CALCULOS AIRE ACONDICIONADO 1 CÁLCULO TÉRMICO Condiciones de diseño : Sala : TBS = 75 PROYECTO SUNAT - HUANUCO HR = 5 Exterior : TBS = 85 ZONA SUPERVICION CSC / 1 PISO TBH = 75 SIN TECHO AL SOL MES/HORA JUNIO 6 AM Conductividad termica : Factor Rad.-vidrio (vent) Nº PERSONAS 3 Vidrio (ventana) 1.0 B Pared exterior 0.35 B AREA 18.0 194.4 ft² Pared interior 0.35 B Piso 0.35 B VOLUMEN 54.0 1911.6 ft³ Techo 0.35 B VENTANA VE-S 0.0 0.0 0.7 x 0 Btu/h-ft² = 0. 0.0 1 10 ºF = 0. VE-SE 0.0 0.0 0.7 x 0 Btu/h-ft² = 0. 0.0 1 10 ºF = 0. VE-E 0.0 0.0 0.7 x 0 Btu/h-ft² = 0. 0.0 1 10 ºF = 0. VE-NE 0.0 0.0 0.7 x 0 Btu/h-ft² = 0. 0.0 1 10 ºF = 0. VE-N 0.0 0.0 0.7 x 0 Btu/h-ft² = 0. 0.0 1 10 ºF = 0. VE-NO 0.0 0.0 0.7 x 0 Btu/h-ft² = 0. 0.0 1 10 ºF = 0. VE-O 0.0 0.0 0.7 x 0 Btu/h-ft² = 0. 0.0 1 10 ºF = 0. VE-SO 0.0 0.0 0.7 x 0 Btu/h-ft² = 0. 0.0 1 10 ºF = 0. VE-INTERIOR 0.0 0.0 1 10 ºF = 0. PARED PA-S 0.0 0.0 0.35 10 ºF = 0. PA-SE 0.0 0.0 0.35 10 ºF = 0. PA-E 0.0 0.0 0.35 10 ºF = 0. PA-NE 0.0 0.0 0.35 1 ºF = 0. PA-N 0.0 0.0 0.35 10 ºF = 0. PA-NO 0.0 0.0 0.35 2 ºF = 0. PA-O 0.0 0.0 0.35 2 ºF = 0. PA-SO 0.0 0.35 10 ºF = 0. P- INTERIOR 51.3 554.0 0.35 10 ºF = 1939. PISO 18.0 194.4 0.35 10 ºF = 680. TECHO 18.0 194.4 0.35 10 ºF = 680. ILUMIN. 25 1.25 x 18.0 m² x 3.41 Btu/h-watts = 1918. EQUIPOS 1250 watts x 3.41 Btu/h-watts = 4262. PERS - Cs 250 Btu/h-persona x 3 personas = 750. = 10230. 200 Btu/h-persona x 3 personas = 600. = 10830. R = 0.94 55.60 ºF 54.70 ºF 19.40 ºF 23.04 Btu/Lb Caudal Aire x persona Aire Exterior (AE) % AE # Cambios / h 488 cfm 20 cfm 60 cfm 12.29 % 1.9 Asumiendo nuevo % AE : 15 % Aire Exterior (AE) % AE # Cambios/h 73 cfm 15 % 2.3 76.50 ºF 64.56 ºF 29.70 Btu/Lb = 11124 Btu/h = 3348 Btu/h = 14471 Btu/h = 804 CFM/TON = 405 TONELADAS = 1.2 ton. m 2 ft 2 x ft 2 x Btu/h-ft 2 -ºF x m 2 ft 2 x ft 2 x Btu/h-ft 2 -ºF x m 2 ft 2 x ft 2 x Btu/h-ft 2 -ºF x m 2 ft 2 x ft 2 x Btu/h-ft 2 -ºF x m 2 ft 2 x ft 2 x Btu/h-ft 2 -ºF x m 2 ft 2 x ft 2 x Btu/h-ft 2 -ºF x m 2 ft 2 x ft 2 x Btu/h-ft 2 -ºF x m 2 ft 2 x ft 2 x Btu/h-ft 2 -ºF x m 2 ft 2 x Btu/h-ft 2 -ºF x m 2 ft 2 x Btu/h-ft 2 -ºF x m 2 ft 2 x Btu/h-ft 2 -ºF x m 2 ft 2 x Btu/h-ft 2 -ºF x m 2 ft 2 x Btu/h-ft 2 -ºF x m 2 ft 2 x Btu/h-ft 2 -ºF x m 2 ft 2 x Btu/h-ft 2 -ºF x m 2 ft 2 x Btu/h-ft 2 -ºF x m 2 ft 2 x Btu/h-ft 2 -ºF x m 2 ft 2 x Btu/h-ft 2 -ºF x m 2 ft 2 x Btu/h-ft 2 -ºF x m 2 ft 2 x Btu/h-ft 2 -ºF x watts/m 2 x QS PERS - CL QT TBSINSUF TBHINSUF Delta TINSUF HINSUF TBSMEZCLA TBHMEZCLA HMEZCLA HS CALOR SENSIBLE HL CALOR LATENTE HT TOTAL Btu/h-m 2

Upload: jose-ulises-cabrera-martinez

Post on 21-Dec-2015

86 views

Category:

Documents


2 download

TRANSCRIPT

Page 1: CALCULOS DE HOSPITAL.xlsx

CALCULOS AIRE ACONDICIONADO

1

CÁLCULO TÉRMICO Condiciones de diseño :

Sala :TBS = 75 ºF

PROYECTO SUNAT - HUANUCO HR = 50 %

Exterior :TBS = 85 ºF

ZONA SUPERVICION CSC / 1 PISO TBH = 75 ºF

SIN TECHO AL SOL

MES/HORA JUNIO 6 AM Conductividad termica :

Factor Rad.-vidrio (vent) 0.7

Nº PERSONAS 3 Vidrio (ventana) 1.0 Btu/h-ft²-ºF

Pared exterior 0.35 Btu/h-ft²-ºF

AREA 18.0 m² 194.4 ft² Pared interior 0.35 Btu/h-ft²-ºF

Piso 0.35 Btu/h-ft²-ºF

VOLUMEN 54.0 m³ 1911.6 ft³ Techo 0.35 Btu/h-ft²-ºF

VENTANA

VE-S 0.00.0 0.7 x 0 Btu/h-ft² = 0.0 Btu/h

0.0 1 10 ºF = 0.0 Btu/h

VE-SE 0.00.0 0.7 x 0 Btu/h-ft² = 0.0 Btu/h

0.0 1 10 ºF = 0.0 Btu/h

VE-E 0.00.0 0.7 x 0 Btu/h-ft² = 0.0 Btu/h

0.0 1 10 ºF = 0.0 Btu/h

VE-NE 0.00.0 0.7 x 0 Btu/h-ft² = 0.0 Btu/h

0.0 1 10 ºF = 0.0 Btu/h

VE-N 0.00.0 0.7 x 0 Btu/h-ft² = 0.0 Btu/h

0.0 1 10 ºF = 0.0 Btu/h

VE-NO 0.00.0 0.7 x 0 Btu/h-ft² = 0.0 Btu/h

0.0 1 10 ºF = 0.0 Btu/h

VE-O 0.00.0 0.7 x 0 Btu/h-ft² = 0.0 Btu/h

0.0 1 10 ºF = 0.0 Btu/h

VE-SO 0.00.0 0.7 x 0 Btu/h-ft² = 0.0 Btu/h

0.0 1 10 ºF = 0.0 Btu/h

VE-INTERIOR 0.0 0.0 1 10 ºF = 0.0 Btu/h

PARED

PA-S 0.0 0.0 0.35 10 ºF = 0.0 Btu/h

PA-SE 0.0 0.0 0.35 10 ºF = 0.0 Btu/h

PA-E 0.0 0.0 0.35 10 ºF = 0.0 Btu/h

PA-NE 0.0 0.0 0.35 1 ºF = 0.0 Btu/h

PA-N 0.0 0.0 0.35 10 ºF = 0.0 Btu/h

PA-NO 0.0 0.0 0.35 2 ºF = 0.0 Btu/h

PA-O 0.0 0.0 0.35 2 ºF = 0.0 Btu/h

PA-SO 0.0 0.35 10 ºF = 0.0 Btu/h

P- INTERIOR 51.3 554.0 0.35 10 ºF = 1939.1 Btu/h

PISO 18.0 194.4 0.35 10 ºF = 680.4 Btu/h

TECHO 18.0 194.4 0.35 10 ºF = 680.4 Btu/h

ILUMIN. 25 1.25 x 18.0 m² x 3.41 Btu/h-watts = 1918.1 Btu/h

EQUIPOS 1250 watts x 3.41 Btu/h-watts = 4262.5 Btu/h

PERS - Cs 250 Btu/h-persona x 3 personas = 750.0 Btu/h

= 10230.6 Btu/h

200 Btu/h-persona x 3 personas = 600.0 Btu/h

= 10830.6 Btu/hR = 0.94

55.60 ºF 54.70 ºF 19.40 ºF 23.04 Btu/Lb

Caudal Aire x persona Aire Exterior (AE) % AE # Cambios / h

488 cfm 20 cfm 60 cfm 12.29 % 1.9

Asumiendo nuevo % AE : 15 %

Aire Exterior (AE) % AE # Cambios/h73 cfm 15 % 2.3

76.50 ºF 64.56 ºF 29.70 Btu/Lb

= 11124 Btu/h

= 3348 Btu/h

= 14471 Btu/h

= 804

CFM/TON = 405

TONELADAS = 1.2 ton.

