APENDICE DE TABLAS DEL CAPITULO 2

Tabla 2.11 Capacidad de conduccin de corriente en amperes de conductores aislados de 0 a 2000 V, 60C a 90C. No ms de 3 conductres en un cable o en una canalizacin y para temperatura ambiente de 30C. 250

Area de la seccin transversal

60C TIPOS TW TWD CCE TWD-UV UF

mm2 (AWG-KCM)

0.8235 (18) 1.307 (16) 2.082 (14) 3.307 (12) 5.260 (10) 8.367 (8) 13.30 (6) 21.15 (4) 33.62 (2) 42.41 (1) 53.48 (1/0) 67.43 (2/0) 85.01 (3/0) 107.2 (4/0) 126.7 (250) 152.0 (300) 177.3 (350) 202.7 (400) 253.4 (500) 304.0 (600) 380.0 (750) 506.7 (1000)

------20 25 30 40 55 70 95 110 125 145 165 195 215 240 260 280 320 355 400 455

Temperaturas mximas de operacin 90C 75C 90C TIPOS TIPOS TIPOS BTC RHW SIS, THW, THHW RHH, RHW-2 RHW RHH, RHW-2 THW-LS, THHWTHW-2, THHW XHHW XHHW LS THHW-LS, BM-AL XHHW-2 THWN, XHHW THWN-2, THHN UF DRS TT XHHW USE UF XHHW-2 USE COBRE ALUMINIO ---14 ---------18 ------20 25 ------25 30 ------35 40 ------50 55 ------65 75 50 60 85 95 65 75 115 130 90 100 130 150 100 115 150 170 120 135 175 195 135 150 200 225 155 175 230 260 180 205 255 290 205 230 285 320 230 255 310 350 250 280 335 380 270 305 380 430 310 350 420 475 340 385 475 535 385 435 545 615 445 500 75C TIPOS

FACTORES DE CORRECCIONTemperatura ambiente C 21 - 25 26 - 30 31 - 35 36 - 40 41 - 45 46 - 50 51 - 55 Para temperatura ambiente diferente de 30C, multiplique las capacidades de corriente de la tabla mostradas arriba por el factor de correccin correspondiente en esta tabla. 1.08 1.05 1.04 1.05 1.04 1.00 1.00 1.00 1.00 1.00 0.91 0.94 0.96 0.94 0.96 0.82 0.88 0.91 0.88 0.91 0.71 0.82 0.87 0.82 0.87 0.58 0.75 0.82 0.75 0.82 0.41 0.67 0.76 0.67 0.76

251

Tabla 2.12 Capacidad de conduccin de corriente en amperes de cables monoconductores aislados de 0 a 2000 V, al aire libre y para una temperatura ambiente de 30C.

Area de la seccin transversal

60C TIPOS TW TWD CCE TWD-UV

75C TIPOS

Temperaturas mximas de operacin 90C 75C TIPOS TIPOS SIS, FEP RHH, RHW-2 THW-2, THHW THHW-LS, THWN-2, THHN XHHW XHHW-2 18 24 35 40 55 80 105 140 190 220 260 300 350 405 455 505 570 615 700 780 885 1055 RHW XHHW BM-AL

90C TIPOS RHH, RHW-2 XHHW XHHW-2 DRS ALUMINIO

mm (AWG-KCM)2

RHW THW, THHW THW-LS, THHWLS THWN, XHHW TT COBRE ------30 35 50 70 95 125 170 195 230 265 310 360 405 445 505 545 620 690 785 935

0.8235 (18) 1.307 (16) 2.082 (14) 3.307 (12) 5.260 (10) 8.367 (8) 13.30 (6) 21.15 (4) 33.62 (2) 42.41 (1) 53.48 (1/0) 67.43 (2/0) 85.01 (3/0) 107.2 (4/0) 126.7 (250) 152.0 (300) 177.3 (350) 202.7 (400) 253.4 (500) 304.0 (600) 380.0 (750) 506.7 (1000)

------25 30 40 60 80 105 140 165 195 225 260 300 340 375 420 455 515 575 655 780

------------------75 100 135 155 180 210 240 280 315 350 395 425 485 540 620 750

------------------80 110 150 175 205 235 275 315 355 395 445 480 545 615 700 845

FACTORES DE CORRECCIONTemperatura ambiente C 21 - 25 26 - 30 31 - 35 36 - 40 41 - 45 46 - 50 51 - 55 Para temperatura ambiente diferente de 30C, multiplique las capacidades de corriente de la tabla mostradas arriba por el factor de correccin correspondiente en esta tabla. 1.08 1.05 1.04 1.05 1.04 1.00 1.00 1.00 1.00 1.00 0.91 0.94 0.96 0.94 0.96 0.82 0.88 0.91 0.88 0.91 0.71 0.82 0.87 0.82 0.87 0.58 0.75 0.82 0.75 0.82 0.41 0.67 0.76 0.67 0.76

252

Tabla 2.13 CAPACIDAD DE CORRIENTE DE CONDUCTORES DE COBRE AISLADOS EN AMPERES SEGN NEC-96*Capacidad de corriente de conductores aislados de 0 a 2000 Volts, 60 a 90, no ms de 3 conductores en canalizacin o cable, temperatura ambiente 30C.Calibre 60C 75C Tipo 90C TA, TBS, SA, SIS FEPW FEP, FEPB, MI RH, RHW, RHH, RHW-2, TW THHW, THWN-2, THHN, UF THW, THWN THHW, THW-2, XHHW, USE2, XHH, USE, ZW XHHW, XHHW-2, ZW-2 --14 --18 20 20 25 25 25 30 30 35 40 40 50 55 55 65 75 70 85 95 85 100 110 95 115 130 110 130 150 125 150 170 145 175 195 165 200 225 195 230 260 215 255 290 240 285 320 260 310 350 280 335 380 320 380 430 355 420 475 385 460 520 400 475 535 410 490 555 435 520 585 455 545 615 495 590 665 520 625 705 545 650 735 560 665 750 Factores de correccin por temperatura 1.08 1.05 1.04 1.00 1.00 1.00 .91 .94 .96 .82 .88 .91 .71 .82 .87 .58 .75 .82 .41 .67 .76 -.58 .71 -.33 .58 --.41

Capacidad de corriente de cables monoconductores aislados de 0 a 2000 Volts, al aire libre, a una temperatura ambiente de 30C.Calibre 60C 75C Tipo FEPW, RH, RHW, THHW, THW, THWN, XHHW, ZW TA, TBS, SA, SIS, FEP, FEPB, MI, RHH, RHW2, THHN, THHW, THW-2, THWN-2, USE-2, XHHW, XHH, XHHW-2 ZW-2 90C

AWG / KCM

AWG / KCM

TW UF

18 16 14 12 10 8 6 4 3 2 1 1/0 2/0 3/0 4/0 250 300 350 400 500 600 700 750 800 900 1000 1250 1500 1750 2000 Temperatura ambiente C 21 - 25 26 - 30 31 - 35 36 - 40 41 - 45 46 - 50 51 - 55 56 - 60 61 - 70 71 - 80

18 16 14 12 10 8 6 4 3 2 1 1/0 2/0 3/0 4/0 250 300 350 400 500 600 700 750 800 900 1000 1250 1500 1750 2000 Temperatura ambiente C 21 - 25 26 - 30 31 - 35 36 - 40 41 - 45 46 - 50 51 - 55 56 - 60 61 - 70 71 - 80

--25 30 40 60 80 105 120 140 165 195 225 260 300 340 375 420 455 515 575 630 655 680 730 780 890 980 1070 1155 1.08 1.00 .91 .82 .71 .58 .41 ----

-18 -24 30 35 35 40 50 55 70 80 95 105 125 140 145 165 170 190 195 220 230 260 265 300 310 350 360 405 405 455 445 505 505 570 545 615 620 700 690 780 755 855 785 885 815 920 870 985 935 1055 1065 1200 1175 1325 1280 1445 1385 1560 Factores de correccin por temperatura 1.05 1.04 1.00 1.00 .94 .96 .88 .91 .82 .87 .75 .82 .67 .76 .58 .71 .33 .58 -.41

National Electrical Code 1996 (E.U.A.)

