    Foreword

    Summary

    The manual describes the HRUC A 012C/S/A/H08 air conditioner instructions,product composition, working principle, wiring,operating instructions, routinemaintenance, troubleshooting, and technical indicators.

    Audience

    This manual applies to the following engineers:

    Technical support engineer

    Maintenance engineer

    Marketing Engineer

    Service Engineer

    Revision records

    Revision records accumulated each document updated instructions.

    The latest version of the document contains all the previous document version updates.

    Change HistoryHRM8811P-V2.0

    2012116

    The first official release is 2012-11-6

    Document versionHRM8811P-V2.0

    Tel: +41416610545 Enclosure Technology GmbH Switzeralnd Fax: +41416610544

    [email protected] www.enclosure-tec.com 2

  • 8/14/2019 8811P Manual Aire Acondicionado

    3/33

    HRM8811P-V2.0 2012-11-6 Catalog

    CatalogForeword..................................................................... ii

    1Instructions.................................................................. 4

    2Product Overview............................................................. 5

    2.1 Product appearance................................................................. .................................................................. 5

    2.2 Application of scence...................................................................................................................... ........... 5

    2.3 Product nameplate..................................................................................................................................... 7

    2.4 Product features......................................................................................................................................... 7

    2.5 Product composition................................................................. .................................................................. 7

    2.6 Technical parameters............................................................... .................................................................. 8

    2.7 Working Principle.......................................................... ................................................................... ........... 9

    2.8 Air duct design............................................................................................................................................ 92.9 Control logic............................................................................................................................................... 10

    2.10User parameter.............................................................. ................................................................... ......... 11

    2.11Alarm and fault management............................................................. ...................................................... 11

    3 Packing and shipping....................................................... 13

    4 Unpacking and Acceptance.................................................. 14

    5 Installation................................................................. 16

    5.1 Structure installation................................................................. ................................................................ 16

    5.2 Cable.......................................................................................................................................................... 18

    5.3 Electrical wiring installation..................................................................................................................... 20

    5.4 Communication line connection............................................................................................................. 22

    6Running and Test............................................................ 25

    6.1 Pre-operational checks............................................................ ................................................................ 25

    6.2 Running............................................................... ................................................................... .................... 25

    6.3 Monitor Operation......................................................... ................................................................... ......... 26

    7 Maintence and Warranty.................................................... 28

    7.1 Product maintance.................................................................................................................................... 28

    7.1.1Prepare tools

    ........................................................... ................................................................... ......... 28

    7.1.2Routine maintenance........................................................ ................................................................. 29

    7.1.3Alarm code and Processing method................................................................ ................................ 30

    7.1.4Other fault analysis and processing................................................................................................ 32

    7.1.5Spare parts list.................................................................. ................................................................. 32

    7.2Service and repair....................................................................................................................................... 33

    Tel: +41416610545 Enclosure Technology GmbH Switzeralnd Fax: +41416610544

    [email protected] www.enclosure-tec.com 3

  • 8/14/2019 8811P Manual Aire Acondicionado

    4/33

    HRM8811P-V2.0 2012-11-6 1 Instructions

    4

    1Instructions

    This manual applies to the following modelHRUC A 012/C/S/A/H08.

    Be sure to read this manual before using the unit

    The user must be in accordance with the regulations manual contentexecution can enjoy normal warranty service.

    Tel: +41416610545 Enclosure Technology GmbH Switzeralnd Fax: +41416610544

    [email protected] www.enclosure-tec.com 4

  • 8/14/2019 8811P Manual Aire Acondicionado

    5/33

    HRM8811P-V2.0 2012-11-6 2 Product Overview

    5

    2Product Overview

    About this chapter

    This chapter describes the shape of the HRUC A 012/C/S/A /H08 air conditioner, applicationscenarios, product nameplates, product features, product composition, technical parameters, theworking principle, duct design, control logic, communication protocols and user parameters, alarm andfaultprocessing of information. Please strictly in accordance with the relevant provisions of this manual!

