.72 4.72

3F 3.66 3.76 3.79 3.79 3.85 3.32 3.39 3.38 3.42 3.42

1F 3.99 4.07 4.09 4.09 4.29 3.83 3.90 3.88 3.91 3.91

3F 4.56 4.65 4.64 4.64 5.07 4.06 4.16 4.20 4.17 4.17

1F 5.12 5.20 5.09 5.09 5.93 4.95 5.05 5.09 4.84 4.84

3F 3.26 3.28 3.24 3.26 3.07 3.46 3.46

1F 2.77 2.78 2.76 2.77 2.65 2.90 2.90

3F 1.09 1.75 1.75 2.24 2.24 2.24 2.24 2.17 2.17 2.17

1F 1.17 1.96 1.96 2.50 2.50 2.50 2.50 1.47 1.47 1.47

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Acueducto ACU 34.5

115Aeropuerto Los Cabos AEC

115

34.5

Bahía de los Angeles BAN 34.5

Bahía Tortugas BTO 34.5

Bahía Asunción BAS

Benito Juárez BJZ 34.5

Benito Juárez Maniobras BJM 34.5

Bledales BLE 115

230

115

115

C.D. Los Cabos TCB

Cabo Bello CAB

Cabo del Sol CAS 115

Cabo Falso CAF 115

Cabo Real CRE 115

Cabo San Lucas Dos CAD 115

Camino Real CAR 115

Caopas CAO 34.5

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 278: Catalogo 2011-2020 r010212 Corto Circuito

278

Coordinación de Planificación

ÁREA BAJA CALIFORNIA SUR

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 1.14 1.14 1.43 1.86 1.86 1.86 1.86 2.39 2.39 2.39

1F 1.02 1.02 1.22 1.46 1.46 1.46 1.46 1.87 1.87 1.87

3F 1.86 2.23 2.59 2.59 3.34 3.02 3.39 4.24 4.73 4.73

1F 2.21 2.66 3.10 3.10 3.92 3.63 4.08 5.41 5.96 5.96

3F 5.81 7.15 7.15

1F 7.29 8.89 8.89

3F 1.23 1.23 1.56 2.08 2.08 2.08 2.08 2.75 2.75 2.75

1F 1.19 1.19 1.46 1.81 1.81 1.81 1.81 2.47 2.47 2.47

3F 0.90 0.90 1.03 1.20 1.20 1.20 1.20 1.33 1.33 1.33

1F 0.71 0.71 0.77 0.84 0.84 0.84 0.84 0.94 0.94 0.94

3F 6.71 6.72 6.72

1F 6.67 6.68 6.68

3F 1.65 1.82 1.96 1.96 2.67 2.25 2.35 2.47 2.58 2.58

1F 2.01 2.17 2.30 2.30 3.31 2.86 2.97 3.10 3.21 3.21

3F 4.12 4.25 4.29 4.29 4.37 3.69 3.78 3.77 3.82 3.82

1F 5.20 5.34 5.38 5.38 5.74 4.94 5.05 5.04 5.08 5.08

3F 4.65 4.72 4.78 4.78 4.85 4.78 4.82 4.67 5.46 5.46

1F 5.17 5.26 5.33 5.33 5.41 5.36 5.40 5.32 6.05 6.05

3F 3.09 3.12 3.13 3.16 3.17 3.12 3.13 2.94 3.25 3.25

1F 2.36 2.38 2.38 2.51 2.52 2.50 2.51 2.40 2.58 2.58

3F 0.67 0.85 0.85 0.95 0.95 0.95 0.95 0.86 0.86 0.86

1F 0.53 0.64 0.64 0.68 0.68 0.68 0.68 0.56 0.56 0.56

3F 0.34 0.38 0.38 0.39 0.39 0.39 0.39 0.41 0.41 0.41

1F 0.29 0.32 0.32 0.33 0.33 0.33 0.33 0.31 0.31 0.31

3F 3.06 3.07 3.07 3.07 3.07 3.07 3.07 3.89 3.95 3.95

1F 3.82 3.83 3.83 3.83 3.83 3.83 3.83 4.69 4.74 4.74

3F 1.42 1.42 1.90 2.76 2.76 2.76 2.76 4.16 4.16 4.16

1F 1.56 1.56 2.10 2.94 2.94 2.94 2.94 5.37 5.37 5.37

3F 0.86 0.86 0.95 1.05 1.05 1.05 1.05 1.27 1.27 1.27

1F 0.83 0.83 0.89 0.94 0.94 0.94 0.94 1.34 1.34 1.34

3F 2.31 2.31 2.31 2.31 2.32 2.32 2.32 3.21 3.28 3.28

1F 2.16 2.16 2.16 2.16 2.17 2.16 2.17 2.99 3.03 3.03

3F 0.50 0.50 0.52 0.55 0.55 0.55 0.55 0.60 0.60 0.60

1F 0.50 0.50 0.51 0.53 0.53 0.53 0.53 0.63 0.63 0.63

3F 0.24 0.24 0.25 0.28 0.28 0.28 0.28 0.32 0.32 0.32

1F 0.19 0.19 0.20 0.21 0.21 0.21 0.21 0.26 0.26 0.26

El Infiernito INF

El Palmar ELP

Jesus María JMA

Entronque

Gasera

Insurgentes INS

230

Ejido Díaz Ordaz

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Colonias COL 34.5

230

230

El Triunfo ETR 115

115

34.5

34.5

34.5

ENT

Guerrero Negro Dos GND

34.5LGO

DIO

Ejido Lagunero

Coromuel COR

115

El Recreo REO 115

115

GAS

Guerrero Negro Uno GNO 34.5

General Agustín Olachea GAO 115

34.5

34.5

La Bocana BCA 34.5

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 279: Catalogo 2011-2020 r010212 Corto Circuito

279

Coordinación de Planificación

ÁREA BAJA CALIFORNIA SUR

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 4.36 4.41 4.44 4.45 4.49 4.44 4.47 4.25 5.01 5.01

