PLANILLA PARA CALCUL EDIFICIO: AVELLANEDA (Sta Fe HORA LATITUD VIVIENDA UNIFAMILIAR 15 35 PISO: PB LOCAL: COMEDOR-HALL-ESTAR L Tipo LADOS AREA AREA A Espes. PARED TOTAL PARED D Orient VIDRIO AREA O A (m) B (m) (m2) VIDRIO 1 E30 2.60 4.80 12.5 12.5 O 0.0 2 E30 0.45 2.60 1.2 1.2 N 0.0 3 E30 0.80 2.60 2.1 1.3 NO 0.50 1.60 0.8 4 E30 1.20 2.60 3.1 1.8 N 0.80 1.60 1.3 5 E30 0.80 2.60 2.1 1.3 NE 0.50 1.60 0.8 6 E30 0.60 2.60 1.6 1.6 N 0.0 7 E15 1.10 2.60 2.9 2.9 E 0.0 8 E15 2.00 2.60 5.2 1.4 N 1.80 2.10 3.8 9 E15 1.10 2.60 2.9 2.9 O 0.0 10 E30 0.45 2.60 1.2 1.2 N 0.0 11 E30 0.80 2.60 2.1 1.3 NO 0.50 1.60 0.8 12 E30 1.20 2.60 3.1 1.8 N 0.80 1.60 1.3 13 E30 0.80 2.60 2.1 1.3 NE 0.50 1.60 0.8 14 E30 0.60 2.60 1.6 1.6 N 0.0 15 I15 4.50 2.60 11.7 11.7

Upload: blacksoul59

Post on 18-Dec-2015

239 views

Category:

Documents


1 download

DESCRIPTION

Cargas Verano Vivienda

TRANSCRIPT

COMEDOR HALL ESTARPLANILLA PARA CALCULO DE CARGAS DE VERANOEDIFICIO:AVELLANEDA (Sta Fe)HORALATITUDTBS ext(C)38.0HR ext( %)75he exterior14.0DEL ABACOVIVIENDA UNIFAMILIAR1535TBS int(C)25.0HR int( %)50he interior10.0PSICROMTRICOPISO:PBLOCAL:COMEDOR-HALL-ESTARDT (C)13.0DG (g/kg)4.0LTipoLADOSAREAAREAKPDteTRANSMISIONCoef.Intens.RADIACIONAEspes.PAREDTOTALPARED(kcal/hm2C)CY EFECTO SOLARProt.SolarSOLARDOrientVIDRIOAREAKVDtVidrio(kcal/hm2)VENTANAOA (m)B (m)(m2)VIDRIO(kcal/hm2C)C(kcal/h)CI(kcal/h)1E302.604.8012.512.51.6168.0161O0.0002E300.452.601.21.21.61611.021N0.0003E300.802.602.11.31.6169.019NO0.501.600.85.000520.704272394E301.202.603.11.81.61611.033N0.801.601.35.000830.901902195E300.802.602.11.31.61613.027NE0.501.600.85.000520.9032236E300.602.601.61.61.61611.028N0.0007E151.102.602.92.90.88513.033E0.0008E152.002.605.21.40.8856.08N1.802.103.83.00014709E151.102.602.92.90.8858.020O0.00010E300.452.601.21.21.61611.021N0.00011E300.802.602.11.31.6169.019NO0.501.600.85.000520.7042723912E301.202.603.11.81.61611.033N0.801.601.35.000830.9019021913E300.802.602.11.31.61613.027NE0.501.600.85.000520.90322314E300.602.601.61.61.61611.028N0.00015I154.502.6011.711.72.4117.01970.00016I158.702.6022.622.62.4117.03820.000TECHO9.004.8043.243.22.0707.06260.000PISO0.00.00TOTALES TRANSM. Y EFECTO SOLAR(kcal/h)TRANSMISION2204E.SOL.VENT962SUB TOTAL CARGA EXTERIOR (kcal/h)3166QLIPersonas (factor)60480Porcentaje prdida conductos(%)8LatenteOtras fuentes (kcal/h)200TOTAL CARGA EXTERIOR(kcal/h)3419InteriorQLI: CALOR LATENTE INT.680QSIPersonas(factor)55FCS0.89TI C15.0%Caud.10(cantidad)8440QECaudal de aire exterior (m3/min)4.0CalorIluminacin(Watt)14501247CalorCalor sens.aire exterior(kcal/h)884Sens.Motores(HP)0AireCalor latent. aire exterior(kcal/h)672Inter.Disipaciones varias (kcal/h)500ExteriorQE:CAL.TOTAL AExt.(kcal/h)1556TOTAL CALOR SENSIBLE INTERIOR (QSI)QT y QST (frig/h),TONELADAS Y CAUDALTOTAL QSI ( kcal/h)5606QT7842TR3QST6490TOTAL QSI ( Kw/h )6.5QT(Kw/h)9.1CAUDALm3/min33