253

Tabla 2.13 continuacin CAPACIDAD DE CORRIENTE DE CONDUCTORES DE COBRE AISLADOS EN AMPERES SEGN NEC-96*Capacidad de corriente de 3 conductores aislados de 0 a 2000 Volts, 150 a 250C, en ducto o cable, temperatura ambiente 40C Calibre 150C 200C Tipo AWG / Z FEP, KCM FEPB, PFA 14 34 36 12 43 45 10 55 60 8 76 83 6 96 110 4 120 125 3 143 152 2 160 171 1 186 197 1/0 215 229 2/0 251 260 3/0 288 297 4/0 332 346 250 --300 --350 --400 --500 --600 --700 --750 --800 --1000 --1500 --2000 --Temperatura ambiente C 41 - 50 51 - 60 61 - 70 71 - 80 81 - 90 91 - 100 101 - 120 121 - 140 141 - 160 161 - 180 181 - 200 201 - 225 Factores de correccin por temperatura .95 .90 .85 .80 .74 .67 .52 .30 ----.97 .94 .90 .87 .83 .79 .71 .61 .50 .35 --Capacidad de corriente de cables monoconductores aislados de 0 a 2000 Volts, 150 a 200C, al aire libre, a una temperatura ambiente de 40C Calibre AWG / KCM 14 12 10 8 6 4 3 2 1 1/0 2/0 3/0 4/0 250 300 350 400 500 600 700 750 800 900 1000 1500 2000 Temperatura ambiente C 41 - 50 51 - 60 61 - 70 71 - 80 81 - 90 91 - 100 101 - 120 121 - 140 141 - 160 161 - 180 181 - 200 201 - 225 150C Tipo Z 200C Conductores desnudos o forrados

FEP, FEPB, PFA 46 54 30 60 68 35 80 90 50 106 124 70 155 165 95 190 220 125 214 252 150 255 293 175 293 344 200 339 399 235 390 467 275 451 546 320 529 629 370 --415 --460 --520 --560 --635 --710 --780 --805 --835 --865 --895 --1205 --1420 Factores de correccin por temperatura .95 .90 .85 .80 .74 .67 .52 .30 ----.97 .94 .90 .87 .83 .79 .71 .61 .50 .35 ---------------

* National Electrical Code 1996 (E.U.A.)

254

Tabla 2.14 a) Factores de correccin por temperatura ambiente (para tablas de ampacidades a 30C de temperatura ambiente)Temperatura ambiente C 31 - 35 36 - 40 41 - 45 46 - 50 51 - 55 56 - 60 61 - 70 71 - 80 81 - 90 91 - 100 101 - 120 Temperatura mxima permisible en el aislamiento, C 60 0.91 0.82 0.71 0.58 0.41 ------------------75 0.94 0.88 0.82 0.75 0.67 0.58 0.33 ------------90 0.96 0.91 0.87 0.82 0.76 0.71 0.58 0.41 ---------150 ------0.95 0.90 0.85 0.80 0.74 0.67 0.52 0.30 ---200 ------0.97 0.94 0.90 0.87 0.83 0.79 0.71 0.61 0.50

Tabla 2.14 b) Factores de correccin por agrupamiento de cables en tuberia conduit (segn NOM-001-SEMP)Nmero de conductores 4-6 7-9 10 - 20 21 - 30 31 - 40 41 y ms Factor 0.80 0.70 0.50 0.45 0.40 0.35

Tabla 2.14 c) Factores de correccin por la variacin en la temperatura ambiente. Cables directamente enterrados o en ductos subterrneos.Mxima temperatura del conductor (C) 60 75 80 90 Temperatura del terreno (C) 15 1.13 1.10 1.09 1.07 20 1.07 1.05 1.04 1.03 25 1.00 1.00 1.00 1.00 30 0.93 0.95 0.96 0.97 35 0.85 0.88 0.90 0.92

Nota: Estos factores se aplican en el caso de ser todos conductores para alumbrado o fuerza. Los conductores neutro que transportan tan slo la corriente de desequilibrio de otros conductores o tierras no se toman en cuenta para los factores de correccin por agrupamiento (segn NOM-001-SEMP-1994).

255

ALTA TENSION Tabla 2.15 Capacidad de conduccin de corriente en amperes de cables Vulcanel EP o XLP, de un solo conjunto de cables aislados monoconductores de cobre, en configuracin triplex, en aire, para temperaturas en el conductor de 90C, para temperatura ambiente de 40C. Pantallas aterrizadas en un solo punto.Area de la seccin transversal mm2 (AWG - KCM) 8.367 (8) 13.30 (6) 21.15 (4) 33.62 (2) 42.41 (1) 53.48 (1/0) 67.43 (2/0) 85.01 (3/0) 107.2 (4/0) 126.7 (250) 177.3 (350) 253.4 (500) 380.0 (750) 506.7 (1000) 2001 - 5000 V Amperes 90C MV - 90 65 90 120 160 185 215 250 290 335 375 465 580 750 880 5001 - 35000 V Amperes 90C MV - 90 ---100 130 170 195 225 260 300 345 380 470 580 730 850

Tabla 2.16 Capacidad de conduccin de corriente de cables Vulcanel DS y DRS, EP XLP, de un solo conjunto de cables aislados monoconductores de aluminio, en configuracin triplex, en aire, para temperaturas en el conductor de 90C, para temperatura ambiente de 40C. Pantallas aterrizadas en un solo punto.Area de la seccin transversal mm2 (AWG - KCM) 13.30 (6) 21.15 (4) 33.62 (2) 42.41 (1) 53.48 (1/0) 67.43 (2/0) 85.01 (3/0) 107.2 (4/0) 126.7 (250) 177.3 (350) 253.4 (500) 380.0 (750) 506.7 (1000) 2001 - 5000 V Amperes 90C MV - 90 70 90 125 145 170 195 225 265 295 365 460 600 715 5001 - 35000 V Amperes 90C MV - 90 75 100 130 150 175 200 230 270 300 370 460 590 700

256

Tabla 2.17 Capacidad de conduccin de corriente en amperes de cables Vulcanel EP XLP de cobre, en aire, para temperaturas en el conductor de 90C, para temperatura ambiente de 40C. Pantallas aterrizadas en un solo punto.Area de la seccin transversal mm2 (AWG - KCM) 8.367 (8) 13.30 (6) 21.15 (4) 33.62 (2) 42.41 (1) 53.48 (1/0) 67.43 (2/0) 85.01 (3/0) 107.2 (4/0) 126.7 (250) 177.3 (350) 253.4 (500) 380.0 (750) 506.7 (1000) 2001 - 5000 V Amperes 90C MV - 90 83 110 145 190 225 260 300 345 400 445 550 695 900 1075 5001 - 15000 V Amperes 90C MV - 90 ---110 150 195 225 260 300 345 400 445 550 685 885 1060 15001 - 35000 V Amperes 90C MV - 90 ------------225 260 300 345 395 440 545 680 870 1040

Tabla 2.18 Capacidad de conduccin de corriente en amperes de cables Vulcanel DS y DRS, EP XLP de aluminio, en aire, para temperaturas en el conductor de 90C, para temperatura ambiente de 40C. Pantallas aterrizadas en un solo punto.Area de la seccin transversal mm2 (AWG - KCM) 13.30 (6) 21.15 (4) 33.62 (2) 42.41 (1) 53.48 (1/0) 67.43 (2/0) 85.01 (3/0) 107.2 (4/0) 126.7 (250) 177.3 (350) 253.4 (500) 380.0 (750) 506.7 (1000) 2001 - 5000 V Amperes 90C MV - 90 85 115 150 175 200 230 270 310 345 430 545 710 855 5001 - 15000 V Amperes 90C MV - 90 87 115 150 175 200 235 270 310 345 430 535 700 840 15001 - 35000 V Amperes 90C MV - 90 ---------175 200 230 270 310 345 430 530 685 825

257

Tabla 2.19 Capacidad de conduccin de corriente en amperes de cables Vulcanel EP XLP, de un solo cable aislado de tres conductores de cobre en aire, para temperaturas en el conductor de 90C, para temperatura ambiente de 40C. Pantallas aterrizadas en un solo punto.Area de la seccin transversal mm2 (AWG - KCM) 8.367 (8) 13.30 (6) 21.15 (4) 33.62 (2) 42.41 (1) 53.48 (1/0) 67.43 (2/0) 85.01 (3/0) 107.2 (4/0) 126.7 (250) 177.3 (350) 253.4 (500) 380.0 (750) 506.7 (1000) 2001 - 5000 V Amperes 90C MV - 90 59 79 105 140 160 185 215 250 285 320 395 485 615 705 5001 - 15000 V Amperes 90C MV - 90 ---93 120 165 185 215 245 285 325 360 435 535 670 770

Tabla 2.20 Capacidad de conduccin de corriente en amperes de cables Vulcanel EP XLP, de un solo cable aislado de tres conductores de aluminio en aire, para temperaturas en el conductor de 90C, para temperatura ambiente de 40C. Pantallas aterrizadas en un solo punto.Area de la seccin transversal mm2 (AWG - KCM) 13.30 (6) 21.15 (4) 33.62 (2) 42.41 (1) 53.48 (1/0) 67.43 (2/0) 85.01 (3/0) 107.2 (4/0) 126.7 (250) 177.3 (350) 253.4 (500) 380.0 (750) 506.7 (1000) 2001 - 5000 V Amperes 90C MV - 90 61 81 110 125 145 170 195 225 250 310 385 495 585 5001 - 15000 V Amperes 90C MV - 90 72 95 125 145 170 190 220 255 280 345 425 540 635

258

Tabla 2.21 Capacidad de conduccin de corriente en amperes de cables Vulcanel EP XLP, de un cable aislado de tres conductores de cobre dentro de un solo tubo conduit en aire, para temperaturas en el conductor de 90C, para temperatura ambiente de 40C. Pantallas aterrizadas en un solo punto.Area de la seccin transversal mm2 (AWG - KCM) 8.367 (8) 13.30 (6) 21.15 (4) 33.62 (2) 42.41 (1) 53.48 (1/0) 67.43 (2/0) 85.01 (3/0) 107.2 (4/0) 126.7 (250) 177.3 (350) 253.4 (500) 380.0 (750) 506.7 (1000) 2001 - 5000 V Amperes 90C MV - 90 52 69 91 125 140 165 190 220 255 280 350 425 525 590 5001 - 15000 V Amperes 90C MV - 90 ---83 105 145 165 195 220 250 290 315 385 470 570 650