1F 4.37 4.41 4.44 4.44 4.48 4.45 4.47 4.29 4.92 4.92

3F 2.79 2.80 2.81 2.81 2.82 2.81 2.81 3.13 3.28 3.28

1F 2.37 2.38 2.38 2.38 2.39 2.38 2.39 2.65 2.73 2.73

3F 2.99 3.04 3.04

1F 2.25 2.27 2.27

3F 0.77 0.77 0.77 0.77 0.77 0.77 0.77 0.85 0.86 0.86

1F 0.57 0.57 0.57 0.57 0.57 0.57 0.57 0.62 0.62 0.62

3F 0.68 0.68 0.68 0.74 0.74 0.74

1F 0.49 0.49 0.49 0.53 0.53 0.53

3F 0.78 0.78 0.78 0.78 4.36 4.38 4.38

1F 0.78 0.78 0.78 0.78 1.35 1.35 1.35

3F 3.65 3.68 3.68

1F 4.06 4.08 4.08

3F 0.79 0.79 0.79 0.79 4.38 4.39 4.39

1F 0.79 0.79 0.79 0.79 1.37 1.37 1.37

3F 2.30 2.30 3.29 3.29 3.29 3.29 3.92 3.92 3.92

1F 2.86 2.86 4.21 4.21 4.21 4.21 1.85 1.85 1.85

3F 3.18 3.18 3.22 2.89 2.94 2.87 2.93 2.93

1F 2.83 2.83 2.91 2.72 2.75 2.71 2.74 2.74

3F 1.07 1.07 1.28 1.58 1.58 1.58 1.58 1.88 1.88 1.88

1F 0.87 0.87 0.98 1.11 1.11 1.11 1.11 1.29 1.29 1.29

3F 0.40 0.45 0.45 0.48 0.48 0.48 0.48 0.50 0.50 0.50

1F 0.36 0.40 0.40 0.41 0.41 0.41 0.41 0.39 0.39 0.39

3F 0.29 0.29 0.30 0.30 0.30 0.30 0.30 0.32 0.32 0.32

1F 0.29 0.29 0.30 0.31 0.31 0.31 0.31 0.33 0.33 0.33

3F 1.88 2.22 2.54 2.54 3.29 2.96 3.27 4.09 4.51 4.51

1F 2.27 2.66 3.01 3.01 3.78 3.48 3.81 4.77 5.17 5.17

3F 4.88 4.97 5.03 5.03 5.11 5.04 5.08 4.94 5.81 5.81

1F 5.93 6.06 6.16 6.16 6.28 6.21 6.27 6.21 7.15 7.15

3F 3.22 3.30 3.32 3.32 3.37 2.97 3.02 3.00 3.04 3.04

1F 3.10 3.14 3.16 3.16 3.27 3.01 3.04 3.03 3.05 3.05

3F 4.14 4.19 4.22 4.22 4.26 4.22 4.24 4.02 4.73 4.73

1F 3.92 3.95 3.98 3.98 4.00 3.98 3.99 3.82 4.36 4.36

3F 0.22 0.22 0.23 0.23 0.23 0.23 0.23 0.24 0.24 0.24

1F 0.23 0.23 0.23 0.24 0.24 0.24 0.24 0.25 0.25 0.25

MINMina

Nuevo Rosarito NRO

Olas Altas OLA

LPSLas Pilas (Las Pocitas)

115

Loreto LRO

115

34.5

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

La Paz LPZ

230

115

Loreto Paraiso LOP 115

Mezquital MSE 115

230

Monte Real MRE 115

Mújica MUJ 34.5

Mulegé MUL 34.5

34.5

230

115

Palmilla PML 115

Palmira PAA 115

Parador PAR 34.5

115

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 280: Catalogo 2011-2020 r010212 Corto Circuito

280

Coordinación de Planificación

ÁREA BAJA CALIFORNIA SUR

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 0.87 0.87 0.87 0.87 0.87 0.87 0.87 0.97 0.98 0.98

1F 0.65 0.65 0.65 0.65 0.65 0.65 0.65 0.71 0.72 0.72

3F 0.29 0.29 0.31 0.35 0.35 0.35 0.35 0.41 0.41 0.41

1F 0.23 0.23 0.24 0.26 0.26 0.26 0.26 0.33 0.33 0.33

3F 0.22 0.22 0.23 0.25 0.25 0.25 0.25 0.28 0.28 0.28

1F 0.17 0.17 0.17 0.18 0.18 0.18 0.18 0.22 0.22 0.22

3F 0.19 0.19 0.20 0.21 0.21 0.21 0.21 0.23 0.23 0.23

1F 0.14 0.14 0.14 0.15 0.15 0.15 0.15 0.17 0.17 0.17

3F 0.37 0.37 0.40 0.47 0.47 0.47 0.47 0.60 0.60 0.60

1F 0.29 0.29 0.30 0.34 0.34 0.34 0.34 0.47 0.47 0.47

3F 5.72 5.80 5.85 5.86 5.92 5.84 5.88 5.35 6.81 6.81

1F 6.76 6.85 6.90 6.90 6.97 6.90 6.94 6.21 8.06 8.06

3F 5.77 5.85 5.90 5.91 5.97 5.89 5.93 5.44 6.95 6.95

1F 6.91 7.00 7.06 7.06 7.13 7.05 7.09 6.41 8.41 8.41

3F 0.63 0.63 0.71 0.79 0.79 0.79 0.79 0.87 0.87 0.87

1F 0.40 0.40 0.42 0.45 0.45 0.45 0.45 0.48 0.48 0.48

3F 2.49 2.50 2.51 2.51 2.52 2.51 2.52 2.50 2.67 2.67

1F 1.99 2.00 2.01 2.01 2.01 2.01 2.01 2.02 2.10 2.10

3F 2.31 2.32 2.32 2.32 2.33 2.32 2.33 2.41 2.52 2.52

1F 1.83 1.84 1.84 1.84 1.84 1.84 1.84 1.91 1.96 1.96

3F 0.64 0.80 0.80 0.87 0.87 0.87 0.87 0.95 0.95 0.95

1F 0.49 0.58 0.58 0.62 0.62 0.62 0.62 0.55 0.55 0.55

3F 0.35 0.35 0.37 0.43 0.43 0.43 0.43 0.53 0.53 0.53

1F 0.26 0.26 0.27 0.30 0.30 0.30 0.30 0.40 0.40 0.40

3F 0.35 0.39 0.39 0.41 0.41 0.41 0.41 0.41 0.41 0.41

1F 0.23 0.25 0.25 0.26 0.26 0.26 0.26 0.25 0.25 0.25

3F 3.45 3.54 3.56 3.57 3.62 3.17 3.24 3.19 3.24 3.24

1F 3.43 3.48 3.50 3.50 3.63 3.32 3.37 3.33 3.37 3.37

3F 0.46 0.46 0.50 0.63 0.63 0.63 0.63 0.88 0.88 0.88

1F 0.38 0.38 0.41 0.47 0.47 0.47 0.47 0.78 0.78 0.78

3F 0.36 0.48 0.48 0.78 0.78 0.78 0.78 3.25 3.26 3.26

1F 0.39 0.53 0.53 0.81 0.81 0.81 0.81 1.41 1.42 1.42

3F 1.28 2.30 2.30 3.25 3.25 3.25 3.25 3.92 3.92 3.92

1F 1.38 2.65 2.65 3.74 3.74 3.74 3.74 1.95 1.95 1.95

3F 0.26 0.26 0.27 0.27 0.27 0.27 0.27 0.28 0.28 0.28

1F 0.26 0.26 0.27 0.27 0.27 0.27 0.27 0.30 0.30 0.30

Punta Abreojos PAO 34.5

Punta Eugenia PEU 34.5

Punta Prieta PPA 34.5

Punta Prieta I PUI 115

Punta Prieta II PUP 115

Rancho el Silencio RSI 34.5

Reformas Agrarias REA 115

EPN

Rofomex RFO 115

San Bruno SNB 34.5

San Hipolito HTO 34.5

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

San Ignacio SIN 34.5

San José del Cabo SJC 115

San Roque SRQ 34.5

Santa Rosalía SRI

115

34.5

Santa Rosaliíta STR 34.5

Puerto Escondido PES 115

Puerto Nuevo 34.5

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 281: Catalogo 2011-2020 r010212 Corto Circuito

281

Coordinación de Planificación

ÁREA BAJA CALIFORNIA SUR

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 2.32 2.34 2.33 2.34 2.35 2.25 2.27 2.17 2.25 2.25