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

watts/m2 x

QS

PERS - CL

QT

TBSINSUF TBHINSUF Delta TINSUF HINSUF

TBSMEZCLA TBHMEZCLA HMEZCLA

HS CALOR SENSIBLE

HL CALOR LATENTE

HT TOTAL

Btu/h-m2

Page 2: CALCULOS DE HOSPITAL.xlsx

CALCULOS DE AIRE ACONDICIONADO

2

CÁLCULO TÉRMICO Condiciones de diseño :

Sala :TBS = 75 ºF

PROYECTO SUNAT - HUANUCO HR = 50 %

Exterior :TBS = 85 ºF

ZONA BACK OFICCE / 1 PISO TBH = 75 ºF

SIN TECHO AL SOL

MES/HORA JUNIO 12 M Conductividad termica :

Factor Rad.-vidrio (vent) 0.7

Nº PERSONAS 2 Vidrio (ventana) 1.0 Btu/h-ft²-ºF

Pared exterior 0.35 Btu/h-ft²-ºF

AREA 11.1 m² 119.9 ft² Pared interior 0.35 Btu/h-ft²-ºF

Piso 0.35 Btu/h-ft²-ºF

VOLUMEN 33.3 m³ 1178.8 ft³ Techo 0.35 Btu/h-ft²-ºF

VENTANA

VE-S 0.00.0 0.7 x 14 Btu/h-ft² = 0.0 Btu/h

0.0 1 10 ºF = 0.0 Btu/h

VE-SE 0.00.0 0.7 x 14 Btu/h-ft² = 0.0 Btu/h

0.0 1 10 ºF = 0.0 Btu/h

VE-E 0.00.0 0.7 x 14 Btu/h-ft² = 0.0 Btu/h

0.0 1 10 ºF = 0.0 Btu/h

VE-NE 0.00.0 0.7 x 79 Btu/h-ft² = 0.0 Btu/h

0.0 1 10 ºF = 0.0 Btu/h

VE-N 0.00.0 0.7 x 120 Btu/h-ft² = 0.0 Btu/h

0.0 1 10 ºF = 0.0 Btu/h

VE-NO 0.00.0 0.7 x 79 Btu/h-ft² = 0.0 Btu/h

0.0 1 10 ºF = 0.0 Btu/h

VE-O 0.00.0 0.7 x 14 Btu/h-ft² = 0.0 Btu/h

0.0 1 10 ºF = 0.0 Btu/h

VE-SO 0.00.0 0.7 x 14 Btu/h-ft² = 0.0 Btu/h

0.0 1 10 ºF = 0.0 Btu/h

VE-INTERIOR 0.0 0.0 1 10 ºF = 0.0 Btu/h

PARED

PA-S 0.0 0.0 0.35 10 ºF = 0.0 Btu/h

PA-SE 0.0 0.0 0.35 16 ºF = 0.0 Btu/h

PA-E 0.0 0.0 0.35 31 ºF = 0.0 Btu/h

PA-NE 0.0 0.0 0.35 28 ºF = 0.0 Btu/h

PA-N 10.7 115.6 0.35 12 ºF = 485.4 Btu/h

PA-NO 0.0 0.0 0.35 2 ºF = 0.0 Btu/h

PA-O 0.0 0.0 0.35 4 ºF = 0.0 Btu/h

PA-SO 0.0 0.35 2 ºF = 0.0 Btu/h

P- INTERIOR 23.8 257.0 0.35 10 ºF = 899.6 Btu/h

PISO 11.1 119.9 0.35 10 ºF = 419.6 Btu/h

TECHO 11.1 119.9 0.35 10 ºF = 419.6 Btu/h

ILUMIN. 25 1.25 x 11.1 m² x 3.41 Btu/h-watts = 1182.8 Btu/h

EQUIPOS 544 watts x 3.41 Btu/h-watts = 1855.0 Btu/h

PERS - Cs 250 Btu/h-persona x 2 personas = 500.0 Btu/h

= 5762.0 Btu/h

200 Btu/h-persona x 2 personas = 400.0 Btu/h

= 6162.0 Btu/h

R = 0.94

55.60 ºF 54.70 ºF 19.40 ºF 23.04 Btu/Lb

Caudal Aire x persona Aire Exterior (AE) % AE # Cambios / h

275 cfm 20 cfm 40 cfm 14.54 % 2.0

Asumiendo nuevo % AE : 15 %

Aire Exterior (AE) % AE # Cambios/h

41 cfm 15 % 2.1

76.50 ºF 64.56 ºF 29.70 Btu/Lb

= 6265 Btu/h

= 1885 Btu/h

= 8151 Btu/h

= 734

CFM/TON = 405

TONELADAS = 0.7 ton.

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

watts/m2 x

QS

PERS - CL

QT

TBSINSUF TBHINSUF Delta TINSUF HINSUF

TBSMEZCLA TBHMEZCLA HMEZCLA

HS CALOR SENSIBLE

HL CALOR LATENTE

HT TOTAL

Btu/h-m2

Page 3: CALCULOS DE HOSPITAL.xlsx

CALCULOS DE AIRE ACONDICIONADO

3

CÁLCULO TÉRMICO Condiciones de diseño :

Sala :TBS = 75 ºF

PROYECTO SUNAT - HUANUCO HR = 50 %

Exterior :TBS = 85 ºF

ZONA TOPICO / 1 PISO TBH = 75 ºF

SIN TECHO AL SOL

MES/HORA JUNIO 12 M Conductividad termica :

Factor Rad.-vidrio (vent) 0.7

Nº PERSONAS 2 Vidrio (ventana) 1.0 Btu/h-ft²-ºF

Pared exterior 0.35 Btu/h-ft²-ºF

AREA 6.2 m² 67.0 ft² Pared interior 0.35 Btu/h-ft²-ºF

Piso 0.35 Btu/h-ft²-ºF

VOLUMEN 18.6 m³ 658.4 ft³ Techo 0.35 Btu/h-ft²-ºF

VENTANA

VE-S 0.00.0 0.7 x 14 Btu/h-ft² = 0.0 Btu/h

0.0 1 10 ºF = 0.0 Btu/h

VE-SE 0.00.0 0.7 x 14 Btu/h-ft² = 0.0 Btu/h

0.0 1 10 ºF = 0.0 Btu/h

VE-E 0.00.0 0.7 x 14 Btu/h-ft² = 0.0 Btu/h

0.0 1 10 ºF = 0.0 Btu/h

VE-NE 0.00.0 0.7 x 79 Btu/h-ft² = 0.0 Btu/h

0.0 1 10 ºF = 0.0 Btu/h

VE-N 0.00.0 0.7 x 120 Btu/h-ft² = 0.0 Btu/h

0.0 1 10 ºF = 0.0 Btu/h

VE-NO 0.00.0 0.7 x 79 Btu/h-ft² = 0.0 Btu/h

0.0 1 10 ºF = 0.0 Btu/h

VE-O 0.00.0 0.7 x 14 Btu/h-ft² = 0.0 Btu/h

0.0 1 10 ºF = 0.0 Btu/h

VE-SO 0.00.0 0.7 x 14 Btu/h-ft² = 0.0 Btu/h

0.0 1 10 ºF = 0.0 Btu/h

VE-INTERIOR 0.0 0.0 1 10 ºF = 0.0 Btu/h

PARED

PA-S 0.0 0.0 0.35 10 ºF = 0.0 Btu/h

PA-SE 0.0 0.0 0.35 16 ºF = 0.0 Btu/h

PA-E 0.0 0.0 0.35 31 ºF = 0.0 Btu/h

PA-NE 0.0 0.0 0.35 28 ºF = 0.0 Btu/h

PA-N 20.0 215.5 0.35 12 ºF = 904.9 Btu/h

PA-NO 0.0 0.0 0.35 2 ºF = 0.0 Btu/h

PA-O 0.0 0.0 0.35 4 ºF = 0.0 Btu/h

PA-SO 0.0 0.35 2 ºF = 0.0 Btu/h

P- INTERIOR 21.0 226.8 0.35 10 ºF = 793.8 Btu/h

PISO 6.2 67.0 0.35 10 ºF = 234.4 Btu/h

TECHO 6.2 67.0 0.35 10 ºF = 234.4 Btu/h

ILUMIN. 25 1.25 x 6.2 m² x 3.41 Btu/h-watts = 660.7 Btu/h

EQUIPOS 144 watts x 3.41 Btu/h-watts = 491.0 Btu/h

PERS - Cs 250 Btu/h-persona x 2 personas = 500.0 Btu/h

= 3819.2 Btu/h

200 Btu/h-persona x 2 personas = 400.0 Btu/h

= 4219.2 Btu/h

R = 0.91

55.15 ºF 54.30 ºF 19.85 ºF 22.80 Btu/Lb

Caudal Aire x persona Aire Exterior (AE) % AE # Cambios / h

178 cfm 20 cfm 40 cfm 22.45 % 3.6

Asumiendo nuevo % AE : 15 %

Aire Exterior (AE) % AE # Cambios/h

27 cfm 15 % 2.4

76.50 ºF 64.56 ºF 29.70 Btu/Lb

= 4146 Btu/h

= 1324 Btu/h

= 5470 Btu/h

= 882

CFM/TON = 391

TONELADAS = 0.5 ton.