    2.1 Product appearance

    Figure2-1 Product appearance

    2.2 Application of scence

    The product is designed for communication or related industrial equipment applications

    and design of high performance AC type air conditioner, Please use the AC230V,50Hz /60Hz power,The installation is the significance of the control cabinet (normal work to a closed state ) of internal

    Tel: +41416610545 Enclosure Technology GmbH Switzeralnd Fax: +41416610544

    [email protected] www.enclosure-tec.com 5

  • 8/14/2019 8811P Manual Aire Acondicionado

    6/33

  • 8/14/2019 8811P Manual Aire Acondicionado

    7/33

    HRM8811P-V2.0 2012-11-6 2 Product Overview

    7

    2.3 Product nameplateFigure2-2 Product nameplate

    2.4 Product features Less dehumidifying comparing traditional aircon

    Suitable for high temperature

    R134aEnvironmental protection refrigerant

    Self testing function

    The multiple protection

    Remote monitoring

    Alarming output to monitoring system

    Easy maintenance

    2.5 Product compositionAir conditioner system is composed of the following parts

    Tel: +41416610545 Enclosure Technology GmbH Switzeralnd Fax: +41416610544

    [email protected] www.enclosure-tec.com 7

  • 8/14/2019 8811P Manual Aire Acondicionado

    8/33

    HRM8811P-V2.0 2012-11-6 2 Product Overview

    8

    Figure2-3Air conditioner composition diagram

    2.6 Technical parametersAir conditioner technical parameters are listed in Table 2-1.

    table2-1Technical parameters for air conditioner

    Performance index Data

    Rated voltage(V) 230VAC 50/60HZ

    Rated cooling capacity(w) 1200

    Rated Heater capacity(w) 800

    Rated powerW 650

    Refrigent R134a/650g

    Ambient temperature range() -15~55

    Relative humidity range 5~90%

    Storage of environmental range

  • 8/14/2019 8811P Manual Aire Acondicionado

    9/33

    HRM8811P-V2.0 2012-11-6 2 Product Overview

    9

    Performance index Data

    Fan life(internal circulation L10/25external circulation

    L10/40(hour)

    25000

    W*D*H (mm) Dimension 4171651117

    2.7 Working Principle

    Air-conditioning using the compressor refrigeration

    Main parts of the refrigeration: compressor, condenser, expansion valve, an evaporator,

    internal fan, external fan, heater

    Principle of refrigeration: Compressor suck refrigerant gas from evaporator, and compressed,the compressed refrigerant gas pushed into condenser to cooled into refrigerant liquid, then pass theexpansive valve, the refrigerant into evaporator and evaporate to cool air.

    2.8 Air duct design

    Internal circulation and external circulation of the air duct is shown in Figure2-3.

    Figure2-3 Air duct design

    Tel: +41416610545 Enclosure Technology GmbH Switzeralnd Fax: +41416610544

    [email protected] www.enclosure-tec.com 9

  • 8/14/2019 8811P Manual Aire Acondicionado

    10/33

  • 8/14/2019 8811P Manual Aire Acondicionado

    11/33

  • 8/14/2019 8811P Manual Aire Acondicionado

    12/33

    HRM8811P-V2.0 2012-11-6 2 Product Overview

    12

    E04Compressor over-current

    E05

    Heater current is too low

    This feature is only applicable tothe models containing heater

    E06

    Heater over-current

    E07Internal fan alarm

    E08External fan alarm

    E11High temperature alarm

    E12Low temperature alarm

    E13Supply voltage overload

    1

    Attention: External alarm input 1 faultDisplay alternately shows the return air temperature

    values and "-- -- "

    2

    High temperature alarmLow temperature alarmSupply voltage overload alarm occurs,dispal shows

    the alarm informatiom , No dry contacts alarm information output.

    Tel: +41416610545 Enclosure Technology GmbH Switzeralnd Fax: +41416610544

    [email protected] www.enclosure-tec.com 12

  • 8/14/2019 8811P Manual Aire Acondicionado

    13/33

    13

    3Packing and shipping

    Air conditioner packed in wooden cases(1pcs/box or 4pcs/box) with EPE protection pad. thepackage includes Annex.( Please refer to table 4-1 packing List)

    The air conditioner during the transportation, please pay attention to the following matters

    figure3-1 Packing mark

    During Handling or transport, Air conditioner must be upward placed as . No inverted, flat,

    excessive tilt and collision.

    Air conditioner is precision instrument, in handling or transport process, should be handled withcare, package boxes do not step, prohibit standing or placing other heavy objects.

    During Handling or transport, pay attention to moisture, water, rain.

    Tel: +41416610545 Enclosure Technology GmbH Switzeralnd Fax: +41416610544

    [email protected] www.enclosure-tec.com 13

  • 8/14/2019 8811P Manual Aire Acondicionado

    14/33

    14

    4Unpacking and Acceptance

    Make sure the package upright as shown in Figure 3-1 before you open the package,

    Please check the packing belt is broken, the wooden box is damaged, deformed, wet.

    Use scissors or a knife dismantling packing belt,then open the wooden box.