Tabla 2.22 Capacidad de conduccin de corriente en amperes de cables Vulcanel EP XLP, de un cable aislado de tres conductores de aluminio dentro de un solo tubo conduit en aire, para temperaturas en el conductor de 90C, para temperatura ambiente de 40C. Pantallas aterrizadas en un solo punto.Area de la seccin transversal mm2 (AWG - KCM) 13.30 (6) 21.15 (4) 33.62 (2) 42.41 (1) 53.48 (1/0) 67.43 (2/0) 85.01 (3/0) 107.2 (4/0) 126.7 (250) 177.3 (350) 253.4 (500) 380.0 (750) 506.7 (1000) 2001 - 5000 V Amperes 90C MV - 90 58 71 96 110 130 150 170 200 220 275 340 430 505 5001 - 15000 V Amperes 90C MV - 90 64 84 115 130 150 170 195 225 250 305 380 470 550

259

Tabla 2.23 Capacidad de conduccin de corriente en amperes de cables Vulcanel EP XLP, de tres cables aislados monoconductores de aluminio en ductos subterrneos (tres cables monoconductores por ducto). Arreglo de ductos: 3 horizontales y 2 verticales, 100% factor de carga. Temperatura del terreno 20C. Resistividad trmica del terreno (Rho) de 90. Temperatura del conductor de 90C. Pantallas aterrizadas en un solo punto.Area de la seccin transversal mm2 (AWG - KCM) 8.367 (8) 13.30 (6) 21.15 (4) 33.62 (2) 42.41 (1) 53.48 (1/0) 67.43 (2/0) 85.01 (3/0) 107.2 (4/0) 126.7 (250) 177.3 (350) 253.4 (500) 380.0 (750) 506.7 (1000) 2001 - 5000 V Amperes 90C MV - 90 48 62 80 105 115 135 150 170 195 210 250 300 365 410 5001 - 15000 V Amperes 90C MV - 90 ---64 82 105 120 135 150 170 190 210 245 290 350 390

Tabla 2.24 Capacidad de conduccin de corriente en amperes de cables Vulcanel DS y DRS, EP XLP, de tres cables aislados monoconductores de aluminio en ductos subterrneos (tres cables monoconductores por ducto). Arreglo de ductos: 3 horizontales y 2 verticales, 100% factor de carga. Temperatura del terreno 20C. Resistividad trmica del terreno (Rho) de 90. Temperatura del conductor de 90C. Pantallas aterrizadas en un solo punto.Area de la seccin transversal mm2 (AWG - KCM) 13.30 (6) 21.15 (4) 33.62 (2) 42.41 (1) 53.48 (1/0) 67.43 (2/0) 85.01 (3/0) 107.2 (4/0) 126.7 (250) 177.3 (350) 253.4 (500) 380.0 (750) 506.7 (1000) 2001 - 5000 V Amperes 90C MV - 90 48 62 80 91 105 115 135 150 165 195 240 290 335 5001 - 15000 V Amperes 90C MV - 90 50 64 80 90 105 115 130 150 165 195 230 280 320

260

Tabla 2.25 Factores de correccin de corriente por nmero de conductores en un cable o grupo de cables en charola. Notas a las tablas anteriores de capacidad de corriente de cables instalados en charolas. Capacidad de corriente de cables de 0 a 2000 V instalados en charolas (Baja Tensin).Nmero de conductores que llevan corriente 1-3 4-6 7 - 24 25 - 42 43 y ms Factores de correccin por agrupamiento 1.00 0.80 0.70 0.60 0.50

a) Para espaciamiento mayor de de 100%. En charolas de tipo escalera, de malla metlica y otras charolas ventiladas, cuando la separacin entre cables monoconductores o multiconductores o en grupos de cables monoconductores en la charola, se mantiene a ms de 100% del dimetro del cable o grupo de cables de mayor dimetro, la capacidad de corriente de los cables debe ser el valor especificado en los parrafos 1) o 2) siguientes: 1) Cables monoconductores. La capacidad de corriente debe ser la especificada en la tabla 2.12. Para grupos de cables monoconductores, como los triplex o cuadruplex, o los grupos de cables monoconductores amarrados entre s, debe aplicarse la capacidad de corriente de la tabla 2.11 aplicando los factores de correccin de la tabla 2.25 para el nmero de conductores de cada grupo. 1) Cables multiconductores. La capacidad de corriente debe ser la especificada en la Tabla 2.11 multiplicada por el factor de la correccin de la Tabla 2.25, segn el nmero de conductores en cada cable. b) Para espaciamiento entre 25% y 100%. En charolas de tipo escalera, de malla metlica y otras charolas ventiladas, cuando la separacin entre cables monoconductores o multiconductores, o grupos de cables monoconductores en la charola se mantiene a no menos de 25% y no ms de 100% del dimetro del cable o grupo de mayor dimetro, la capacidad de corriente de los cables debe ser el valor especificado en el inciso a) o b) segn corresponda, multiplicado por el factor de correccin de la Tabla 2.25. a) Para espaciamiento menor del 25%. En charolas de tipo escalera, de malla metlica y otras charolas ventiladas cuando la separacin entre cables monoconductores o multiconductores en la charola es menor de 25%, la capacidad de corriente de los cables monoconductores, multiconductores o grupos de cables monoconductores, debe ser el valor especificado en la Tabla 2.11 multiplicado por el factor de correccin de la Tabla 2.25 para el nmero total de conductores en la charola. a) Charolas y canales de fondo slido. En charolas y canales de fondo slido, para cualquier separacin entre los cables monoconductores o multiconductores o grupos de cables monoconductores en la charola o canal, la capacidad de corriente debe ser el valor especificado en la tabla 2.11 multiplicado por el valor especificado en la Tabla 2.25 para el nmero total de conductores en la charola o canal. 261

a) Charolas con tapa. Cuando las charolas tengan cubiertas continuas del tipo cerrado sin ventilacin, en una distancia mayor de 1.80 m, las capacidades de corriente de los cables monoconductores, multiconductores o grupos de cables monoconductores, indicadas en los parrafos a), b), c) y d) anteriores, deben multiplicarse por un factor de reduccin de 0.95. a) Correccin por temperatura. Cuando las charolas estn instaladas en un local con temperatura ambiente de ms de 30C de deben aplicar a las capacidades de corriente de los incisos a), b), c) y d) anteriores, y los factores de correccin por temperatura ambiente de las Tablas 2.11 y 2.12. Tabla 2.26 Factores de correccin de corriente por el nmero de conductores con espaciamiento reducido en una charola.Nmero de cables horizontalmente Verticalmente 1 2* 1 1.00 0.89 2 0.93 0.83 3 0.87 0.79 4 0.84 0.76 5 0.83 0.75 6 0.82 0.74

*Nota: Cuando los cables o grupos de cables se pueden instalar en ms de una capa en la charola ***Figura*** Capacidad de corriente de cables de ms de 2000 V (alta tensin). a) Cables multiconductores MV y MC de ms de 2000 volts. La capacidad de corriente de los cables multiconductores MV y MC debe ser la siguiente: 1) Cables sin espaciamiento. En charolas de tipo escalera, de malla metlica y otras charolas ventiladas, cuando no hay espaciamiento emtre los cables monoconductores en la charola o este es menor del 25% del dimetro () del cable de mayor dimetro, la capacidad de corriente de los cables debe ser el valor especificado en las Tablas 2.21 y 2.22. 1) Para espaciamiento mayor del 100%. En charolas de tipo escalera, de malla metlica y otras charolas ventiladas, cuando la separacin entre cables multiconductores en la charola se mantiene a ms de 100% del dimetro del cable de mayor dimetro, la capacidad de corriente de los cables debe ser el valor especificado en las tablas 2.19 y 2.20. Excepcin. Cuando las charolas tengan cubiertas continuas del tipo cerrado sin ventilacin, en una distancia mayor de 1.80 m, las capacidades de corriente de los cables multiconductores, indicados en los incisos 1) y 2) anteriores, deben multiplicarse por un factor de reduccin de 0.95. b) Cables monoconductores de ms de 2000 volts.

262

La capacidad de corriente de cables monoconductores, o de cables monoconductores cableados entre s, (triplex cuaduplex), de ms de 2000 volts, debe cumplir con lo siguiente: 1) Cables sin espaciamiento. Cuando los cables monoconductores o grupos de cables monoconductores cableados entre s (triplex cuaduplex), son instalados sin espaciamiento entre ellos, en charolas ventiladas, su capacidad de corriente no debe sobrepasar del 75% de las indicadas en las Tablas 2.17 y 2.18. 2) Para espaciamiento mayor del 100%. Cuando los cables monoconductores estn instalados en una sola capa en charolas sin tapa, con una separacin mantenida entre cables individuales de por lo menos un dimetro del cable de mayor dimetro, la capacidad de corriente de los cables no debe exceder de la capacidad de corriente permisible en las Tablas 2.17 y 2.18. Cuando se instalan cables monoconductores en configuracin triplex o cuaduplex * en charolas sin tapa, con una distancia mantenida entre circuitos, no menor de 2.15 veces del dimetro exterior de uno de los conductores, la capacidad de corriente no debe exceder de las capacidades de corriente permisibles en las Tablas 2.15 y 2.16. *Nota: La capacidad de corriente de los cables cuadruplex se obtiene de las mismas tablas de los cables triplex, si el neutro solo lleva la corriente de desbalance de las fases. Excepcin. Cuando las charolas tengan cubiertas continuas del tipo cerrado sin ventilacin, en una distancia mayor de 1.80 metros, las capacidades de corriente de los cables monoconductores y triplex o cuadruplex indicadas en los incisos 1) y 2) anteriores, deben multiplicarse por un factor de reduccin de 0.95 NOTA ADICIONAL: Cuando los cables instalados en charolas estn expuestos a los rayos solares, las capacidades de corriente afectados por sus correspondientes factores de agrupamiento y temperatura, deben multiplicarse por 0.85.