1F 1.72 1.73 1.72 1.73 1.75 1.71 1.72 1.68 1.71 1.71

3F 1.89 1.89 1.89 1.89 1.89 1.89 1.89 2.44 2.48 2.48

1F 1.57 1.57 1.57 1.57 1.57 1.57 1.57 1.96 1.98 1.98

3F 0.46 0.54 0.54 0.58 0.58 0.58 0.58 0.51 0.51 0.51

1F 0.33 0.37 0.37 0.38 0.38 0.38 0.38 0.34 0.34 0.34

3F 0.30 0.30 0.37 0.71 0.71 0.71 0.71 1.28 1.28 1.28

1F 0.32 0.32 0.39 0.71 0.71 0.71 0.71 0.54 0.54 0.54

3F 0.31 0.34 0.34 0.35 0.35 0.35 0.35 0.37 0.37 0.37

1F 0.26 0.28 0.28 0.28 0.28 0.28 0.28 0.27 0.27 0.27

3F 2.08

1F 2.18

3F 0.36 0.47 0.47 0.74 0.74 0.74 0.74 2.66 2.66 2.66

1F 0.39 0.47 0.47 0.69 0.69 0.69 0.69 1.04 1.04 1.04

3F 1.17 1.17 1.46 1.89 1.89 1.89 1.89 2.39 2.39 2.39

1F 0.88 0.88 1.00 1.14 1.14 1.14 1.14 1.36 1.36 1.36

3F 3.25 3.38 3.38

1F 2.22 2.26 2.26

3F 3.12 3.12 3.12 3.12 3.13 3.12 3.13 5.00 5.17 5.17

1F 3.37 3.37 3.38 3.38 3.38 3.38 3.38 5.93 6.10 6.10

3F 0.76 0.76 0.87 1.01 1.01 1.01 1.01 1.14 1.14 1.14

1F 0.55 0.55 0.60 0.65 0.65 0.65 0.65 0.72 0.72 0.72

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Secundaria SEC 34.5

Sitio Vizcaíno VIZ 115

Tiburones TIB 34.5

Todos Santos TOS 230

Santiago SNT 115

Tres Vírgenes GLV 115

Santo Domingo DOM 115

Valle de Vizcaíno VVI 34.5

Villa Constitución VIO

230

115

Zapata ZAP 34.5

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____

Page 282: Catalogo 2011-2020 r010212 Corto Circuito

282

Coordinación de PlanificaciónESTUDIO DE CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

ÁREA PENINSULAR

______________Catálogo de Corto Circuito 2011-2020 _______Catálogo de Corto Circuito 2011-2020_____

Page 283: Catalogo 2011-2020 r010212 Corto Circuito

283

Coordinación de PlanificaciónRED ELÉCTRICA PRINCIPAL 2011

ÁREA PENINSULAR

26.89- 900

TICUL II

XUL – HA

ESCÁRCEGA

VALLADOLID

+300 MVAr

-300 MVAr

EDZNÁ

+150 MVAr

-50 MVAr

OP. INI.

OP. INI. 230 KV

XPUJIL

SANTA LUCÍA

A TA

BA

SC

O

PO

TE

NC

IA

A MACUSPANA II

A LOS RÍOS

151.04 -1113

266.9

3-1

113

157.95 -1113

62.56-1113

270.22- 477

2 C/F

64.3

3-

900

60.7

2-

1113 145.12 - 900

MAKE

BY

ELL

168.23-1113

157.64-1113

173.

26-1

113

154.

06-1

113

298.02

-111

3

141.71 - 900

126.12 - 900

1 X 71 MW

1 X 80 MW

1 X 70.5 MW

1 X 525 MW

1 X 100 MVA

230/115 kV

1 X 252.4 MW

1 X 100 MVA

230/115 kV

1 x 15 MVAr

2 X 375 MVA

400/230 kV

1 X 225 MVA

230/115 kV

2 X 100 MVA

230/115 kV

2 X 25 MVAr

2 X14 MW

2 X 100 MVA

230/115 kV

+40 MVAr

-10 MVAr

NORTE

MÉRIDA

POTENCIA

CAUCEL

POTENCIA

KANASÍN

POTENCIA

A VALLADOLID

-1113

31.0

5

1 X 225 MVA

230/115 kV17.4

8-1

113

1 X 225 MVA

230/115 kV-111

3

11.1

7

1 X 484 MW

29.93 -1113

- 900

64.3

3 A TICUL II

2 X 100 MVA

230/115 kV

- 1113

60.72

145.12 - 900

OP. INI. 115 kV

230 kV

18 MVAr

16.5 MVAr

75 MVAr

21 MVAr

18 MVAr

18 M

VA

r

16.5 MVAr

18 MVAr

21MVAr

16.5 MVAr18 MVAr

BALAM

NIZUC

161.77 -1113

168.23 -1113

A VALLADOLID

38.13 -1113

70.2

6-1

113

157.64-1113

40.2

5-1

113

29.5

7-1

113

2 X 100 MVA

230/115 kV

2 X 225 MVA

230/115 kV

+100 MVAr

-30 MVAr

OP. IN

I. 230 kV

PLAYA DEL

CARMEN

2 X 100 MVA

230/115 kV

1 x 18 MVAr

2 X 44 MW

2 X 18 MVAr

30 - 1113

21

MV

Ar

Zona Mérida

Zonas Cancún Y Riviera Maya

115 k

V

INI.

OP.

100 MVAr

18 MVAr

S i m b o l o g í a

400 kV

Ciclo Combinado

Geotermoeléctrica

Hidroeléctrica

Térmica Convencional

Dual

Carboeléctrica

Nivel de Tensión

230 kV

115 kV

161 kV, 69 kV

y media tensión

Subestación

Línea de Transmisión

Reactor

Compensador Estático de Vars

Estructura de Doble Circuito

Tendido del Primero

Nuevos proyectos

Retiros o trasladosTurbogás

CARMEN

1 X 14 MW

1 X 16 MW

1 X 17 MW

LERMA

3 X 37.5 MW

13.5

– 795

+ 44

.2 –1

113

33.27 – 477 +

44.2

– 1113 + 3

.3 - 995

SABANCUY II

+ 3.3 –995 + 26.14 –477

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 284: Catalogo 2011-2020 r010212 Corto Circuito

284

Coordinación de PlanificaciónRED ELÉCTRICA PRINCIPAL 2020

ÁREA PENINSULAR

26.89- 900

TICUL II

XUL – HA

ESCÁRCEGA

VALLADOLID

+300 MVAr

-300 MVAr

EDZNÁ

+150 MVAr

-50 MVAr

SANTA LUCÍA

A TA

BA

SC

O

PO

TE

NC

IA

A MACUSPANA II

A LOS RÍOS

151.04 -1113

266.9

3-1

113

157.95 -1113

-1113

270.22- 477

2 C/F

64.3

3-

900

60.7

2-

1113 145.12 - 900

MAKE

BY

ELL

168.23-1113

157.64-1113

173.

26-1

113

154.