COM DIARIOPLANILLA PARA CALCULO DE CARGAS DE VERANOEDIFICIO:AVELLANEDA (Sta Fe)HORALATITUDTBS ext(C)38.0HR ext( %)75he exterior14.0DEL ABACOVIVIENDA UNIFAMILIAR1535TBS int(C)25.0HR int( %)50he interior10.0PSICROMTRICOPISO:PBLOCAL:COMEDOR DIARIODT (C)13.0DG (g/kg)4.0LTipoLADOSAREAAREAKPDteTRANSMISIONCoef.Intens.RADIACIONAEspes.PAREDTOTALPARED(kcal/hm2C)CY EFECTO SOLARProt.SolarSOLARDOrientVIDRIOAREAKVDtVidrio(kcal/hm2)VENTANAOA (m)B (m)(m2)VIDRIO(kcal/hm2C)C(kcal/h)CI(kcal/h)17E306.452.6016.816.81.6168.0217O0.00018I155.352.6013.913.92.4117.02350.00019I152.702.607.05.42.4117.0910.802.051.63.50075020I151.002.602.61.02.4117.0160.802.051.63.50075021I153.602.609.47.72.4117.01300.802.051.63.50075022E300.602.601.61.61.6164.010S0.00023E301.412.603.71.91.6169.027SE1.201.501.85.0001170.90386224E301.252.603.31.71.6164.011S1.001.601.65.0001040.90385525E301.412.603.71.91.6165.015SO1.201.501.85.0001170.9023037326E300.602.601.61.61.6164.010S0.000TECHO4.407.7534.112.62.0707.01834.305.0021.50.6001680PISO0.00.00TOTALES TRANSM. Y EFECTO SOLAR(kcal/h)TRANSMISION1676E.SOL.VENT490SUB TOTAL CARGA EXTERIOR (kcal/h)2166QLIPersonas (factor)80480Porcentaje prdida conductos(%)8LatenteOtras fuentes (kcal/h)TOTAL CARGA EXTERIOR(kcal/h)2339InteriorQLI: CALOR LATENTE INT.480QSIPersonas(factor)60FCS0.90TI C15.0%Caud.10(cantidad)6360QECaudal de aire exterior (m3/min)3.0CalorIluminacin(Watt)15001290CalorCalor sens.aire exterior(kcal/h)663Sens.Motores(HP)0AireCalor latent. aire exterior(kcal/h)504Inter.Disipaciones varias (kcal/h)500ExteriorQE:CAL.TOTAL AExt.(kcal/h)1167TOTAL CALOR SENSIBLE INTERIOR (QSI)QT y QST (frig/h),TONELADAS Y CAUDALTOTAL QSI ( kcal/h)4489QT6136TR2QST5152TOTAL QSI ( Kw/h )5.2QT(Kw/h)7.1CAUDALm3/min26

COCINAPLANILLA PARA CALCULO DE CARGAS DE VERANOEDIFICIO:AVELLANEDA (Sta Fe)HORALATITUDTBS ext(C)38.0HR ext( %)75he exterior14.0DEL ABACOVIVIENDA UNIFAMILIAR1535TBS int(C)25.0HR int( %)50he interior10.0PSICROMTRICOPISO:PBLOCAL:COCINA - LAVADERODT (C)13.0DG (g/kg)4.0LTipoLADOSAREAAREAKPDteTRANSMISIONCoef.Intens.RADIACIONAEspes.PAREDTOTALPARED(kcal/hm2C)CY EFECTO SOLARProt.SolarSOLARDOrientVIDRIOAREAKVDtVidrio(kcal/hm2)VENTANAOA (m)B (m)(m2)VIDRIO(kcal/hm2C)C(kcal/h)CI(kcal/h)27I152.002.605.25.22.4117.0880.00028I151.002.602.61.02.4117.0160.802.051.63.50075029I150.602.601.61.62.4117.0260.00030I153.202.608.38.32.4117.01400.00031E152.702.607.04.90.88513.056E1.201.802.25.0001400.40353032E154.302.6011.29.60.8853.025S1.800.901.65.0001050.203812TECHO4.302.7011.611.62.0707.01680.000PISO0.00.00TOTALES TRANSM. Y EFECTO SOLAR(kcal/h)TRANSMISION839E.SOL.VENT42SUB TOTAL CARGA EXTERIOR (kcal/h)881QLIPersonas (factor)80240Porcentaje prdida conductos(%)8LatenteOtras fuentes (kcal/h)600TOTAL CARGA EXTERIOR(kcal/h)951InteriorQLI: CALOR LATENTE INT.840QSIPersonas(factor)60FCS0.81TI C15.0%Caud.10(cantidad)3180QECaudal de aire exterior (m3/min)2.1CalorIluminacin(Watt)15001290CalorCalor sens.aire exterior(kcal/h)464Sens.Motores(HP)1700AireCalor latent. aire exterior(kcal/h)353Inter.Disipaciones varias (kcal/h)500ExteriorQE:CAL.TOTAL AExt.(kcal/h)817TOTAL CALOR SENSIBLE INTERIOR (QSI)QT y QST (frig/h),TONELADAS Y CAUDALTOTAL QSI ( kcal/h)3621QT5278TR2QST4085TOTAL QSI ( Kw/h )4.2QT(Kw/h)6.1CAUDALm3/min21