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

watts/m2 x

QS

PERS - CL

QT

TBSINSUF TBHINSUF Delta TINSUF HINSUF

TBSMEZCLA TBHMEZCLA HMEZCLA

HS CALOR SENSIBLE

HL CALOR LATENTE

HT TOTAL

Btu/h-m2

Page 4: CALCULOS DE HOSPITAL.xlsx

CALCULOS DE AIRE ACONDICIONADO

4

CÁLCULO TÉRMICO Condiciones de diseño :

Sala :TBS = 75 ºF

PROYECTO SUNAT - HUANUCO HR = 50 %

Exterior :TBS = 85 ºF

ZONA LOCKERS / 1 PISO TBH = 75 ºF

SIN TECHO AL SOL

MES/HORA JUNIO 12 M Conductividad termica :

Factor Rad.-vidrio (vent) 0.7

Nº PERSONAS 4 Vidrio (ventana) 1.0 Btu/h-ft²-ºF

Pared exterior 0.35 Btu/h-ft²-ºF

AREA 4.0 m² 43.2 ft² Pared interior 0.35 Btu/h-ft²-ºF

Piso 0.35 Btu/h-ft²-ºF

VOLUMEN 12.0 m³ 424.8 ft³ Techo 0.35 Btu/h-ft²-ºF

VENTANA

VE-S 0.00.0 0.7 x 14 Btu/h-ft² = 0.0 Btu/h

0.0 1 10 ºF = 0.0 Btu/h

VE-SE 0.00.0 0.7 x 14 Btu/h-ft² = 0.0 Btu/h

0.0 1 10 ºF = 0.0 Btu/h

VE-E 0.00.0 0.7 x 14 Btu/h-ft² = 0.0 Btu/h

0.0 1 10 ºF = 0.0 Btu/h

VE-NE 0.00.0 0.7 x 79 Btu/h-ft² = 0.0 Btu/h

0.0 1 10 ºF = 0.0 Btu/h

VE-N 0.00.0 0.7 x 120 Btu/h-ft² = 0.0 Btu/h

0.0 1 10 ºF = 0.0 Btu/h

VE-NO 0.00.0 0.7 x 79 Btu/h-ft² = 0.0 Btu/h

0.0 1 10 ºF = 0.0 Btu/h

VE-O 0.00.0 0.7 x 14 Btu/h-ft² = 0.0 Btu/h

0.0 1 10 ºF = 0.0 Btu/h

VE-SO 0.00.0 0.7 x 14 Btu/h-ft² = 0.0 Btu/h

0.0 1 10 ºF = 0.0 Btu/h

VE-INTERIOR 0.0 0.0 1 10 ºF = 0.0 Btu/h

PARED

PA-S 0.0 0.0 0.35 10 ºF = 0.0 Btu/h

PA-SE 0.0 0.0 0.35 16 ºF = 0.0 Btu/h

PA-E 0.0 0.0 0.35 31 ºF = 0.0 Btu/h

PA-NE 0.0 0.0 0.35 28 ºF = 0.0 Btu/h

PA-N 10.7 115.6 0.35 12 ºF = 485.4 Btu/h

PA-NO 0.0 0.0 0.35 2 ºF = 0.0 Btu/h

PA-O 0.0 0.0 0.35 4 ºF = 0.0 Btu/h

PA-SO 0.0 0.35 2 ºF = 0.0 Btu/h

P- INTERIOR 21.0 226.8 0.35 10 ºF = 793.8 Btu/h

PISO 4.0 43.2 0.35 10 ºF = 151.2 Btu/h

TECHO 4.0 43.2 0.35 10 ºF = 151.2 Btu/h

ILUMIN. 25 1.25 x 4.0 m² x 3.41 Btu/h-watts = 426.3 Btu/h

EQUIPOS 144 watts x 3.41 Btu/h-watts = 491.0 Btu/h

PERS - Cs 250 Btu/h-persona x 4 personas = 1000.0 Btu/h

= 3498.8 Btu/h

200 Btu/h-persona x 4 personas = 800.0 Btu/h

= 4298.8 Btu/h

R = 0.81

53.00 ºF 52.00 ºF 22.00 ºF 21.44 Btu/Lb

Caudal Aire x persona Aire Exterior (AE) % AE # Cambios / h

147 cfm 20 cfm 80 cfm 54.33 % 11.3

Asumiendo nuevo % AE : 15 %

Aire Exterior (AE) % AE # Cambios/h

22 cfm 15 % 3.1

76.50 ºF 64.56 ºF 29.70 Btu/Lb

= 3772 Btu/h

= 1641 Btu/h

= 5413 Btu/h

= 1353

CFM/TON = 326

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

watts/m2 x

QS

PERS - CL

QT

TBSINSUF TBHINSUF Delta TINSUF HINSUF

TBSMEZCLA TBHMEZCLA HMEZCLA

HS CALOR SENSIBLE

HL CALOR LATENTE

HT TOTAL

Btu/h-m2

Page 5: CALCULOS DE HOSPITAL.xlsx

CALCULOS DE AIRE ACONDICIONADO

4

TONELADAS = 0.5 ton.

Page 6: CALCULOS DE HOSPITAL.xlsx

CALCULOS DE AIRE ACONDICIONADO

5

CÁLCULO TÉRMICO Condiciones de diseño :

Sala :TBS = 75 ºF

PROYECTO SUNAT - HUANUCO HR = 50 %

Exterior :TBS = 85 ºF

ZONA SALA DE ESPERA Y HALL / 1 PISO TBH = 75 ºF

SIN TECHO AL SOL

MES/HORA JUNIO 12 M Conductividad termica :

Factor Rad.-vidrio (vent) 0.7

Nº PERSONAS 75 Vidrio (ventana) 1.0 Btu/h-ft²-ºF

Pared exterior 0.35 Btu/h-ft²-ºF

AREA 226.0 m² 2440.8 ft² Pared interior 0.35 Btu/h-ft²-ºF

Piso 0.35 Btu/h-ft²-ºF

VOLUMEN 678.0 m³ 24001.2 ft³ Techo 0.35 Btu/h-ft²-ºF

VENTANA

VE-S 0.00.0 0.7 x 14 Btu/h-ft² = 0.0 Btu/h

0.0 1 10 ºF = 0.0 Btu/h

VE-SE 0.00.0 0.7 x 14 Btu/h-ft² = 0.0 Btu/h

0.0 1 10 ºF = 0.0 Btu/h

VE-E 0.00.0 0.7 x 14 Btu/h-ft² = 0.0 Btu/h

0.0 1 10 ºF = 0.0 Btu/h

VE-NE 0.00.0 0.7 x 79 Btu/h-ft² = 0.0 Btu/h

0.0 1 10 ºF = 0.0 Btu/h

VE-N 0.00.0 0.7 x 120 Btu/h-ft² = 0.0 Btu/h

0.0 1 10 ºF = 0.0 Btu/h

VE-NO 42.0453.6 0.7 x 79 Btu/h-ft² = 25084.1 Btu/h

453.6 1 10 ºF = 4536.0 Btu/h

VE-O 0.00.0 0.7 x 14 Btu/h-ft² = 0.0 Btu/h

0.0 1 10 ºF = 0.0 Btu/h

VE-SO 0.00.0 0.7 x 14 Btu/h-ft² = 0.0 Btu/h

0.0 1 10 ºF = 0.0 Btu/h

VE-INTERIOR 0.0 0.0 1 10 ºF = 0.0 Btu/h

PARED

PA-S 34.5 372.6 0.35 10 ºF = 1304.1 Btu/h

PA-SE 0.0 0.0 0.35 16 ºF = 0.0 Btu/h

PA-E 21.0 226.8 0.35 31 ºF = 2460.8 Btu/h

PA-NE 38.4 414.7 0.35 28 ºF = 4064.3 Btu/h

PA-N 10.7 115.6 0.35 12 ºF = 485.4 Btu/h

PA-NO 0.0 0.0 0.35 2 ºF = 0.0 Btu/h

PA-O 0.0 0.0 0.35 4 ºF = 0.0 Btu/h

PA-SO 0.0 0.35 2 ºF = 0.0 Btu/h

P- INTERIOR 78.0 842.4 0.35 10 ºF = 2948.4 Btu/h

PISO 226.0 2440.8 0.35 10 ºF = 8542.8 Btu/h

TECHO 226.0 2440.8 0.35 10 ºF = 8542.8 Btu/h

ILUMIN. 25 1.25 x 226.0 m² x 3.41 Btu/h-watts = 24083.1 Btu/h

EQUIPOS 4500 watts x 3.41 Btu/h-watts = 15345.0 Btu/h

PERS - Cs 250 Btu/h-persona x 75 personas = 18750.0 Btu/h

= 116146.7 Btu/h

200 Btu/h-persona x 75 personas = 15000.0 Btu/h

= 131146.7 Btu/h

R = 0.89

54.80 ºF 53.80 ºF 20.20 ºF 22.50 Btu/Lb

Caudal Aire x persona Aire Exterior (AE) % AE # Cambios / h

5324 cfm 20 cfm 1500 cfm 28.17 % 3.7

Asumiendo nuevo % AE : 15 %

Aire Exterior (AE) % AE # Cambios/h

799 cfm 15 % 2.0

76.50 ºF 64.56 ºF 29.70 Btu/Lb

= 125927 Btu/h

= 44652 Btu/h

= 170578 Btu/h

= 755

CFM/TON = 375

TONELADAS = 14.2 ton.