263

Tabla 2.27 Factores de correccin por agrupamiento en charolas (al aire libre y sin incidencia de rayos solares*) a) Cables monofsicos con espaciamiento (circulacin de aire restringida)Nmero de charolas 1 2 3 6 1 0.95 0.90 0.88 0.86 Nmero de circuitos 2 0.90 0.85 0.83 0.81 3 0.88 0.83 0.81 0.79

***Figura*** b) Cables monofsicos con espaciamientoNmero de charolas 1 2 3 6 1 1.00 0.97 0.96 0.94 Nmero de circuitos 2 0.97 0.94 0.93 0.91 3 0.96 0.93 0.92 0.90

***Figura*** c) Cables triplex o monopolares en configuracin trebol (circulacin de aire restringida)Nmero de charolas 1 2 3 6 1 0.95 0.90 0.88 0.86 Nmero de circuitos 2 0.90 0.85 0.83 0.81 3 0.88 0.83 0.81 0.79

***Figura*** d) Cables triplex o monopolares en configuracin trbolNmero de charolas 1 2 3 6 1 1.00 1.00 1.00 1.00 Nmero de circuitos 2 0.98 0.95 0.94 0.93 3 0.96 0.93 0.92 0.90

***Figura***

e) Cables trifasicos con espaciamiento (circulacin de aire restringida) 264

Nmero de charolas 1 2 3 6 1 0.95 0.90 0.88 0.86 2 0.90 0.85 0.83 0.81

Nmero de cables trifsicos 3 0.88 0.83 0.81 0.79

6 0.85 0.81 0.79 0.77

9 0.84 0.80 0.78 0.76

f) cables trifsicos con espaciamientoNmero de charolas 1 2 3 6 1 1.00 1.00 1.00 1.00 2 0.98 0.95 0.94 0.93 Nmero de cables trifsicos 3 0.96 0.93 0.92 0.90 6 0.93 0.90 0.89 0.87 9 0.92 0.89 0.83 0.86

g) Cables trifsicos juntos (circulacin de aire restringida)Nmero de charolas 1 2 3 6 1 0.95 0.95 0.95 0.95 2 0.84 0.80 0.78 0.76 Nmero de cables trifsicos 3 0.80 0.76 0.74 0.72 6 0.75 0.71 0.70 0.68 9 0.73 0.69 0.68 0.66

h) Cables trifsicos juntosNmero de charolas 1 2 3 6 1 0.95 0.95 0.95 0.95 2 0.84 0.80 0.78 0.76 Nmero de cables trifsicos 3 0.80 0.76 0.74 0.72 6 0.75 0.71 0.70 0.68 9 0.73 0.69 0.68 0.66

i) Cuando d < e y h < dNmero de charolas 1 2 3 6 1 1.00 0.89 0.80 0.74 2 0.93 0.83 0.76 0.69 Nmero de cables trifsicos 3 0.87 0.79 0.72 0.64 6 0.84 0.76 0.70 0.63 9 0.83 0.75 0.69 0.62

*En el caso de que los cables estn instalados al aire libre y expuestos a los rayos solares, los factores anteriores debern multiplicarse por 0.85

265

Tabla 2.28 Factores de correccin por agrupamiento de ductos en instalacin subterrnea de cables (F.C.A.) a) Un cable triplex o tres cables monofsicos en el mismo ducto, o un cable tripolar por ducto.Nmero de filas de tubo verticalmente 1 2 3 4 5 6 1 1.00 0.87 0.77 0.72 0.68 0.65 2 0.87 0.71 0.62 0.57 0.53 0.50 Nmero de tubos horizontalmente 3 4 0.77 0.72 0.62 0.57 0.53 0.48 0.48 0.44 0.45 0.40 0.42 0.38 5 0.68 0.53 0.45 0.40 0.37 0.35 6 0.65 0.50 0.42 0.38 0.35 0.32

Nota: Si la separacin es mayor o igual que el dimetro del tubo mayor, el factor es 1. b) Un cable monofsico por ducto (no magntico)Nmero de filas verticalmente 1 2 3 4 5 6 1 1.00 0.88 0.79 0.74 0.71 0.68 2 0.88 0.73 0.65 0.60 0.57 0.55 Nmero de ternas horizontalmente 3 4 0.79 0.74 0.65 0.61 0.56 0.52 0.52 0.49 0.50 0.47 0.48 0.45 5 0.71 0.57 0.49 0.46 0.44 0.42 6 0.69 0.56 0.47 0.45 0.42 0.40

Los factores de correccin de un cable monofsico por ducto se aplican tambin a cables directamente enterrados. Tabla 2.29 Factores por agrupamiento de tubos conduit aereosNmero de filas de tubo verticalmente 1 2 3 4 5 6 1 1.00 0.92 0.85 0.82 0.80 0.79 Nmero de filas de tubos horizontalmente 2 3 4 5 0.94 0.91 0.88 0.87 0.87 0.84 0.81 0.80 0.81 0.78 0.76 0.75 0.78 0.74 0.73 0.72 0.76 0.72 0.71 0.70 0.75 0.71 0.70 0.69 6 0.86 0.79 0.74 0.72 0.70 0.68

Nota: Separacin entre tubos de a 1 vez el dimetro de uno de ellos.

266

Tabla 2.30 Factores de correccin por incremento en la profundidad de instalacin (F.C.P.)Profundidad de instalacin en metros 0.90 1.00 1.20 1.50 1.80 2.50 Cables directamente enterrados 5 kV a 23 kV 35 kV 1.00 ---0.99 ---0.98 1.00 0.97 0.99 0.96 0.98 0.95 0.96 Conductor en ductos subterrneos 5 kV a 23 kV 35 kV 1.00 ---0.99 ---0.98 1.00 0.97 0.99 0.95 0.97 0.91 0.92

Tabla 2.31 factores de correccin por variacin de la resistividad termica del terreno, en C-cm / WConstruccin del cable Area del conductor mm2 AWG KCM 16 6 70 2/0 150 300 240 500 300 600 500 1000 16 6 70 2/0 150 300 240 500 300 600 500 1000 Cables enterrados directamente Rsistividad trmica del terreno 60 1.27 1.31 1.32 1.33 1.34 1.35 1.17 1.22 1.24 1.26 1.27 1.29 90 1.11 1.13 1.13 1.13 1.14 1.14 1.07 1.09 1.10 1.11 1.11 1.12 120 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 150 0.91 0.91 0.91 0.91 0.91 0.90 0.94 0.93 0.92 0.92 0.92 0.91 180 0.85 0.84 0.84 0.84 0.83 0.83 0.88 0.87 0.87 0.86 0.85 0.85 240 0.75 0.74 0.74 0.73 0.73 0.72 0.80 0.78 0.77 0.76 0.75 0.75 60 1.14 1.17 1.19 1.20 1.21 1.23 1.08 1.11 1.12 1.13 1.15 1.16 90 1.06 1.07 1.08 1.08 1.09 1.10 1.04 1.05 1.05 1.06 1.07 1.07 Cables en ductos 120 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 150 0.95 0.94 0.94 0.93 0.93 0.92 0.97 0.96 0.95 0.95 0.95 0.94 180 0.90 0.89 0.88 0.88 0.87 0.86 0.93 0.92 0.91 0.91 0.90 0.89 240 0.83 0.81 0.80 079 0.78 0.77 0.88 0.86 0.84 0.83 0.83 0.81

Unipolares

Tripolares

267

Tabla 2.32 Nmero mximo de conductores que pueden alojarse en tubo conduitCalibre de conductor AWG KCM THW 14 THW - LS 12 THHW THHW - LS 10 XHHW 8 RHW y RHH 14 (sin 12 cubierta 10 exterior) 8 6 4 THW 2 THW - LS 1/0 THHW 2/0 THHW - LS 3/0 RHW 4/0 y 250 RHH 300 (sin 350 cubierta 400 exterior) 500 750 Tipo de conductor Tipo de conductor Dimetro nominal de tubo conduit o tuberias (mm) 32 38 51 63 76 89 44 60 99 142 ------35 47 78 111 171 ---26 36 60 85 131 176 12 17 28 40 62 84 29 40 65 93 143 192 24 32 53 76 117 157 19 26 43 61 95 127 10 13 22 32 49 66 7 10 16 23 36 48 5 7 12 17 27 36 4 5 9 13 20 27 2 3 5 8 12 16 1 3 5 7 10 14 1 2 4 6 9 12 1 1 3 5 7 10 1 1 2 4 6 8 1 1 2 3 5 7 1 1 1 3 4 6 1 1 1 2 4 5 1 1 1 1 3 4 ---1 1 1 2 3