06-1

113

298.02

-111

3

141.71 - 900

126.12 - 900

1 X 71 MW

1 X 80 MW

1 X 70.5 MW

1 X 525 MW

2 X 100 MVA

230/115 kV

1 X 252.4 MW

2 X 100 MVA

230/115 kV

1 x 15 MVAr

2 X 375 MVA

400/230 kV

1 X 225 MVA

230/115 kV

2 X 100 MVA

230/115 kV

2 X 25 MVAr

2 X14 MW

2 X 100 MVA

230/115 kV

+40 MVAr

-10 MVAr

NORTE

MÉRIDA

POTENCIA

CAUCEL

POTENCIA

KANASÍN

POTENCIA

A VALLADOLID

-1113

31.0

5

1 X 225 MVA

230/115 kV17.4

8-1

113

1 X 225 MVA

230/115 kV-111

3

11.1

7

1 X 484 MW

29.93 -1113

- 900

64.3

3 A TICUL II

2 X 100 MVA

230/115 kV

- 1113

60.72

145.12 - 900

OP. INI. 115 kV

18 MVAr

16.5 MVAr

75 MVAr

21 MVAr

18 MVAr

18 M

VA

r

16.5 MVAr

62 MVAr

16.5 MVAr

18 MVAr

30 - 1113

21

MV

Ar

Zona Mérida

Zonas Cancún Y Riviera Maya

CHICHI

SUÁREZ1 X 225 MVA

230/115 kV

OP. INI. 115 kV

-1113105

50 MVAr

62.56

XPUJIL

40.2

5-1

113

2 X 100 MVA

230/115 kV

A VALLADOLID

70.2

6-1

113

29.5

7

+100 MVAr

-30 MVAr

PLAYA DEL

CARMEN

BALAM

161.77 -1113

168.23 -1113

157.64-1113

2 X 225 MVA

230/115 kV

RIVIERA

MAYA

2 X 44 MW

2 X 18 MVAr

1 X 375 MVA

400/230 Kv

1 X 375 MVA

400/115 kV

-111

3

3 X 100 MVA

230/115 kV

1 x 18 MVAr

38.13 -1113

100 MVAr

18 MVAr

+300 MVAr

-90 MVAr

NIZUC

16.5

- 1

113

DZITNUP

S i m b o l o g í a

400 kV

Ciclo Combinado

Geotermoeléctrica

Hidroeléctrica

Térmica Convencional

Dual

Carboeléctrica

Nivel de Tensión

230 kV

115 kV

161 kV, 69 kV

y media tensión

Subestación

Línea de Transmisión

Reactor

Compensador Estático de Vars

Estructura de Doble Circuito

Tendido del Primero

Nuevos proyectos

Retiros o trasladosTurbogás

CARMEN

1 X 14 MW

1 X 16 MW

1 X 17 MW

SABANCUY II1 X 225 MVA

230/115 kV

13.5

– 795

+ 44

.2 –1

113

33.27 – 477 +

44.2

– 1113 + 3

.3 - 995

+ 3.3 –995 + 26.14 –477

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 285: Catalogo 2011-2020 r010212 Corto Circuito

285

Coordinación de PlanificaciónADICIONES Y RETIROS DE GENERACIÓN

ÁREA PENINSULAR

ADICIONES:

Nombre de la Central Año Capacidad

Mérida 2020 567 MW

RETIROS:

Nombre de la Central Año Capacidad

Lerma (U2, U3 y U4) 2011 112.5 MW

Felipe Carrillo Puerto (U1 y U2) 2011 75 MW

Mérida II (U1 y U2) 2020 168 MW

El retiro de las unidades de generación de Lerma y Felipe Carrillo Puerto provoca un decremento en los niveles de corto

circuito para las subestaciones adyacentes en 230 kV y 115 kV, esta situación se presenta en las zonas Mérida,B

Campeche, Ciudad del Carmen y Tizimín.

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 286: Catalogo 2011-2020 r010212 Corto Circuito

286

Coordinación de PlanificaciónPRINCIPALES PROYECTOS DE TRANSMISIÓN Y TRANSFORMACIÓN

ÁREA PENINSULAR

Proyecto Año Nivel de tensión

Playa del Carmen Banco 3 2014 230 /115

Riviera Maya Banco 1 2014 400 /230

Riviera Maya Banco 2 2014 400 /115

Ticul Banco 4 2015 230 /115

Xpujil - Xul Ha 2017 230

Chichi Suárez Banco 1 2018 230 /115

Escárcega - Sabancuy II 2019 230

Sabancuy II Banco 2 2019 230 /115

Valladolid Banco 4 2019 230 /115

El proyecto de transmisión y transformación Conversión a 400 kV Ticul– Valladolid – Riviera Maya no impactará

prácticamente en el nivel de corto circuito monofásico y trifásico a las zonas Cancún y Riviera Maya. Para el periodo

2013-2014, en la subestación Ticul II 400 kV el nivel de corto circuito trifásico se mantiene en 5.4 kA, en la subestación

Valladolid 230 kV el nivel de corto circuito trifásico disminuye de 12.5 kA a 10.2 kA, ya que entra en operación el

corredor de 400 kV. En las subestaciones Balam y Nizuc 230 kV el nivel de corto circuito trifásico se incrementa de 6.2

kA a 6.5 kA y de 6.8 kA a 7.4 kA, respectivamente.

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 287: Catalogo 2011-2020 r010212 Corto Circuito

287

Coordinación de PlanificaciónPRINCIPALES PROYECTOS DE TRANSMISIÓN Y TRANSFORMACIÓN

ÁREA PENINSULAR

Otro de los proyectos importantes para el área peninsular es el enlace entre las subestaciones Xul Ha y Xpujil, aislado

en 230 kV con un circuito operado en 115 kV propuesto para 2017. Por lo tanto, para el periodo 2016-2017, en la

subestación Xpujil 115 kV el nivel de corto circuito trifásico aumenta de 2.2 kA a 3 kA y en la subestación Xul Ha 115 kV

el nivel de corto circuito trifásico aumenta de 2.7 kA a 3.5 kA y para la misma subestación pero en 230 kV también

aumenta el nivel de corto circuito trifásico de 1.4 kA a 1.7 kA.

A continuación para 2020 , se muestran los valores máximos obtenidos en su nivel de corto circuito de acuerdo a la

tensión:

. Subestación Tensión Corriente de Falla

3F 1F

Mérida II 115 kV 21.8 kA 25.2 kA

Mérida Potencia 230 kV 11.8 kA 13.7 kA

Ticul II 400 kV 5.8 kA 5.3 kA

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 288: Catalogo 2011-2020 r010212 Corto Circuito

288

Coordinación de Planificación

ÁREA PENINSULAR

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 6.22 6.22 6.22 6.15 6.37 6.37 6.37 6.41 6.40 6.57

