Download - Metrado de Cargas v01
PREDIMENSIONAMIENTO DE ELEMENTOS ESTRUCTURALESLOSA ALIGERADA
L (m) FACTOR
4.68 25.00 0.19
VIGASVIGA PRINCIPAL
L (m) FACTOR
7.00 10.00 0.70
B (m)0.30 SE USA EL ANCHO MINIMO PARA VIGA PRINCIPAL
LA VIGA PRINCIPAL SERA DE : 0.30m. X 0.70m.
VIGASVIGA SECUNDARIA
L (m) FACTOR
4.68 10.00 0.47
NOTA: POR DECISION PROPIA PARA EN ANALISIS SE USARA LA MISMA ALTURA DE LA VIGA PRINCIPAL
B (m)0.30 SE USA EL MISMO ANCHO QUE LA VIGA PRINCIPAL
LA VIGA SECUNDARIA SERA DE : 0.30m. X 0.70m.
COLUMNAS
PS n f'c (Kg/cm2)
92181.60 0.45 280
DETERMINACION DE LA CARGA DE SERVICIO PS
Kg/m3 Kg/m2 LONGITUD 1LOSA ALIGERADA 300.00 3.50VIGA SECUNDARIA 2400.00VIGA PRINCIPAL 2400.00ACAB. + TABIQU. 250.00 3.50COLUMNA 2400.00
ALTURA DE LOSA ALIGERADA
ALTURA DE VIGA PRINCIPAL
ALTURA DE VIGA SECUNDARIA
SOBRECARGA 250.00 3.50
VERIFICACION DEL AREA DE COLUMNA1000cm21000cm2
ALTERNATIVA PARA ANCHO DE COLUMNAH de viga
0.70VERIFICACION DEL AREA DE COLUMNA
1000cm21000cm2
LA COLUMNA SERA DE : 0.56m. X 0.30m.
COLOCACION DE CARGASLOSA ALIGERADA
CARGA MUERTAPESO DEL LADRILLO 80.00 Kg/m2TABIQ. + ACAB. 250.00 Kg/m2
330.00 Kg/m2
0.40 m.
CARGA DISTRIBUIDA 132.00 Kg/m
CARGA VIVAS/C 250.00 Kg/m2
250.00 Kg/m2
0.40 m.
CARGA DISTRIBUIDA 100.00 Kg/m
CALCULO DEL PESO 2°,3°y 4° piso
Kg/m3 Kg/m2 LONGITUD 1
LOSA ALIGERADA 300.00 7.00VIGA PRINCIPAL 2400.00VIGA SECUNDARIA 2400.00ACAB. + TABIQU. 250.00 7.00COLUMNA 2400.00SOBRECARGA 250.00 7.00
CALCULO DEL PESO 5°PISO
ANCHO SUPERIOR DE LOSA ALIGERADA
ANCHO SUPERIOR DE LOSA ALIGERADA
Kg/m3 Kg/m2 LONGITUD 1
LOSA ALIGERADA 300.00 7.00VIGA PRINCIPAL 2400.00VIGA SECUNDARIA 2400.00ACABADOS 100.00 7.00COLUMNA 2400.00SOBRECARGA 100.00 7.00
CALCULO DEL PESO 1°PISO
Kg/m3 Kg/m2 LONGITUD 1
LOSA ALIGERADA 300.00 7.00VIGA PRINCIPAL 2400.00VIGA SECUNDARIA 2400.00ACAB. + TABIQU. 250.00 7.00COLUMNA 2400.00SOBRECARGA 250.00 7.00
DX 7.00 mDY 21.00 m
CALCULO DE LA CORTANTE BASAL
Z 0.4U 1Cx 2.5Cy 2.5S 1.4R 8
Vx 0.175
Vy 0.175
V=𝑍𝑈𝐶𝑆/𝑅 𝑋 𝑃
Vx=𝑍𝑈𝐶𝑆/𝑅 Vy=𝑍𝑈𝐶𝑆/𝑅
FACTOR DE AMPLIFICACION SISMICA ( C )
Tx= 0.43428571429 mH 15.20
Ctx= 35Tp= 0.9
Cx 5.18092105263Cx 2.5
VX 0.175*P 122518.767 KGVY 0.175*P 122518.767 KG
NIVELES ALT ACUM. PESO ALT*PESO5 15.200 112068.600 1703442.7204 12.200 146888.700 1792042.1403 9.200 146888.700 1351376.0402 6.200 146888.700 910709.9401 3.200 147372.540 471592.128
700107.240 6229162.968
x -8.5y -1.5
Cx=2.5 𝑋 (𝑇𝑝/𝑇𝑥 ) ≤ 2.5
0.20 m
m
SE USA EL ANCHO MINIMO PARA VIGA PRINCIPAL
0.70 m
NOTA: POR DECISION PROPIA PARA EN ANALISIS SE USARA LA MISMA ALTURA DE LA VIGA PRINCIPAL
SE USA EL MISMO ANCHO QUE LA VIGA PRINCIPAL
^
AREA DE COLUMNA
731.6 cm2
LONGITUD 2 ALTURA SECCION 1 SECCION 2 N° DE PISOS4.68 5.004.68 0.70 0.30 5.003.50 0.70 0.30 5.004.68 5.00
3.00 0.30 0.56 5.00
ALTURA DE LOSA ALIGERADA(red.)
