    47Flkt Woods EN 2009.09 All rights reserved.

    Smoke extraction damper ETER TECHNICAL DATA

    ETER Smoke extraction damper

    ETER smoke extraction damper is intended to extract ue gases and to reducepressure in the ventilation ducts or re separating compartments. The objec-tive is to considerably restrict the spread of smoke through re compartmentsand to facilitate evacuation and/or re ghting. The damper is inserted intoventilation duct or into a smoke extraction duct that is common to all re com-partments, or it can be used as an air terminal device that leads any existingsmoke outside. The extraction of gases/reduction of pressure can be intensi-ed by using fans.

    The re damper is closed during normal ventilation. When the smoke detector detects smoke, the power supply to the actuator is

    interrupted and the damper opens automatically. The re damper is equipped with electrical switches for indicating the end

    positions of the damper (open/closed).

    The air ow direction has no effect on the functioning of the re damper.

    The damper opens within 20 seconds after the smoke detector has been acti-vated.

    The standard delivery of the re damper includes a built-in spring-returnactuator 24 V or 230 V and switches for indicating the end positions of thedamper. The damper spring is normally tensioned but in case of a power cut itopens the damper automatically.

    Product dataSizes 100 - 500 mm(ETES and connection piece FDR areused for bigger sizes)

    The re damper fulls the require-ments of tightness class 3 according toEN 1751.

    The damper casing fulls the require-ments of tightness class C according toEN 1751.

    Pressure drop across a closed dampermay amount to 2500 Pa.

    Product code example:

    Smoke extraction damperETER-315-03-1

  • 8/2/2019 Damper - Fuego

    2/4

    48Flkt Woods EN 2009.09 All rights reserved.

    Smoke extraction damper ETER TECHNICAL DATA

    Dimensions and weights

    Size D B C E F G Li Weight

    100 100 205 129 160 80 110 35 2,5

    125 125 205 134 185 80 110 35 2,8

    160 160 205 159 220 80 110 35 3,1

    200 200 205 203 260 80 110 35 3,5

    250 250 205 237 310 80 110 40 4,0

    315 315 205 281 380 80 110 40 5,0

    400 400 280 390 470 80 110 60 7,4

    500 500 280 480 570 80 110 60 9,4

    B E

    C

    D

    Li

    G

    Dimensions and weights, pressure drop

    Pressure drop

    Pressure drop, when the damper is fully open

    100

    125

    160

    200

    250

    315

    400

    500

    p

    t,

    Pa

    100

    50

    20

    10

    10 20 50 100

    qv, l/s

    200 500 1000 2000 5000 10000

    1

    2

    5

    35

    40

    Lp10A

    , dB(A)

    Sound power level correction by octave bandsOCTAVE BAND (Hz) 125 250 500 1000 2000 4000 8000

    CORRECTION Koct 16 10 5 0 -7 -13 -18

    TOLERANCE +/- 6 3 3 3 3 3 3 LWoct = Lp10A + Koct

  • 8/2/2019 Damper - Fuego

    3/4

    49Flkt Woods EN 2009.09 All rights reserved.

    Smoke extraction damper ETER TECHNICAL DATA

    InstallationThe duct outlet must be placed so that the extractiondamper is protected from water coming from outside aswell as ice and snow that could hinder the opening of thedamper. There may be no openings or air terminal devi-ces in the duct between the smoke extraction damper andduct outlet.

    The ductwork section between the smoke extractiondamper and duct outlet must be designed and insulatedso that the re resistance and tightness requirements aremet. Also take account of possible condensation.

    DescriptionFlkt Woods smoke extraction damper ETER.

    Product code

    Smoke extraction damper ETER - aaa - bb - c

    SizeConnection diameter 100500 mm

    Actuator

    03 = 24 V AC/DC motor with heat detector

    04 = 24V AC/DC motor

    05 = 230V AC motor with heat detector06 = 230 V AC motor

    Material1 = Hot-galvanized steel

    Accessories

    Extension piece FLD - aaa - 1

    Size (diameter mm)100, 125, 160, 200, 250, 315, 400, 500

    Grille FND - aaa - 1 -1

    Size (diameter mm)

    100, 125, 160, 200, 250, 315, 400, 500

    Control systems FICO-128/FICO-2

    See separate brochure.

    Product code and installation

  • 8/2/2019 Damper - Fuego

    4/4

    50Flkt Woods EN 2009.09 All rights reserved.

    Smoke extraction damper ETER TECHNICAL DATA

    Extension piece FLD

    A

    B C

    D

    Grille FND

    Accessories

    D A B C

    100 80 35 10

    125 80 35 10

    160 80 35 10

    200 80 35 10

    250 100 45 10

    315 100 45 10

    400 162 75 12

    500 162 75 12