1F 4.60 4.60 4.60 4.57 4.69 4.69 4.69 4.71 4.71 4.77

3F 4.12 4.12 4.12 4.09 4.11 4.11 4.14 4.15 4.14 4.17

1F 3.55 3.55 3.55 3.53 3.54 3.54 3.56 3.56 3.56 3.58

3F 3.57 3.58 3.58 3.59 3.59 3.60 3.60

1F 2.63 2.63 2.62 2.62 2.61 2.61 2.61

3F 3.87 3.87 3.86 3.99 3.68 3.68 3.68 3.96 3.97 3.94

1F 2.84 2.84 2.84 3.10 2.86 2.86 2.86 3.15 3.15 3.06

3F 16.22 16.22 16.21 16.03 16.09 16.09 16.10 16.25 16.21 18.65

1F 17.59 17.59 17.57 17.44 17.49 17.49 17.49 17.67 17.64 19.72

3F 3.70 3.70 3.70 3.70 3.70 3.70 3.70 4.52 4.53 4.54

1F 3.02 3.02 3.02 3.02 3.02 3.02 3.02 3.72 3.72 3.71

3F 1.41

1F 0.85

3F 12.66 12.66 12.88 13.43 13.66 13.66 13.67 13.68 13.68 13.71

1F 15.96 15.96 16.29 16.90 17.15 17.15 17.15 17.16 17.16 17.18

3F 6.13 6.13 6.18 6.50 6.57 6.57 6.57 6.58 6.58 6.60

1F 7.02 7.02 7.10 7.40 7.46 7.46 7.46 7.47 7.46 7.48

3F 11.02 11.12 11.22 11.58 11.78 11.78 11.78 11.79 11.79 11.82

1F 12.20 12.30 12.36 12.65 12.80 12.80 12.80 12.81 12.81 12.83

3F 11.32 11.32 11.31 11.62 11.92 11.92 11.92 11.93 11.93 11.97

1F 12.23 12.23 12.22 12.47 12.69 12.69 12.70 12.70 12.70 12.73

3F 5.00 5.00 4.99 5.09 5.35 5.35 5.35 5.82 5.84 5.85

1F 4.24 4.24 4.23 4.47 4.85 4.85 4.85 5.29 5.29 5.30

3F 2.94 2.94 2.94 2.93 2.97 2.97 2.97 2.97 2.97 3.00

1F 1.93 1.93 1.93 1.93 1.95 1.95 1.95 1.95 1.95 1.96

3F 10.49 10.49 10.48 10.41 10.44 10.44 10.44 12.92 12.88 13.87

1F 8.77 8.77 8.77 8.73 8.75 8.75 8.75 11.69 11.67 12.20

3F 13.67 13.67 13.49 13.94 14.27 14.27 14.27 14.28 14.28 14.33

1F 20.48 20.48 20.20 20.88 21.37 21.37 21.37 21.39 21.39 21.47

3F 1.63 1.63 1.63 1.68 1.67 1.67 1.67

1F 1.17 1.17 1.17 1.18 1.18 1.18 1.18

3F 11.32 11.32 11.27 11.62 11.83 11.83 11.83 11.84 11.84 11.87

1F 12.39 12.39 12.37 12.65 12.81 12.81 12.81 12.81 12.82 12.84

3F 2.62 2.62 2.62 2.62 2.62 2.62 2.67 3.05 3.05 3.05

1F 3.93 3.93 3.93 3.93 3.93 3.93 4.00 4.57 4.57 4.58

Candelaria CDL 115

115

115

Canek CEK

Carmen CRE

Campestre CPE 115

Cancún CNC 115

115

115

Calica CLC

Calkini II CKD

Bonampak BNP 115

Bonfil BNI 115

Ayim AYM 115

115Balam BLM

230

Alom ALO 115

Aventura Palace AVP 115

Aktunchen AKT 115

Akumal AKM 115

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Acanceh AAH 115

Akin pech AKP 115

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 289: Catalogo 2011-2020 r010212 Corto Circuito

289

Coordinación de Planificación

ÁREA PENINSULAR

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 17.50 17.50 17.48 17.27 17.34 17.34 17.34 17.49 17.45 20.06

1F 20.94 20.94 20.90 20.71 20.78 20.78 20.78 21.02 20.98 23.59

3F 10.33 10.33 10.34 10.17 10.21 10.21 10.22 10.27 10.24 11.23

1F 11.63 11.63 11.64 11.50 11.54 11.54 11.55 11.74 11.72 12.59

3F 2.34 2.34 2.34 2.33 2.34 2.34 2.35 2.36 2.36 2.37

1F 1.69 1.69 1.69 1.69 1.69 1.69 1.69 1.70 1.70 1.70

3F 11.77 11.77 11.77 11.68 11.72 11.72 11.72 11.86 11.84 13.40

1F 10.33 10.33 10.33 10.29 10.31 10.31 10.31 10.40 10.40 11.40

3F 13.15 13.15 13.16 13.04 13.09 13.09 13.10 14.21 14.17 15.61

1F 12.06 12.06 12.06 12.00 12.03 12.03 12.03 13.43 13.41 14.29

3F 10.77 10.77 10.60 10.55 10.53 10.53 10.53 10.54 10.54 10.01

1F 10.72 10.72 10.32 9.92 9.87 9.87 9.88 9.88 9.88 9.02

3F 3.84 3.84 3.84 3.83 3.84 3.84 3.93 4.12 4.12 4.14

1F 3.17 3.17 3.17 3.16 3.16 3.16 3.21 3.38 3.38 3.38

3F 2.90 2.91 3.00 3.00

1F 1.92 1.92 1.95 1.95

3F 2.04 2.04 2.04 2.43 2.43 2.43 2.42

1F 2.21 2.21 2.21 2.50 2.50 2.50 2.50

3F 2.28 2.28 2.28 2.27 2.27 2.27 2.76 2.76 2.76 2.76

1F 2.72 2.72 2.72 2.71 2.71 2.71 3.16 3.16 3.16 3.15

3F 3.28 3.28 3.29 3.28 3.28 3.29 3.46 3.81 3.81 3.93

1F 2.96 2.96 2.96 2.96 2.96 2.96 3.05 3.54 3.54 3.27

3F 17.92 17.83 19.76

1F 21.42 21.33 23.16

3F 10.11 10.08 11.01

1F 11.13 11.11 11.86

3F 11.30 11.30 11.29 11.21 11.24 11.24 11.24 12.75 12.71 13.67

1F 9.75 9.75 9.74 9.70 9.72 9.72 9.72 11.47 11.45 11.97

3F 13.43 13.43 13.44 13.31 13.35 13.35 13.36 13.68 13.65 14.93

1F 12.92 12.92 12.92 12.84 12.87 12.87 12.87 13.18 13.16 13.96

3F 2.44 2.44 2.44 2.44 2.44 2.44 2.48 2.84 2.84 2.84

1F 3.05 3.05 3.05 3.05 3.05 3.05 3.10 3.46 3.46 3.47

3F 7.16 7.17 7.17 7.28

1F 6.14 6.14 6.14 6.20

3F 3.34 3.35

1F 2.05 2.06

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

115

230

Cayal CYL 115

Cementos Maya CMY 115

Centro CNO 115

Chaac HAA 115

Champotón CMO 115

115

115

115

230

CCS

Chetumal Norte CTE 115

Chicbul CBU 115

Cholul HOL 115

Chuburna CBR 115

Dzitas DZS 115

Caucel Potencia CCP

Chetumal Centro CCO

Chemax CHX

Chichi Suárez

Concordia CNR 115

Dzan DZN 115

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 290: Catalogo 2011-2020 r010212 Corto Circuito

290

Coordinación de Planificación

ÁREA PENINSULAR

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 4.23 4.44 4.44 4.44 4.45 4.46 4.53