ALTURA DE VIGA SECUNDARIA A USAR
4.68 5.00
PS
≤ A. columna ≥ 2000cm2≤ 731.6 ≥ 2000cm2 NO PASA
% ANCHO DE COLUMNA80% 0.56 m
≤ A. columna ≥ 2000cm2≤ 1680.00 ≥ 2000cm2 OK
LA COLUMNA SERA DE : 0.56m. X 0.30m.
LONGITUD 2 ALTURA SECCION 1 SECCION 2 CANTIDAD
21.00 1.007.00 0.70 0.30 6.00
21.00 0.70 0.30 2.0021.00 1.00
3.00 0.56 0.30 12.0021.00
LONGITUD 2 ALTURA SECCION 1 SECCION 2 CANTIDAD
21.00 1.007.00 0.70 0.30 6.00
21.00 0.70 0.30 2.0021.00 1.00
1.50 0.56 0.30 12.0021.00
LONGITUD 2 ALTURA SECCION 1 SECCION 2 CANTIDAD
21.00 1.007.00 0.70 0.30 6.00
21.00 0.70 0.30 2.0021.00 1.00
3.10 0.56 0.30 12.0021.00
Tx= 0.4342857142857 mH 15.20
Ctx= 35Tp= 0.9
Cy 5.1809210526316Cy 2.5
F SISMICA X VX MTZ X F SISMICA Y VY33504.293 33504.293 35179.508 33504.293 33504.29335246.918 68751.211 37009.263 35246.918 68751.21126579.643 95330.853 27908.625 26579.643 95330.85317912.368 113243.221 18807.986 17912.368 113243.221
9275.546 122518.767 9739.323 9275.546 122518.767122518.767 122518.767
Cy=2.5 𝑋 (𝑇𝑝/𝑇𝑥 ) ≤ 2.5
PESO PARCIAL24570.0011793.60
8820.0020475.00
6048.00
20475.00
92181.60 Kg.
PESO PARCIAL
44100.0021168.0021168.0036750.0014515.20
25% 9187.50
146888.70 Kg. Para 2°,3°y 4°piso
factor RNE art.16.3
PESO PARCIAL
44100.0021168.0021168.0014700.00
7257.6025% 3675.00
112068.60 Kg.
PESO PARCIAL
44100.0021168.0021168.0036750.0014999.04
25% 9187.50
147372.54 Kg.
factor RNE art.16.3
factor RNE art.16.3
MTZ Y11726.50312336.421
9302.8756269.3293246.441
CARGAS DE FUERZA AXIAL Kgf
EJE A-1EJE A-2EJE A-3EJE A-4EJE A-5EJE A-6
DISTORSIONES ELASTICAS
N° DE PISOSX SY
X Y X Y1 0 0 0.00019 0.0025752 0.002019 0.000058 0.000193 0.0026123 0.001045 0.000049 0.000156 0.0022364 0.001467 0.000034 0.000116 0.0017075 0.000955 0.000017 0.000065 0.001003
LO SOLICITADO POR LA NORMA E-030 0.007
DISTORSIONES INELASTICAS
N° DE PISOSX SX
X Y X Y1 0.00000000 0.00000000 OK OK2 0.01211400 0.00034800 NO PASA OK3 0.00627000 0.00029400 NO PASA OK4 0.00880200 0.00020400 NO PASA OK5 0.00573000 0.00010200 OK OK
N° DE PISOSY SY
X Y X Y1 0.00114000 0.01545000 OK NO PASA2 0.00115800 0.01567200 OK NO PASA3 0.00093600 0.01341600 OK NO PASA4 0.00069600 0.01024200 OK NO PASA5 0.00039000 0.00601800 OK NO PASA
6