13 9 7 5 2 6 4 4 1 1 1 1 -------------------------------

19 15 12 9 4 10 8 6 3 2 1 1 1 1 1 ----------------------

25 25 19 15 7 16 13 11 5 4 3 2 1 1 1 1 1 1 -------------

102 ---------108 ------163 85 62 47 34 21 18 15 13 10 9 8 7 6 4

127 ---------------------133 97 73 54 33 29 24 20 16 14 12 11 9 6

152 ------------------------141 106 78 49 41 35 29 23 20 18 16 14 9

Calibre de Dimetro nominal de tubo conduit o tuberias conductor (mm) AWG KCM 13 19 25 32 38 51 63 76 89 102 127 152 14 3 6 10 18 25 41 58 90 121 155 ------12 3 5 9 15 21 35 50 77 103 132 ------10 2 4 7 13 18 29 41 64 86 110 ------8 1 2 4 7 9 16 22 35 47 60 94 137 6 1 1 2 5 6 11 15 24 32 41 64 93 RHW 4 1 1 1 3 5 8 12 18 24 31 50 72 y 2 ---1 1 3 4 6 9 14 19 24 ------RHH 1/0 ---1 1 1 2 4 6 9 12 16 25 37 (con 2/0 ------1 1 2 3 5 8 11 14 22 32 cubierta 3/0 ------1 1 1 3 4 7 9 12 19 28 exterior) 4/0 ------1 1 1 2 4 6 8 10 16 24 250 ---------1 1 1 3 5 6 8 13 19 300 ---------1 1 1 3 4 5 7 11 17 400 ---------1 1 1 1 3 4 6 9 14 500 ---------1 1 1 1 3 4 5 8 11 750 ---------------1 1 1 3 3 5 8 14 13 24 39 69 94 154 ------------------12 10 18 29 51 70 114 164 ---------------10 6 11 18 32 44 73 104 160 ------------8 3 5 9 16 22 36 51 79 106 136 ------6 1 4 6 11 15 26 37 57 76 98 154 ---4 1 2 4 7 9 16 22 35 47 60 94 137 THWN 2 1 1 3 5 7 11 16 25 33 43 67 97 y 1/0 ---1 1 3 4 7 10 15 21 27 42 61 THHN 2/0 ---1 1 2 3 6 8 13 17 22 35 51 3/0 ---1 1 1 3 5 7 11 14 18 29 42 4/0 ---1 1 1 2 4 6 9 12 15 24 35 250 ------1 1 1 3 4 7 10 12 20 28 300 ------1 1 1 3 4 6 8 11 17 24 400 ---------1 1 1 3 5 6 8 13 19 500 ---------1 1 1 2 4 5 7 11 16 750 ------------1 1 1 2 3 4 7 11 Notas - Esta tabla est basada en factores de relleno de 40 por ciento para tres conductores o ms. 30 por ciento para dos conductores y 53 por ciento en el caso de un conductor. - Debe tenerse en cuenta que para ms de tres conductores en un tubo, la capacidad de corriente permisible en los mismos se ve reducida de acuerdo a los factores de correccin de la tabla *** y ***. Tomado de NOM-001-SEMP.

Tabla 2.33 Factores de cada de tensin unitaria (milivolts / ampere - metro) Sistema 268

Calibre AWG / KCM 14 12 10 8 6 4 2 1/0 2/0 3/0 4/0 250 300 350 400 500 600 750 1000 Nota (1)

Monofsico Tubo conduit (1) Metlico No metlico 21.54 21.54 13.56 13.56 8.52 8.52 5.36 5.36 3.37 3.37 2.12 2.12 1.35 1.33 0.86 0.84 0.68 0.67 0.55 0.53 0.44 0.42 0.38 0.36 0.32 0.30 0.27 0.26 0.24 0.22 0.20 0.18 0.17 0.15 0.14 0.12 0.12 0.09

Trifsico Tubo conduit (1) Metlico No metlico 18.65 18.65 11.74 11.74 7.38 7.38 4.64 4.64 2.92 2.92 1.84 1.84 1.18 1.16 0.74 0.73 0.59 0.59 0.48 0.47 0.38 0.36 0.33 0.31 0.28 0.26 0.24 0.23 0.21 0.19 0.17 0.16 0.16 0.14 0.12 0.10 0.10 0.09

Valores vlidos para todo tipo de canalizacin.

269

Tabla 2.34 Constantes para el clculo de la cada de tensin en % en baja tensin. Calibre AWG y KCM 14 12 10 8 6 4 2 1/0 2/0 3/0 4/0 250 300 400 500 Circuitos monofsicos a 127 V 0.01305 0.00820 0.00515 0.00323 0.00203 0.00128 0.00081 0.00050 0.00040 0.00032 0.00025 0.00021 0.00018 0.00013 0.00011 Circuitos monofsicos a 220 V 0.00754 0.00474 0.00298 0.00187 0.00117 0.00074 0.00047 0.00029 0.00029 0.00018 0.00015 0.00012 0.00010 0.00008 0.00006 Circuitos Circuitos trifsicos a 220 V trifsicos a 440 V 0.00650 0.00410 0.00258 0.00162 0.00103 0.00064 0.00040 0.00025 0.00020 0.00016 0.00013 0.00011 0.00009 0.00007 0.00005 0.00326 0.00205 0.00129 0.00081 0.00051 0.00032 0.00020 0.00013 0.00013 0.00008 0.00008 0.00005 0.00004 0.00003 0.00002

Notas relativas a la tabla 1. Los valores de la tabla son aplicables a todos los tipos de conductores de baja tensin (VINANEL NYLON, VINANEL - 900, TW VULCANEL EP y VULCANEL XLP) 2. Dado que los valores anotados en la tabla solamente expresan las constantes, para obtener la cada de tensin en %, es necesario multiplicar los valores de la tabla por la longitud del circuito en metros, en un solo sentido y por la corriente en amperes que circule por el mismo.

270

Tabla 2.35 Resistencia elctrica nominal de conductores flexibles de cobre suave estaado clase K Calibre AWG / KCM ------16 ------------8 ---6 ---5 4 ---3 2 1/0 2/0 ---3/0 ---4/0 ---313.1 350.0 444.4 535.3 900.0 1000 mm2 0.5 1.0 ---1.5 2.5 4.0 6.0 ---10 ---16 ------25 ------------70 ---95 ---150 ------------------Resistencia elctrica en Ohms / km Corriente directa Corriente alterna 75C 90C 75C 90C 46.570 48.667 46.570 48.667 23.280 24.333 23.280 24.333 17.554 18.346 17.554 18.346 15.847 16.56 15.847 16.560 9.533 9.963 9.533 9.963 5.912 6.179 5.912 6.179 3.937 4.115 3.937 4.115 2.664 2.793 2.664 2.793 2.353 2.459 2.353 2.459 1.703 1.786 1.703 1.786 1.438 1.503 1.438 1.503 1.350 1.416 1.350 1.416 1.073 1.125 1.073 1.125 0.923 0.964 0.924 0.965 0.850 0.892 0.850 0.892 0.675 0.708 0.675 0.708 0.428 0.449 0.428 0.449 0.339 0.356 0.339 0.357 0.328 0.343 0.330 0.345 0.269 0.282 0.270 0.284 0.244 0.255 0.247 0.258 0.214 0.224 0.217 0.227 0.154 0.161 0.158 0.165 0.146 0.153 0.151 0.157 0.130 0.136 0.133 0.138 0.103 0.108 0.109 0.114 0.084 0.088 0.092 0.095 0.051 0.054 0.059 0.061 0.042 0.044 0.052 0.054

271

Tabla 2.36 Constantes para clculo de cada de voltaje en lneas primarias. Se utilizaron los siguientes datos de la siguiente tabla para calcular la cada de voltaje para todas las tensiones elctricas nominales de las lneas areas primarias de distribucin en toda estructura normal (menos est. Tipo C y H. Se supone un sistema trifsico balanceado). Se multiplica la cada de voltaje correspondiente al calibre y material del conductor por la corriente de fase y por la longitud en kilmetros, la cada de voltaje ser entre fases

C O B R E A L U M I N I O

Cada de voltaje por ampere por kilmetro Conductor Factor de potencia en % Calibre Material 75 80 85 90 95 6 COBRE 2.332 2.396 2.453 2.489 2.491 4 COBRE 1.668 1.690 1.704 1.701 1.664 2 COBRE 1.246 1.246 1.233 1.209 1.152 1/0 COBRE 0.964 0.946 0.920 0.881 0.888 3/0 COBRE 0.778 0.753 0.718 0.668 0.590 2 1/0 3/0 266.4 336.8 ACSR ACSR ACSR ACSR ACSR 1.682 1.247 0.962 0.740 0.673 1.709 1.247 0.946 0.718 0.647 1.727 1.237 0.922 0.687 0.614 1.728 1.213 0.882 0.644 0.567 1.694 1.154 0.811 0.573 0.493

100 2.336 1.474 0.946 0.595 0.375 1.512 0.953 0.600 0.375 0.397

272

Tabla 2.37 Radio geomtrico de conductores CONSTRUCCION DEL CONDUCTOR Alambre slido Cable de un solo material 7 hilos 19 hilos 37 hilos 61 hilos 91 hilos 127 hilos r = Radio del conductor Tabla 2.38 Caractersticas de conductores (cables) CALIBRE KCM AWG 8 6 4 2 1/0 2/0 3/0 4/0 250 350 500 600 750 1000 MM2