1F 3.72 3.92 3.92 3.92 3.93 3.93 3.97

3F 13.39 13.39 13.26 13.30 13.30 13.31 13.62 13.59 14.87

1F 12.84 12.84 12.76 12.79 12.79 12.79 13.09 13.07 13.86

3F 3.40 3.40 3.40 3.36 3.37 3.38 3.41 3.42 3.42 3.45

1F 3.73 3.73 3.73 3.69 3.71 3.71 3.74 3.74 3.74 3.77

3F 5.34 5.34 5.35 5.34 5.34 5.34 5.96 5.81 5.81 5.84

1F 6.83 6.83 6.84 6.83 6.83 6.84 7.50 7.39 7.39 7.41

3F 3.55 3.55 3.57 3.55 3.56 3.56 3.78 3.94 3.94 3.95

1F 4.55 4.55 4.56 4.55 4.56 4.56 4.80 5.07 5.07 5.08

3F 4.76 4.76 4.79 4.86 4.91 4.91 4.91 4.92 4.92 4.97

1F 3.38 3.38 3.39 3.46 3.52 3.52 3.52 3.52 3.52 3.55

3F 2.83 2.83 2.83 2.81 2.87 2.87 2.87 2.88 2.88 2.89

1F 1.94 1.94 1.94 1.94 1.97 1.97 1.97 1.97 1.97 1.97

3F 15.73 15.73 15.73 15.57 15.63 15.63 15.64 15.89 15.86 18.79

1F 16.40 16.40 16.40 16.29 16.33 16.33 16.34 16.58 16.56 19.25

3F 9.90 10.02 10.10 10.38 10.62 10.62 10.62 10.63 10.63 10.59

1F 9.30 9.50 9.67 9.86 10.01 10.01 10.01 10.01 10.01 9.92

3F 5.68 5.68 5.68 5.65 5.66 5.66 5.66 5.68 5.67 5.92

1F 4.06 4.06 4.06 4.05 4.05 4.05 4.05 4.06 4.06 4.15

3F 5.18 5.18 5.18 3.52 7.91 7.91 7.92 7.96 7.96 8.00

1F 4.04 4.04 4.04 2.73 6.87 6.87 6.87 6.89 6.89 6.91

3F 2.30 2.30 2.30 2.29 2.29 2.29 2.79 2.79 2.79 2.79

1F 2.77 2.77 2.77 2.75 2.76 2.76 3.22 3.22 3.22 3.22

3F 12.70 12.70 12.71 12.60 12.65 12.65 12.65 13.14 13.11 14.66

1F 11.34 11.34 11.34 11.28 11.31 11.31 11.31 11.79 11.78 12.72

3F 3.24 3.24 3.24 3.24 3.24 3.24 3.24 3.44 3.13 3.16

1F 2.09 2.09 2.09 2.09 2.09 2.09 2.09 2.14 1.87 1.88

3F 10.18 10.32 10.46 10.77 11.02 11.02 11.02 11.03 11.03 10.26

1F 9.97 10.10 10.24 10.46 10.61 10.61 10.61 10.62 10.62 9.33

3F 4.82 4.82 4.83 4.79 4.81 4.81 4.85 4.86 4.86 4.90

1F 4.44 4.44 4.44 4.41 4.43 4.43 4.45 4.46 4.46 4.48

3F 1.74 1.74 1.74 1.73 1.77 1.77 1.81 1.81 1.81 1.78

1F 1.15 1.15 1.15 1.15 1.17 1.17 1.18 1.18 1.18 1.11

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

400

115

Edzna EDA 230

Dzitnup DZP

400

Hecelchacan HCE 115

115

230

115

Iberostar IBR 115

Hidrogeneradora Yucateca HRA 115

Hunab Ku HBK 115

115

115

Izamal IZL 115

Itzaes IZE

Kambul KBL 115

Kabah KAB 115

Kala KAL 115

Dzitya DZT

Escárcega ESA

Insurgentes INS

Hunucma HNC

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 291: Catalogo 2011-2020 r010212 Corto Circuito

291

Coordinación de Planificación

ÁREA PENINSULAR

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 15.47 15.47 15.48 15.27 15.39 15.39 15.40 15.87 15.83 17.28

1F 21.46 21.46 21.47 21.20 21.37 21.37 21.38 22.11 22.06 23.93

3F 11.07 11.07 11.07 10.82 10.88 10.88 10.89 11.03 11.01 11.97

1F 11.52 11.52 11.53 11.36 11.45 11.45 11.46 11.89 11.87 12.61

3F 2.35

1F 1.51

3F 5.14 5.14 5.13 5.20 5.23 5.23 5.23 5.23 5.24 5.25

1F 3.75 3.75 3.75 3.78 3.79 3.79 3.79 3.79 3.79 3.79

3F 3.16 3.16 3.16 3.15 3.16 3.16 3.16 3.59 3.60 3.65

1F 2.04 2.04 2.04 2.04 2.04 2.04 2.04 2.33 2.34 2.35

3F 10.92 10.92 10.93 11.28 11.47 11.47 11.47 11.48 11.48 11.50

1F 11.66 11.66 11.69 11.96 12.10 12.10 12.10 12.11 12.11 12.12

3F 2.49 2.49 2.49 2.48 2.49 2.49 2.53 2.89 2.89 2.89

1F 3.26 3.26 3.26 3.26 3.26 3.26 3.31 3.71 3.71 3.72

3F 1.75 1.75 1.75 1.75 1.75 1.75 1.94 1.94 1.94 1.91

1F 1.45 1.45 1.45 1.45 1.45 1.45 1.53 1.53 1.53 1.50

3F 6.42 6.42 6.43 6.36 6.39 6.39 6.46 6.49 6.49 6.56

1F 7.90 7.90 7.90 7.83 7.87 7.87 7.94 7.97 7.97 8.04

3F 0.95 0.95 0.95 0.95 0.95 0.95 1.00 1.00 1.00 0.99

1F 0.67 0.67 0.67 0.67 0.67 0.67 0.69 0.69 0.69 0.68

3F 11.14 11.52 11.89 12.27 12.51 12.51 12.51 12.52 12.52 12.55

1F 13.57 13.93 14.28 14.64 14.86 14.86 14.87 14.88 14.88 14.91

3F 5.94 5.94 5.95 5.89 6.09 6.09 6.09 6.12 6.12 6.27

1F 4.35 4.35 4.35 4.33 4.44 4.44 4.44 4.45 4.45 4.50

3F 4.71 4.71 4.71 4.67 4.82 4.82 4.82 4.83 4.83 4.92

1F 3.23 3.23 3.23 3.22 3.29 3.29 3.29 3.30 3.30 3.32

3F 7.09 7.11 7.13 7.15 7.18 7.18 7.19 7.24 7.24 7.27

1F 6.26 6.28 6.29 6.30 6.31 6.31 6.31 6.34 6.35 6.36

3F 17.78 17.78 17.78 17.58 17.66 17.66 17.67 17.99 17.95 21.79

1F 20.53 20.53 20.53 20.35 20.42 20.42 20.43 20.81 20.78 25.20

3F 12.12 12.12 12.12 12.01 12.06 12.06 12.07 12.78 12.75 13.71

1F 11.50 11.50 11.50 11.43 11.47 11.47 11.48 12.18 12.16 12.73

3F 10.88 10.88 10.88 10.71 10.75 10.75 10.76 10.84 10.82 11.72

1F 12.79 12.79 12.80 12.64 12.68 12.68 12.69 12.87 12.85 13.69

3F 13.13 13.13 13.13 13.01 13.07 13.07 13.08 13.37 13.34 15.00

1F 11.93 11.93 11.93 11.87 11.90 11.90 11.90 12.14 12.12 13.16

Kaxaytuk KXT 115

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Kanasín Potencia KNP

115

230

Kohunlinch KHU 115

Kopte KOP 115

Kukulkan KUK 115

Laguna de Términos LTE 115

Lázaro Cárdenas LAC 115

Lerma LRA 115

Mahahual MHH 115

Malecón Cancún MCN 115

115

115

Mayacoba MYK 115

Manufacturera Lee de México LEE

Maxcanú MAX

Mérida Potencia MDP 230

Metropolitana MTO 115

Mérida II MDA 115

Mérida Oriente MDN 115

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 292: Catalogo 2011-2020 r010212 Corto Circuito