DORM 1PLANILLA PARA CALCULO DE CARGAS DE VERANOEDIFICIO:AVELLANEDA (Sta Fe)HORALATITUDTBS ext(C)38.0HR ext( %)75he exterior14.0DEL ABACOVIVIENDA UNIFAMILIAR1535TBS int(C)25.0HR int( %)50he interior10.0PSICROMTRICOPISO:PBLOCAL:DORMITORIO 1DT (C)13.0DG (g/kg)4.0LTipoLADOSAREAAREAKPDteTRANSMISIONCoef.Intens.RADIACIONAEspes.PAREDTOTALPARED(kcal/hm2C)CY EFECTO SOLARProt.SolarSOLARDOrientVIDRIOAREAKVDtVidrio(kcal/hm2)VENTANAOA (m)B (m)(m2)VIDRIO(kcal/hm2C)C(kcal/h)CI(kcal/h)33E302.604.8012.512.51.6168.0161O0.00034E300.452.601.21.21.61611.021N0.00035E300.802.602.11.31.6169.019NO0.501.600.85.00520.7042723936E301.202.603.11.81.61611.033N0.801.601.35.00830.9019021937E300.802.602.11.31.61613.027NE0.501.600.85.00520.90322338E300.602.601.61.61.61611.028N0.00039I152.502.606.56.52.4117.01100.00040I152.152.605.65.62.4117.0940.00041I152.002.605.25.22.4117.0880.00042I155.352.6013.913.92.4117.02350.000TECHO21.421.40.80418.03100.000PISO21.421.42.077.0310TOTALES TRANSM. Y EFECTO SOLAR(kcal/h)TRANSMISION1623E.SOL.VENT481SUB TOTAL CARGA EXTERIOR (kcal/h)2104QLIPersonas (factor)60120Porcentaje prdida conductos(%)8LatenteOtras fuentes (kcal/h)100TOTAL CARGA EXTERIOR(kcal/h)2272InteriorQLI: CALOR LATENTE INT.220QSIPersonas(factor)55FCS0.94TI C15.0%Caud.10(cantidad)2110QECaudal de aire exterior (m3/min)1.9CalorIluminacin(Watt)750645CalorCalor sens.aire exterior(kcal/h)420Sens.Motores(HP)0AireCalor latent. aire exterior(kcal/h)319Inter.Disipaciones varias (kcal/h)200ExteriorQE:CAL.TOTAL AExt.(kcal/h)739TOTAL CALOR SENSIBLE INTERIOR (QSI)QT y QST (frig/h),TONELADAS Y CAUDALTOTAL QSI ( kcal/h)3227QT4186TR1QST3647TOTAL QSI ( Kw/h )3.8QT(Kw/h)4.9CAUDALm3/min19