RMG 0.779 r 0.726 r 0.758 r 0.768 r 0.772 r 0.774 r 0.776 r

8.37 13.30 21.15 33.60 53.49 67.40 85.01 107.21 127 177 253 304 380 507

DIAMETRO NOMINAL CONDUCTOR MM 3.4 4.3 5.4 6.8 8.5 9.6 10.7 12.1 13.2 15.7 18.7 20.7 23.1 26.9

NUMERO DE ALAMBRES 7 7 7 7 19 19 19 19 37 37 37 61 61 61

273

Tabla 2.39 Formulas de clculo del DMG de inductancia total (H / KM)Ar

SC

A

S L Fm

C- 4

= o r m e q u

2

R

x

M

1

0 G

l nSB

a c i n t r i a n i d i s t a n t e

g

E l v a l o r m e d i o t o t a l d e l s i s t e m - 4 L = 2 x 1 0 l R M G S d o n d e D M G e m e d i a g e o m t c o m o u l a r d e f i n i d aA B

a n

d

e l a e s : D M

i n G

d

s l a r i c a : xC

d i s t a n y q u e SA

S

C

D B

M

3

G

A

B

= =

B

S

C

x

S

S

F

SA B o r m

=

SB C a c i n

SC A t r i a n

g

u

l a r

S

S L L = =A 2- 4

L x R 1 M

=B 0 G

L

=C l n F

L o

S S r m

S a c i n p

E l v a l o r m e d i o d e i n d u c t a n c i a t o t a l e - 4 L = 2 x 1 0 l n D M R M G d o n a d e3

D

M

G

=

2

l a n

Tabla 2.40 Dimetros y pesos de cables de energa Vulcanel 2000M.R. EP XLP 5, 15, 25 y 35 kV.Conductor Calibre Area Dimetro nominal AWG / KCM mm2 mm 8 8.37 3.4 6 13.30 4.3 4 21.15 5.4 2 33.62 6.8 1/0 53.48 8.5 2/0 67.43 9.6 3/0 85.01 10.7 4/0 107.20 12.1 250 127.20 13.2 350 177.30 15.7 500 253.40 18.7 600 304.0 20.7 750 380.0 23.1 1000 506.7 26.9 Peso aproximado Dimetro nominal sobre Dimetro exterior nominal XLP EP aislamiento 5 kV 15 kV 25 kV 35 kV 5 kV 15 kV 25 kV 35 kV 5 kV 15 kV 25 kV 35 kV 5 kV 15 kV 25 kV mm mm mm mm mm mm mm mm kg/km kg/km kg/km kg/km kg/km kg/km kg/km 9.4 ---- ---- ---- 14.9 ---- ---- ---- 255 ---- ---- ---- 270 ---- ---10.0 ---- ---- ---- 16.3 ---- ---- ---- 335 ---- ---- ---- 350 ---- ---11.1 ---- ---- ---- 17.4 ---- ---- ---- 430 ---- ---- ---- 450 ---- ---12.5 16.8 ---- ---- 18.8 24.3 ---- ---- 510 770 ---- ---- 600 820 ---14.2 18.6 22.9 27.2 20.5 26.0 30.3 35.2 790 1000 1185 1340 815 1060 1280 15.3 19.6 23.9 28.2 21.5 27.2 31.3 36.2 940 1155 1345 1665 965 1220 1445 16.5 20.8 25.1 29.4 23.8 28.2 33.0 37.4 1175 1355 1580 1820 1205 1420 1690 17.8 22.1 26.4 30.7 25.1 29.5 34.3 38.7 1410 1600 1835 2200 1440 1670 1955 19.2 23.5 27.8 32.1 26.5 30.9 35.7 40.1 1630 1825 2075 2330 1665 1905 2200 21.7 26.0 30.3 34.6 29.0 33.9 38.2 42.6 2155 2395 2630 2900 2195 2495 2770 24.7 29.0 33.0 37.6 32.0 36.9 41.2 47.6 2925 3190 3445 3920 2970 3300 3600 26.9 31.2 35.5 39.8 34.7 39.1 44.9 49.8 3485 3740 4145 4505 3545 3860 4315 29.4 33.7 38.0 42.3 37.2 41.6 47.9 52.3 4250 4520 4990 5325 4310 4645 5180 33.1 37.5 41.8 46.1 41.0 46.9 51.7 56.1 5510 5935 6300 6660 5570 6080 6510

35 kV kg/km ------------1490 1755 1975 2245 2505 3095 4140 4745 5580 6945

Nota 1: Estos cables se fabrican tambin con un nivel de aislamiento del 133% (N.A. 133%). Estos datos son aproximados y estn sujetos a tolerancias de manufactura. Nota 2: Estos cables se fabrican tambin en construcciones trifsicas (cubierta comn). Nota 3: Estos cables se pueden fabricar bajo la norma UL-1072, y su asignacin ser cable tipo MV-90 (con aprobacin UL). Nota 4: estos cables se fabrican tambin con conductores de aluminio.

274

Tabla 2.41 Alambres y cables de cobre desnudoCalibre Dimetro nominal AWG mm 18 1.02 17 1.15 16 1.29 14 1.63 12 2.05 10 2.59 9 2.91 8 3.26 7 3.67 6 4.12 4 5.19 3 5.83 2 6.54 1/0 8.25 Area mm2 0.82 1.04 1.31 2.08 3.31 5.26 6.63 8.37 10.55 13.30 21.15 26.67 33.62 53.48 Temple duro Temple semiduro Temple suave Peso Nmero de Carga de Nmero de Carga de Nmero de Carga de producto ruptura producto ruptura producto ruptura kg/km kg kg kg 7.32 020032 39 020521 35 020066 22 9.24 020515 49 020520 43 020065 28 11.60 020514 61 020046 55 020064 35 18.50 020031 97 020045 86 020062 56 29.40 020030 154 020044 135 020060 90 46.77 020028 239 020043 212 020058 143 58.95 020511 301 020042 267 020057 175 74.38 020027 375 020041 333 020056 218 93.80 020510 468 020040 419 020055 275 118.20 020509 583 020039 522 020054 346 188.00 020026 897 020038 821 020052 551 237.10 020025 1102 020944 1033 020051 694 298.90 020024 1353 020037 1267 020050 876 475.50 020036 2045 ------021282 1355

Nota: Estos datos son aproximados y estn sujetos a tolerancias de manufactura.Calibre AWG / KCM 12 10 8 6 4 2 1/0 1/0 2/0 2/0 3/0 3/0 4/0 4/0 250 250 300 500 500 750 1000 Construccin No. de hilos dimetro en mm. 7/0.77 7/0.98 7/1.23 7/1.55 7/1.96 7/2.47 7/3.12 19/1.89 7/3.50 19/2.13 7/3.93 19/2.39 7/4.42 19/2.68 19/2.14 37/2.09 19/3.21 19/4.12 37/2.95 37/3.62 37/4.18 Dimetro del cable mm 2.33 2.93 3.70 4.67 5.88 7.42 9.36 9.47 10.51 10.63 11.80 11.94 13.25 13.40 1457 14.62 15.96 20.67 20.67 25.37 29.27 Area mm2 3.31 5.26 8.37 13.30 21.15 33.62 53.49 53.49 67.43 67.43 85.01 85.01 107.2 107.2 126.7 126.7 152.0 253.4 253.4 380.0 506.7 B B B B AyB AyB A B A B A B AA y A B A B A AA AyB AA AA Clase de cableado Peso kg/km 30 47.7 76 121 192 305 485 485 612 612 771 771 972 972 1149 1149 1379 2298 2298 3446 4595

Nota: Estos datos son aproximados y estn sujetos a tolerancias de manufactura.