292

Coordinación de Planificación

ÁREA PENINSULAR

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 6.68 6.69 6.70 6.70 6.71 6.71 6.71 6.72 6.72 6.74

1F 5.10 5.11 5.11 5.11 5.11 5.11 5.12 5.12 5.12 5.13

3F 15.55 15.55 15.55 15.39 15.47 15.47 15.47 17.68 17.60 19.58

1F 16.20 16.20 16.20 16.08 16.15 16.15 16.15 20.11 20.04 21.75

3F 10.56 10.56 10.44 10.78 10.96 10.96 10.96 10.97 10.97 10.96

1F 10.83 10.83 10.52 10.76 10.88 10.88 10.88 10.88 10.88 10.85

3F 11.37 11.37 11.19 11.48 11.87 11.87 11.88 11.89 11.89 11.93

1F 12.04 12.04 11.78 12.05 12.34 12.34 12.34 12.35 12.35 12.38

3F 14.23 14.23 14.16 14.59 15.29 15.29 15.29 15.32 15.32 15.38

1F 19.49 19.49 19.38 20.13 21.03 21.03 21.03 21.06 21.07 21.14

3F 6.81 6.81 6.80 7.42 7.42 7.42 7.43 7.44 7.44 7.49

1F 7.34 7.34 7.31 8.13 8.14 8.14 8.14 8.16 8.16 8.19

3F 15.99 15.99 15.94 15.76 15.81 15.81 15.82 16.63 16.58 18.31

1F 18.75 18.75 18.69 18.52 18.58 18.58 18.59 19.75 19.70 21.32

3F 9.99 9.99 9.99 9.83 9.87 9.87 9.87 9.94 9.91 10.86

1F 10.86 10.86 10.86 10.73 10.77 10.77 10.78 11.11 11.09 11.89

3F 2.47 2.47 2.47 2.47 2.47 2.47 2.52 3.00 3.00 3.01

1F 2.30 2.30 2.30 2.30 2.30 2.30 2.33 2.74 2.74 2.74

3F 8.03 8.03 8.02 7.83 9.08 9.08 9.08 9.21 9.22 9.26

1F 9.10 9.10 9.09 9.52 10.85 10.85 10.85 10.98 10.99 11.03

3F 4.70 4.70 4.70 5.53 5.61 5.61 5.62 5.65 5.65 5.69

1F 4.45 4.45 4.44 5.93 6.01 6.01 6.01 6.04 6.04 6.07

3F 7.80 7.80 7.88 8.08 8.16 8.16 8.17 8.17 8.17 8.18

1F 6.90 6.90 6.96 7.07 7.11 7.11 7.11 7.11 7.11 7.12

3F 7.14 7.14 7.14 6.99 8.03 8.03 8.03 8.13 8.14 8.17

1F 7.38 7.38 7.37 7.65 8.82 8.82 8.82 8.90 8.91 8.94

3F 12.27 12.27 10.91 11.24 11.51 11.51 11.51 11.52 11.52 11.43

1F 13.61 13.61 10.99 11.24 11.41 11.41 11.42 11.42 11.42 11.23

3F 1.49 1.49 1.49 1.49 1.51 1.51 1.55 1.55 1.55 1.46

1F 1.01 1.01 1.01 1.00 1.01 1.01 1.03 1.03 1.03 0.94

3F 16.15 16.15 16.10 15.92 15.98 15.98 15.99 16.20 16.16 18.24

1F 17.49 17.49 17.41 17.27 17.32 17.32 17.32 17.59 17.56 19.22

3F 2.70 2.70 2.70 2.71 2.72 2.72 2.72 2.72 2.73 2.74

1F 1.74 1.74 1.74 1.75 1.75 1.75 1.75 1.75 1.75 1.76

3F 1.58

1F 0.99Presumida PRS 115

Nizuc NIZ

Norte NTE

Palmar PMR

Poniente PTE 115

Popolnah PPH 115

Poktapok PKP 115

Polyuc PYU 115

Playa Mujeres PYM 115

Playacar PLY 115

115

230

Playa del Carmen PCN

115

230

115

115

230

Nichupte NCT 115

Nicte ha NIH 115

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Moon Palace MPA 115

Nachicocom NCM 115

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 293: Catalogo 2011-2020 r010212 Corto Circuito

293

Coordinación de Planificación

ÁREA PENINSULAR

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 12.24 12.24 12.34 12.82 13.05 13.05 13.05 13.06 13.06 13.09