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

watts/m2 x

QS

PERS - CL

QT

TBSINSUF TBHINSUF Delta TINSUF HINSUF

TBSMEZCLA TBHMEZCLA HMEZCLA

HS CALOR SENSIBLE

HL CALOR LATENTE

HT TOTAL

Btu/h-m2

Page 7: CALCULOS DE HOSPITAL.xlsx

CALCULOS DE AIRE ACONDICIONADO

6

CÁLCULO TÉRMICO Condiciones de diseño :

Sala :TBS = 75 ºF

PROYECTO SUNAT - HUANUCO HR = 50 %

Exterior :TBS = 85 ºF

ZONA CABINAS PDT / 1 PISO TBH = 75 ºF

SIN TECHO AL SOL

MES/HORA JUNIO 12 M Conductividad termica :

Factor Rad.-vidrio (vent) 0.7

Nº PERSONAS 10 Vidrio (ventana) 1.0 Btu/h-ft²-ºF

Pared exterior 0.35 Btu/h-ft²-ºF

AREA 25.9 m² 279.7 ft² Pared interior 0.35 Btu/h-ft²-ºF

Piso 0.35 Btu/h-ft²-ºF

VOLUMEN 77.7 m³ 2750.6 ft³ Techo 0.35 Btu/h-ft²-ºF

VENTANA

VE-S 0.00.0 0.7 x 14 Btu/h-ft² = 0.0 Btu/h

0.0 1 10 ºF = 0.0 Btu/h

VE-SE 0.00.0 0.7 x 14 Btu/h-ft² = 0.0 Btu/h

0.0 1 10 ºF = 0.0 Btu/h

VE-E 0.00.0 0.7 x 14 Btu/h-ft² = 0.0 Btu/h

0.0 1 10 ºF = 0.0 Btu/h

VE-NE 0.00.0 0.7 x 79 Btu/h-ft² = 0.0 Btu/h

0.0 1 10 ºF = 0.0 Btu/h

VE-N 0.00.0 0.7 x 120 Btu/h-ft² = 0.0 Btu/h

0.0 1 10 ºF = 0.0 Btu/h

VE-NO 0.00.0 0.7 x 79 Btu/h-ft² = 0.0 Btu/h

0.0 1 10 ºF = 0.0 Btu/h

VE-O 0.00.0 0.7 x 14 Btu/h-ft² = 0.0 Btu/h

0.0 1 10 ºF = 0.0 Btu/h

VE-SO 0.00.0 0.7 x 14 Btu/h-ft² = 0.0 Btu/h

0.0 1 10 ºF = 0.0 Btu/h

VE-INTERIOR 0.0 0.0 1 10 ºF = 0.0 Btu/h

PARED

PA-S 19.0 205.1 0.35 10 ºF = 717.8 Btu/h

PA-SE 0.0 0.0 0.35 16 ºF = 0.0 Btu/h

PA-E 11.3 122.1 0.35 31 ºF = 1325.3 Btu/h

PA-NE 0.0 0.0 0.35 28 ºF = 0.0 Btu/h

PA-N 0.0 0.0 0.35 12 ºF = 0.0 Btu/h

PA-NO 0.0 0.0 0.35 2 ºF = 0.0 Btu/h

PA-O 0.0 0.0 0.35 4 ºF = 0.0 Btu/h

PA-SO 0.0 0.35 2 ºF = 0.0 Btu/h

P- INTERIOR 23.8 257.0 0.35 10 ºF = 899.6 Btu/h

PISO 25.9 279.7 0.35 10 ºF = 979.0 Btu/h

TECHO 25.9 279.7 0.35 10 ºF = 979.0 Btu/h

ILUMIN. 25 1.25 x 25.9 m² x 3.41 Btu/h-watts = 2760.0 Btu/h

EQUIPOS 3100 watts x 3.41 Btu/h-watts = 10571.0 Btu/h

PERS - Cs 250 Btu/h-persona x 10 personas = 2500.0 Btu/h

= 20731.8 Btu/h

200 Btu/h-persona x 10 personas = 2000.0 Btu/h

= 22731.8 Btu/h

R = 0.91

55.15 ºF 54.30 ºF 19.85 ºF 22.80 Btu/Lb

Caudal Aire x persona Aire Exterior (AE) % AE # Cambios / h

967 cfm 20 cfm 200 cfm 20.68 % 4.4

Asumiendo nuevo % AE : 15 %

Aire Exterior (AE) % AE # Cambios/h

145 cfm 15 % 3.2

76.50 ºF 64.56 ºF 29.70 Btu/Lb

= 22505 Btu/h

= 7189 Btu/h

= 29693 Btu/h

= 1146

CFM/TON = 391

TONELADAS = 2.5 ton.

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

watts/m2 x

QS

PERS - CL

QT

TBSINSUF TBHINSUF Delta TINSUF HINSUF

TBSMEZCLA TBHMEZCLA HMEZCLA

HS CALOR SENSIBLE

HL CALOR LATENTE

HT TOTAL

Btu/h-m2

Page 8: CALCULOS DE HOSPITAL.xlsx

CALCULOS DE AIRE ACONDICIONADO

7

CÁLCULO TÉRMICO Condiciones de diseño :

Sala :TBS = 75 ºF

PROYECTO SUNAT - HUANUCO HR = 50 %

Exterior :TBS = 85 ºF

ZONA BIBLIOTECA / 2 PISO TBH = 75 ºF

SIN TECHO AL SOL

MES/HORA JUNIO 12 M Conductividad termica :

Factor Rad.-vidrio (vent) 0.7

Nº PERSONAS 12 Vidrio (ventana) 1.0 Btu/h-ft²-ºF

Pared exterior 0.35 Btu/h-ft²-ºF

AREA 16.5 m² 178.2 ft² Pared interior 0.35 Btu/h-ft²-ºF

Piso 0.35 Btu/h-ft²-ºF

VOLUMEN 49.5 m³ 1752.3 ft³ Techo 0.35 Btu/h-ft²-ºF

VENTANA

VE-S 0.00.0 0.7 x 14 Btu/h-ft² = 0.0 Btu/h

0.0 1 10 ºF = 0.0 Btu/h

VE-SE 0.00.0 0.7 x 14 Btu/h-ft² = 0.0 Btu/h

0.0 1 10 ºF = 0.0 Btu/h

VE-E 0.00.0 0.7 x 14 Btu/h-ft² = 0.0 Btu/h

0.0 1 10 ºF = 0.0 Btu/h

VE-NE 0.00.0 0.7 x 79 Btu/h-ft² = 0.0 Btu/h

0.0 1 10 ºF = 0.0 Btu/h

VE-N 6.064.8 0.7 x 120 Btu/h-ft² = 5443.2 Btu/h

64.8 1 10 ºF = 648.0 Btu/h

VE-NO 0.00.0 0.7 x 79 Btu/h-ft² = 0.0 Btu/h

0.0 1 10 ºF = 0.0 Btu/h

VE-O 0.00.0 0.7 x 14 Btu/h-ft² = 0.0 Btu/h

0.0 1 10 ºF = 0.0 Btu/h

VE-SO 0.00.0 0.7 x 14 Btu/h-ft² = 0.0 Btu/h

0.0 1 10 ºF = 0.0 Btu/h

VE-INTERIOR 0.0 0.0 1 10 ºF = 0.0 Btu/h

PARED

PA-S 19.0 205.1 0.35 10 ºF = 717.8 Btu/h

PA-SE 0.0 0.0 0.35 16 ºF = 0.0 Btu/h

PA-E 7.5 81.0 0.35 31 ºF = 878.8 Btu/h

PA-NE 0.0 0.0 0.35 28 ºF = 0.0 Btu/h

PA-N 0.0 0.0 0.35 12 ºF = 0.0 Btu/h

PA-NO 0.0 0.0 0.35 2 ºF = 0.0 Btu/h

PA-O 0.0 0.0 0.35 4 ºF = 0.0 Btu/h

PA-SO 0.0 0.35 2 ºF = 0.0 Btu/h

P- INTERIOR 30.0 324.0 0.35 10 ºF = 1134.0 Btu/h

PISO 16.5 178.2 0.35 10 ºF = 623.7 Btu/h

TECHO 16.5 178.2 0.35 10 ºF = 623.7 Btu/h

ILUMIN. 25 1.25 x 16.5 m² x 3.41 Btu/h-watts = 1758.3 Btu/h

EQUIPOS 700 watts x 3.41 Btu/h-watts = 2387.0 Btu/h

PERS - Cs 250 Btu/h-persona x 12 personas = 3000.0 Btu/h

= 17214.6 Btu/h

200 Btu/h-persona x 12 personas = 2400.0 Btu/h

= 19614.6 Btu/h

R = 0.88

54.60 ºF 53.60 ºF 20.40 ºF 22.38 Btu/Lb

Caudal Aire x persona Aire Exterior (AE) % AE # Cambios / h

781 cfm 20 cfm 240 cfm 30.72 % 8.2

Asumiendo nuevo % AE : 15 %

Aire Exterior (AE) % AE # Cambios/h

117 cfm 15 % 4.0

76.50 ºF 64.56 ºF 29.70 Btu/Lb

= 18651 Btu/h

= 6800 Btu/h

= 25451 Btu/h

= 1543

CFM/TON = 368

TONELADAS = 2.1 ton.