    Figure4-1 Open the wooden box

    Tel: +41416610545 Enclosure Technology GmbH Switzeralnd Fax: +41416610544

    [email protected] www.enclosure-tec.com 14

  • 8/14/2019 8811P Manual Aire Acondicionado

    15/33

    15

    After opening the package, please check the products according to the packing list.

    Table 4-1 Packing list

    Attention:The number in table 4-1 is for 1 pcs air conditioner only.

    For the 2 pcs air conditioner ,the number is 2pcs

    For the 3 pcs air conditioner ,the number is 3pcs

    For the 4 pcs air conditioner ,the number is 4pcs

    Serial number Name Model / Specification Number

    1Air Condition

    HRUC A 012/C/S/A/H08 1pcs

    2Usermanual

    HRM8811P-V2.0 1pcs

    3Certificate

    8811P 1pcs

    4Water tube 10*14

    Silicone hose1pcs

    5Seal

    EPDM 252mm 1pcs

    6Power cord

    UL1015 16AWG 1pcs

    7Alarm cord

    UL1015 20AWG 1pcs

    8

    Communicationcord 2.5m 1pcs

    Tel: +41416610545 Enclosure Technology GmbH Switzeralnd Fax: +41416610544

    [email protected] www.enclosure-tec.com 15

  • 8/14/2019 8811P Manual Aire Acondicionado

    16/33

    16

    5Installation

    About this chapterAir conditioner installation and wiring

    5.1 Structure installation Installation diagram

    Figure5-1 Installation diagram

    Attention :Length of M6 screw can not greater than the Cabinet material

    thickness+6(mm)

    Tel: +41416610545 Enclosure Technology GmbH Switzeralnd Fax: +41416610544

    [email protected] www.enclosure-tec.com 16

  • 8/14/2019 8811P Manual Aire Acondicionado

    17/33

  • 8/14/2019 8811P Manual Aire Acondicionado

    18/33

    18

    7)

    Mount the out cover to the shelter---only side and half embeded needed. ( the purpose of theout cover is provent rain penetrate into the product also protection the product access fromexternal side).

    !! Note: the out cover is not a standard part of product, normally it is provided by

    an engineering company who install the product.

    8)

    The mechenical part of installation is finished till now. please double check.

    Double check lists

    1)

    Dont apply this unit in high oli, burning gas, explosive gas, strong corrosivity condition, the

    ambient air must be under 60, and the humidity not higher than 95%.

    2)

    Make sure that the lean of the product nor more than 3.

    3)

    Make sure that the cabinet should be sealled well to avoid the cooling losing and avoidambient moisture penetrate into cabinet, this will avoid produce more condensate water.

    4)

    Dont power on the unit immediately after finish the installation until the uint keep up standfor more than 30 min.

    5.2 Cable

    Air conditioner with power linesalarm lines and communication lines each one As an

    optional accessories;

    Tel: +41416610545 Enclosure Technology GmbH Switzeralnd Fax: +41416610544

    [email protected] www.enclosure-tec.com 18

  • 8/14/2019 8811P Manual Aire Acondicionado

    19/33

    19

    Figure5-3 Alarm line

    Figure5-4 Power line

    Figure5-5 Communication line

    Tel: +41416610545 Enclosure Technology GmbH Switzeralnd Fax: +41416610544

    [email protected] www.enclosure-tec.com 19

  • 8/14/2019 8811P Manual Aire Acondicionado

    20/33

  • 8/14/2019 8811P Manual Aire Acondicionado

    21/33

    21

    Figure5-7 Air conditioner wiring diagram

    Tel: +41416610545 Enclosure Technology GmbH Switzeralnd Fax: +41416610544

    [email protected] www.enclosure-tec.com 21

  • 8/14/2019 8811P Manual Aire Acondicionado

    22/33

    22

    5.4 Communication line connection

    RS 422 communication connection

    As shown below, the communication line terminal is directly inserted in the communicationinterface " OUT"

    Communication connection

    Tel: +41416610545 Enclosure Technology GmbH Switzeralnd Fax: +41416610544

    [email protected] www.enclosure-tec.com 22

  • 8/14/2019 8811P Manual Aire Acondicionado

    23/33

    23

    RS 485 communication connedtion

    The attachment of the communication line according to the connection, then the communicationline terminal is inserted in the communication interface:

    Communication connection

    As shown aboveThe line labeled "TX2+ " and The line labeled "RX2+ " are shorted together

    as "T/R+ " line ; The line labeled "TX2- " and The line labeled "RX2- " are shorted together as

    "T/R- " line ;then the "T/R+ " line and "T/R- " line can be connected as RS485 communication

    line.