275

Tabla 2.42 Resistencia elctrica de cables y conductores de cobre cableado de clase B.Calibre AWG / KCM 12 10 8 6 4 2 1/0 2/0 3/0 4/0 250 300 500 750 1000 Designacin del conductor Calibre Area AWG / KCM mm2 20 0.519 18 0.823 16 1.307 14 2.082 12 3.307 10 5.260 8 8.367 6 13.30 4 21.15 2 33.62 -35.00 -50.00 1/0 53.48 2/0 67.43 -70.00 3/0 85.01 4/0 107.20 250 126.70 -150.00 300 152.00 350 177.30 400 202.70 -240.00 500 253.40 600 304.00 750 380.00 1000 506.70 Duro 96.16 5.53 3.48 2.19 1.38 0.865 0.544 0.342 0.271 0.215 0.171 0.144 0.120 0.072 0.048 0.036 Resistencia c.d. a 20C en ohms / km Semiduro Conductividad 96.66 5.50 3.46 2.17 1.37 0.86 0.541 0.340 0.270 0.214 0.170 0.143 0.119 0.072 0.048 0.036 Resistencia elctrica en ohms / km Corriente directa 20C 33.900 21.400 13.500 8.450 5.320 3.340 2.100 1.320 0.8320 0.5230 0.5030 0.3520 0.3290 0.2610 0.2510 0.2070 0.1640 0.1390 0.1170 0.1160 0.0992 0.0868 0.0733 0.0694 0.0579 0.0463 0.0347 60C 39.010 24.626 15.535 9.724 6.122 3.843 2.417 1.519 0.9574 0.6018 0.5788 0.4051 0.3786 0.3003 0.2888 0.2382 0.1887 0.1600 0.1346 0.1335 0.1142 0.0999 0.0843 0.0799 0.0666 0.0533 0.0399 75C 41.241 26.034 16.423 10.280 6.472 4.063 2.555 1.606 1.012 0.6363 0.6119 0.4282 0.4002 0.3175 0.3054 0.2518 0.1995 0.1691 0.1423 0.1411 0.1207 0.1056 0.0892 0.0844 0.0704 0.0563 0.0422 90C 43.240 27.296 17.219 10.778 6.786 4.260 2.679 1.684 1.061 0.6671 0.6416 0.4490 0.4196 0.3329 0.3202 0.2640 0.2092 0.1773 0.1492 0.1480 0.1265 0.1107 0.0935 0.0885 0.0739 0.0591 0.0443 20C 33.900 21.400 13.500 8.450 5.320 3.340 2.100 1.320 0.8322 0.5234 0.5034 0.3526 0.3297 0.2620 0.2521 0.2085 0.1661 0.1419 0.1208 0.1181 0.1043 0.0932 0.0819 0.0788 0.0708 0.0651 0.0645 Corriente alterna 60C 39.010 24.626 15.535 9.724 6.122 3.844 2.417 1.519 0.9576 0.6023 0.5793 0.4058 0.3794 0.3015 0.2901 0.2399 0.1912 0.1632 0.1390 0.1359 0.1200 0.1073 0.0942 0.0907 0.0815 0.0749 0.0743 75C 41.241 26.034 16.423 10.280 6.472 4.063 2.555 1.606 1.012 0.6367 0.6124 0.4290 0.4011 0.3188 0.3067 0.2536 0.2021 0.1726 0.1470 0.1437 0.1269 0.1134 0.0996 0.0959 0.0862 0.0792 0.0785 90C 43.240 27.296 17.219 10.778 6.786 4.260 2.679 1.684 1.061 0.6676 0.6421 0.4498 0.4206 0.3342 0.3215 0.2659 0.2119 0.1809 0.1541 0.1506 0.1330 0.1189 0.1045 0.1006 0.0903 0.0830 0.0823 Suave 100.0 5.320 3.340 2.100 1.320 0.8320 0.5230 0.3290 0.2610 0.2070 0.1640 0.1390 0.1160 0.0694 0.0463 0.0347

Cables en configuracin plana separados 20 cm. Tabla 2.43 Cables ACSR de aluminio con refuerzo de acero galvanizadoNmero de hilos Dimetro nominal Peso Carga de

276

Calibre

Designacin

Alumini o 6 6 6 6 6 6 6 6 6 26 26 30 26 30 26 30 30 26 30 54 26 26 54 26 54 54 45 45

Acero

Ncleo mm 1.7 2.1 2.4 2.7 3.0 3.4 3.8 4.3 4.8 6.0 6.7 8.1 7.3 8.8 8.0 9.6 9.8 8.7 10.4 8.1 9.3 9.8 8.8 10.4 9.2 9.8 7.4 8.0

Cable mm 5.0 6.4 7.1 8.0 9.0 10.1 11.4 12.8 14.3 16.3 18.3 18.8 19.9 20.5 21.8 22.4 23.0 23.5 24.2 24.2 25.1 26.7 26.3 28.1 27.8 29.5 29.3 32.0

Aluminio kg/km 36 58 73 92 116 147 185 233 294 375 470 471 557 557 667 669 701 778 780 849 875 1006 1006 1117 1116 1262 1339 1563

Acero kg/km 17 27 35 44 55 69 87 110 139 171 217 311 256 366 308 440 461 359 513 310 409 460 366 512 408 461 260 304

Cable kg/km 53 85 108 136 171 216 272 343 433 546 687 782 813 923 975 1109 1162 1137 1293 1159 1284 1466 1377 1629 1524 1723 1599 1867

ruptura kN 5.29 8.27 10.24 12.7 15.8 19.5 23.6 29.7 37.47 50.3 62.7 77.0 725 90.3 86.7 106.0 110.0 101.0 124.0 104.0 112.0 126.0 116.0 140.0 125.0 143.72 115.0 137.72

AWG / KCM 6 TURKEY 4 SWAN 3 SWALLOW 2 SPARROW 1 ROBIN 1/0 RAVEN 2/0 QUAIL 3/0 PIGEON 4/0 PENGUIN 2668 PARTRIDGE 3364 LINNET 336.4 ORIOLE 397.5 IBIS 397.5 LARK 477.0 HAWK 477.0 HEN 500.0 HERON 556.5 DOVE 556.5 EAGLE 605.0 DUCK 636.0 GROSBEAK 715.5 STARLING 715.5 CROW 795.0 DRAKE 795.0 CONDOR 900.0 CANARY 954.0 RAIL 1113 BLUEJAY

1 1 1 1 1 1 1 1 1 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7

Nota: Estos datos son aproximados y estn sujetos a tolerancias de manufactura.

277

Tabla 2.44 Resistencia elctrica de conductores ACSRCalibre Designacin Turkey Swan Swallow Sparrow Robin Raven Quail Pigeon Penguin Partridge Linnet Oriole Ibis Lark Hawk Hen Heron Dove Eagle Duck Grosbeak Starling Crow Drake Condor Canary Rail Bluejay AWG / KCM 6 4 3 2 1 1/0 2/0 3/0 4/0 266.8 336.4 336.4 397.5 397.5 477 477 500 556.5 556.5 605 636 715.5 715.5 795 795 900 954 1113 Resistencia c.d. ohms/km 20C 2.114 1.328 1.076 0.834 0.662 0.524 0.416 0.330 0.262 0.210 0.166 0.165 0.141 0.140 0.117 0.116 0.109 0.100 0.100 0.095 0.088 0.079 0.079 0.071 0.70 0.062 0.059 0.051 Resistencia c.a. ohms/km 50C 2.449 1.565 1.281 1.012 0.811 0.654 0.530 0.429 0.354 0.236 0.187 0.186 0.159 0.157 0.132 0.131 0.123 0.113 0.113 0.106 0.099 0.088 0.088 0.080 0.080 0.071 0.068 0.058

25C 2.150 1.354 1.108 0.853 0.677 0.537 0.426 0.339 0.270 0.215 0.170 0.169 0.144 0.143 0.120 0.119 0.112 0.103 0.103 0.097 0.090 0.080 0.80 0.073 0.73 0.065 0.062 0.054

75C 2.685 1.717 1.405 1.108 0.891 0.717 0.580 0.470 0.383 0.257 0.204 0.202 0.173 0.172 0.144 0.143 0.135 0.124 0.123 0.116 0.108 0.096 0.096 0.087 0.087 0.077 0.074 0.064

278

Tabla 2.45 Resistencia elctrica de conductores de aluminio cableado clase B

Designacin del conductor Calibre Area AWG / KCM mm2 8 8.367 6 13.30 4 21.15 2 33.62 1/0 53.48 2/0 67.43 3/0 85.01 4/0 107.20 250 126.70 300 152.00 350 177.30 400 202.70 500 253.40 750 380.00 1000 506.70

Resistencia elctrica en ohms/km Corriente directa 20C 3.450 2.170 1.360 0.858 0.539 0.428 0.339 0.269 0.228 0.190 0.163 0.142 0.114 0.0759 0.0569 60C 4.007 2.520 1.580 0.997 0.626 0.497 0.394 0.312 0.265 0.221 0.189 0.165 0.132 0.088 0.066 75C 4.218 2.653 1.663 1.049 0.659 0.523 0.414 0.329 0.279 0.232 0.199 0.174 0.139 0.093 0.070 90C 4.423 2.782 1.744 1.100 0.691 0.549 0.435 0.345 0.292 0.244 0.209 0.182 0.146 0.097 0.073 20C 3.4500 2.1701 1.3601 0.8582 0.5394 0.4286 0.3399 0.2703 0.2298 0.1913 0.1662 0.1461 0.1201 0.0887 0.0785 Corriente alterna 60C 4.007 2.520 1.580 0.997 0.627 0.498 0.395 0.314 0.267 0.222 0.193 0.170 0.139 0.103 0.091 75C 4.218 2.653 1.663 1.049 0.659 0.524 0.416 0.330 0.281 0.234 0.203 0.179 0.147 0.108 0.096 90C 4.423 2.782 1.744 1.100 0.692 0.550 0.436 0.347 0.295 0.245 0.213 0.187 0.154 0.114 0.101

Cables en configuracin plana separados 20 cm.