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

watts/m2 x

QS

PERS - CL

QT

TBSINSUF TBHINSUF Delta TINSUF HINSUF

TBSMEZCLA TBHMEZCLA HMEZCLA

HS CALOR SENSIBLE

HL CALOR LATENTE

HT TOTAL

Btu/h-m2

Page 9: CALCULOS DE HOSPITAL.xlsx

CALCULOS DE AIRE ACONDICIONADO

8

CÁLCULO TÉRMICO Condiciones de diseño :

Sala :TBS = 75 ºF

PROYECTO SUNAT - HUANUCO HR = 50 %

Exterior :TBS = 85 ºF

ZONA SALA DE REUNIONES / 2 PISO TBH = 75 ºF

SIN TECHO AL SOL

MES/HORA JUNIO 12 M Conductividad termica :

Factor Rad.-vidrio (vent) 0.7

Nº PERSONAS 8 Vidrio (ventana) 1.0 Btu/h-ft²-ºF

Pared exterior 0.35 Btu/h-ft²-ºF

AREA 25.0 m² 270.0 ft² Pared interior 0.35 Btu/h-ft²-ºF

Piso 0.35 Btu/h-ft²-ºF

VOLUMEN 75.0 m³ 2655.0 ft³ Techo 0.35 Btu/h-ft²-ºF

VENTANA

VE-S 0.00.0 0.7 x 14 Btu/h-ft² = 0.0 Btu/h

0.0 1 10 ºF = 0.0 Btu/h

VE-SE 0.00.0 0.7 x 14 Btu/h-ft² = 0.0 Btu/h

0.0 1 10 ºF = 0.0 Btu/h

VE-E 0.00.0 0.7 x 14 Btu/h-ft² = 0.0 Btu/h

0.0 1 10 ºF = 0.0 Btu/h

VE-NE 2.122.7 0.7 x 79 Btu/h-ft² = 1254.2 Btu/h

22.7 1 10 ºF = 226.8 Btu/h

VE-N 6.064.8 0.7 x 120 Btu/h-ft² = 5443.2 Btu/h

64.8 1 10 ºF = 648.0 Btu/h

VE-NO 3.538.1 0.7 x 79 Btu/h-ft² = 2105.3 Btu/h

38.1 1 10 ºF = 380.7 Btu/h

VE-O 0.00.0 0.7 x 14 Btu/h-ft² = 0.0 Btu/h

0.0 1 10 ºF = 0.0 Btu/h

VE-SO 0.00.0 0.7 x 14 Btu/h-ft² = 0.0 Btu/h

0.0 1 10 ºF = 0.0 Btu/h

VE-INTERIOR 0.0 0.0 1 10 ºF = 0.0 Btu/h

PARED

PA-S 0.0 0.0 0.35 10 ºF = 0.0 Btu/h

PA-SE 0.0 0.0 0.35 16 ºF = 0.0 Btu/h

PA-E 0.0 0.0 0.35 31 ºF = 0.0 Btu/h

PA-NE 0.0 0.0 0.35 28 ºF = 0.0 Btu/h

PA-N 0.0 0.0 0.35 12 ºF = 0.0 Btu/h

PA-NO 10.7 115.7 0.35 2 ºF = 81.0 Btu/h

PA-O 0.0 0.0 0.35 4 ºF = 0.0 Btu/h

PA-SO 0.0 0.35 2 ºF = 0.0 Btu/h

P- INTERIOR 18.8 203.1 0.35 10 ºF = 711.0 Btu/h

PISO 25.0 270.0 0.35 10 ºF = 945.0 Btu/h

TECHO 25.0 270.0 0.35 10 ºF = 945.0 Btu/h

ILUMIN. 25 1.25 x 25.0 m² x 3.41 Btu/h-watts = 2664.1 Btu/h

EQUIPOS 700 watts x 3.41 Btu/h-watts = 2387.0 Btu/h

PERS - Cs 250 Btu/h-persona x 8 personas = 2000.0 Btu/h

= 19791.2 Btu/h

200 Btu/h-persona x 8 personas = 1600.0 Btu/h

= 21391.2 Btu/h

R = 0.93

55.45 ºF 54.60 ºF 19.55 ºF 22.98 Btu/Lb

Caudal Aire x persona Aire Exterior (AE) % AE # Cambios / h

937 cfm 20 cfm 160 cfm 17.07 % 3.6

Asumiendo nuevo % AE : 15 %

Aire Exterior (AE) % AE # Cambios/h

141 cfm 15 % 3.2

76.50 ºF 64.56 ºF 29.70 Btu/Lb

= 21507 Btu/h

= 6523 Btu/h

= 28031 Btu/h

= 1121

CFM/TON = 401

TONELADAS = 2.3 ton.

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

watts/m2 x

QS

PERS - CL

QT

TBSINSUF TBHINSUF Delta TINSUF HINSUF

TBSMEZCLA TBHMEZCLA HMEZCLA

HS CALOR SENSIBLE

HL CALOR LATENTE

HT TOTAL

Btu/h-m2

Page 10: CALCULOS DE HOSPITAL.xlsx

CALCULOS DE AIRE ACONDICIONADO

9

CÁLCULO TÉRMICO Condiciones de diseño :

Sala :TBS = 75 ºF

PROYECTO SUNAT - HUANUCO HR = 50 %

Exterior :TBS = 85 ºF

ZONA SALA DE ESPERA / 2 PISO TBH = 75 ºF

CON TECHO AL SOL

MES/HORA JUNIO 12 M Conductividad termica :

Factor Rad.-vidrio (vent) 0.7

Nº PERSONAS 15 Vidrio (ventana) 1.0 Btu/h-ft²-ºF

Pared exterior 0.35 Btu/h-ft²-ºF

AREA 134.3 m² 1450.4 ft² Pared interior 0.35 Btu/h-ft²-ºF

Piso 0.35 Btu/h-ft²-ºF

VOLUMEN 402.9 m³ 14262.7 ft³ Techo 0.35 Btu/h-ft²-ºF

VENTANA

VE-S 0.00.0 0.7 x 14 Btu/h-ft² = 0.0 Btu/h

0.0 1 10 ºF = 0.0 Btu/h

VE-SE 0.00.0 0.7 x 14 Btu/h-ft² = 0.0 Btu/h

0.0 1 10 ºF = 0.0 Btu/h

VE-E 0.00.0 0.7 x 14 Btu/h-ft² = 0.0 Btu/h

0.0 1 10 ºF = 0.0 Btu/h

VE-NE 0.00.0 0.7 x 79 Btu/h-ft² = 0.0 Btu/h

0.0 1 10 ºF = 0.0 Btu/h

VE-N 0.00.0 0.7 x 120 Btu/h-ft² = 0.0 Btu/h

0.0 1 10 ºF = 0.0 Btu/h

VE-NO 42.0453.6 0.7 x 79 Btu/h-ft² = 25084.1 Btu/h

453.6 1 10 ºF = 4536.0 Btu/h

VE-O 0.00.0 0.7 x 14 Btu/h-ft² = 0.0 Btu/h

0.0 1 10 ºF = 0.0 Btu/h

VE-SO 0.00.0 0.7 x 14 Btu/h-ft² = 0.0 Btu/h

0.0 1 10 ºF = 0.0 Btu/h

VE-INTERIOR 30.3 327.2 1 10 ºF = 3272.4 Btu/h

PARED

PA-S 0.0 0.0 0.35 10 ºF = 0.0 Btu/h

PA-SE 60.0 648.0 0.35 16 ºF = 3628.8 Btu/h

PA-E 0.0 0.0 0.35 31 ºF = 0.0 Btu/h

PA-NE 0.0 0.0 0.35 28 ºF = 0.0 Btu/h

PA-N 0.0 0.0 0.35 12 ºF = 0.0 Btu/h

PA-NO 0.0 0.0 0.35 2 ºF = 0.0 Btu/h

PA-O 0.0 0.0 0.35 4 ºF = 0.0 Btu/h

PA-SO 0.0 0.35 2 ºF = 0.0 Btu/h

P- INTERIOR 78.0 842.4 0.35 10 ºF = 2948.4 Btu/h

PISO 134.3 1450.4 0.35 10 ºF = 5076.5 Btu/h

TECHO 134.3 1450.4 0.35 16 ºF = 8122.5 Btu/h

ILUMIN. 25 1.25 x 134.3 m² x 3.41 Btu/h-watts = 14311.3 Btu/h

EQUIPOS 1550 watts x 3.41 Btu/h-watts = 5285.5 Btu/h

PERS - Cs 250 Btu/h-persona x 15 personas = 3750.0 Btu/h

= 76015.5 Btu/h

200 Btu/h-persona x 15 personas = 3000.0 Btu/h

= 79015.5 Btu/h

R = 0.96

55.80 ºF 54.90 ºF 19.20 ºF 23.16 Btu/Lb

Caudal Aire x persona Aire Exterior (AE) % AE # Cambios / h

3666 cfm 20 cfm 300 cfm 8.18 % 1.3

Asumiendo nuevo % AE : 15 %

Aire Exterior (AE) % AE # Cambios/h

550 cfm 15 % 2.3

76.50 ºF 64.56 ºF 29.70 Btu/Lb

= 82713 Btu/h

= 23975 Btu/h

= 106688 Btu/h

= 794

CFM/TON = 412

TONELADAS = 8.9 ton.