    Tel: +41416610545 Enclosure Technology GmbH Switzeralnd Fax: +41416610544

    [email protected] www.enclosure-tec.com 23

  • 8/14/2019 8811P Manual Aire Acondicionado

    24/33

    24

    Figure5-7 Air conditioner system wiring diagram

    Tel: +41416610545 Enclosure Technology GmbH Switzeralnd Fax: +41416610544

    [email protected] www.enclosure-tec.com 24

  • 8/14/2019 8811P Manual Aire Acondicionado

    25/33

    25

    6Running and Test

    About this chapter

    Introduce the ari conditioning running and test

    6.1 Pre-operational checks

    After Air conditioner installation and the electrical connection is completed, please check thefollowing checklist:

    Table6-1 Pre-operational checks

    Serial numberCheck items

    1Ensure the screw is fastening

    2 Ensure that there is enough space near the internal and externalof the air condition

    3 Power line to connect the right polarity

    Alarm signal cables are connected correctly

    4 Using a multimeter to check the supply voltage, power supplyvoltage is normal, consistent with the requirements on thenameplate.

    6.2 Running

    Power on the switch, the product will perform a self-test running program firstly, and then the unitwill run normally.

    Tel: +41416610545 Enclosure Technology GmbH Switzeralnd Fax: +41416610544

    [email protected] www.enclosure-tec.com 25

  • 8/14/2019 8811P Manual Aire Acondicionado

    26/33

    26

    Self-test: Power on the switch, the product will perform a self-test running program firstly.The self-test process can refer to2.9 Control logic

    If there is any trouble during self-test,the alarm will be generated,the monitor Display alarm faultcode,the system according to the alarm fault code to enter fault handling operation.

    If there is no trouble during the self-test, system will be normal running automatically.

    Normal mode:include standby operation, cooling heatingThe Details can refer to2.9 Control

    logic

    When the air conditioner is running ,if there is abnormal noise,vibration,please cut off powerimmediately and notify the professionals to inspect.

    6.3 Monitor OperationThe interface of the monitor is as follows:

    Figure6-1Interface of the monitor

    The definition of the symbols from left to right are as follows:

    Table6-2 Definition of the symbols

    Indicator Definition Light Flicker

    Point setting Under settingNA

    Cooling Cooling running Wait for cooling

    Tel: +41416610545 Enclosure Technology GmbH Switzeralnd Fax: +41416610544

    [email protected] www.enclosure-tec.com 26

  • 8/14/2019 8811P Manual Aire Acondicionado

    27/33

    27

    Heating Heating runningNA

    External fanExtrenal fan

    running

    NA

    Alarm NA Alarm

    Parameter setting

    Long press "M" key for 5 seconds, enter the parameter setting mode, then display the code of

    parameters, with "

    " key to select the code of parameters, select a code and press "Set" buttonwill display corresponding parameter values of the code, then re-use "" button can set theparameters, after finished the setting, press "Set "button, back to display states. During the settingmode, Press "M" key to exit the parameter setting mode, in the process of the parameter valuessetting by pressing "M" button that give up, quit, but does not change the parameter value.

    Current query

    Under the return air temperature interface,pressonce will show compressor current,pressagain ,the monitor will show internal fan current,press the third time,the monitor will show theexternal fan current.Press the fourth will return the main interface.

    Voltoge query

    Under the main interface,press both andbutton will show the voltage,the unit is V.Press Mto return the main interface.

    Tel: +41416610545 Enclosure Technology GmbH Switzeralnd Fax: +41416610544

    [email protected] www.enclosure-tec.com 27

  • 8/14/2019 8811P Manual Aire Acondicionado

    28/33

    28

    7Maintence and Warranty

    This chapter introduce maintenance and warranty

    7.1 Product maintance

    7.1.1 Prepare tools

    Table7-2 Maintance Tools

    Number Tools

    1 Multimeter

    2Phillips screwdriver

    3Slotted screwdriver

    Tel: +41416610545 Enclosure Technology GmbH Switzeralnd Fax: +41416610544

    [email protected] www.enclosure-tec.com 28

  • 8/14/2019 8811P Manual Aire Acondicionado

    29/33

    29

    7.1.2 Routine maintenance

    Table7-2 Routine maintenance

    NUM. Check items Check methods Solution

    1 Power line firm

    1

    Turn off the supply power

    2

    Pulled the power linewatch whether the

    line is loosening

    3

    Screw the screws on the power cordterminals with a screwdriver, watchwhether the screw is loosening

    If there is a power line toloose or loosening, Youshould be used to tie tightpower line; use ascrewdriver to loose screw

    2VoltageStability

    Use the multimeter to measure airconditioner input voltage to watch whetherthe voltage is within normal range.