279

Tabla 2.46 Caractersticas elctricas de conductores de cobre.Calibre AWG / KCM 12 12 10 10 9 8 8 7 6 6 4 4 3 2 2 1/0 1/0 1/0 2/0 2/0 3/0 4/0 4/0 250 250 300 500 750 1000 Nmero de hilos 1 7 1 7 1 1 7 1 1 7 1 7 1 1 7 1 7 19 7 19 19 7 19 19 37 19 19 37 37 RMG cm 0.080 0.085 0.101 0.107 0.113 0.127 0.135 0.143 0.160 0.170 0.202 0.214 0.227 0.225 0.269 0.321 0.360 0.359 0.382 0.403 0.453 0.481 0.508 0.553 0.561 0.606 0.781 0.972 1.123 Reactancia inductiva (Xa) a 30.48 cm de espaciamiento ohms/km 0.448 0.444 0.431 0.426 0.422 0.413 0.409 0.404 0.396 0.391 0.378 0.374 0.370 0.361 0.357 0.343 0.335 0.335 0.330 0.326 0.317 0.313 0.309 0.302 0.301 0.295 0.276 0.260 0.249

280

Tabla 2.47 Caractersticas elctricas de conductores ACSR.Calibre AWG / KCM 6 4 3 2 1 1/0 2/0 3/0 4/0 266.8 336.4 336.4 397.5 397.5 477 477 500 556.5 556.5 605 636 715.5 715.5 795 795 900 954 1113 Nmero de hilos Al 6 6 6 6 6 6 6 6 6 26 26 30 26 30 26 30 30 26 30 54 26 26 54 26 54 54 45 45 Ac 1 1 1 1 1 1 1 1 1 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 RMG cm 0.120 0.133 0.131 0.127 0.127 0.136 0.155 0.183 0.248 0.661 0.744 0.777 0.808 0.847 0.884 0.927 0.948 0.954 1.000 0.978 1.021 1.082 1.064 1.143 1.122 1.192 1.187 1.296 Reactancia inductiva (Xa) a 30.48 cm de espaciamiento ohms/km 0.418 0.410 0.411 0.413 0.413 0.408 0.398 0.386 0.361 0.289 0.280 0.277 0.274 0.270 0.267 0.264 0.262 0.261 0.258 0.259 0.256 0.252 0.253 0.248 0.245 0.244 0.245 0.238

281

Tabla 2.48 Factor de espaciamiento (Xa) de la reactancia inductiva en ohm/kmpies (cm) 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 (0) (30.48) (60.96) (91.44) (121.92) (152.40) (182.88) (213.36) (243.84) (274.32) (304.80) (335.28) (365.76) (396.24) (426.72) (457.20) (487.68) (518.16) (548.64) (579.12) (609.60) (640.08) (670.56) (701.04) (731.52) (762.00) (792.48) (822.96) (853.44) (883.92) (914.40) 0 (0) -0 0.0523 0.0829 0.105 0.121 0.135 0.147 0.157 0.166 0.174 0.181 0.187 0.193 0.199 0.204 0.209 0.214 0.218 0.222 0.226 0.230 0.233 0.236 0.240 0.243 0.246 0.249 0.251 0.254 0.256 1 (2.54) -0.187 0.0061 0.0554 0.0849 0.106 0.123 0.136 0.148 2 (5.08) -0.135 0.0116 0.0483 0.0869 0.108 0.124 0.137 0.149 3 (7.62) -0.104 0.0168 0.0612 0.0889 0.109 0.125 0.138 0.149 4 (10.16) 0.083 0.0217 0.0639 0.0908 0.111 0.126 0.139 0.150 5 (12.7) -0.066 0.0263 0.0666 0.0927 0.112 0.127 0.140 0.151 pulgadas (cm) 6 7 (15.24) (17.78) -0.052 -0.041 0.0306 0.0347 0.0691 0.0716 0.0945 0.0965 0.113 0.115 0.129 0.130 0.141 0.142 0.152 0.153

8 (20.32) -0.031 0.0385 0.0740 0.0980 0.116 0.131 0.143 0.154

9 (22.86) -0.022 0.0422 0.763 0.0997 0.117 0.132 0.144 0.154

10 (25.4) -0.014 0.0457 0.785 0.101 0.119 0.133 0.145 0.155

11 (27.94) -0.007 0.0491 0.0807 0.103 0.120 0.134 0.146 0.156

Xa a 60 ciclos. Xa = 0.1736 log D - 0.2576. D = separacin en cm.Radio medio geomtrico RMG Construccin del conductor Alambre sldo 0.779r Cable de un slo material 7 hilos 0.726r 19 hilos 0.758r 37 hilos 0.768r 61 hilos 0.772r 91 hilos 0.774r 127 hilos 0.776r

Cables ACSR 30 hilos en 2 capas 0.826r 26 hilos en 2 capas 0.809r 54 hilos en 3 capas 0.810r Una sola capa 0.35 - 0.70r

donde: r = radio del conductor. El radio medio geomtrico (RMG) junto con el dimetro medio geomtrico (DMG) se utiliza para calcular la inductancia.

282

Tabla 2.49 Cable de energa VulcanelM.R. EP XLP tipo DS para 15, 25 y 35 kV.Calibre Nmero Dimetro Peso de Conductor Sobre aislamiento Total EP XLP hilos 15 kV 25 kV 35 kV AWG / e=4.45 e=6.60 e=8.80 15 kV 25 kV 35 kV 15 kV 25 kV 35 kV 15 kV 25 kV 35 kV KCM mm2 mm mm mm mm mm mm mm kg/km kg/km 2 33.62 7 6.8 17.1 ------24.1 ------640 ------609 ------1/0 53.48 19 8.5 18.8 23.2 27.6 25.8 30.2 35.0 750 980 1300 746 946 1235 2/0 67.43 19 9.6 19.9 24.3 28.7 26.9 31.3 36.1 843 1100 1400 830 1050 1352 3/0 85.01 19 10.7 21.0 25.4 29.8 28.0 32.8 37.2 910 1295 1505 881 1125 1448 4/0 107.20 19 12.1 22.4 27.1 31.6 29.4 34.5 39.0 1035 1320 1620 964 1231 1583 250 127.20 37 13.2 23.8 28.4 33.0 30.8 35.8 40.4 1125 1483 1907 1144 1460 1877 350 177.30 37 15.7 26.3 30.9 35.5 33.7 38.3 42.9 1350 1854 2384 1430 1825 2346 500 253.40 37 18.7 29.3 33.9 38.5 36.7 41.3 48.1 1695 2099 2642 1668 1985 2552 600 304.0 61 20.7 31.5 36.2 40.7 38.9 45.2 50.3 2015 2430 3083 1983 2360 3034 750 380.0 61 23.1 33.9 38.6 43.1 41.3 48.2 52.7 2406 2863 3244 2368 2818 3193 900 456.0 61 25.4 38.6 40.9 45.4 43.6 50.5 55.0 2786 3315 3756 2742 3263 3697 1000 506.7 61 26.9 39.7 42.4 46.9 45.1 52.0 56.5 2966 3530 3999 2919 3474 3936 Area

Nota: Estos datos son aproximados y estn sujetos a tolerancias de manufactura. La letra e significa espesor de aislamiento. Estos cables tambin se fabrican con conductos de cobre en nivel de aislamiento 133%. Estos cables pueden tambin fabricarse con barreras contra el ingreso de humedad de acuerdo a la norma CFE-E 000016.

283

Tabla 2.50 Capacidad mxima o ajuste del dispositivo de proteccin contra corto circuito y falla a tierra para el circuito derivado de motores.Tipo de motor Fusible sin retraso de tiempo Monofsico, todos los tipos sin letra de cdigo Todos los motores monofsicos y polifsicos jaula de ardilla con arranque a voltaje pleno, o arranque por reactor o resistor. Sin letra de cdigo Letras de cdigo F a V Letras de cdigo B a E Letra de cdigo A Todos los motores de jaula de ardilla y sincronos con arranque por autotransformador no mayores de 30 amperes Sin letra de cdigo Letras de cdigo F a V Letras de cdigo B a E Letra de cdigo A Jaula de ardilla con alta reactancia no mayores de 30 amperes sin letra de cdigo Mayores de 30 amperes sin letra de cdigo Letras de cdigo F a V Letras de cdigo B a E Letra de cdigo A Jaula de ardilla con alta reactancia no mayores de 30 amperes sin letra de cdigo Mayores de 30 amperes sin letra de cdigo Rotor devanado sin letra de cdigo 300 300 300 250 150 250 200 250 200 150 250 200 250 200 150 250 200 150 Por ciento de la corriente a plena carga automtico Elemento dual Interruptor con Interruptor de tiempo (fusible con retraso) disparo instantneo inverso 175 175 175 175 150 175 175 175 175 150 175 175 175 175 150 175 175 150 700 700 700 700 700 700 700 700 700 700 700 700 700 700 700 700 700 250 250 250 250 200 150 200 200 200 200 150 200 200 200 200 150 250 200 150

284

Tabla 2.50a Capacidad mxima de los dispositivos de proteccin en los circuitos derivados, para motores sin letra de cdigo, indicando los KVA con rotor bloqueado.Tipo de motores Tipo instantneo Todos los motores monofsicos, polifsicos, jaula de ardilla y sincronos, con arranque a tensin plena o a tensin reducida con resistencia o con reactancia Todos los motores jaula de ardilla y sncronos con arranque con autotranformador. No ms de 30 amperes Ms de 30 amperes Motores de rotor devanado Motores de corriente continua No ms de 50 HP Ms de 50 HP Por ciento de la corriente a pena carga Fusibles Doble elemento (con retardo) Interruptores Tipo instantneo Con lmite de tiempo

300

175

700

250

250 200 150 150 150

175 175 150 150 150

700 700 250 250 175

200 250 150 150 150