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

watts/m2 x

QS

PERS - CL

QT

TBSINSUF TBHINSUF Delta TINSUF HINSUF

TBSMEZCLA TBHMEZCLA HMEZCLA

HS CALOR SENSIBLE

HL CALOR LATENTE

HT TOTAL

Btu/h-m2

Page 11: CALCULOS DE HOSPITAL.xlsx

CALCULOS DE AIRE ACONDICIONADO

10

CÁLCULO TÉRMICO Condiciones de diseño :

Sala :TBS = 75 ºF

PROYECTO SUNAT - HUANUCO HR = 50 %

Exterior :TBS = 85 ºF

ZONA LOCKERS / 2 PISO TBH = 75 ºF

CON TECHO AL SOL

MES/HORA JUNIO 12 M Conductividad termica :

Factor Rad.-vidrio (vent) 0.7

Nº PERSONAS 4 Vidrio (ventana) 1.0 Btu/h-ft²-ºF

Pared exterior 0.35 Btu/h-ft²-ºF

AREA 5.9 m² 63.7 ft² Pared interior 0.35 Btu/h-ft²-ºF

Piso 0.35 Btu/h-ft²-ºF

VOLUMEN 17.7 m³ 626.6 ft³ Techo 0.35 Btu/h-ft²-ºF

VENTANA

VE-S 0.00.0 0.7 x 14 Btu/h-ft² = 0.0 Btu/h

0.0 1 10 ºF = 0.0 Btu/h

VE-SE 0.00.0 0.7 x 14 Btu/h-ft² = 0.0 Btu/h

0.0 1 10 ºF = 0.0 Btu/h

VE-E 0.00.0 0.7 x 14 Btu/h-ft² = 0.0 Btu/h

0.0 1 10 ºF = 0.0 Btu/h

VE-NE 0.00.0 0.7 x 79 Btu/h-ft² = 0.0 Btu/h

0.0 1 10 ºF = 0.0 Btu/h

VE-N 0.00.0 0.7 x 120 Btu/h-ft² = 0.0 Btu/h

0.0 1 10 ºF = 0.0 Btu/h

VE-NO 0.00.0 0.7 x 79 Btu/h-ft² = 0.0 Btu/h

0.0 1 10 ºF = 0.0 Btu/h

VE-O 0.00.0 0.7 x 14 Btu/h-ft² = 0.0 Btu/h

0.0 1 10 ºF = 0.0 Btu/h

VE-SO 0.00.0 0.7 x 14 Btu/h-ft² = 0.0 Btu/h

0.0 1 10 ºF = 0.0 Btu/h

VE-INTERIOR 0.0 0.0 1 10 ºF = 0.0 Btu/h

PARED

PA-S 0.0 0.0 0.35 10 ºF = 0.0 Btu/h

PA-SE 5.6 59.9 0.35 16 ºF = 335.7 Btu/h

PA-E 0.0 0.0 0.35 31 ºF = 0.0 Btu/h

PA-NE 0.0 0.0 0.35 28 ºF = 0.0 Btu/h

PA-N 0.0 0.0 0.35 12 ºF = 0.0 Btu/h

PA-NO 0.0 0.0 0.35 2 ºF = 0.0 Btu/h

PA-O 0.0 0.0 0.35 4 ºF = 0.0 Btu/h

PA-SO 0.0 0.0 0.35 2 ºF = 0.0 Btu/h

P- INTERIOR 22.8 246.2 0.35 10 ºF = 861.8 Btu/h

PISO 5.9 63.7 0.35 10 ºF = 223.0 Btu/h

TECHO 5.9 63.7 0.35 16 ºF = 356.8 Btu/h

ILUMIN. 25 1.25 x 5.9 m² x 3.41 Btu/h-watts = 628.7 Btu/h

EQUIPOS 144 watts x 3.41 Btu/h-watts = 491.0 Btu/h

PERS - Cs 250 Btu/h-persona x 4 personas = 1000.0 Btu/h

= 3897.1 Btu/h

200 Btu/h-persona x 4 personas = 800.0 Btu/h

= 4697.1 Btu/h

R = 0.83

53.60 ºF 52.60 ºF 21.40 ºF 21.78 Btu/Lb

Caudal Aire x persona Aire Exterior (AE) % AE # Cambios / h

169 cfm 20 cfm 80 cfm 47.44 % 7.7

Asumiendo nuevo % AE : 15 %

Aire Exterior (AE) % AE # Cambios/h

25 cfm 15 % 2.4

76.50 ºF 64.56 ºF 29.70 Btu/Lb

= 4209 Btu/h

= 1734 Btu/h

= 5943 Btu/h

= 1007

CFM/TON = 340

TONELADAS = 0.5 ton.

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

watts/m2 x

QS

PERS - CL

QT

TBSINSUF TBHINSUF Delta TINSUF HINSUF

TBSMEZCLA TBHMEZCLA HMEZCLA

HS CALOR SENSIBLE

HL CALOR LATENTE

HT TOTAL

Btu/h-m2

Page 12: CALCULOS DE HOSPITAL.xlsx

CALCULOS DE AIRE ACONDICIONADO

11

CÁLCULO TÉRMICO Condiciones de diseño :

Sala :TBS = 75 ºF

PROYECTO SUNAT - HUANUCO HR = 50 %

Exterior :TBS = 85 ºF

ZONA CUARTO DE EQUIPOS / 2 PISO TBH = 75 ºF

CON TECHO AL SOL

MES/HORA JUNIO 12 M Conductividad termica :

Factor Rad.-vidrio (vent) 0.7

Nº PERSONAS 3 Vidrio (ventana) 1.0 Btu/h-ft²-ºF

Pared exterior 0.35 Btu/h-ft²-ºF

AREA 13.5 m² 145.8 ft² Pared interior 0.35 Btu/h-ft²-ºF

Piso 0.35 Btu/h-ft²-ºF

VOLUMEN 40.5 m³ 1433.7 ft³ Techo 0.35 Btu/h-ft²-ºF

VENTANA

VE-S 0.00.0 0.7 x 14 Btu/h-ft² = 0.0 Btu/h

0.0 1 10 ºF = 0.0 Btu/h

VE-SE 0.00.0 0.7 x 14 Btu/h-ft² = 0.0 Btu/h

0.0 1 10 ºF = 0.0 Btu/h

VE-E 0.00.0 0.7 x 14 Btu/h-ft² = 0.0 Btu/h

0.0 1 10 ºF = 0.0 Btu/h

VE-NE 0.00.0 0.7 x 79 Btu/h-ft² = 0.0 Btu/h

0.0 1 10 ºF = 0.0 Btu/h

VE-N 0.00.0 0.7 x 120 Btu/h-ft² = 0.0 Btu/h

0.0 1 10 ºF = 0.0 Btu/h

VE-NO 0.00.0 0.7 x 79 Btu/h-ft² = 0.0 Btu/h

0.0 1 10 ºF = 0.0 Btu/h

VE-O 0.00.0 0.7 x 14 Btu/h-ft² = 0.0 Btu/h

0.0 1 10 ºF = 0.0 Btu/h

VE-SO 0.00.0 0.7 x 14 Btu/h-ft² = 0.0 Btu/h

0.0 1 10 ºF = 0.0 Btu/h

VE-INTERIOR 0.0 0.0 1 10 ºF = 0.0 Btu/h

PARED

PA-S 0.0 0.0 0.35 10 ºF = 0.0 Btu/h

PA-SE 11.0 118.6 0.35 16 ºF = 664.1 Btu/h

PA-E 0.0 0.0 0.35 31 ºF = 0.0 Btu/h

PA-NE 10.4 112.8 0.35 28 ºF = 1105.0 Btu/h

PA-N 0.0 0.0 0.35 12 ºF = 0.0 Btu/h

PA-NO 0.0 0.0 0.35 2 ºF = 0.0 Btu/h

PA-O 0.0 0.0 0.35 4 ºF = 0.0 Btu/h

PA-SO 0.0 0.35 2 ºF = 0.0 Btu/h

P- INTERIOR 10.9 117.3 0.35 10 ºF = 410.5 Btu/h

PISO 13.5 145.8 0.35 10 ºF = 510.3 Btu/h

TECHO 13.5 145.8 0.35 16 ºF = 816.5 Btu/h

ILUMIN. 25 1.25 x 13.5 m² x 3.41 Btu/h-watts = 1438.6 Btu/h

EQUIPOS 3100 watts x 3.41 Btu/h-watts = 10571.0 Btu/h

PERS - Cs 250 Btu/h-persona x 3 personas = 750.0 Btu/h

= 16265.9 Btu/h

200 Btu/h-persona x 3 personas = 600.0 Btu/h

= 16865.9 Btu/h

R = 0.96

55.80 ºF 54.90 ºF 19.20 ºF 23.16 Btu/Lb

Caudal Aire x persona Aire Exterior (AE) % AE # Cambios / h

784 cfm 20 cfm 60 cfm 7.65 % 2.5

Asumiendo nuevo % AE : 15 %

Aire Exterior (AE) % AE # Cambios/h

118 cfm 15 % 4.9

76.50 ºF 64.56 ºF 29.70 Btu/Lb

= 17699 Btu/h

= 5130 Btu/h

= 22829 Btu/h

= 1691

CFM/TON = 412

TONELADAS = 1.9 ton.