    If the voltage is not withinthe normal range,Pleaseturn off the power supply

    immediately.Power on theair conditioner until thesupply voltage withinnormal range.

    3Screw firmly

    Use scrowdriver to screw the screws andwatch whether the screw is loosening

    If the screw isloosening,please tighten it.

    4Cooling

    Power on the switch and watch whether theself-test is correct.If it is currect ,the monitorwill display compressor current as self-testprogram

    1

    While self-testing ,

    if there is abnormalnoise,vibration,please cutoff power immediately andnotify the professionals toinspect.

    2

    If it is alarm while self-test,please process

    As table7-3

    Tel: +41416610545 Enclosure Technology GmbH Switzeralnd Fax: +41416610544

    [email protected] www.enclosure-tec.com 29

  • 8/14/2019 8811P Manual Aire Acondicionado

    30/33

    30

    7.1.3 Alarm code and Processing method

    Table 7-3 Alam information

    CodeCode Name Principle Process Method

    E01 Return airtemperature sensor

    alarm

    Return air temperaturesensor is short circuit or opencircuit

    Check whether thereturn air temperaturesensor is short circuit oropen circuit.

    E03 Compressor currentis too low

    Compressor current is notwithin normal range

    1

    Check whether thecompressor line islossening

    2

    Compressor fault,pleasecontact professionalmaintenance.

    E04 Compressor over-current

    Compressor current is notwithin normal range

    1

    Check whether thecondenser is dirty block.

    2

    Compressor fault,pleasecontact professionalmaintenance.

    Tel: +41416610545 Enclosure Technology GmbH Switzeralnd Fax: +41416610544

    [email protected] www.enclosure-tec.com 30

  • 8/14/2019 8811P Manual Aire Acondicionado

    31/33

  • 8/14/2019 8811P Manual Aire Acondicionado

    32/33

    32

    7.1.4 Other fault analysis and processing

    Table7-4 other fault analysis and processing

    Fault state Analysis of the reasons Solutions

    Power on theswitch ,thecabinettemperature is

    too high but theair conditioneris not working

    1

    Power failure or no power

    2

    The cooling set temperature is higher than the

    cabinet temperature4

    Systerm fault

    1

    Check the power supply andthe eletric circuit

    2

    Setting cooling temperatureaccording to the needs

    3

    Please contact professionalmaintenance.

    The air

    conditioner isrunning but thecooling effect isnot good

    1

    The cooling capacity of the air conditioner is notmatch with the load.

    2

    The ambience temperature is too high

    3

    Other system fault

    3

    To add or choose another airconditioner according to theload.

    4

    Ensure the machine is used inthe correct range.

    5

    Please contact professionalmaintenance.

    The machine is

    stoppingsuddenly ,andthe electricsystem isnormal

    1

    The cabinet temperature greater than or equal

    to the cooling set temperature.

    2

    Other system fault

    1

    Setting cooling temperature

    according to the needs2

    Please contact professionalmaintenance.

    7.1.5 Spare parts list

    Table7-5 Spare parts list

    Tel: +41416610545 Enclosure Technology GmbH Switzeralnd Fax: +41416610544

    [email protected] www.enclosure-tec.com 32

  • 8/14/2019 8811P Manual Aire Acondicionado

    33/33

    Serial NUM. Name Mode Num.

    1 internalfan R2E 190-A026-05 1

    2 externalfan R2E 190-A026-05 1

    3 heater 800W PTC 1

    4 main control board AC Control V2.0 1

    5 monitor board AC Pannel V2.0 1

    7.2 Service and repair Warranty period

    The product guarantee period is 12 monthsfrom product up-running time or Max. 18 monthfromproduct delivery date.

    Warranty coverage

    During the warranty period, all belong to the product itself quality problems caused by fault, thecompany will be free for you to repair, Household repair is required to provide the product label. But byany of the following causes the failure does not belong to our warranty.

    1) Out of the Warranty period

    2) Can not provide the product label(the product lable is on the nameplate);3) Because of the abnormal condition or environment ,or the instructions specified in the

    inappropriate installation installation, maintenance or operation causes the fault;

    4) Not caused by equipment failure,caused by user`s other equipment or software.

    5) User changed or disassemble by theirself,or maintanced by the person without authorization.

    6) Caused by force majeure such as fires, earthquakes, floods and other damage to the fault.

    Disclaimer

    The warranty is limited to the delivered products.

    Division I is irresponsible for any loss that may be derived by equipment failure.

    .

    Tel: +41416610545 Enclosure Technology GmbH Switzeralnd Fax: +41416610544