  • 8/12/2019 Desarrollo Aci 318 11

    1/4

    ACI-318-11

    Longitud de desarrollo de varillas

    corrugadas a tensinProyecto: fecha: Sep-13

    Fy = 59684 psi 4200 kg/cm^2f 'c = 3013 psi 212 kg/cm^2

    yt = 1

    ye = 1

    dim. = 1 in

    l = 1 conc. Peso normal

    Fy yt ye / l(f 'c)^.5 = 1087.39

    caso = 2

    0 20 0 0 20

    d = 54.37 dimetrosusar 44 dimetros

    ACI 12.2.2

    Factors for Use in the Expressions for Determining Required Development Lengths for

    Deformed Bars and Deformed Wires in Tension (ACI 12.2.4)

    (1) t = reinforcement location factor

    Horizontal reinforcement so placed that more than 12 in. of fresh concrete is cast in the member

    below the development length or splice . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.3

    Other reinforcement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.0

    (2) e = coating factor

    Epoxy-coated bars or wires with cover less than 3db, or clear spacing less than 6db . . . . . . . . . . . 1.5

    All other epoxy-coated bars or wires . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.2

    Uncoated and zinc-coated reinforcement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.0

    However, the product of te need not be taken as greater than 1.7.

    Para aplicar la frmula 12-1, seguir el siguiente procedimiento:

    (3) s = reinforcement size factor

    CASO 1 CASO 2

    CASO 3 CASO 4

  • 8/12/2019 Desarrollo Aci 318 11

    2/4

    No. 6 and smaller bars and deformed wires . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.8

    No. 7 and larger bars . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.0

    In SI units

    No. 19 and smaller bars and deformed wires . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.8

    No. 22 and larger bars . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.0

    (4) (lambda) = lightweight aggregate concrete factorWhen lightweight aggregate concrete is used, shall not exceed . . . . . . . . . . . . . . . . . . . . . . . . . 0.75

    However, when fct is specified, shall be permitted to be taken as 6.7 *

    fct = resistencia promedio a la tensin (traccin)

    Its in SI

    but not greater than . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.0

    When normal weight concrete is used . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.0

    (5) cb = spacing or cover dimension, in.

    Use the smaller of either the distance from the center of the bar or wire to the nearest concrete surface,

    or one-half the center-to-center spacing of the bars or wires being developed.

    In the following paragraphs, all of the terms in ACI Equation 12-1 that have not previously

    been introduced are described. their values for different situations were given in

    the previous page.

    1. Location of reinforcementHorizontal bars that have a least 12 in.[3] of fresh concrete

    placed beneath them do not bond as well to concrete as do bars placed nearer the bottom

    of the concrete. These bars are referred to as top bars. During the placing and vibration

    of the concrete, some air and excess water tend to rise toward the top of the concrete,

    and some portion may be caught under the higher bars. In addition, there may be some

    settlement of the concrete below. As a result, the reinforcement does not bond as well to

    the concrete underneath, and increased development lengths will be needed. To account

    for this effect, the reinforcement location factor, t, is used.

    2. Coating of barsEpoxy-coated reinforcing bars are frequently used today to protect the

    steel from severe corrosive situations, such as where deicing chemicals are used. Bridge

    decks and parking garage slabs in the colder states fit into this class. When bar coatings

    are used, bonding is reduced and development lengths must be increased. To account

    for this fact, the term ethe coating factoris used in the equation.

    3. Sizes of reinforcingIf small bars are used in a member to obtain a certain total crosssectional

    area, the total surface area of the bars will be appreciably larger than if fewer

    but larger bars are used to obtain the same total bar area. As a result, the required

    development lengths for smaller bars with their larger surface bonding areas (in proportion

    to their cross-sectional areas) are less than those required for larger-diameter bars.

    This factor is accounted for with the reinforcement size factor, s.

    4. Lightweight aggregatesThe dead weight of concrete can be substantially reduced by

    substituting lightweight aggregate for the regular stone aggregate. The use of such aggregates

    (expanded clay or shale, slag, etc.) generally results in lower-strength concretes.Such concretes have lower splitting strengths, and so development lengths will have to

    be larger. In the equation, is the lightweight concrete modification factor discussed in

    Section 1.12.

    5. Spacing of bars or cover dimensionsShould the concrete cover or the clear spacing

    between the bars be too small, the concrete may very well split, as was previously

    shown in Figure 7.6. This situation is accounted for with the (cb Ktr)/db term in the

    development length expression. It is called the confinement term. In the equation, cb

    fctcf /'

    fctcf 8.1/'

  • 8/12/2019 Desarrollo Aci 318 11

    3/4

    represents the smaller of the distance from the center of the tension bar or wire to the

    nearest concrete surface, or one-half the center-to-center spacing of the reinforcement.

    In this expression, Ktr is a factor called the transverse reinforcement index. It is used to

    account for the contribution of confining reinforcing (stirrups or ties) across possible splitting

    planes.

    Ktr = 40Atr / sn

    where:

    Atr = the total cross-sectional area of all transverse reinforcement having the

    center-to-center spacing s and a yield strength fyt

    n = the number of bars or wires being developed along the plane of splitting. If steel

    is in two layers, n is the largest number of bars in a single layer.

    s = center-to-center spacing of transverse reinforcing

    The code in Section 12.2.3 conservatively permits the use of Ktr = 0 to simplify the calculations,

    even if transverse reinforcing is present. ACI 12.2.3 limits the value of (cb + Ktr)/db

    used in the equation to a maximum value of 2.5. (It has been found that if values larger than

    2.5 are used, the shorter development lengths resulting will increase the danger of pullout-type

    failures.)

    The calculations involved in applying ACI Equation 12-1 are quite simple, as is illustratedin Example 7.2.(del libro de Mcormac y Brown, 9a edicin)

    In SI units, Ktr = Atr fyt / 10sn

    dimetro de estribos = 3/8 in

    ramas verticales = 2

    Atr = 0.221 in^2

    db = 1 in acero longitudinal

    cb = 1.5 in recub. o dist a c-c de vrs long.

    ys = 1

    espaciam. Entre estribos "s"= 8 incant de vrs long "n" = 3

    Ktyr = 40 Atr/sn = 0.368

    Fy yt ye ys / l(f 'c) .5 = 1087.3945

    (cb+Ktr/db) = 1.87 in o.k.

    debe ser =< 2.5

    d = 44 dimetros

  • 8/12/2019 Desarrollo Aci 318 11

    4/4

    ACI-318-11, 12.3

    Longitud de desarrollo de varillas

    corrugadas a compresinProyecto: fecha: Sep-13

    = 1 Concreto de peso normalFy = 411.85 Mpa

    f 'c = 35 Mpa

    diam de varillas = 1.5 in

    12.3.2 SI

    eq. 1 (0.24fy /(fc)^.5 )db

    eq. 2 (0.043fy)db

    db = 38 mm

    eq. 1 eq. 2635 673 mm

    Esta longitud puede ser multiplicada por:

    rel= As req./As real

    rel L dc

    0.7 471 mm

    0.75 505 mm

    0.8 538 mm

    0.85 572 mm

    0.9 606 mm

    12.3.1 L dc no debe ser menor de 200 mm

    12.2.3 Si el ref est confinado por una espiral de dimetro. => 6 mm y una separacin =