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

watts/m2 x

QS

PERS - CL

QT

TBSINSUF TBHINSUF Delta TINSUF HINSUF

TBSMEZCLA TBHMEZCLA HMEZCLA

HS CALOR SENSIBLE

HL CALOR LATENTE

HT TOTAL

Btu/h-m2

Page 13: CALCULOS DE HOSPITAL.xlsx

CALCULOS DE AIRE ACONDICIONADO

12

CÁLCULO TÉRMICO Condiciones de diseño :

Sala :TBS = 75 ºF

PROYECTO SUNAT - HUANUCO HR = 50 %

Exterior :TBS = 85 ºF

ZONA SUPERVISOR CCF / 2 PISO TBH = 75 ºF

SIN TECHO AL SOL

MES/HORA JUNIO 12 M Conductividad termica :

Factor Rad.-vidrio (vent) 0.7

Nº PERSONAS 2 Vidrio (ventana) 1.0 Btu/h-ft²-ºF

Pared exterior 0.35 Btu/h-ft²-ºF

AREA 16.0 m² 172.8 ft² Pared interior 0.35 Btu/h-ft²-ºF

Piso 0.35 Btu/h-ft²-ºF

VOLUMEN 48.0 m³ 1699.2 ft³ Techo 0.35 Btu/h-ft²-ºF

VENTANA

VE-S 0.00.0 0.70 x 14 Btu/h-ft² = 0.0 Btu/h

0.0 1.00 10 ºF = 0.0 Btu/h

VE-SE 0.00.0 0.70 x 14 Btu/h-ft² = 0.0 Btu/h

0.0 1.00 10 ºF = 0.0 Btu/h

VE-E 0.00.0 0.70 x 14 Btu/h-ft² = 0.0 Btu/h

0.0 1.00 10 ºF = 0.0 Btu/h

VE-NE 0.00.0 0.70 x 79 Btu/h-ft² = 0.0 Btu/h

0.0 1.00 10 ºF = 0.0 Btu/h

VE-N 0.00.0 0.70 x 120 Btu/h-ft² = 0.0 Btu/h

0.0 1.00 10 ºF = 0.0 Btu/h

VE-NO 0.00.0 0.70 x 79 Btu/h-ft² = 0.0 Btu/h

0.0 1.00 10 ºF = 0.0 Btu/h

VE-O 0.00.0 0.70 x 14 Btu/h-ft² = 0.0 Btu/h

0.0 1.00 10 ºF = 0.0 Btu/h

VE-SO 0.00.0 0.70 x 14 Btu/h-ft² = 0.0 Btu/h

0.0 1.00 10 ºF = 0.0 Btu/h

VE-INTERIOR 0.0 0.0 1.00 10 ºF = 0.0 Btu/h

PARED

PA-S 0.0 0.0 0.35 10 ºF = 0.0 Btu/h

PA-SE 0.0 0.0 0.35 16 ºF = 0.0 Btu/h

PA-E 0.0 0.0 0.35 31 ºF = 0.0 Btu/h

PA-NE 0.0 0.0 0.35 28 ºF = 0.0 Btu/h

PA-N 0.0 0.0 0.35 12 ºF = 0.0 Btu/h

PA-NO 0.0 0.0 0.35 2 ºF = 0.0 Btu/h

PA-O 0.0 0.0 0.35 4 ºF = 0.0 Btu/h

PA-SO 0.0 0.35 2 ºF = 0.0 Btu/h

P- INTERIOR 0.0 0.0 0.35 10 ºF = 0.0 Btu/h

PISO 16.0 172.8 0.35 10 ºF = 604.8 Btu/h

TECHO 16.0 172.8 0.35 10 ºF = 604.8 Btu/h

ILUMIN. 25 1.25 x 16.0 m² x 3.41 Btu/h-watts = 1705.0 Btu/h

EQUIPOS 400 watts x 3.41 Btu/h-watts = 1364.0 Btu/h

PERS - Cs 250 Btu/h-persona x 2 personas = 500.0 Btu/h

= 4778.6 Btu/h

200 Btu/h-persona x 2 personas = 400.0 Btu/h

= 5178.6 Btu/h

R = 0.92

55.30 ºF 54.50 ºF 19.70 ºF 22.92 Btu/Lb

Caudal Aire x persona Aire Exterior (AE) % AE # Cambios / h

225 cfm 20 cfm 40 cfm 17.81 % 1.4

Asumiendo nuevo % AE : 15 %

Aire Exterior (AE) % AE # Cambios/h

34 cfm 15 % 1.2

76.50 ºF 64.56 ºF 29.70 Btu/Lb

= 5190 Btu/h

= 1586 Btu/h

= 6776 Btu/h

= 424

CFM/TON = 398

TONELADAS = 0.6 ton.

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

watts/m2 x

QS

PERS - CL

QT

TBSINSUF TBHINSUF Delta TINSUF HINSUF

TBSMEZCLA TBHMEZCLA HMEZCLA

HS CALOR SENSIBLE

HL CALOR LATENTE

HT TOTAL

Btu/h-m2

Page 14: CALCULOS DE HOSPITAL.xlsx

CALCULOS DE AIRE ACONDICIONADO

13

CÁLCULO TÉRMICO Condiciones de diseño :

Sala :TBS = 75 ºF

PROYECTO SUNAT - HUANUCO HR = 50 %

Exterior :TBS = 85 ºF

ZONA SUM / 2 PISO TBH = 75 ºF

SIN TECHO AL SOL

MES/HORA JUNIO 12 M Conductividad termica :

Factor Rad.-vidrio (vent) 0.7

Nº PERSONAS 55 Vidrio (ventana) 1.0 Btu/h-ft²-ºF

Pared exterior 0.35 Btu/h-ft²-ºF

AREA 57.9 m² 625.3 ft² Pared interior 0.35 Btu/h-ft²-ºF

Piso 0.35 Btu/h-ft²-ºF

VOLUMEN 173.7 m³ 6149.0 ft³ Techo 0.35 Btu/h-ft²-ºF

VENTANA

VE-S 0.00.0 0.7 x 14 Btu/h-ft² = 0.0 Btu/h

0.0 1 10 ºF = 0.0 Btu/h

VE-SE 0.00.0 0.7 x 14 Btu/h-ft² = 0.0 Btu/h

0.0 1 10 ºF = 0.0 Btu/h

VE-E 0.00.0 0.7 x 14 Btu/h-ft² = 0.0 Btu/h

0.0 1 10 ºF = 0.0 Btu/h

VE-NE 15.0162.0 0.7 x 79 Btu/h-ft² = 8958.6 Btu/h

162.0 1 10 ºF = 1620.0 Btu/h

VE-N 0.00.0 0.7 x 120 Btu/h-ft² = 0.0 Btu/h

0.0 1 10 ºF = 0.0 Btu/h

VE-NO 0.00.0 0.7 x 79 Btu/h-ft² = 0.0 Btu/h

0.0 1 10 ºF = 0.0 Btu/h

VE-O 0.00.0 0.7 x 14 Btu/h-ft² = 0.0 Btu/h

0.0 1 10 ºF = 0.0 Btu/h

VE-SO 0.00.0 0.7 x 14 Btu/h-ft² = 0.0 Btu/h

0.0 1 10 ºF = 0.0 Btu/h

VE-INTERIOR 0.0 0.0 1 10 ºF = 0.0 Btu/h

PARED

PA-S 0.0 0.0 0.35 10 ºF = 0.0 Btu/h

PA-SE 11.0 118.6 0.35 16 ºF = 664.1 Btu/h

PA-E 0.0 0.0 0.35 31 ºF = 0.0 Btu/h

PA-NE 12.0 129.6 0.35 28 ºF = 1270.1 Btu/h

PA-N 0.0 0.0 0.35 12 ºF = 0.0 Btu/h

PA-NO 15.3 165.2 0.35 2 ºF = 115.7 Btu/h

PA-O 0.0 0.0 0.35 4 ºF = 0.0 Btu/h

PA-SO 0.0 0.35 2 ºF = 0.0 Btu/h

P- INTERIOR 44.3 478.5 0.35 10 ºF = 1674.9 Btu/h

PISO 57.9 625.3 0.35 10 ºF = 2188.6 Btu/h

TECHO 57.9 625.3 0.35 10 ºF = 2188.6 Btu/h

ILUMIN. 25 1.25 x 57.9 m² x 3.41 Btu/h-watts = 6170.0 Btu/h

EQUIPOS 1000 watts x 3.41 Btu/h-watts = 3410.0 Btu/h

PERS - Cs 250 Btu/h-persona x 55 personas = 13750.0 Btu/h

= 42010.5 Btu/h

200 Btu/h-persona x 55 personas = 11000.0 Btu/h

= 53010.5 Btu/h

R = 0.79

52.40 ºF 51.40 ºF 22.60 ºF 21.09 Btu/Lb

Caudal Aire x persona Aire Exterior (AE) % AE # Cambios / h

1721 cfm 20 cfm 1100 cfm 63.91 % 10.7

Asumiendo nuevo % AE : 15 %

Aire Exterior (AE) % AE # Cambios/h

258 cfm 15 % 2.5

76.50 ºF 64.56 ºF 29.70 Btu/Lb

= 45214 Btu/h

= 20732 Btu/h

= 65946 Btu/h

= 1139

CFM/TON = 313

TONELADAS = 5.5 ton.