DORM 2PLANILLA PARA CALCULO DE CARGAS DE VERANOEDIFICIO:AVELLANEDA (Sta Fe)HORALATITUDTBS ext(C)38.0HR ext( %)75he exterior14.0DEL ABACOVIVIENDA UNIFAMILIAR1535TBS int(C)25.0HR int( %)50he interior10.0PSICROMTRICOPISO:PBLOCAL:DORMITORIO 2DT (C)13.0DG (g/kg)4.0LTipoLADOSAREAAREAKPDteTRANSMISIONCoef.Intens.RADIACIONAEspes.PAREDTOTALPARED(kcal/hm2C)CY EFECTO SOLARProt.SolarSOLARDOrientVIDRIOAREAKVDtVidrio(kcal/hm2)VENTANAOA (m)B (m)(m2)VIDRIO(kcal/hm2C)C(kcal/h)CI(kcal/h)43E302.732.607.16.51.61611115N0.800.800.65.00420.9019010944E300.802.602.11.31.6169.019NO0.501.600.85.00520.7042723945E301.202.603.11.81.61611.033N0.801.601.35.00830.9019021946E300.802.602.11.31.61613.027NE0.501.600.85.00520.90322347E300.602.601.61.61.61611.028N0.00048I154.502.6011.711.72.4117.01970.00049I153.202.608.38.32.4117.01400.00050I152.152.605.65.62.4117.0940.00051I152.002.605.25.22.4117.0880.00052I152.352.606.16.12.4117.01030.000TECHO17.117.10.804182480.000PISO17.117.12.077.0248TOTALES TRANSM. Y EFECTO SOLAR(kcal/h)TRANSMISION1569E.SOL.VENT590SUB TOTAL CARGA EXTERIOR (kcal/h)2159QLIPersonas (factor)60120Porcentaje prdida conductos(%)8LatenteOtras fuentes (kcal/h)100TOTAL CARGA EXTERIOR(kcal/h)2332InteriorQLI: CALOR LATENTE INT.220QSIPersonas(factor)55FCS0.94TI C15.0%Caud.10(cantidad)2110QECaudal de aire exterior (m3/min)1.9CalorIluminacin(Watt)750645CalorCalor sens.aire exterior(kcal/h)420Sens.Motores(HP)0AireCalor latent. aire exterior(kcal/h)319Inter.Disipaciones varias (kcal/h)200ExteriorQE:CAL.TOTAL AExt.(kcal/h)739TOTAL CALOR SENSIBLE INTERIOR (QSI)QT y QST (frig/h),TONELADAS Y CAUDALTOTAL QSI ( kcal/h)3287QT4246TR1QST3707TOTAL QSI ( Kw/h )3.8QT(Kw/h)4.9CAUDALm3/min19

DORM 3PLANILLA PARA CALCULO DE CARGAS DE VERANOEDIFICIO:AVELLANEDA (Sta Fe)HORALATITUDTBS ext(C)38.0HR ext( %)75he exterior14.0DEL ABACOVIVIENDA UNIFAMILIAR1535TBS int(C)25.0HR int( %)50he interior10.0PSICROMTRICOPISO:PBLOCAL:DORMITORIO 3DT (C)13.0DG (g/kg)4.0LTipoLADOSAREAAREAKPDteTRANSMISIONCoef.Intens.RADIACIONAEspes.PAREDTOTALPARED(kcal/hm2C)CY EFECTO SOLARProt.SolarSOLARDOrientVIDRIOAREAKVDtVidrio(kcal/hm2)VENTANAOA (m)B (m)(m2)VIDRIO(kcal/hm2C)C(kcal/h)CI(kcal/h)53I156.652.6017.317.32.4117.02920.00054E303.352.608.75.41.61611.097N2.051.603.35.00213055E306.652.6017.317.31.6168.0224E0.00056E153.352.608.78.70.885323S0.000TECHO22.322.30.804183220.000PISO22.322.32.077.0323TOTALES TRANSM. Y EFECTO SOLAR(kcal/h)TRANSMISION1494E.SOL.VENT0SUB TOTAL CARGA EXTERIOR (kcal/h)1494QLIPersonas (factor)60120Porcentaje prdida conductos(%)8LatenteOtras fuentes (kcal/h)100TOTAL CARGA EXTERIOR(kcal/h)1614InteriorQLI: CALOR LATENTE INT.220QSIPersonas(factor)55FCS0.92TI C15.0%Caud.10(cantidad)2110QECaudal de aire exterior (m3/min)1.5CalorIluminacin(Watt)750645CalorCalor sens.aire exterior(kcal/h)332Sens.Motores(HP)0AireCalor latent. aire exterior(kcal/h)252Inter.Disipaciones varias (kcal/h)200ExteriorQE:CAL.TOTAL AExt.(kcal/h)584TOTAL CALOR SENSIBLE INTERIOR (QSI)QT y QST (frig/h),TONELADAS Y CAUDALTOTAL QSI ( kcal/h)2569QT3373TR1QST2901TOTAL QSI ( Kw/h )3.0QT(Kw/h)3.9CAUDALm3/min15

ResumenLocalQtotal(frig/h)(kW/h)(TR)Comedor - Hall - Estar78429.122.61Comedor Diario61367.132.05Cocina52786.141.76TOTAL P.B.1925622.396.42LocalQtotal(frig/h)(kW/h)(TR)Dormitorio 141864.871.40Dormitorio 242464.941.42Dormitorio 333733.921.12TOTAL P.A.1180513.733.94