1F 14.51 14.51 14.66 15.11 15.32 15.32 15.32 15.33 15.33 15.36

3F 5.24 5.24 5.23 3.57 9.94 9.94 9.95 9.99 9.99 10.04

1F 3.96 3.96 3.95 2.48 9.29 9.29 9.30 9.32 9.32 9.35

3F 3.83 3.83 3.83 3.82 3.82 3.82 3.82 3.87 3.87 3.95

1F 2.60 2.60 2.60 2.60 2.60 2.60 2.60 2.62 2.62 2.65

3F 9.01 9.01 9.13 9.40 9.51 9.51 9.51 9.52 9.52 9.53

1F 8.63 8.63 8.72 8.89 8.96 8.96 8.96 8.96 8.96 8.97

3F 1.57

1F 0.93

3F 11.48 11.51 11.51 11.52 11.57 11.58 11.66

1F 12.18 12.21 12.21 12.21 12.26 12.26 12.32

3F 6.92 6.97 6.97 6.97 7.00 7.00 7.06

1F 8.27 8.39 8.39 8.39 8.42 8.43 8.48

3F 3.87 4.19 4.19 4.20 4.21 4.21 4.26

1F 4.39 4.82 4.82 4.82 4.83 4.84 4.87

3F 3.69 3.69 3.69 3.68 3.69 3.69 3.85 5.67 5.67 5.70

1F 3.44 3.44 3.44 3.43 3.44 3.44 3.53 7.30 7.30 7.33

3F 3.11 3.13

1F 3.70 3.70

3F 4.98 4.98 4.98 4.94 4.96 4.96 5.00 5.01 5.01 5.06

1F 4.83 4.83 4.83 4.81 4.82 4.82 4.85 4.86 4.86 4.89

3F 4.68 4.68 4.69 4.65 4.67 4.67 4.70 4.72 4.72 4.75

1F 4.34 4.34 4.34 4.32 4.33 4.33 4.35 4.36 4.36 4.38

3F 4.74 4.74 4.73 4.72 4.72 4.72 4.72 4.79 4.79 4.92

1F 3.32 3.32 3.32 3.31 3.31 3.31 3.31 3.35 3.35 3.39

3F 6.02 6.02 6.07 6.06 6.07 6.08 6.19 6.27 6.27 6.28

1F 6.63 6.63 6.67 6.68 6.68 6.78 6.87 6.93 6.93 6.94

3F 2.34 2.34 2.34 2.34 2.34 2.34 2.34 2.43 2.45 2.46

1F 1.47 1.47 1.47 1.47 1.47 1.47 1.47 1.53 1.53 1.54

3F 3.91 3.91 3.93

1F 3.05 3.05 3.06

3F 14.94 14.94 14.89 14.74 14.78 14.78 14.79 15.50 15.45 16.94

1F 16.48 16.48 16.44 16.31 16.35 16.35 16.36 17.25 17.22 18.44

3F 2.74 2.74 2.74 2.74 2.74 2.74 2.74 2.79 2.83 2.84

1F 1.75 1.75 1.75 1.75 1.75 1.75 1.75 1.78 1.80 1.80

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Puerto Juárez PJU 115

Puerto Morelos PMO 115

Rio Lagartos RLA

Puerto Progreso PPO 115

Punta Sam PUS 115

115

230

115

115

230

400

115

Santa Lucía SLC 230

Samula SAM 115

Samula II SAD 115

115

Sucila SUC 115

Santo Domingo SDM 115

Si Ho Chac SHC 115

Riviera Maya RMY

Sabancuy SBY

Siyusa SYU

San Ignacio IGN

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 294: Catalogo 2011-2020 r010212 Corto Circuito

294

Coordinación de Planificación

ÁREA PENINSULAR

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 15.00 15.00 15.00 14.83 14.93 14.93 14.93 15.50 15.46 17.35

1F 14.86 14.86 14.87 14.76 14.82 14.83 14.83 15.39 15.36 16.70

3F 2.94 2.94 2.94 2.91 3.10 3.10 3.12 3.12 3.12 3.12

1F 2.03 2.03 2.03 2.03 2.13 2.13 2.13 2.13 2.13 2.12

3F 1.79

1F 1.07

3F 2.36 2.36 2.36 2.36 2.36 2.36 2.36 2.47 2.49 2.50

1F 1.48 1.48 1.48 1.48 1.48 1.48 1.48 1.56 1.56 1.57

3F 7.19 7.19 7.81 7.61 9.59 9.59 9.61 9.61 9.61 9.82

1F 6.65 6.65 7.59 7.46 9.63 9.63 9.65 9.66 9.65 9.79

3F 8.69 8.69 8.70 8.44 10.95 10.95 10.98 10.99 10.98 11.26

1F 9.08 9.08 9.09 8.91 12.18 12.18 12.20 12.22 12.21 12.44

3F 10.66 10.66 10.68 9.54 9.77 9.77 9.81 9.83 9.82 10.20

1F 9.15 9.15 9.16 8.61 9.30 9.30 9.32 9.36 9.36 9.58

3F 5.21 5.21 5.22 5.44 5.61 5.61 5.62 5.63 5.63 5.78

1F 4.46 4.46 4.47 4.82 5.15 5.15 5.16 5.17 5.17 5.26

3F 1.73

1F 1.04

3F 4.60 4.40 4.49

1F 2.91 2.74 2.76

3F 3.40 3.40 3.40 3.40 3.40 3.40 3.40 3.44 3.53 3.54

1F 2.23 2.23 2.23 2.23 2.23 2.23 2.23 2.25 2.29 2.29

3F 2.71 2.71 2.71 2.71 2.75 2.75 2.75 3.91 3.93 3.91

1F 1.81 1.81 1.81 1.81 2.01 2.01 2.01 2.97 2.99 2.87

3F 17.01 17.01 16.99 16.79 16.86 16.86 16.86 17.01 16.97 19.42

1F 19.74 19.74 19.71 19.54 19.60 19.60 19.60 19.83 19.79 22.08

3F 6.54 6.54 6.54 6.49 6.56 6.56 6.56 6.63 6.62 6.89

1F 4.64 4.64 4.64 4.63 4.65 4.65 4.66 4.69 4.69 4.79

3F 9.90 9.90 9.90 9.84 9.73 9.73 9.73 9.88 12.44 12.50

1F 11.22 11.22 11.22 11.17 11.06 11.06 11.06 11.20 14.75 14.81

3F 12.53 12.53 12.53 10.18 10.18 10.18 10.18 10.19 10.41 10.47

1F 14.59 14.59 14.60 12.14 12.14 12.14 12.14 12.15 12.51 12.57

3F 6.89 6.89 6.89 6.86 6.81 6.81 6.80 6.88 8.04 8.06

1F 6.14 6.14 6.14 6.12 6.09 6.09 6.09 6.14 7.07 7.08

3F 6.33 6.33 6.33 6.80 7.28 7.28 7.28 7.34 7.34 7.37

1F 5.69 5.69 5.69 6.11 6.54 6.54 6.54 6.57 6.57 6.59

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Sur SUR 115

Tekax II TKD 115

Telchac TCH 115

Temax TXS 115

Ticul TIU 115

Ticul II TIC

115

230

400

115

115

Tizimin TZM 115

115

Tulum TUM 115

Ucu UCU 115

Xaman Ha XAM 115

Tihosuco THS

Tixkokob TIX

Valladolid VAD

230

Valladolid Distribución VDD 115

Uman UMA 115

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____ _____

Page 295: Catalogo 2011-2020 r010212 Corto Circuito

295

Coordinación de Planificación

ÁREA PENINSULAR

SUBESTACIÓN BUS kV TIPO 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020

3F 6.60 6.60 6.59 7.03 7.46 7.46 7.47 7.51 7.52 7.55

1F 6.16 6.16 6.15 6.33 6.50 6.50 6.51 6.53 6.53 6.55

3F 2.14 2.14 2.14 2.14 2.14 2.14 2.97 2.95 2.95 2.95

1F 0.69 0.69 0.69 0.69 0.69 0.69 1.46 1.46 1.46 1.46

3F 2.75 2.75 2.75 2.73 2.74 2.74 3.49 3.48 3.48 3.47

1F 4.12 4.12 4.13 4.10 4.10 4.10 5.23 5.22 5.22 5.21

3F 1.41 1.41 1.41 1.40 1.40 1.40 1.71 1.70 1.70 1.70

1F 1.95 1.95 1.93 1.93 1.94 1.94 2.32 2.32 2.32 2.32

3F 4.97 4.98 5.00 5.00 5.00 5.06 5.07 5.07

1F 4.26 4.28 4.26 4.26 4.26 4.37 4.37 4.33

3F 9.31 9.31 9.43 9.72 9.85 9.85 9.85 9.85 9.85 9.87

1F 9.09 9.09 9.20 9.39 9.46 9.46 9.46 9.47 9.47 9.47

3F 6.76 6.76 6.75 7.16 7.56 7.56 7.57 7.64 7.64 7.67

1F 6.41 6.41 6.41 6.77 7.14 7.14 7.14 7.19 7.19 7.21

3F 10.70

1F 10.00

3F 7.41 7.41 7.47 7.48 7.51

1F 6.58 6.59 6.62 6.62 6.63

115

230

CORRIENTES DE FALLA TRIFÁSICA Y MONOFÁSICA EN KILOAMPERES

Xcalacoco XCO 115

Xpujil XPJ 115

Zaci

Zazil Ha ZAZ 115

Yalku YLK 115

115

115

115ZCI

Xul ha XUL

Yaxche YXE

Zac Nicte ZAC

RESULTADOS CORTO CIRCUITO TRIFÁSICO Y MONOFÁSICO

_______Catálogo de Corto Circuito 2011-2020_____