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

watts/m2 x

QS

PERS - CL

QT

TBSINSUF TBHINSUF Delta TINSUF HINSUF

TBSMEZCLA TBHMEZCLA HMEZCLA

HS CALOR SENSIBLE

HL CALOR LATENTE

HT TOTAL

Btu/h-m2

Page 15: CALCULOS DE HOSPITAL.xlsx

CALCULOS DE AIRE ACONDICIONADO

14

CÁLCULO TÉRMICO Condiciones de diseño :

Sala :TBS = 75 ºF

PROYECTO SUNAT - HUANUCO HR = 50 %

Exterior :TBS = 85 ºF

ZONA LACTARIO / 3 PISO TBH = 75 ºF

CON TECHO AL SOL

MES/HORA JUNIO 12 M Conductividad termica :

Factor Rad.-vidrio (vent) 0.7

Nº PERSONAS 6 Vidrio (ventana) 1.0 Btu/h-ft²-ºF

Pared exterior 0.35 Btu/h-ft²-ºF

AREA 10.3 m² 111.2 ft² Pared interior 0.35 Btu/h-ft²-ºF

Piso 0.35 Btu/h-ft²-ºF

VOLUMEN 30.9 m³ 1093.9 ft³ Techo 0.35 Btu/h-ft²-ºF

VENTANA

VE-S 0.00.0 0.70 x 14 Btu/h-ft² = 0.0 Btu/h

0.0 1.00 10 ºF = 0.0 Btu/h

VE-SE 0.00.0 0.70 x 14 Btu/h-ft² = 0.0 Btu/h

0.0 1.00 10 ºF = 0.0 Btu/h

VE-E 0.00.0 0.70 x 14 Btu/h-ft² = 0.0 Btu/h

0.0 1.00 10 ºF = 0.0 Btu/h

VE-NE 0.00.0 0.70 x 79 Btu/h-ft² = 0.0 Btu/h

0.0 1.00 10 ºF = 0.0 Btu/h

VE-N 0.00.0 0.70 x 120 Btu/h-ft² = 0.0 Btu/h

0.0 1.00 10 ºF = 0.0 Btu/h

VE-NO 0.00.0 0.70 x 79 Btu/h-ft² = 0.0 Btu/h

0.0 1.00 10 ºF = 0.0 Btu/h

VE-O 0.00.0 0.70 x 14 Btu/h-ft² = 0.0 Btu/h

0.0 1.00 10 ºF = 0.0 Btu/h

VE-SO 0.00.0 0.70 x 14 Btu/h-ft² = 0.0 Btu/h

0.0 1.00 10 ºF = 0.0 Btu/h

VE-INTERIOR 1.3 13.6 1.00 10 ºF = 136.1 Btu/h

PARED

PA-S 0.0 0.0 0.35 10 ºF = 0.0 Btu/h

PA-SE 10.9 117.3 0.35 16 ºF = 656.8 Btu/h

PA-E 0.0 0.0 0.35 31 ºF = 0.0 Btu/h

PA-NE 0.0 0.0 0.35 28 ºF = 0.0 Btu/h

PA-N 0.0 0.0 0.35 12 ºF = 0.0 Btu/h

PA-NO 0.0 0.0 0.35 2 ºF = 0.0 Btu/h

PA-O 0.0 0.0 0.35 4 ºF = 0.0 Btu/h

PA-SO 9.8 105.6 0.35 2 ºF = 73.9 Btu/h

P- INTERIOR 18.3 197.6 0.35 10 ºF = 691.7 Btu/h

PISO 10.3 111.2 0.35 10 ºF = 389.3 Btu/h

TECHO 10.3 111.2 0.35 16 ºF = 622.9 Btu/h

ILUMIN. 25 1.25 x 10.3 m² x 3.41 Btu/h-watts = 1097.6 Btu/h

EQUIPOS 300 watts x 3.41 Btu/h-watts = 1023.0 Btu/h

PERS - Cs 250 Btu/h-persona x 6 personas = 1500.0 Btu/h

= 6191.4 Btu/h

200 Btu/h-persona x 6 personas = 1200.0 Btu/h

= 7391.4 Btu/h

R = 0.84

53.80 ºF 52.80 ºF 21.20 ºF 21.90 Btu/Lb

Caudal Aire x persona Aire Exterior (AE) % AE # Cambios / h

270 cfm 20 cfm 120 cfm 44.38 % 6.6

Asumiendo nuevo % AE : 15 %

Aire Exterior (AE) % AE # Cambios/h

41 cfm 15 % 2.2

76.50 ºF 64.56 ºF 29.70 Btu/Lb

= 6691 Btu/h

= 2695 Btu/h

= 9386 Btu/h

= 911

CFM/TON = 346

TONELADAS = 0.8 ton.

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

watts/m2 x

QS

PERS - CL

QT

TBSINSUF TBHINSUF Delta TINSUF HINSUF

TBSMEZCLA TBHMEZCLA HMEZCLA

HS CALOR SENSIBLE

HL CALOR LATENTE

HT TOTAL

Btu/h-m2

Page 16: CALCULOS DE HOSPITAL.xlsx

CALCULOS DE AIRE ACONDICIONADO

15

CÁLCULO TÉRMICO Condiciones de diseño :

Sala :TBS = 75 ºF

PROYECTO SUNAT - HUANUCO HR = 50 %

Exterior :TBS = 85 ºF

ZONA COMEDOR / 3 PISO TBH = 75 ºF

CON TECHO AL SOL

MES/HORA JUNIO 12 M Conductividad termica :

Factor Rad.-vidrio (vent) 0.7

Nº PERSONAS 2 Vidrio (ventana) 1.0 Btu/h-ft²-ºF

Pared exterior 0.35 Btu/h-ft²-ºF

AREA 15.0 m² 162.0 ft² Pared interior 0.35 Btu/h-ft²-ºF

Piso 0.35 Btu/h-ft²-ºF

VOLUMEN 45.0 m³ 1593.0 ft³ Techo 0.35 Btu/h-ft²-ºF

VENTANA

VE-S 0.00.0 0.7 x 14 Btu/h-ft² = 0.0 Btu/h

0.0 1 10 ºF = 0.0 Btu/h

VE-SE 0.00.0 0.7 x 14 Btu/h-ft² = 0.0 Btu/h

0.0 1 10 ºF = 0.0 Btu/h

VE-E 0.00.0 0.7 x 14 Btu/h-ft² = 0.0 Btu/h

0.0 1 10 ºF = 0.0 Btu/h

VE-NE 0.00.0 0.7 x 79 Btu/h-ft² = 0.0 Btu/h

0.0 1 10 ºF = 0.0 Btu/h

VE-N 0.00.0 0.7 x 120 Btu/h-ft² = 0.0 Btu/h

0.0 1 10 ºF = 0.0 Btu/h

VE-NO 0.00.0 0.7 x 79 Btu/h-ft² = 0.0 Btu/h

0.0 1 10 ºF = 0.0 Btu/h

VE-O 0.00.0 0.7 x 14 Btu/h-ft² = 0.0 Btu/h

0.0 1 10 ºF = 0.0 Btu/h

VE-SO 5.559.0 0.7 x 14 Btu/h-ft² = 577.9 Btu/h

59.0 1 10 ºF = 589.7 Btu/h

VE-INTERIOR 0.0 0.0 1 10 ºF = 0.0 Btu/h

PARED

PA-S 0.0 0.0 0.35 10 ºF = 0.0 Btu/h

PA-SE 11.0 118.6 0.35 16 ºF = 664.1 Btu/h

PA-E 0.0 0.0 0.35 31 ºF = 0.0 Btu/h

PA-NE 10.4 112.8 0.35 28 ºF = 1105.0 Btu/h

PA-N 0.0 0.0 0.35 12 ºF = 0.0 Btu/h

PA-NO 15.8 170.7 0.35 2 ºF = 119.5 Btu/h

PA-O 0.0 0.0 0.35 4 ºF = 0.0 Btu/h

PA-SO 7.8 84.1 0.35 2 ºF = 58.9 Btu/h

P- INTERIOR 43.9 473.7 0.35 10 ºF = 1657.9 Btu/h

PISO 15.0 162.0 0.35 10 ºF = 567.0 Btu/h

TECHO 15.0 162.0 0.35 16 ºF = 907.2 Btu/h

ILUMIN. 25 1.25 x 15.0 m² x 3.41 Btu/h-watts = 1598.4 Btu/h

EQUIPOS 1000 watts x 3.41 Btu/h-watts = 3410.0 Btu/h

PERS - Cs 250 Btu/h-persona x 2 personas = 500.0 Btu/h

= 11755.6 Btu/h

200 Btu/h-persona x 2 personas = 400.0 Btu/h

= 12155.6 Btu/h

R = 0.97

56.00 ºF 55.10 ºF 19.00 ºF 23.28 Btu/Lb

Caudal Aire x persona Aire Exterior (AE) % AE # Cambios / h

573 cfm 20 cfm 40 cfm 6.98 % 1.5

Asumiendo nuevo % AE : 20 %

Aire Exterior (AE) % AE # Cambios/h

115 cfm 20 % 4.3

77.00 ºF 65.26 ºF 30.26 Btu/Lb

= 13113 Btu/h

= 4681 Btu/h

= 17794 Btu/h

= 1186

CFM/TON = 386

TONELADAS = 1.5 ton.

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2ft2 x

ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

m2 ft2 x Btu/h-ft2-ºF x

watts/m2 x

QS

PERS - CL

QT

TBSINSUF TBHINSUF Delta TINSUF HINSUF

TBSMEZCLA TBHMEZCLA HMEZCLA

HS CALOR SENSIBLE

HL CALOR LATENTE

HT TOTAL

Btu/h-m2

Page 17: CALCULOS DE HOSPITAL.xlsx

CALCULOS DE AIRE ACONDICIONADO

16

UBICACIÓN ZONACARGA TERMICA

(Toneladas)

1º PISO

SUPERVISOR CSC 1.50BACK OFFICE 0.70LOCKERS 0.50SALA DE ESPERA Y HALL 14.20CABINAS 2.50

2º PISO

BIBLIOTECA 2.10SALA DE REUNIONES 2.30LOCKERS 0.50CUARTO DE EQUIPOS 1.90SALA DE ESPERA 2 8.90SUPERVISOR CCF 0.60SUM 5.50

3º PISOLACTARIO 0.80COMEDOR 2.90

Page 18: CALCULOS DE HOSPITAL.xlsx

CALCULOS DE AIRE ACONDICIONADO

16

CARGA TERMICA(Btu/H)1800084006000

1704003000025200276006000

22800106800

7200660009600

34800